Iskra WM3x6 Series, WM3-6, WM3M6 User And Installation Manual

Users Manual
Energy meters WM3x6 Three-phase electrical energy meter WM3-6 Three-phase electrical energy meter WM3M6
November 2018 • Version 1.01
ii
User’s Manual
Three-phase electrical energy meter
WM3x6
User and Installation manual
User’s Manual
iii
Security Advices and Warnings
Please read this chapter carefully and examine the equipment carefully for potential damages which might arise during transport and to become familiar with it before continue to install, energize and work with a three-phase energy meter WM3x6. This chapter deals with important information and warnings that should be considered for safe installation and handling with a device in order to assure its correct use and continuous operation.
Everyone using the product should become familiar with the contents of chapter »Security Advices and Warnings«.
If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
PLEASE NOTE
This booklet contains instructions for installation and use of three-phase energy meter WM3x6. Installation and use of a device also includes handling with dangerous currents and voltages therefore should be installed, operated, serviced and maintained by qualified personnel only. ISKRA Company assumes no responsibility in connection with installation and use of the product. If there is any doubt regarding installation and use of the system in which the device is used for measuring or supervision, please contact a person who is responsible for installation of such system.
Before switching the device ON
Check the following before switching on the device:
Nominal voltage. Terminals integrity. Protection fuse for voltage inputs (recommended maximal external fuse size is 65 A). External switch or circuit breaker must be included in the installation for disconnection of the
devices’ power supply. It must be suitably located and properly marked for reliable disconnection of the device when needed.
Proper connection and voltage level of I/O module.
iv
User’s Manual
SYMBOL
EXPLANATION
DANGER
Indicates proximity of hazardous high voltage, which might result in serious injury or death if not handled with care.
WARNING
Indicates situations where careful reading of this manual is required and following requested steps to avoid potential injury is advised.
Compliance of the product with directive 2002/96/EC, as first priority, the prevention of waste electrical and electronic equipment (WEEE), and in addition, the reuse, recycling and other forms of recovery of such wastes so as to reduce the disposal of waste. It also seeks to improve the environmental performance of all operators involved in the life cycle of electrical and electronic equipment.
Compliance of the product with European CE directives.
Used symbols on devices’ housing and labels
Disposal
It is strongly recommended that electrical and electronic equipment (WEEE) is not deposit as municipal waste. The manufacturer or provider shall take waste electrical and electronic equipment free of charge. The complete procedure after lifetime should comply with the Directive 2002/96/EC about restriction on the use of certain hazardous substances in electrical and electronic equipment.
BASIC DESCRIPTION AND OPERATION
User’s Manual
v
Table of contents
1 BASIC DESCRIPTION AND OPERATION 1
1.1 DESCRIPTION OF THE DEVICE 2
1.2 THREE-PHASE ENERGY METERS APPLICATION 3
1.3 MAIN FEATURES 3
2 CONNECTION 4
2.1 MOUNTING 5
2.2 ELECTRICAL CONNECTION 6
3 FIRST STEPS 10
3.1 INDIVIDUAL PHASE MEASUREMENT UNIT 11
3.2 DISPLAY OF DEVICE INFO 12
3.3 SOFTWARE FUNCTIONS 13
3.4 LCD USER INTERFACE 14
3.5 LIMITS 24
3.6 FREEZE COUNTERS 29
4 SETTINGS 31
4.1 INTRODUCTION 32
4.2 MIQEN SOFTWARE 32
5 TECHNICAL DATA 39
5.1 ACCURACY 40
5.2 MECHANICAL CHARACTERISTICS OF INPUT 41
5.3 ELECTRICAL CHARACTERISTICS OF INPUT 41
5.4 SAFETY AND AMBIENT CONDITIONS 43
5.5 EU DIRECTIVES CONFORMITY 44
5.6 DIMENSIONS 44
6 ABBREVIATION/GLOSSARY 45
7 APPENDICES 46
7.1 APPENDIX A: MODBUS COMMUNICATION PROTOCOL 46
7.2 APPENDIX B: M-BUS 60
BASIC DESCRIPTION AND OPERATION
User’s Manual
1 BASIC DESCRIPTION AND OPERATION
The following chapter presents basic information about a three-phase energy meter WM3x6 required to understand its purpose, applicability and basic features connected to its operation. In this chapter you will find:
1.1 DESCRIPTION OF THE DEVICE 2
1.2 THREE-PHASE ENERGY METERS APPLICATION 3
1.3 MAIN FEATURES 3
BASIC DESCRIPTION AND OPERATION
User’s Manual
1 Current terminals – to load 2 AUX terminals (options):
- RS485
- M-BUS
- PULSE OUTPUT
- TARIFF INPUT
3 IR COMM PORT –ON SIDE 4 Information display 5 DIN-Rail fitting 6 User button and LED
indicator (1000 imp/kWh)
7 Current terminal – source
(max 65 A)
1
2
3
4
6
2
7
5
1.1 Description of the device
The three-phase energy meters WM3-6, WM3M6 (MID certified) are intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Meters measure energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates active/reactive/apparent power and energy, current, voltage, frequency, power factor, power angle and frequency (for each phase and total sum) from the measured signals. This smart meter can also perform basic harmonic analysis (THDU, THDI). This enables quick overview of harmonic distortion either coming from a network or generated by the load. Microprocessor also controls LCD, LED, IR communication and optional extensions. Connecting terminals can be sealed up against non-authorised access with protection covers. They are built to be fastened according to EN 60715 standard.
1.1.1 Appearance
Figure 1: Appearance of three-phase electric energy meter WM3x6
LCD
Number of digits: 8 (7+1) Height of digits: 4.52 mm
LED
Colour: red Pulse rate: 1000 imp/kWh LED on: no load indication
BASIC DESCRIPTION AND OPERATION
User’s Manual
1.2 Three-phase energy meters application
Energy meters have built-in optical (IR) communication port on the side as a standard. Special WM-USB adapter (size 1 DIN module) can easily be attached to it. It can be used for direct communication with a PC to change settings of devices without any communication installed. Energy meters could also be connected with iHUB-L1 or Bicom by optical communication (IR). Optional the meter can be equipped with the following communications:
RS485 serial communication with the MODBUS protocol, M-BUS serial communication,
Communication modules enables data transmission and thus connection of the measuring places into the network for the control and management with energy. Instead of communication modules, there can be also tariff input (option) or built-in pulse output (option). Tariff input provides measurement of two tariffs for selected energy registers. Pulse output is sending data to the devices for checking and monitoring consumed energy. On the housing there are only two terminals, thus only one functional extension is possible (serial communication, tariff input, pulse output).
1.3 Main features
Three-phase direct connected DIN-rail mounting meters up to maximum current (I Basic current (Ib) 5 A.  MID approval (option for WM3M6). Class 1 for active energy according to EN 62053-21 and B according to EN 50470-3 . Class 2 for reactive energy according to EN 62053-23. Reference frequency 50 Hz and 60 Hz. Bidirectional energy measurement (import/export). Reference voltage 3x230 V/400 V ().  Voltage operating range (-20 % ... +15 %).  Pulse output according to EN 62053-31 (option). Tariff input (option). RS485 serial communication (option). M-BUS serial communication (option). Display LCD 7+1 digit (100 Wh resolution). Multifunctional front LED. LED constant 1000 imp/kWh. Built-in optical (IR) communication port. Measurement of
o power (active, reactive, apparent) and energy (each phase and total). o Voltage (each phase). o Current (each phase). o Phase to phase voltage. o Phase to phase angle. o Frequency. o Power factor (each phase and total). o Power angle (each phase and total). o Active tariff (option).
3-DIN rail width mounting according to EN 60715. Sealable terminal cover. THD of voltage and THD of current.
max
) 65 A.
CONNECTION
User’s Manual
2 CONNECTION
This chapter deals with the instructions for three-phase electrical energy meter WM3x6 connection. Both the use and connection of the device includes handling with dangerous currents and voltages. Connection shall therefore be performed ONLY a by a qualified person using an appropriate equipment. ISKRA, d.d. does not take any responsibility regarding the use and connection. If any doubt occurs regarding connection and use in the system which device is intended for, please contact a person who is responsible for such installations. In this chapter you will find:
2.1 MOUNTING 5
2.2 ELECTRICAL CONNECTION 6
CONNECTION
User’s Manual
2.1 Mounting
Threee-phase electrical energy meter WM3x6 is intended only for panel mounting. Pluggable connection terminals allow easier installation and quick replacement should that be required. This device is not intended for usage as portable equipment and should be used only as a fixed panel mounted device.
Figure 2: Dimensional drawing and rear connection terminals position
CONNECTION
User’s Manual
2.2 Electrical connection
WARNING
Wrong or incomplete connection of voltage or other terminals can cause non-operation or damage to the device.
Figure 3: Neutral connection of energy meters
Meter is used for direct connection into the four-wire networks. Meter can be equipped with different modules. Pictures below are showing equipped combinations. Recommended installation:
1 Mounting to DIN rail according to DIN EN60715 2 Power contacts:
a. Power contacts capacity 2.5 mm2 – 16 mm2 b. Connection screws M5 c. Max torque 3.5 Nm
3 Auxiliary terminals:
a. Auxiliary terminals contact capacity 1 mm2 – 2.5 mm2 b. Auxiliary terminals screws M3 c. Max torque 1.2 Nm
PLEASE NOTE
Neutral wire must be connected to the meter.
CONNECTION
User’s Manual
Figure 4: Connection
diagram for M-BUS option
Figure 5: Connection diagram for pulse output option
Figure 6: Connection diagram for tariff input option
CONNECTION
User’s Manual
Figure 7: Connection diagram for RS485
Complete WM3x6 system is assembled with three main units and optionally communication unit:
Individual phase measurement unit. Power supply unit (based on configuration). Processing unit (MCU) with IR communication, LED indicator, LCD support and EEPROM. Optionally available different communication units or extension modules (RS485, M-BUS,
TARIFF, PULSE).
2.2.1 Communication connection
For communication with outside world multiple manners are used:
IR communication module using MODBUS protocol is equipped on each meter. It can be used
for setting and testing the meter using WM-USB adapter.
Pulse output (option) module is used for counting number of pulses depending on consumed
energy.
Tariff input (option) module is used to set active tariff. LED diode is used for indication of no-load condition and test output proportional to measured
active energy. It can be also switched to reactive energy for test purpose using IR communication.
RS485 (option) communication module is galvanic isolated form meter. It enables setting the
meter, data readout in the network and tariff setting.
M-BUS (option) communication module is galvanic isolated form meter. It enables setting the
meter, data readout in the network and tariff setting.
Push button is used to select display of desired measured or group of them.
CONNECTION
User’s Manual
Auxiliary terminal
15
16
M-Bus
M-
M+
Pulse output
SO-
SO+
Tariff input
AC2
AC1
RS485*
B
A
*It is recommended to use ferrite bead on communication line RS485 (two turns) to reduce radiated emission.
Auxiliary terminal
15
16
Digital input
X
L (switch)
Digital output
N (latching switch)
X
Table 1: Survey of communication connection
PLEASE NOTE
Check labels on the side of the meter to check what modules are built in.
PLEASE NOTE
The digital input connects the phase via the switch. Through the digital output, the latching switch gets connected to a neutral wire. The switch is only active when the latching switch is off.
FIRST STEPS
10
User’s Manual
3 FIRST STEPS
Programming a three-phase electrical energy meter WM3x6 is very transparent and user friendly. Numerous settings are organized in groups according to their functionality. In this chapter you will find basic programming steps:
3.1 INDIVIDUAL PHASE MEASUREMENT UNIT 11
3.2 DISPLAY OF DEVICE INFO 12
3.3 SOFTWARE FUNCTIONS 13
3.4 LCD USER INTERFACE 14
3.5 LIMITS 24
3.6 FREEZE COUNTERS 29
FIRST STEPS
User’s Manual
11
3.1 Individual phase measurement unit
The microprocessor is used to process the voltage and current samples from the AD converter. It calculates the RMS voltage, RMS current, active and reactive power, U-I phase angle, first harmonic of voltage, first harmonic of current, the DC voltage, DC current, peak to peak voltage, peak to peak current, THD of voltage and THD of current. The internal temperature and supply voltage is measured also. Metering functions are done with the processing unit. There are four different energy counters, which can be configured each to measure one of seven different types of energy. For MID meters, this energy counters are configured only in production. For Non-MID counters they can be also reconfigured during use. These are:
Total Absolute Active Energy (kWh) Total Absolute Reactive Energy (kvarh) Total Absolute Apparent Energy (kVAh) Import Active Energy (kWh) Export Active Energy (kWh) Import Reactive Energy (kvarh) Export Reactive Energy (kvarh)
The energy register is a count of pulses. The number of CE units per pulse is a constant in the meter calibration data. Function add () adds the current interval’s power data to a “remainder” variable. If this variable is larger than one pulse, then the number of pulses is added to the energy register, and remainder variable is decreased by the number of CE units that represent the same amount of energy. Measuring values are averaged within 1 second and displayed on the LCD at the same interval. Parameters which can be shown are:
1 Energy registers:
I. Energy counter 1 (mandatory) II. Energy counter 2 III. Energy counter 3 IV. Energy counter 4
2 Actual measured values:
I. Active Power, total, ph1, ph2, ph3 II. Reactive Power, total, ph1, ph2, ph3 III. Apparent Power total, ph1, ph2, ph3 IV. Power Factor, total, ph1, ph2, ph3 V. Voltages U1, U2, U3 VI. Phase to phase voltages U12, U13, U23 VII. Frequency VIII. Current I1, I2, I3 IX. Power Angle total
Parameter cycling period is settable from 5 seconds to 60 seconds. Cycling period and the definition of parameters for LCD scrolling are configured via RS485 or IR communication.
FIRST STEPS
12
User’s Manual
1 Tariff setting for displayed counter / actual tariff 2 (→) Energy import/active power import
(←) Energy export/active power export 3 kWh display 4 kvarh display 5 Actual Value 6 Info:
VAh display
PF – power factor
VA – apparent power
PA – power angle
Four numbers - Code of MID approved energy
counter.
7 A – currently active counter, nr – non resettable
counter or r – resettable counter 8 W – active power
var – reactive power 9 Inductive or capacitive load 10 Active phase display
Figure 8: Layout of LCD
For MID approved meters only active energy is approved – non resettable counters. The approved active energy counters are coded with the following codes: 1110 – Import Active Power, Tariff 1 1120 – Import Active Power, Tariff 2 1130 – Import Active Power, Tariff 1&2 1210 – Export Active Power, Tariff 1 1220 – Export Active Power, Tariff 2 1230 – Export Active Power, Tariff 1&2 1310 – Total Active Power, Tariff 1 1320 – Total Active Power, Tariff 2 1330 – Total Active Power, Tariff 1&2 Import/export is defined on the basis of sum of phase powers P1 + P2 + P3. If the sum of phase powers is positive, import register counts, if the sum of phase powers is negative, export register counts.
3.2 Display of device info
Energy meters have LCD display with following layout.
Energy counter displays (up to 4 counters) are displaying current energy counter settings (tariff, import/export/total, active/reactive/apparent), its value and actual activity (counting (A)/not counting ( )). Other displays are displaying actual value of measured quantity (P-W, Q-var, S, PF, U, f and I), direction of active energy flow (import / export), reactance (inductive / capacitive) and active tariff (regarding tariff input). Energy registers are displayed with resolution 7 + 1 (kWh, kvarh and kVAh). The meter can be set to Test measuring mode which displays energy registers with better resolution. The test mode is used for test purposes during type testing and test of meter constant during initial verification. After power off meter automatically goes back to normal operation.
FIRST STEPS
User’s Manual
13
Test output is provided as LED with number of impulses proportional to active energy. Pulse constant is 1000 imp/kWh. Optionally the S0 impulse output with the same constant can be used for active energy. Pulse output is defined to be (32 ± 2) ms long according EN 62053-31. Energy measurement is blocked for the currents less than 20 mA. The meter measures actual voltage and frequency. Current and power values are set to zero and there is no energy registration. No load condition is indicated with the LED on. If the supply voltage is too low, the energy measurements are also blocked and communication is disabled. LCD stops to cycle and displays only value of voltage.
3.3 Software functions
Identification – SW version can be read from LCD or using RS485 or IR communication. The check sum (CRC) of complete firmware is calculated and displayed during initialization and later it can be read from LCD Info menu or MODBUS registers. If CRC for code is changed and does not correspond to the initial CRC an ERROR is detected during startup and ERR 2 is shown on the LCD. This is checked after every restart of the meter. MID SW is separated from non MID SW – MID versions are 2.xx as non MID versions are 1.xx. The MID version uses a MID key that prevents the upgrade of software and modification of parameters related to energy measurement. Unlocking the key is possible only at special operating conditions which do not appear on the field. In case the MID meter is not locked the ERR 4 is shown on the LCD. The MID SW version counts the number of times the instrument was MID unlocked and the number could be read from the LCD ( 5.8.1.3 LCD Info menu). Calibration parameters can only be changed in production. They cannot be changed by upgrade or different processes. Special factory software is used to calibrate the parameters for current, voltage, phase angle and linearity. If these parameters were deliberately or accidentally changed, an error type 1 is detected and ERR 1 is shown on the LCD. Calibration parameters are checked every minute for consistency and if error is found, ERR 1 is immediately shown on LCD. It is possible to upgrade the firmware via factory software protocol. This option is available only for WM3-6 (non MID) type of meter. The number of upgrade is counted and it could be read from the LCD ( 5.8.1.3 LCD Info menu). There is an option for a password to protect the instrument. Password has four levels of protection. Meter has possibility of two level user defined password (4 characters from A to Z). Password Level 1 – enables resetting the counters (MID and non MID meters) and tariff setting (non MID meters). Password Level 2 – enables all available settings and resets. If meter password is forgotten, device serial number should be sent to Iskra, d.d. to receive device default password. WM3-6 supports MODBUS protocol. RTU mode is used. RTU messages start and end with a silent interval of at least 3,5 character times (t1-t2-t3-t4 as shown below). Each message is transmitted in a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the frame, the device flushes the incomplete message and assumes that the next byte will be the address field of a new message. Cyclic Redundancy Check (CRC) is used. All parameterization is done via communication with MiQen software (version 2.1 or later). WM3M6 (MID) has limited parameterization. Counter and tariff settings are not enabled. If these settings or any measuring relevant parameters on WM3M6 (MID) were tenaciously or accidentally changed, an error type 1 is detected and ERR 1 is shown on the LCD. Settings are checked every minute for consistency and if error is found, ERR 1 is immediately shown on LCD. Firmware allows also user defined parameterization software using MODBUS protocol with specified MODBUS registers.
FIRST STEPS
14
User’s Manual
3.4 LCD User Interface
The LCD display allows displaying the following measurement values:
1 Four Energy registers:
I. Energy counter 1 (mandatory) II. Energy counter 2 III. Energy counter 3 IV. Energy counter 4
2 Actual measured values:
I. Active Power, total, ph1, ph2, ph3 II. Reactive Power, total, ph1, ph2, ph3 III. Apparent Power total, ph1, ph2, ph3 IV. Power Factor, total, ph1, ph2, ph3 V. Voltages U1, U2, U3 VI. Phase to phase voltages U12, U13, U23 VII. Frequency VIII. Current I1, I2, I3 IX. Power Angle total
The measured values can be scrolled automatically or can be selected by pressing button.
FIRST STEPS
User’s Manual
15
Active power total Active power ph. 1
Active power ph. 2 Active power ph. 3
Current ph. 1 Current ph. 2 Current ph. 3
Energy counters are represented as shown on LCD examples bellow:
Non-MID meters show resettable counters (letter r representing it)
MID meters show non resettable counters (letters nr representing it) Counter 1 shows: Import Active Energy = 6250.3 kWh at Tarif 2 Counter 2 shows: Export Active Energy = 70352.5 kWh at Tarif 1 Counter 3 shows: Total Active Energy = 2369025.3 kWh at both Tarif 1 and 2 Counter 4 shows: Total Active Energy = 105101.5 kWh at Tarif 1 Active power:
Phase currents:
FIRST STEPS
16
User’s Manual
Voltage ph. 1
Voltage ph. 2
Voltage ph. 3
Volt. ph to ph U12 Volt. ph to ph U23 Volt. ph to ph U13
Reactive pow. total Reactive pow. ph 1 Reactive pow. ph 2 Reactive pow. ph 3
Apparent pow. total
Apparent pow. ph 1 Apparent pow. ph 2
Apparent pow. ph 3
Power factor total Power factor ph 1 Power factor ph 2 Power factor ph 3
Power angle total Frequency
Phase Voltages:
Phase to phase Voltages:
Reactive powers:
Apparent powers:
Power factors:
Power angle: Frequency:
FIRST STEPS
User’s Manual
17
3.4.2 Display menu structure
The display menu is entered by holding the push button for more than one second. Blinking of the screen indicates that. Short clicks then move user through the main menu.
By holding the button when positioned on certain screen ( e.g. measure, set, etc…) the sub-menu is entered.
FIRST STEPS
18
User’s Manual
3.4.2.1 Measure sub-menu
When in measure sub-menu, short clicks move user through it, allowing her/him to select a dedicated menu.
FIRST STEPS
User’s Manual
19
3.4.2.1.1 Counter menu
Holding button on any of screens 2.1.1 through 2.1.8 sets this screen as a meter screen. In the Counter menu all counters (resettable and non resettable) are displayed for both – MID and non MID meters
3.4.2.1.2 Power menu
Holding button on any of screens 2.2.1 through 2.2.4 sets this screen as a meter screen.
3.4.2.1.3 Current menu
Holding button on any of screens 2.3.1 through 2.3.3 sets this screen as a meter screen.
3.4.2.1.4 Voltage menu
Holding button on any of screens 2.4.1 through 2.4.6 sets this screen as a meter screen.
FIRST STEPS
20
User’s Manual
3.4.2.1.5 Reactive and apparent power menu
Holding button on any of screens 2.5.1 through 2.5.8 sets this screen as a meter screen.
3.4.2.1.6 Power factor, power angle and frequency menu
Holding button on any of screens 2.6.1 through 2.6.6 sets this screen as a meter screen.
FIRST STEPS
User’s Manual
21
3.4.2.2 Set sub-menu
When in set sub-menu, short clicks move user through it, allowing her/him to select a dedicated menu.
The screens 3.2 to 3.4 appear only in case the actual option is available on the meter.
FIRST STEPS
22
User’s Manual
3.4.2.2.1 Reset counters menu
Holding button on any of screens 3.1.1 through 3.1.5 resets any of counters or all of them respectively.
3.4.2.2.2 RS485 menu
Screen 3.2.1 shows the address of RS 485 communication and screen 3.2.2 shows the baud rate.
3.4.2.2.3 M-bus menu
Screens 3.3.1 shows the primary address of M-bus communication, screen 3.3.2 shows baud rate and screen 3.3.3 shows the secondary address.
3.4.2.2.4 Wi-Fi menu
Screen 3.4.1 shows Wi-Fi status, screen 3.4.2 shows IP address of gateway module and screeen 3.4.3 resets the Wi-Fi.
FIRST STEPS
User’s Manual
23
3.4.2.4 Info sub-menu
When in info sub-menu, short clicks move user through it, allowing her/him to get required information about smart meter.
Screen 4.1 shows the serial number of the smart meter. Screen 4.2 shows the software version present on smart meter. Screen 4.3 shows CRC code and below the number of Firmware upgrades. Screen 4.4 shows CRC of parameters and below the number of times the WM3M6 (MID version) was unlocked. Screen 4.5 shows operating time (days:hour:minute) of WM3-6. Screen 4.6 shows initial LCD screen with all segments on. Screens 4.7 through 4.9 show software versions of each of phase modules.
FIRST STEPS
24
User’s Manual
3.4.3 Set device ModBus address
Non configured devices have the same factory Modbus address set to 33. One of the options for changing the Modbus address is the following. Holding the button for more than 6 seconds, the energy meter will switch to Modbus address configuration mode (you will see the screen below).
During this time, the WM3-6 responds to the 149 address via the ModBus. The device remains in configuration mode until the ModBus address is modified or when 3 minutes pass or with a long press of 1 second to 3 seconds. The purpose of the procedure is to modify Modbus address in case if you want to connect more devices with the same address to the RS485 network.
3.5 Limits
WM3-6 has a built-in limit function which can control the bistable relay using IR communication. The user can set one or two logically combined limits. 1 The following logic operations can be selected:
Limit A Limit B Limit A AND Limit B Limit A OR Limit B
2 Limit function can monitor the following measured values:
Voltages: U1, U2, U3, U12, U23, U13  Currents: I1, I2, I3  Active power: P Reactive Power: Q Apparent Power: A Power Factor: PF Frequency Energy: Counter1, Counter2, Counter3, Counter4
Limits can be set by setting the correct Modbus registers.
, P1, P2, P3
tot
, Q1, Q2, Q3
tot
, A1, A2, A3
tot
, PF1, PF2, PF3
tot
FIRST STEPS
User’s Manual
25
3.5.1 Limit A
User can set the ON state of an output A, when the threshold is reached (any from the above specified measured values can be set as a threshold). Likewise the OFF state can be set, when the same measured value falls below the OFF state threshold. Optionally the delay time can be set (the time between reaching a threshold and setting output A). Figure below (example 1) shows the example using U1 as a limit A and delay time t
delay
.
3.5.2 Limit B
User can set the OFF state of an output B, when the threshold is reached (any from the above specified measured values can be set as a threshold). Likewise the ON state can be set, when the same measured value falls below the ON state threshold. Optionally the delay time can be set (the time between reaching a threshold and setting output B). Figure below (example 2) shows the example using Ptot as a limit B and no delay time.
FIRST STEPS
26
User’s Manual
Limit A AND Limit B
Limit A AND Limit B is a logical operation, which sets the output A AND B ON, when both output A and output B are in ON. Figure below (example 3) shows the example of output A AND B being ON. For clearer picture refer also to output A (example 1) and output B (example 2) figures.
Limit A OR Limit B
Limit A OR Limit B is a logical operation, which sets the output A OR B ON, when any of output A or output B is ON. Figure below (example 4) shows the example when output A OR B is ON. For clearer picture refer also to output A (example 1) and output B (example 2) figures.
Below graphical representation of both output A AND B as well as output A OR B.
FIRST STEPS
User’s Manual
27
Address
Contents
Data
Ind
Values
min
max
P. Level
LIMIT
40187
Limits enabled
T1 0 None 1
Limit 1 2
Limit 2
3
Limit 1 OR Limit 2
4 Limit 1 AND Limit 2
40188
Display notification
T1 0 None 0 2 2 1
Relay ON
2 Relay OFF
40189
Limit 1: Parameter
T1 See OutTypes
40190
Limit 1: Compare relation
T1 0 measurement > limit
0 1 2 1 measurement < limit
40191
Limit 1: ON level
T17
% of parameter value
-300
300 2 40192
Limit 1: OFF level
T17
% of parameter value
-300
300 2 40193
Limit 1: Compare time delay
T1 seconds
0
600 2 40194
40198
Limit 2
see Limit 1
Code
Ident
Parameter
Limit WM1
-8
WM3
-8
Value 100%
1 U U U * *
Un 2 U1
U1
U1 * * Un 3 U2
U2
U2 * * Un 4 U3
U3
U3 * * Un 5 U12
U12
U12 * * Un 6 U23
U23
U23 * * Un 7 U31
U31
U31 * * Un 9 I I I * * In
10
I1
I1
I1 * * In
11
I2
I2
I2 * * In
12
I3
I3
I3 * * In
16 P P
Active Power P
* * *
Pn
17
P1
P1
Active Power Phase L1 (P1)
* *
Pn
18
P2
P2
Active Power Phase L2 (P2)
* *
Pn
19
P3
P3
Active Power Phase L3 (P3)
* *
Pn
20 Q Q
Reactive Power Q
* * *
Pn
21
Q1
Q1
Reactive Power Phase L1 (Q1)
* *
Pn
22
Q2
Q2
Reactive Power Phase L2 (Q2)
* *
Pn
23
Q3
Q3
Reactive Power Phase L3 (Q3)
* *
Pn
24 S S
Apparent Power S
* * *
Pn
25
S1
S1
Apparent Power Phase L1 (S1)
* *
Pn
26
S2
S2
Apparent Power Phase L2 (S2)
* *
Pn
27
S3
S3
Apparent Power Phase L3 (S3)
* *
Pn
28
PF
PF
Power Factor PF
* * *
1
29
PF1
PF1
Power Factor Phase 1 (PF1)
* *
Pn
30
PF2
PF2
Power Factor Phase 2 (PF2)
* *
Pn
Following Modbus registers define Limit function:
OutTypes:
FIRST STEPS
28
User’s Manual
Code
Ident
Parameter
Limit WM1
-8
WM3
-8
Value 100%
31
PF3
PF3
Power Factor Phase 3 (PF3)
* *
Pn
36
PA
PA
PA angle between U and I
* * *
100°
37
PA1
PA1
j1 (angle between U1 and I1)
* * 1 38
PA2
PA2
j2 (angle between U2 and I2)
* * 1 39
PA3
PA3
j3 (angle between U3 and I3)
* * 1 40
A12
fi U12
j12 (angle between U1 and U2)
* *
100°
41
A23
fi U23
j23 (angle between U2 and U3)
* *
100°
42
A31
fi U31
j31 (angle between U3 and U1)
* *
100°
43 f f
Frequency
* * *
100%=Fn+10Hz, 0%=Fn,
-100%=Fn-10Hz
70
E1
E1
Energy Counter 1 (resetable)
* * *
(32-bit value) MOD 20000
71
E2
E2
Energy Counter 2 (resetable)
* * *
(32-bit value) MOD 20000
72
E3
E3
Energy Counter 3 (resetable)
* * *
(32-bit value) MOD 20000
73
E4
E4
Energy Counter 4 (resetable)
* * *
(32-bit value) MOD 20000
Un = Modbus register 30015 In = Modbus register 30017 Pn = Un * In Fn = 55 Hz
FIRST STEPS
User’s Manual
29
3.6 Freeze counters
3.6.1 Meaning
Since WM3-6 energy meter does not support internaly synchronised real-time clock (RTC) for the purpose of simultaneous capture of measurements, the freeze function is implemented. Use is enabled only when the meter is on. Freeze function enables using WM3x6 smart meters for billing or sub-billing purposes and to compare sub-metering data with main energy meter. Reading several hundred serially connected counters can last more than 10 minutes. That is why WM3x6 supports command Freeze counters. Its purpose is to freeze data simultaneously on all devices in the network. The freeze function operation is also performed in case of device power supply failure or device reset.
3.6.2 Set up
To perform the freeze function, the energy meters should be connected to the serial communication RS485 and belonging software which use Modbus registers. The energy meter WM3x6 enables several ways to activate freeze function:
Freeze status register, time to freeze register, auto freeze interval register.
3.6.3 Time to freeze register (41902)
The purpose of the time to freeze register is to freeze all energy meters simultaneously. Set the number of time to freeze register (41902), the value of appropriate time (in seconds) before the time of the freeze and time of the freeze. After an expired time, the freeze command is executed automatically. Due to unreliability in communication, it is recommended that the desired time is sent more than ones, to ensure that freeze is simultaneous on all instruments. The desired time need to be sent in the interval of one minute. For example, if you want that freeze function is executed at 10 am, run the command seven times, starting 7 s before 10 am and repeat it with a one second interval (see the picture below).
All instruments that received one of the commands will freeze at the same time. This is the advantage
of the described register, so it is recommended to use it. It is also possible to individually enter the appropriate time in register 41902 of each instrument.
3.6.4 Auto freeze interval register (41901)
The purpose of the auto freeze interval register is to freeze energy meters in the same time interval, for example, every day. Set the certain auto freeze interval (in minutes). Maximum allowed value is 65535 minutes. Periodic synchronization is activated automatically after the entered interval. If the interval is set to 0, the auto freeze interval function is turned off. The disadvantage of this register is that the time is not appropriate if the meters reset or in case of another failure.
FIRST STEPS
30
User’s Manual
3.6.5 Status register of freeze (41905)
The purpose of the status register is to test the reliability of RS485 communication. Enter the broadcast command of different identification codes between 1 to FFFD in the freeze status register (41905). Repeatedly send a different identification code to the freeze status register (41905) in order to increase the reliability of receiving commands. The reliability of reading different numbers of identification code enables analysis of communication reliability. In the case of 100% reliability of communication, all instruments have the value of the first sent identification code, when reading the status register. After the instrument receives the identification code, it ignores all entries in the status register in the interval of one minute. Send as many different identification codes in a short time interval. For example, send the different identification codes ten times within one second. Use numbers from 1 to FFFD (1 -
65533). For example, first use value 1, then D, AAA and at the end FFFD (see picture below). Please note that you never know if all the meters will freeze, so send as many commands as possible within one minute.
PLEASE NOTE
Please do not use the values 0000, FFFF or FFFE. The 0000 is reserved to start the meter when connected to the power supply. Freeze function is performed. The FFFF is reserved to trigger freezing function automatically (same as time to freeze register 41902). The FFFE is reserved for the auto interval freeze.
Send the command for reading the register, so you can see which identification code has been accepted
by the individual instrument. The server calculates time from a freeze of the device.
3.6.6 Access and interpretation of data
After the execution of the freeze command, the counters are stored into registers 41906 to 41938, which can be read by the master. Register 41906 displays frozen tariff counter and registers 41907 to 41938 display frozen energy counters (1 - 16). The data we read on all devices can this way be compared. Encoded information should be read with Modbus table (see Appendix A). In addition, the time since the last freeze can be checked with time from freeze register (41903, 41904). The purpose of these register is to control if displayed measurements are relevant. The register contains time (in seconds) from the last freeze counters execution.
SETTINGS
User’s Manual
31
4 SETTINGS
A setting structure, which is similar to a file structure in an explorer is displayed in the left part of the MiQen setting window. Available settings of that segment are displayed in the right part by clicking any of the stated parameters. In this chapter you will find detailed description of all WM3x6 features and settings. Chapter is organized in a way to follow settings organisation as in setting software MiQen.
4.1 INTRODUCTION 32
4.2 MIQEN SOFTWARE 32
SETTINGS
32
User’s Manual
4.1 INTRODUCTION
Parameterization can be modified by serial communication (RS485 or Mbus) or by a special WM-USB adapter (size 1 DIN module) and MiQen software version 2.0 or higher.
4.2 MiQen software
MiQen software is a tool for a complete programming and monitoring of ISKRA measuring instruments, connected to a PC via serial communication or by a special WM-USB adapter. A user-friendly interface consists of five segments: devices management (Connection), instrument settings (Settings), real-time measurements (Measurements), data analysis (Analysis), and software upgrading (Upgrades). These segments are easily accessed by means of five icons on the left side. Two editions of MiQen software are available:
Professional edition with full functionality and supports all software functionality. CDKey is
required for the installation.
Standard edition, freeware edition which supports all software functionality except data
analysis.
Figure 9: MiQen programming and monitoring software
SETTINGS
User’s Manual
33
MiQen version 2.1 or higher is required for programming and monitoring WM3x6. Software installation is stored on a CD as a part of consignment or it can be downloaded from https://www.iskra.eu/en/Iskra-
Software/MiQen-Settings-Studio/
PLEASE NOTE
MiQen has very intuitive help system. All functions and settings are described in Info window on the bottom of MiQen window.
4.2.1 Devices management
Figure 10: MiQen Device Management window
Use Scan the network explorer to set and explore the network of the device. Communication parameters of all devices and their addresses in a network can be easily set. Selected devices can be added to the list of My devices.
Set Communication port parameters
Under Communication port current communication parameters are displayed. To change those parameters click on button. A Communication port window opens with different
communication interfaces.
Figure 11: Communication port window
WM3x6 supports only serial communication, so only serial communication parameters can be set.
SETTINGS
34
User’s Manual
Set device Modbus address number
Each device connected to a network has its unique Modbus address number. In order co communicate with that device an appropriate address number should be set.
Factory default Modbus address for all devices is 33. Therefore it is required to change Modbus address number of devices if they are connected in the network so each device will have its unique address number.
Start communicating with a device
Click on REFRESH button and devices information will be displayed. When devices are connected to a network and a certain device is required it is possible to browse a network for devices. For this purpose choose Scan the
network.
4.2.2 Device settings
Multi Register Edit technology assures a simple modification of settings that are organized in a tree structure. Besides transferring settings into the instrument, storing and reading from the setting files is also available.
4.2.2.1 General settings
General settings set the LCD properties and Security settings (passwords). Description and location segment is intended for easier recognition of a certain unit. They are especially used for identification of the device or location on which measurements are performed. LCD Mode defines whether displayed values automatically cycle between different measurands or display only one measurement.
LCD Cycling period sets the period of cycling, valid values from 5 s to 60 s . LCD measurements sets the measurements displayed on the LCD. A user can select them on the drop-
down menu (Counter1 is Preset and is mandatory selected):
Figure 12: Set of optional measurements
SETTINGS
User’s Manual
35
Operating Mode segment is intended for selection between Normal Mode and various test modes.
After reset or power cycle meter starts in Normal Mode.
4.2.2.1.1 Communication
Communication segment is intended for setting the serial communication parameters (M-Bus or RS485).
4.2.2.1.2 Security
A password consists of four letters taken from the British alphabet from A to Z. When setting a password, only the letter being set is visible while the others are covered with *. Settings parameters are divided into three groups regarding security level: PL1 >password level 1, PL2 >password level 2 and BP >a backup password.
PLEASE NOTE
A serial number of device is stated on the label and is also accessible with MiQen software. It can be found on the LCD under info sub-menu as well.
Password-Level 1 >PL1
Password for first level is required. It can be used only if Password – Level 2 is also applied. Available settings:
Energy meters reset (locked on communication port and pushbutton) Active tariff settings
Password-Level 2 >PL2
Password for second level is required. All settings are available.
A Backup Password->BP
A backup password >BP is used if passwords at level 2 >PL2 has been forgotten, and it is different for each device, depending on a serial number of the device. The BP password is available in the user support department in ISKRA d.d., and is entered instead of the password PL1 or/and PL2. Do not forget to state the device serial number when contacting the personnel in ISKRA, d.d.
Password locks time >min
Password lock time is fixed – 1 minute.
Password setting
A password consists of four letters taken from the British alphabet from A to Z.
Password modification
A password is optionally modified; however, PL1 and PL2 password can be modified with access level of password PL2.
Password disabling
A password is disabled by setting the "AAAA" password.
PLEASE NOTE
A factory set password is "AAAA" at both access levels >PL1 and PL2. This password does not limit access.
4.2.2.2 ENERGY
Active tariff
Changing tariff settings is allowed only on NonMID meters. Switching between tariffs is done with a tariff input or by selecting values in a drop-down menu.
SETTINGS
36
User’s Manual
4.2.2.2.1 Counters
Changing counter settings is allowed only on NonMID meters.
There are four pairs of counters, which are user configurable. Each counter setting applies to one resetable and one non-resetable counter. User can set Active, Reactive, Apparent Energy, energy flow direction and tariff. In Custom setting there are additional options for measurment in individual quadrants and energy measurement for individual phases.
Figure 14: MiQen energy counters
WARNING!
In case of modification of energy parameters during operation, the values of energy counters must be recorded to avoid wrong interpretation of readings.
IR Relay operating mode defines how WM3x6 controls external bistable switch BI432 via proprietery IR communication. Available modes are: Not Connected, Manual and Limit control. Preset is Not connected, Manual mode enables control of BI432 via RS485 communication, Limit Control enables WM3x6 internal set limits for switching BI432. For a more precise description of Limits please see chapter Limits on page 46. Resetting counters function is applicable onlyfor four resettable counters. MID approval applies only to parallel non-resettable counters, which can not be reset.
Figure 13: MiQen reset counters
4.2.3 Real-time measurements
Measurements can be seen ONLINE when device is connected to aux. power supply and is communicating with MiQen. When device is not connected it is possible to see OFFLINE measurements simulation. The latter is useful for presentations and visualisation of measurements without presence of actual device. In ONLINE mode all supported measurements and alarms can be seen in real time in a tabelaric or graphical form. All data can be exported to an Access database, Excel worksheets or as a text file.
SETTINGS
User’s Manual
37
Figure 15: Measurements in tabular form
Figure 16: Measurements in graphical form
For further processing of the results of measurements, it is possible to set a recorder ( button) on active device that will record and save selected measurements to MS Excel .csv file format.
Figure 17: Measurements Recorder
SETTINGS
38
User’s Manual
4.2.4 DATA ANALYSIS
PLEASE NOTE
The energy meter WM3x6 do not support data analysis.
4.2.5 MY DEVICES
My devices section enables the personal selection of devices.
4.2.6 Software upgrading
MID version does not support software upgrade. Always use the latest version of software, both MiQen and software in the device. The program automatically informs you about available upgrades (device firmware upgrades and MiQen software upgrades) that can be transferred from the web site and used for upgrading.
PLEASE NOTE
MiQen cannot be used for execution of firmware upgrades of devices. It only informs that new version is available and offers link to download it from the server. Software for execution of firmware upgrades is included in downloaded zip file together with upgrade file, upgrade procedure description and revision history.
PLEASE NOTE
More information about MiQen software can be found in MiQen Help system!
In order to modify instrument settings with MiQen, current parameters must be loaded first. Instrument settings can be acquired via a communication link (serial or USB to IR adapter) or can be loaded off-line from a file on a local disk. Settings are displayed in the MiQen Setting Window - the left part displays a hierarchical tree structure of settings, the right part displays parameter values of the chosen setting group.
PLEASE NOTE
Supported settings and functions depend on the type of device.
TECHNICAL DATA
User’s Manual
39
5 TECHNICAL DATA
In following chapter all technical data regarding operation of a three-phase electrical energy meter is presented.
5.1 ACCURACY 40
5.2 MECHANICAL CHARACTERISTICS OF INPUT 41
5.3 ELECTRICAL CHARACTERISTICS OF INPUT 41
5.4 SAFETY AND AMBIENT CONDITIONS 43
TECHNICAL DATA
40
User’s Manual
Measured values
Accuracy class
Active energy:
class 1 EN 62053-21
class B EN 50470-3
±1.5% from

to 
±1% from  to

Reactive energy:
class 2 EN 62053-23
±2.5% from

to 
±2% from  to

Voltage:
±1% of measured value
Current:
±1% of

from  to

±1% of measured value from

to

Active Power:
±1% of nominal power ( 

) from  to

±1% of measured value from

to

Reactive, Apparent power:
±2% of nominal power from  to

±2% of measured value from

to

Frequency:
±0.5% of measured value
5.1 Accuracy
TECHNICAL DATA
User’s Manual
41
Terminals
Max. conductor cross-sections
Main inputs
Contacts capacity:
2.5  ... 25 (16) 
Connection screws:
M5
Max torque:
3.5 Nm (PZ2)
Length of removed isolation:
10 mm
Optional modules
Contacts capacity:
1 mm2... 2.5 mm
2
Connection screws:
M3
Max torque:
1.2 Nm
Length or removed isolation:
8 mm
Inputs and outputs
Measuring input
Type (connection):
three-phase (4u)
Reference current (

)
5 A
Maximum current (

󰇜:
65 A or 80 A
Minimum current (

):
0.25 A
Transitional current ():
0.5 A
Starting current:
20 mA
Power consumption at

0.1 VA
Nominal voltage ():
230 V (-20 - +15)%
Power consumption per phase at :
< 8 VA
Nominal frequency ():
50 Hz and 60 Hz
Minimum measuring time:
10 s
5.2 Mechanical characteristics of input
Rail mounting according DIN EN 60715.
5.3 Electrical characteristics of input
TECHNICAL DATA
42
User’s Manual
Pulse output (option)
Pulse rate:
1000 imp/kWh
Pulse duration:
32 ± 2 ms
Rated voltage DC:
27 V max
Switched current
27 mA max
Standard:
EN 62053-31 (A&B)
M-BUS Serial communication (option)
Type:
M-BUS
Speed:
300 bit/s to 9600 bit/s (default 2400 bit/s)
Protocol:
M-BUS
Primary address:
0 – (default)
RS485 Serial communication (option)
Type:
RS485
Speed:
1200 bit/s to 19200 bit/s (default 19200 bit/s)
Frame:
8, N, 2
Protocol:
MODBUS RTU
Address:
33 – (default)
Optical communication
Type:
IR
Connection:
via WM-USB adapter
Speed:
19200 bit/s
Frame:
8, N, 2
Protocol:
MODBUS RTU
Address:
33
Remark:
All settings are fixed
Tariff input (option)
Rated voltage:
230 V (+15 %- 20 %)
Input resistance:
450 kOhm
Rated voltage:
230 V (+15 %- 20 %)
Maximum load current:
50 mA
TECHNICAL DATA
User’s Manual
43
Dust/water protection:
IP50 (For IP51 it should be installed in appropriate cabinet.)
Operating temperature:
-25 °C - +55 °C (non-condensig humudity)
Storage temperature:
-40 °C - + 70 °C
Enclosure:
self extinguish, complying UL94-V
Indoor meter:
Yes
Degree of pollution:
2
Protection class:
II
Standard:
IEC 62052-31
Mechanical environment:
M1
Electromagnetic environment:
E2
Humidity:
non condensing
Weight (with packaging):
216 g (230 g)
Installation:
DIN Rail 35 mm
Dimensions (W x H x D):
53,6 mm x 84 mm x 64 mm (69 mm)
Package dimensions (W x H x D):
57 mm x 93 mm x 85 mm
Colour:
RAL 7035
5.4 Safety and ambient conditions
According to standards for indoor active energy meters. Temperature and climatic condition according to EN 62052-11.
TECHNICAL DATA
44
User’s Manual
Construction
Appearance
Dimensions
All dimensions are in mm
5.5 EU DIRECTIVES CONFORMITY
5.5.1 WM3M6 MID certified meters
MID approval applies to non-resettable active energy counters. EU Directive on Measuring Instruments 2014/32/EU EU Directive on EMC 2014/30/EU EU Directive on Low Voltage 2014/35/EU EU Directive WEEE 2002/96/EC EU RED Directive 2014/53/EU
5.6 Dimensions
5.6.1 Dimensional drawing
ABBREVIATION/GLOSSARY
User’s Manual
45
Term
Explanation
MODBUS / DNP3
Industrial protocol for data transmission
MiQen
Setting Software for ISKRA instruments
PI
Pulse input module
AC
Alternating quantity
IR
Infrared (optical) communication
Pt1000
Temperature sensor
RMS
Root Mean Square
PO
Pulse output
PA
Power angle (between current and voltage)
PF
Power factor
THD
Total harmonic distortion
6 ABBREVIATION/GLOSSARY
Abbreviations are explained within the text where they appear the first time. Most common abbreviations and expressions are explained in the following table:
List of common abbreviations and expressions
APPENDICES
46
User’s Manual
Device address
Function Code
nx8 bit data bytes
Error check
Device address
Function Code
nx8 bit data bytes
Error check
7 APPENDICES
7.1 APPENDIX A: MODBUS communication protocol
Modbus protocol enables operation of device on Modbus networks. For WM3-6\WM3M6 with serial communication the Modbus protocol enables multi drop communication via RS485 communication. Modbus protocol is a widely supported open interconnect originally designed by Modicon. The memory reference for input and holding registers is 30000 and 40000 respectively. Communication operates on a master-slave basis where only one device (the master) can initiate transactions called ‘Requests’. The other devices (slaves) respond by supplying the requested data to the master. This is called the ‘Request - Response Cycle’. The master could send the MODBUS request to the slaves in two modes:
- Unicast mode, where the master sends the request to an individual slave. It returns a replay to the master after the request is
received and processed. A MODBUS transaction consists of two messages. Each slave should have an unique address.
- Broadcast mode, where the master sends a request to all slaves and an answer is never followed. All devices should accept the
broadcast request function. The Modbus address 0 is reserved to identify the broadcast request.
Master to Slave Request
Slave to Master Response
Request
This Master to Slave transaction takes the form:
Device address: master addressing a slave (Address 0 is used for the broadcast address, which all slave devices recognize.) Function code e.g. 03 asks the slave to read its registers and respond with their contents. Data bytes: tells the slave which register to start at and how many registers to read.
Response
This Slave to Master transaction takes the form:
Device address: to let the master know which slave is responding. Function code: this is an echo of the request function code. Data bytes: contains the data collected from the slave.
APPENDICES
User’s Manual
47
Starting Register
Register Count
CRC
Slave Address
Function Code
HI LO
HI LO
LO HI
21
04
00 6B
00 02
Register Data
CRC
Slave Address
Function Code
Byte Count
HI LO HI LO
LO HI
21
04
04
FE 00 59 96
Address
Contents
Data
Ind
Values / Dependencies
Input Registers
READ ONLY INFO
30000
Device group
T1
4
WM
30001
30008
Model Number
T_Str16
WM3-6 Energy
30009
30012
Serial Number
T_Str8
WM######
30013
Software Reference
T1
100=1.00
30014
Hardware Reference
T_Str2
A (B,C,D…)
30015
Calibration voltage
T4
230 V
30017
Calibration current
T4
65 A
30019
Accuracy class
T17
100=1.0
30020
MiNet Flag
T1
0 30024
COM1: Communication
T1
2
RS485
Type 9
Infra-red
13
M-BUS
30029
I/O 1
T1
0
No I/O
5
Tariff Input
10
Digital input
30030
I/O 2
T1
0
No I/O
12
Pulse Output (SO)
26
Load control Output
30047
30048
Calibration Time Stamp
T10
30079
MID unlock counter
T1
Request Frame
Response Frame
Request- response cycle example
Address number of slave: 21 Function code: 04 30000
Starting register HI…LO: 00…6B
REGISTER TABLE FOR THE ACTUAL MEASUREMENTS.)
Register count HI…LO: 00…02
Data type: T5 (Unsigned Measurement (32 bit) – see table of DATA types decoding) Register data: FE 00 59 74
(16)
(16)
(16)
2
107
(10)
+30000
(10)
(10)
(Two registers: 30107 and 30108)
22934   V = 229,34 V
= 30107
(Meaning that actual measurement is U1. For further informations see
(10)
REGISTER TABLE FOR THE ACTUAL MEASUREMENTS
The tables below represent the complete set of MODBUS register map.
SETTINGS
APPENDICES
48
User’s Manual
Address
Contents
Data
Ind
Values / Dependencies
Input Registers
30080
FW upgrade counter
T1
30090
phase module 0 CheckSum
T1
30091
phase module 1 CheckSum
T1
30092
phase module 2 CheckSum
T1
30093
phase module 0 SW reference
T1
100=1,0
30094
phase module 1 SW reference
T1
100=1,0
30095
phase module 2 SW reference
T1
100=1,0
30096
CheckSum Parameters
T1
30097
CheckSum Firmware
T1
30098
Active Communication Port
T1
0
IR
1
COM1
30099
Modbus Max. Register Read at
Once
T1
30101 Phase valid measurement
T1
Bit 0
Invalid measurement phase 1
Bit 1
Invalid measurement phase 2
Bit 2
Invalid measurement phase 3
APPENDICES
User’s Manual
49
Address
Contents
Data
Ind
Values / Dependencies
Input Registers
ACTUAL MEASUREMENTS
30105
30106
Frequency
T5
30107
30108
U1
T5
30109
30110
U2
T5
30111
30112
U3
T5
30115
angle between U1 and U2
T17
30116
angle between U2 and U3
T17
30117
angle between U3 and U1
T17
30126
30127
I1
T5
30128
30129
I2
T5
30130
30131
I3
T5
30140
30141
Active Power Total (Pt)
T6
30142
30143
Active Power Phase L1(P1)
T6
30144
30145
Active Power Phase L2(P2)
T6
30146
30147
Active Power Phase L3(P3)
T6
30148
30149
Reactive Power Total (Qt)
T6
30150
30151
Reactive Power Ph L1 (Q1)
T6
30152
30153
Reactive Power Ph L2 (Q2)
T6
30154
30155
Reactive Power Ph L3 (Q3)
T6
30156
30157
Apparent Power Total (St)
T5
30158
30159
Apparent Power Ph L1 (S1)
T5
30160
30161
Apparent Power Ph L2 (S2)
T5
30162
30163
Apparent Power Ph L3 (S3)
T5
30164
30165
Power Factor Total (PFt)
T7
30166
30167
Power Factor Ph 1 (PF1)
T7
30168
30169
Power Factor Ph 2 (PF2)
T7
30170
30171
Power Factor Ph 3 (PF3)
T7
30172
Power Angle Total(atan2(Pt,Qt))
T17
30173
angle between U1 and I1
T17
APPENDICES
50
User’s Manual
30174
angle between U2 and I2
T17
30175
angle between U3 and I3
T17
30182 U1 THD%
T16
30183 U2 THD%
T16
30184 U3 THD%
T16
30188 I1 THD%
T16
30189 I2 THD%
T16
30190 I3 THD%
T16
30197
External relay status
T1
0
Off
1
On
250
Comm. Error
255
Not connected
30198
Load control output status
T1
0
Off
1
On
30199
Digital input status
T1
0
Off
1
On
30200
Limit control output status
T1
0
Off 1 On
255
Disabled
30201
Button status
T1
0
Not pressed
1
pressed
APPENDICES
User’s Manual
51
Address
Contents
Data
Ind
Values / Dependencies
Input Registers
ENERGY
30400
Error register
T1
0
No Error
Bit 0
Error Parameter CRC
Bit 1
Error Firmware CRC
Bit 2
MID version is not locked
30401
Energy Counter 1 Exponent (resettable)
T2
30402
Energy Counter 2 Exponent (resettable)
T2
30403
Energy Counter 3 Exponent (resettable)
T2
30404
Energy Counter 4 Exponent (resettable)
T2
30405
Current Active Tariff
T1
30406
30407
Energy Counter 1 (resettable)
T3
30408
30409
Energy Counter 2 (resettable)
T3
30410
30411
Energy Counter 3 (resettable)
T3
30412
30413
Energy Counter 4 (resettable)
T3
30414
Energy Counter 1 Exponent (Non-reset)
T2
30415
Energy Counter 2 Exponent (Non-reset)
T2
30416
Energy Counter 3 Exponent (Non-reset)
T2
30417
Energy Counter 4 Exponent (Non-reset)
T2
30418
30419
Energy Counter 1 (Non-reset)
T3
30420
30421
Energy Counter 2 (Non-reset)
T3
30422
30423
Energy Counter 3 (Non-reset)
T3
30424
30425
Energy Counter 4 (Non-reset)
T3
30426
30427
1000 x Energy Counter 1 (res.)
T3
30428
30429
1000 x Energy Counter 2 (res.)
T3
30430
30431
1000 x Energy Counter 3 (res.)
T3
30432
30433
1000 x Energy Counter 4 (res.)
T3
30434
30435
1000 x Energy Counter 1 (Non -res.)
T3
30436
30437
1000 x Energy Counter 1 (Non -res.)
T3
30438
30439
1000 x Energy Counter 1 (Non -res.)
T3
30440
30441
1000 x Energy Counter 1 (Non -res.)
T3
34999
35000
Run time
T3
seconds
APPENDICES
52
User’s Manual
Address
Contents
Data
Ind
Values
min
max
P.
Level
RAM logger
36000
Measurement parameter
T1 See OutTypes
36001
Time interval
T1 minutes
36002
Number of valid results
T1
36003
Time stamp of last result
T2 minutes since midnight (<0 if no time)
36004
36131
Logger table (newest to oldest)
T17 Normalised values
ACTUAL MEASUREMENTS
SYSTEM COMMANDS
40001
40002
User Password (L1, L2)
T_Str4
A…Z
Password to attempt user access level upgrade
0
40003
40005
Factory Password (FAC)
T_Str6
A…Z
Password to attempt factory access level upgrade
0
40006
40007
Level 1 - User password
T_Str4
A…Z 2
40008
40009
Level 2 - User password
T_Str4
A…Z 2
40010
Active Access Level
T1
0
Full protection
0 0 0
1
Access up to level 1 user password
2
Access up to level 2 user password
3
Access up to level 2 (backup pass.)
4
Factory access level
40011
Manual password activation
T1
1
Lock instrument
0
40012
Operator Command Register
T1
1
Save Settings
1
2
Abort Settings
3
Restart Instrument
APPENDICES
User’s Manual
53
Address
Contents
Data
Ind
Values
min
max
P.
Level
40013
Reset command register 1
T1
Bit-0
Reset counter 1
1
Bit-1
Reset counter 2
Bit-2
Reset counter 3
Bit-3
Reset counter 4
Bit-4
Reset alarm output relay 2
40015
IR external relay command action
T1
0
Off
0 1 0
1
On
40016
Load control Output state
0
Off
0 1 0
1
On
40017
Digital input function
0
1
Tariff input
2
IR relay push button
3
IR relay switch
4
External relay push button
5
External relay switch
40101
40120
Description
T_Str16
2
40121
40140
Location
T_Str16
2
APPENDICES
54
User’s Manual
Address
Contents
Data
Ind
Values
min
max
P.
Level
40151
CT connection
T1
2
Reverse Energy flow direction (Fixed)
2
2
2
40173
LCD Mode
T1
0
Manual 0 1
2
1 Cycling
40174
LCD cycling period
T1
Seconds
5
60
2
40183
WM3 - LCD parameters
T1
Bit 0
Active Power P1
1
65535
2
Bit 1
Active Power P2
Bit 2
Active Power P3
Bit 3
Reactive Power Q1
Bit 4
Reactive Power Q2
Bit 5
Reactive Power Q3
Bit 6
Apparent Power S1
Bit 7
Apparent Power S2
Bit 8
Apparent Power S3
Bit 9
Power Factor PF1
Bit 10
Power Factor PF2
Bit 11
Power Factor PF3
Bit 12
Voltage U12
Bit 13
Voltage U23
Bit 14
Voltage U31
40184
LCD parameters
T1
Bit 0
Counter 1 (Always)
1
65535
2
Bit 1
Counter 2
Bit 2
Counter 3
Bit 3
Counter 4
Bit 4
Active Power Total (Pt)
Bit 5
Reactive Power Total (Qt)
Bit 6
Apparent Power Total (St)
Bit 7
Power Factor Total (PFt)
Bit 8
Power Angle total(atan2(Pt,Qt))
Bit 9
Voltage ph.1
Bit 10
Voltage ph.2
Bit 11
Voltage ph.3
Bit 12
Frequency
40184
LCD parameters
T1
Bit 13
Current ph.1
Bit 14
Current ph.2
Bit 15
Current ph.3
40185
Operation mode
0 Normal mode
0
1
0
1 Test mode P-Fast
2
Test mode P –Fast (Counter only)
4 Test mode Q
5 Test mode Q - Fast
6
Test mode Q – Fast (Counter only)
40186
External relay operating mode
T1
0
Not connected
0
1
2
APPENDICES
User’s Manual
55
1 Manual
40187
Limits enabled
0 None 0 4
2
1 Limit 1
2 Limit 2
3 Limit 1 OR Limit 2
4 Limit 1 AND Limit 2
40188
Display notification
0 None 0 2 2
1 Relay ON
2 Relay OFF
Address
Contents
Data
Ind
Values
min
max
P.
Level
LIMIT
40189
Limit 1: Parameter
T1
See OutTypes
40190
Limit 1: Compare relation
T1
0
measurement > limit
0 1 2
1
measurement < limit
40191
Limit 1: ON level
T17
% of parameter value
-300
300
2
40192
Limit 1: OFF level
T17
% of parameter value
-300
300
2
40193
Limit 1: Compare time delay
T1
seconds
0
600
2
40194
40198
Limit 2
see Limit 1
COMMUNICATION
40202
Port 1: Device Address (Modbus)
T1
1
247
2
40203
Port 1: Baud Rate
T1
0
Baud rate 1200
1
7
2
1
Baud rate 2400
2
Baud rate 4800
3
Baud rate 9600
4
Baud rate 19200
40204
Port 1: Stop Bit
T1
0
1 Stop bit
0
1 2
1
2 Stop bits
40205
Port 1: Parity
T1
0
No parity
0
2
2
1
Odd parity
2
Even parity
40206
Port 1: Data Bits
T1
0
8 bits 0 0
2
WIFI adapter
42750
WIFI LCD menu time enabled
T1 Seconds 42751
WIFI status
T1 WIFI status
42752
42753
WIFI IP
T3 example:
129.168.001.255
42754
WIFI command
T1 reset WIFI
42755
42760
Reserved for WIFI numbers
T1
42761
42770
WIFI status text 1
T_Str20
42771
42780
WIFI status text 2
T_Str20
APPENDICES
56
User’s Manual
Address
Contents
Data
Ind
Values
min
max
P.
Level
ENERGY
40401
Active Tariff
T1
0
Tariff input
0 2 1
1..2
Tariff 1..2
40421
Energy Counter 1 Parameter
T1
1
Active Power
1
15
2
2 Reactive Power
3 Apparent Power
40422
Energy Counter 1 Configuration
T1
Bit-0
Quadrant I Enabled
0
63
2
Bit-1
Quadrant II Enabled
Bit-2
Quadrant III Enabled
Bit-3
Quadrant IIII Enabled
Bit-4
Absolute Value
Bit-5
Invert Value
40424
Energy Counter 1 Tarif Selector
T1
Bit-0
Tarif 1 Enabled
0
15
2
Bit-1
Tarif 2 Enabled
40425
40430
Reserved
40431
Energy Cnt 2 Parameter
T1
See Energy Counter 1 Parameter
40432
Energy Cnt 2 Configuration
T1
see Energy Counter 1 Configuration
0
63*
2
40434
Energy Cnt 2 Tarif Selector
T1
see Energy Counter 1 Tarif Selector
0 3 2
40441
Energy Cnt 3 Parameter
T1
see Energy Counter 2 Parameter
0
3*
2
40442
Energy Cnt 3 Configuration
T1
see Energy Counter 1 Configuration
0
63*
2
40444
Energy Cnt 3 Tarif Selector
T1
see Energy Counter 1 Tarif Selector
0 3 2
40451
Energy Cnt 4 Parameter
T1
see Energy Counter 2 Parameter
0
3*
2
40452
Energy Cnt 4 Configuration
T1
see Energy Counter 1 Configuration
0
63*
2
40454
Energy Counter 4 Tarif Selector
T1
see Energy Counter 1 Tarif Selector
0 3 2
APPENDICES
User’s Manual
57
Counter freeze
41901
Auto freeze interval [minutes]
T1
41902
time to freeze [s]
T1
41903
41904
time from freeze [s]
T3u
41905
Freeze status
T1
41906
Current Active Tariff
T1
41907
41908
Energy Counter 1 (resetable)
T3
41909
41910
Energy Counter 2 (resetable)
T3
41911
41912
Energy Counter 3 (resetable)
T3
41913
41914
Energy Counter 4 (resetable)
T3
41915
41916
Energy Counter 1 (Non-reset)
T3
41917
41918
Energy Counter 2 (Non-reset)
T3
41919
41920
Energy Counter 3 (Non-reset)
T3
41921
41922
Energy Counter 4 (Non-reset)
T3
41923
41924
1000x Energy Counter 1 (resetable)
T3
41925
41926
1000x Energy Counter 2 (resetable)
T3
41927
41928
1000x Energy Counter 3 (resetable)
T3
41929
41930
1000x Energy Counter 4 (resetable)
T3
41931
41932
1000x Energy Counter 1 (Non-reset)
T3
41933
41934
1000x Energy Counter 2 (Non-reset)
T3
41935
41936
1000x Energy Counter 3 (Non-reset)
T3
41937
41938
1000x Energy Counter 4 (Non-reset)
T3
Code DEC
Code HEX
Function
References
3
03
to read from holding registers
(4XXXX memory references)
4
04
to read from input registers
(3XXXX memory references)
6
06
to write to a single holding register
(4XXXX memory references)
16
10
to write to one or more holding register
(4XXXX memory references)
Type
Value / Bit Mask
Description
T1 Unsigned Value (16 bit)
Example: 12345 stored as 12345 = 3039
(16)
T2 Signed Value (16 bit)
Example: -12345 stored as -12345 = CFC7
(16)
T3 Signed Long Value (32 bit)
Example: 123456789 stored as 123456789 = 075B CD 15
(16)
T4 Short Unsigned float (16 bit)
bits # 15..14
Decade Exponent(Unsigned 2 bit)
bits # 13..00
Binary Unsigned Value (14 bit)
Example: 10000*102 stored as A710
(16)
SUPPORTED FUNCTIONS AND USAGE
DATA TYPES DECODING
Registers defined in the Modbus database will define data as one of the data types described in the following table:
APPENDICES
58
User’s Manual
Type
Value / Bit Mask
Description
T5 Unsigned Measurement (32 bit)
bits # 31..24
Decade Exponent(Signed 8 bit)
bits # 23..00
Binary Unsigned Value (24 bit)
Example: 123456*10-3 stored as FD01 E240
(16)
T6 Signed Measurement (32 bit)
bits # 31..24
Decade Exponent (Signed 8 bit)
bits # 23..00
Binary Signed value (24 bit)
Example: - 123456*10-3 stored as FDFE 1DC0
(16)
T7 Power Factor (32 bit)
bits # 31..24
Sign: Import/Export (00/FF)
bits # 23..16
Sign: Inductive/Capacitive (00/FF)
bits # 15..00
Unsigned Value (16 bit), 4 decimal places
Example: 0.9876 CAP stored as 00FF 2694
(16)
T8 Time stamp (32 bit)
bits # 31..24
Minutes 00 - 59 (BCD)
bits # 23..16
Hours 00 - 23 (BCD)
bits # 15..08
Day of month 01 - 31 (BCD)
bits # 07..00
Month of year 01 - 12 (BCD)
Example: 15:42, 1. SEP stored as 4215 0109
(16)
T9 Time (32 bit)
bits # 31..24
1/100s 00 - 99 (BCD)
bits # 23..16
Seconds 00 - 59 (BCD)
bits # 15..08
Minutes 00 - 59 (BCD)
bits # 07..00
Hours 00 - 24 (BCD)
Example: 15:42:03.75 stored as 7503 4215
(16)
T10 Date (32 bit)
bits # 31..24
Day of month 01 - 31 (BCD)
bits # 23..16
Month of year 01 - 12 (BCD)
bits # 15..00
Year (unsigned integer) 1998..4095
Example: 10, SEP 2000 stored as 1009 07D0
(16)
T_Str4
Text String 4 characters
(T11)
Two characters per 16 bit register
T_Str6
Text String 6 characters
(T12)
Two charcters per 16 bit register
T_Str8
Text String 8 characters
Two characters per 16 bit register.
T_Str16
Text String 16 characters
Two characters per 16 bit register.
T_Str20
Text String 20 characters
Two characters per 16 bit register.
T16 Unsigned Value (16 bit), 2 decimal places
Example: 123.45 stored as 123.45 = 3039
(16)
T17 Signed Value (16 bit), 2 decimal places
Example: -123.45 stored as -123.45 = CFC7
(16)
APPENDICES
User’s Manual
59
Type
Value / Bit Mask
Description
T_Time
Time and Date (64 bit)
bits # 63..56
1/100s 00 - 99 (BCD)
bits # 55..48
Seconds 00 - 59 (BCD)
bits # 47..40
Minutes 00 - 59 (BCD)
bits # 39..32
Hours 00 - 24 (BCD)
bits # 31..24
Day of month 01 - 31 (BCD)
bits # 23..16
Month of year 01 - 12 (BCD)
bits # 15..00
Year (unsigned integer) 1998..4095
Example: 15:42:03.75, 10. SEP 2000 stored as 7503 4215 1009 07D0
(16)
T_TimeIEC
Time and Date (64 bit) = IEC870-5-4 "Binary Time 2a"
bits # 63..55
Reserved
bits # 54..48
Years (0 .. 99)
bits # 47..44
Reserved
bits # 43..40
Months (1 .. 12)
bits # 39..37
Day of Week (1 .. 7)
bits # 36..32
Day of Month (1 .. 31)
bit # 31
Summer Time (0 .. 1): Summer time (1), Standard time (0)
bits # 30..29
Reserved
bits # 28..24
Hours (0 .. 23)
bit # 23
Invalid (0 .. 1): Invalid (1), Valid (0)
bit # 22
Reserved
bits # 21..16
Minutes (0 .. 59)
bits # 15..00
Miliseconds (0 .. 59999)
Example: 15:42, 1. SEP stored as 4215 0109
(16)
T_Data
Record Data
Size and SubTypes depends on the Actual Memory Part
T_Str40
Text String 40 characters
Two characters per 16 bit register.
T_float
IEEE 754 Floating-Point Single Precision Value (32 bit)
bits # 31
Sign Bit (1 bit)
bits # 30..23
Exponent Field (8 bit)
bits # 22..0
Significand (23 bit)
Example: 123.45 stored as 123.45000 = 42F6 E666
(16)
T9A Time (16 bit)
bits # 15..08
Minutes 00 - 59 (BCD)
bits # 07..00
Hours 00 - 24 (BCD)
Example: 15:42 stored as 4215
(16)
T10A
Date (16 bit)
bits # 15..08
Day of month 00 - 31 (BCD)
bits # 07..00
Month of year 00 - 12 (BCD)
Example: 30, SEP stored as 3009
(16)
T18 Signed Value (16 bit), 4 decimal places
Example: -0.2345 stored as -2345 = F6D7
(16)
T_DSK
HEX value 16 bytes
APPENDICES
60
User’s Manual
7.2 APPENDIX B: M-BUS
The M-BUS interface fully complies with M-BUS European standard EN13757-2. The entire communication is ensured with 8 Data Bits, Even Parity, 1 Stop Bit and a Baud Rate from 300 to 9600 Bauds.
Communication settings
Default communication settings are: 2400, 8, E, 1 primary address 0 and secondary address is set to serial number of device.
Initialize M-Bus (SNK_NKE)
This Short Telegram initializes the M-BUS WM3-6. The M-BUS WM3-6 confirms correct receipt by Single Character Acknowledgement (ACK = E5). If the telegram was not correctly received the WM3-6 will not send an acknowledgement.
Select M-BUS WM3-6 Using Secondary Address (SND_UD)
This Telegram enables to select M-BUS WM3-6. The M-BUS WM3-6 confirms the correct receipt by ACK. If the telegram has not been correctly received the M-BUS WM3-6 will not send an Acknowledgement. After issue of the Single Character Acknowledgement the M-BUS WM3-6 is ready to transmit the entire Read-out Data within 3 seconds from receiving the Telegram „Transmit Read-out Data“. At the end of 3 seconds the M-BUS WM3-6 will switch back to normal mode.
Transmit Read-out Data via Primary/Secondary Address (REQ_UD2)
This Short Telegram enables to select the M-BUS WM3-6 and to command it to transmit the Read-out Data parameterized. The M-BUS WM3­6 confirms correct receipt by transmitting of the Read-out Data. If the Short Telegram has not been received correctly; no Data will be transmitted by the M-BUS WM3-6. The Read-out Data are sent within 35 ms – 75 ms from receipt of the Short Telegram by the M-BUS Meter (fom more infomations see section M-Bus telegrams).
Set Baud Rate via Primary/Secondary Address (SND_UD)
This telegram enables to set the desired Baud Rate. The M-BUS WM3-6 confirms the correct receipt by ACK. If the telegram was not received correctly the M-BUS WM3-6 does not send an Acknowledgement. The (ACK) is sent by the M-BUS WM3-6 in the Old Baud Rate. As soon as ACK is transmitted the M-BUS Meter switches to the baud rate newly parameterized. If the WM3-6 now does not receive a new Telegram under the new baud rate within a period of 30 seconds – 40 seconds, it automatically switches back to the old baud rate. This is apt to prevent that a faulty setting of the baud rate may interrupt communication.
Set Primary Address via Primary/Secondary Address (SND_UD)
This Telegram enables to set a new Primary Address. The M-BUS WM3-6 confirms the correct receipt by ACK. If the telegram has not been correctly received the M-BUS WM3-6 will not send an Acknowledgement.
Set Secondary Address via Primary/Secondary Address (SND_UD)
This Telegram enables to set a new Secondary Address. The M-BUS WM3-6 confirms the correct receipt by ACK. If the telegram has not been correctly received the M-BUS WM3-6 will not send an Acknowledgement. Secondary Address (UD) consists of: Identification Number: 00000000 – 99999999 8-digit Secondary Address number Manufacturer’s Code: 73 26 2 Byte Company Constant (Iskra = “73 26”) Version Number: 01 – FF 1 Byte Medium: 02 1 Byte Constant Electricit
Reset, Restart M-BUS MC350 via Primary/Secondary Address (SND_UD)
This Telegram reset/restarts M-BUS MC350. The M-BUS WM3-6 confirms correct receipt by ACK. If the telegram was not correctly received the M-BUS WM3-6 will not send an acknowledgement.
APPENDICES
User’s Manual
61
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA
xx.xx.xx.xx
T0:
04
none
none T1:
84
10
none T2:
84
20
none
A+: 05
None
none
none
*10
5-3
Wh
A-: 85
3C
none
none
*10
5-3
Wh
R+: FB
82
75
none
*10
5-3
varh
R-: FB
82
F5
3C
*10
5-3
varh
App: FB
84
75
none
*10
5-3
VAh
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA
01
FF
01
xx
DIF
DIFE
DIFE
VIF
VIFE
DATA
04
2A xx.xx.xx.xx
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA 04 FB
97
72
xx.xx.xx.xx
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA
04 FB
B4
75
xx.xx.xx.xx
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA 04
A8
B4
35
xx.xx.xx.xx
DIF
DIFE
VIF
VIFE
VIFE
DATA
04 FD
59
xx.xx.xx.xx
DIF
DIFE
DIFE
VIF
VIFE
VIFE
VIFE
DATA 04
FB
2C
xx.xx.xx.xx
M-Bus Telegram
Total Energy counters 0, 1, 2, 3
Energy counters could represent: +/- active energy, +/-reactive energy or apparent energy and one of 4-th tariff.
Active Tariff number
Tariff number in progress (1 to 4)
DATA: value represent as 8-bit integer
Active Power Total Pt (W)
Active power total in 32 bit x 10
(2-3)
W
Active Power Total (kvar)
Reactive power total in 32bit x10
(2-3)
var
Instant Apparent Power Total (VA)
Apparent power total in 32 bit x 10
n - 0…7
(5-6)
VA
Power Factor: -: leading et +: lagging: PF
Power factor as 32-bit integer * 10-3
Unit : W/V/A
Current Total (A)
Total current as 32 bit x 10
(9-12)
A
System frequency (Hz/1000)
Contains the line frequency 32-bit integer in mHz.
APPENDICES
62
User’s Manual
DIF
DIFE
DIFE
VIF
VIFE
VIFE
DATA 04
xx.xx.xx.xx
P1: AA
FC
01 P2: AA
FC
02 P3: AA
FC
03
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA
04
xx.xx.xx.xx
I1:
FD
D9
FC
01 I2:
FD
D9
FC
02 I3:
FD
D9
FC
03
DIF
DIFE
VIF
VIFE
VIFE
VIFE
DATA 04
xx.xx.xx.xx
U1:
FD
C7
FC
01 U2:
FD
C7
FC
02 U3:
FD
C7
FC
03 U12:
FD
C7
FC
05 U23:
FD
C7
FC
06 U31:
FD
C7
FC
07
Active Power in Phase 1, 2, 3 (W)
Active power in 32bit x 10
(2-3)
W
Current in Phase 1, 2, 3, Neutral (A)
Phase current as 32 bit x 10
(9-12)
A
Voltages (V)
Voltage as 32 bit x 10
(7-9)
V
––
• Published by Iskra, d. d. • Subject to change without notice • Version 1.01 November 2018 EN K 22.433.920
Loading...