1. General information
Keep the documents in a safe place and hand them over to
the new facility drive if you transfer the system.
Symbols used in these instructions
REMARK A remark draws attention to important
information which may make work
easier for you.
NOTE A note warns of potential damage
to the device and explains how it can
be avoided.
ATTENTION This symbol points out dangers which
may result in personal injury or even
death.
Unless specified otherwise,
all dimensions are given in mm.
“Translation of the original instructions”
2ISEO
IS 9100
—
2. Safety
This documentation contains important instructions for
installation and safe operation. Read these instructions
carefully before beginning the installation.
Follow all of the enclosed instructions to guarantee your
safety.
Incorrect installation may result in serious injuries.
The use of control elements, settings or procedures which
are not described in this documentation may cause electric
shock, danger due to electric voltages/currents and/or danger
due to mechanical processes.
2.1 Intended Use
IS 9100 is electromechanical swing door drive and is used
exclusively for opening and closing interior swing doors with
a door leaf weight of max. 160 kg.
Before installing the device on a smoke or fire door, check
that it is approved in conjunction with the door.
Before getting started with the installation, ensure that your
device is suitable for the respective door situation using the
comments in Chapter 4 and that the door is equipped with
hinges suitable for automatic mode.
The cable length for external components must not exceed
30 m.
2.2 Limitation of Liability
IS 9100 must only be used according to their intended use.
ISEO accepts no liability for damages resulting from
unauthorized changes made to the door system. No liability
is accepted for the use of accessories which have not been
approved by ISEO.
2.3 Risk Assessment by the Installer
The manufacturer, i.e. the person performing the
installation, and the contracting authority/facility drive must
jointly perform an individual risk assessment when planning
the system.
Due to particular spatial circumstances and the door user
groups to be expected, it may be sensible to use safety
sensors also in low-energy mode.
2.7 Safety Instructions
Work on electrical equipment must
be performed by qualified electricians only.
Never stick metal objects into the door system’s
openings. Otherwise there is a risk of electric shock.
Safety glass must be used for glass door leaves.
If installing the IS 9100 on a metallic door leaf, ground
the door leaf properly.
Never allow children to play with the IS 9100 or its
control and regulating devices.
Keep remote controls out of the reach of children.
The IS 9100 must be protected against water and
other liquids.
Only properly qualified persons may open the mains
connection unit.
Deenergize the IS 9100 before removing the protective
cover.
2.8 Dangers at Closing Edges
There may be crushing, shearing, collision and
drawing-in risks at the different closing edges of
automatic doors.
Secondary closing edge
2.9 Dangers due to the Slide Channel Lever and Arm
There are risks of crushing and shearing at the slide
channel lever and arm.
Opposing closing edge
Main closing edge
2.4 Particular Safeguard Requirement with Regard
to Vulnerable Persons
If the risk assessment indicates that the door leaf could hit
and therefore injure someone, additional sensors must be
attached to eliminate the danger.
This must particularly be taken into consideration if children,
older persons or disabled individuals use the door system,
too.
2.5 Standards, Laws, Guidelines and Regulations
The latest versions of the generally valid and countryspecific standards, laws, guidelines and regulations must be
observed.
2.6 Information/Regulations to be Observed when Using
IS 9100 on Fire and Smoke Doors:
• Data sheet on using hold-open systems
• Guidelines for hold-open systems issued by the DIBt
(German Institute for Civil Engineering), Berlin
2.10 Residual Risk
Depending on the structural circumstances, door variant and
potential safeguards, residual risks (such as minor crushing,
impact with limited force and the risk to unsupervised
children) cannot be excluded.
The danger spot on the secondary closing edge of all swing
doors (including those which are manually operated) is
generally known to all door users. It cannot be influenced
by the drive manufacturer Its safeguard is often not feasible
from a constructive and functional standpoint.
Clamping protection (such as a rubber or textile cover) which
may be suitable for this can be obtained from specialist
dealers and is not included in the scope of delivery.
2.11 Briefing
Once the door system has been successfully set,
commissioned and functionally tested, the installation
and operating instructions must be handed over to the
facility drive. A briefing must take place on operating and
maintaining the door system.
3ISEO
IS 9100
—
3. Product description
3.1 Drive Unit
The drive unit comprises all the core components.
1. Mains switch
2. Mains connection
3. Connection unit
4. Axle output on both sides
5. Drive unit (motor/gear/closer spring)
6. Closing force adjuster
7. C o n t r ol un i t
8. Switching power supply unit
321
4
4
9. Slot for ISEO Upgrade Cards
10. User interface with information display
11. Internal program switch
12. * Slide channel (set)
13. * Standard arm
14. * Complete cover
* Not included in the drive unit’s scope of delivery.
5
12
6
876
9
13
1110
3.2 Functions
3.2.1 Operating modes
The IS 9100 can be operated in 2 modes: as a door closer
or an automatic swing door drive. In the door closer mode
(see chapter parameterization/service, parameter hd = 1),
the drive unit is optimized for manual use. This operating
mode is to be used with the power-assist function optionally
available in this operating mode if the doors are operated
mainly manually and if a door closer-like behavior is
desired. The automatic mode (see chapter parameterization/
service, parameter hd = 0) is designed for the automatic
passage following a pulse generated by a motion sensor or
pushbutton.
3.2.2 Power-assist function
In the door closer mode, the power-assist function
(see chapter parameterization/service, parameter hd = 1)
can be activated. Power assistance will then be available
during the manual opening. The power assistance will be
automatically adjusted to the set door closer parameter.
The power assistance can be adjusted so that the
requirements of the DIN 18040, DIN Spec 1104, CEN/TR
15894, and BS 8300/2100 are met even up to EN 4.
4ISEO
14
The smallest adjustable opening moment is
23 Nm/5 lbf unless the hold-open system has been
activated or the power failed.
This power-assist function allows you to comply with the
requirements of the EN 1154 and at the same time to allow
for a barrier-free access in normal mode.
A combination with the Push & Go function or the wind load
control is not possible as they counteract the easy manual
opening.
3.2.3 Push & Go
The Push & Go function
(see chapter parameterization/service, parameter PG = 1)
can be used only in automatic mode. The door will then be
automatically opened when the door is manually moved from
the “CLOSED” position by an angle of 4° into the “OPEN”
direction.
IS 9100
—
3.2.4 Wind load control
The IS 9100 is especially suited for external doors that are
exposed to changing wind loads or internal doors separating
rooms in which pressure differences might occur. In
automatic mode, the wind load control monitors the actual
speed and will compensate for it if the speed deviates from
the set value. In combination with the Upgrade Card Full
Energy the drive unit can provide up to 150 N at the main
closing edge, which can then be used to compensate for
environmental influences.
The closing process during the last 5° can be additionally
supported by the electronic latching speed.
DIN L
< 3s Quit
> 3s Reset
<3s
>3s
PRG
>3s
LEARN
>8s
Fact-Setup
The door can be passed through manually. We recommend
the Push & Go function.
3.3 Low energy product
The IS 9100 can be adjusted so that the requirements
of a low energy application (low energy drive unit) are in
accordance with the EN 16005 or DIN 18650, ANSI 156.19
and BS 7036-4. During the commissioning, the drive
parameters must be adjusted according to the specifications
of the respective standard.
The required safety of the system will be achieved with the
following characteristics:
• Reduced dynamic door panel forces/contact forces
• Low speeds
• Reduced static door panel forces/contact forces
•Force limitation
Due to system tolerances, the actual forces on the door
panel have to be measured after the teach-in run and
adjusted, if necessary, in order to comply with the local
standards and regulations.
Additional safety sensors to safeguard the rotational
movement are not required but optional if this becomes
necessary due to a risk assessment to be carried out
individually.
The safeguarding of the secondary closing edge must be
considered separately.
3.4 Control elements
The drive unit IS 9100 is electromechanical drives. The
interaction between motor gear unit and control unit makes
the automatic opening and closing possible in the first place.
The control unit must know certain parameters of the door in
order to achieve the ideal behavior.
The control unit is equipped with a user interface featuring 4
pushbuttons and a 2 digit display. This allows you to make
all settings specified in the parameter list.
During the commissioning, the key functions and the display
are configured so that - independent of the installation
direction of the pushbuttons - always the same functions and
the numbers and digits are correctly shown. The legend of
the pushbuttons can be removed and turned.
< 3s Quit
> 3s Reset
<3s
>3s
LEARN
>8s
Fact-Setup
>3s
PRG
DIN R
By pressing the pushbuttons, you can execute the following
functions:
Lower pushbutton
• Setting of the installation direction following a mains
reset
• Browsing in parameter and error messages
• Reducing the parameter value
• Opening pulse
• Teach-in run
• Reset with factory setting (Fact-Setup)
Upper pushbutton
• Browsing in parameter and error messages
• Increasing the parameter value
Right pushbutton
• Open parameter menu
• Change selected parameter
• Save changed value
Left pushbutton
• Cancel parameter change
• Exit parameter menu
Left and right pushbutton simultanuously
•Error acknowledgement
•Reset
5ISEO
IS 9100
—
3.5 Upgrade Card
The Upgrade Card allows you to extend the functional range
of the automatic swing door drive unit is 9100. During
the installation of the Upgrade Card, information between
the control unit and the Upgrade Card is exchanged and
assigned. The desired function can be used as long as the
Upgrade Card is installed in the drive system.
• The first installed Upgrade Card becomes the container
module. The functions of additional Upgrade Cards
are saved in the container module. Each control unit
features only 1 container module.
• The status of the Upgrade card is indicated by 3
integrated LEDs.
3.5.1 Upgrade Card Full Energy – blue
The Upgrade Card Full Energy allows you to make use of
the full setting range of the opening and closing speed
parameters as well as the opening and closing torque. It can
be used for 2-panel systems.
3.6 Accessories
In addition to an extensive range of ISEO accessories, many
activators, locking devices, safety sensors and accessories
of other manufacturers are available and could be used
together with the drive unit IS 9100.
ISEO cannot guarantee the compatibility with devices from
other manufacturers. If those devices are always used, the
full functional range of the drive units may not be available
or the devices may not function properly.
3.6.2 Locking device
In general, the following types of devices are locking devices:
electrical door opener (E-opener), motor locks, multi-point
locking device with response contact, holding magnets.
Motor locks without a locking response can be directly
connected to the drive unit if the locking time is less than
4 seconds. In order to ensure the safe operation of the
combined drive unit and locking device, the locking device
must meet the following specifications:
Minimum requirements:
Operating voltage when supplied by the drive unit:
24 V DC +/- 5 %
Operating voltage with an external supply:
max. 48 V DC/AC
Load of the contact relay locking:
max. 1 A
Switch-on time electrical door opener:
min. 30 %
Switch-on time motor lock:
100 %
The drive unit or the connected device may also become
damaged.
The operator can provide a maximum 1.5 A with 24 V DC for
external consumers. Should more be required (even if only
temporarily), an external power supply is to be used in order
to prevent a malfunction of the drive unit.
3.6.1 Activator
In general, the following types of devices are activators:
radar motion sensors, passive infrared motion sensors,
pushbuttons, switches, sensor buttons, radio, IR-receivers,
access control systems, telephone and intercom systems.
Activator, inside outside, night/bank and intercom system
may be connected to the device. The activator inside is
usually found inside a building or room. The activator outside
is found on the outside of a building or room. The activator
night/bank is installed on the outside and often designed as
a card reader or key switch button.
Minimum requirements:
Operating voltage when supplied by the drive unit:
24 V DC +/- 5 %
Pulse duration:
min. 200 ms
Potential-free output:
(in case a signal input internal is used,
external detector or night /bank)
Energized output (telephone systems):
max. 24 V DC/AC +/- 5 %
6ISEO
IS 9100
—
3.7 Technical data
Application conditions
Ambient temperature- 15 – + 50 °C
Only for dry rooms
Power supply
Protection classIP 20
General
Dimensions (WxHxD)685 x 70 x 130 mm
Max. power input120 Watt
Closing torque EN 1154EN 2 – 4 infinitely variable
Max. door panel weight
up to a lintel depth of 250 mm
Door panel width700 – 1,100 mm
Max. opening speed**50° (27°*)/second
Max. closing speed**50° (27°*)/second
Axis extension30/60 mm
Lintel depth standard arm0 – 225 mm
min. clearance between hinges
2-panels
min. clearance between hinges
2-panels with door coordinator
min. clearance between hinges
2-panels with full casing
FE With installed Full-Energy Upgrade Card, LE Low-Energy basic device without Upgrade Card
* If power-assist support set to maximum, effective from an opening width of approx. 3°.
** The torque is available in the event of automatic opening in automatic mode.
*** In the push version of the slide channel installation type, the forces reduce by approx. 33%
pull version of slide channel
minimummaximumminimummaximum
23232323
Lintel mounting on opposite hinge side,
push version of standard arm/
push version of slide channel
7ISEO
IS 9100
—
4. Preparing for installation
1. Depending on the installation situation, select the corresponding drilling pattern on pages 9-12.
Assembly on the hinge side pull version with slide channel
pages 9 and 10
1
Assembly on the opposite hinge side push version with slide
channel
page 11
Warning : mounting on opposite hinge side with slide
channel is not suitable on fire and smoke doors.
2
Assembly on the opposite hinge side push version with
standard arm
page 12
3
2. Drill the holes shown in the drilling pattern in the door leaf and frame/wall.
8ISEO
IS 9100
—
Assembly on the hinge side pull version with slide channel and 12.5 mm lever pin
150
45
106
32
12 010 0
12 01 2095
B
D
Door without rabbet
15 5
63
Rooms for cable feed
Ø 6.6
45
12,5 mm lever pin
45 1
A
19
Upper edge door
C
Upper edge door
Lintel depth maximum ± 30 mm
Axis extensionABCD
Standard (9 mm)31 mm50 mm22 mm41 mm
30 mm61 mm80 mm52 mm71 mm
60 mm91 mm110 mm82 mm101 mm
9ISEO
IS 9100
—
Assembly on the hinge side pull version with slide channel and 25 mm lever pin
15 0
10 612012 09 5
45
32
120100
B
D
Door with rabbet
15 5
Space for cable feed
63
Ø 6.6
451
45
25 mm lever pin
A
32
Upper edge door
C
10 ISEO
Upper edge door
Lintel depth maximum ± 30 mm
Axis extensionABCD
Standard (9 mm)31 mm63 mm22 mm54 mm
30 mm61 mm93 mm52 mm84 mm
60 mm91 mm123 mm82 mm114 mm
IS 9100
—
Assembly on the opposite hinge side push version with slide channel and 12.5 mm lever pin
120100
150
10612012095
45
32
C
A
35
Lower edge frame
45
451
63
Ø 6.6
Space for cable feed
145
B
D
The maximum opening width is 95°
The axis adaptor is turned 45°.
Not suitable for fire and smoke control doors!
Axis extensionABCD
Standard (9 mm)15 mm49 mm6 mm40 mm
30 mm45 mm79 mm36 mm70 mm
60 mm75 mm109 mm66 mm100 mm
Lower edge frame
Lintel depth maximum 60 mm
11ISEO
IS 9100
—
Assembly on the opposite hinge side push version with standard arm
150
12010012 0120
10695
45
32
C
Lower edge frame
Lower edge frame
63
Ø 6.6
A
33
45
50
Rooms for cable feed
245
B
D
12 ISEO
0 mm – 225 mm
Axis extensionABCD
Standard (9 mm)19 mm51 mm9 mm42 mm
30 mm49 mm81 mm39 mm72 mm
60 mm79 mm111 mm69 mm102 mm
7
IS 9100
—
5. Installing the drive unit
Secure the workspace against trespassing. Dropped
parts or tools may result in injuries.
The described procedure is only an example.
A different procedure might be preferable due to structural
or local conditions, available tools or other circumstances.
Requirements
• A 230 V/50-60 Hz connection with a fuse protection of
16 A must be available at the place of installation.
• The door panel must be in a sound mechanical
condition and smooth-running.
Standard tightening torques
M 5 ......... 5 Nm
M 6 ...... 9.5 Nm
M 8 ....... 23 Nm
M 10 ..... 46 Nm
M 12 ..... 79 Nm
5.1 Removing the drive unit from the mounting plate
1. Loosen the 8 fastening screws.
Required tools
5 mm13 mm
1/2/3
2.5 mm insulated
6 mm
1
2.5 mm
6 mm
5 mm
2. Unplug the 230 V connector.
3. Disconnect the drive unit from the mounting plate.
Use a screwdriver as a lever between the drive unit and
the base plate. |
4. Place a piece of wood or similar underneath the drive
unit so that the connecting part cannot become loose.
5.2 Mounting the receiver (optional)
1. Connect the receiver, if you need.
For more information on installation, refer to its
mounting instruction.
1.
2.
2
3
57 57a
142
3
141
+ 24 V
Pulse
0 V
0 V
3
1
15
1
1
13ISEO
IS 9100
—
5.3 Mounting the mounting plate
1. Fasten the mounting plate with 12 screws into the
prepared holes.
For the fastening, use dowels and screws that match
the background.
2. Use 3mm allen hey to drive the supplied holding pin
into the lower one of the 2 holes.
3. Connect the 230 V connecting cable.
4. Bend the cable end of the ground conductor to form an
eye and fasten it to the grounding screw.
Work on electrical equipment must be performed by
qualified electricians only.
5.4 Fastening the drive unit to the mounting plate
1. Remove the protective sheet from the thermally
conductive pads on the bottom side of the mains
adaptor.
The thermally conductive pads may not become soiled.
1
3 mm
L1 N
2
1
2. Feed the connecting cables through the housing and
place the drive unit onto the bolts on the base plate.
3. Push the drive unit until it clicks into place.
4. Tighten the 8 screws.
5. Plug in the mains connector. |
14 ISEO
2
1.
2.
3 mm
3
IS 9100
—
5.5 Driving the axis extension into the lever
1. Drive the axis extension into the lever.
Mounting position on the hinge side in case of an
installation with slide channel and on the opposite
hinge side in case of a normal arm assembly.
Mounting position on the opposite hinge side in case of
an installation with slide channel, the square must be
turned by 45°.
9 mm30 mm90 mm
1
5.6 Mounting the slide channel
1. Insert the lever pin (12.5 or 25 mm) into the sliding
piece and fasten it with the retaining washer.
The short pin is used for doors without rabbet.
2. Place the individual parts into the slide channel as
shown in the illustration and fasten the mounting part.
1 Slide channel
2 Latching action
3 Buffer
4 Sliding piece
5 Mounting piece
3. Screw the slide channel with 2 screws into the
prepared holes.
25 mm
12.5 mm
1
1 2 3 4 55
DIN L
1 4 3 2 55
DIN R
2
2.5 mm
For the fastening, use dowels and screws that match
the background.
4. Insert the casing onto the slide channel.
5. Insert the end caps onto the spacers.
6. Insert the spacers with the end caps into the casing. |
Ensure the correct mounting position; the spacers and
end caps must be installed as shown in figure 4.
7. Align everything so that the end caps are flush with the
casing on both sides.
3
2.
1.
4
15ISEO
IS 9100
—
5.6 Mounting the lever of slide channel set.-pull version
1. Screw disk using a high tightening torque (35 Nm) to
the drive shaft.
Use only the supplied self-locking screw. If this screw
is loosened during repair or maintenance work, it needs
to be replaced with a new self-locking screw.
2. Screw the lever to the sliding piece.
35 Nm
1
5 mm
5 mm
5.7 Mounting the lever of slide channel set.-push version
1. Screw disk using a high tightening torque (35 Nm) to
the drive shaft.
Use only the supplied self-locking screw. If this screw
is loosened during repair or maintenance work, it needs
to be replaced with a new self-locking screw.
2. Screw the lever to the sliding piece.
2
1
SW 13 mm
35 Nm
5 mm
5 mm
SW 13 mm
2
16 ISEO
IS 9100
—
5.8 Mounting the normal arm assembly
1. Screw the tensioning screw (A) with 2 screws into the
prepared holes.
2. Screw the lever (B) using a high tightening torque (35
Nm) to the drive shaft.
Use only the supplied self-locking screw. If this screw
is loosened during repair or maintenance work, it needs
to be replaced with a new self-locking screw.
3. Align the tensioning screw perpendicular to the door
panel with the door closed.
4. Loosen the counternut on the tensioning screw.
A
1
B
35 Nm
5 mm
5. Screw or unscrew the tensioning screw until the
tensioning screw is perpendicular to the door panel in
the clipped together state of the arm assembly. |
6. Push the ball head of the tensioning screw into the
receiver on the lever.
7. Tighten the counternut. |
5.9 Setting the braking circuit
1. Ensure that the mains voltage is disconnected.
2. Insert the connector depending on the type of
installation.
connector is not correctly connected. The door can
close with a high speed.
A
B
1
17ISEO
IS 9100
—
5.10 Adjusting the spring force
The spring is not tensioned when delivered. A primary
tension of at least 10 rotations is required for the operation.
The adjustment will be tested during the teach-in run. The
teach-in run will be aborted if the spring force is too low. A
new teach-in run must be carried out if the spring has been
readjusted.
1. Refer to the table to find the required rotations for the
spring adjustment and adjust the spring force.
Selection EN class
Door panel width in mm 8509501100
EN classEN 2 EN 3EN 4
min. closing torque in
case of 2°
Rotations for the spring
adjustment
The table shows approximate values. You must
therefore test and correct, if necessary, the closing
torque at 2° in accordance with EN 1154. In case of
lintel depths larger than 225 mm, you must also check
the minimum closing torque between 88° – 92°.
13 Nm 18 Nm26 Nm
101416
5 mm
1
5.11 Adjusting the closing speed in an deenergized state
1. Adjust the closing speed on the potenziometer.
The speed must be adjusted. If the door closes in less
than 3 seconds, it will lead to the error message 73
(braking circuit test).
1
5.12 Commissioning the drive unit
1. Commissioning the drive unit. See commissioning on page 21
5.13 Adjusting the end stop on the slide channel
The end stop must be adjusted so that the set opening angle
cannot be exceeded when manually pushed.
1. Turn the program switch to the PERMANENT OPEN
position.
Ź The door will open to the adjusted opening width.
2. Move the buffer and the end stop to 5 mm to the
sliding piece.
5
3. Tighten the end stop.
We recommend the use of a door stop.
In case a normal arm assembly is used, you must use
a door stopper.
18 ISEO
2.5 mm
1
IS 9100
—
5.14 Installing the 2-panel door
1. For more information on installation, referto mounting
instruction of extra cover for double door.
5.15 Installing the casing
1. Push the cover onto the drive unit and press until it
clicks into place.
Do not connect any cables.
1
2. Attach the axis covers.
3. Attach the side covers.
On the side with the program switch, you can vary
the insertion depth using the notches in order to
compensate for slight differences in length of the
cover.
1
2
3
19ISEO
IS 9100
—
6. Connecting the accessories
1 Connect the connecting cables to the connector and insert the connector into the connection board.
• Maximum 1.5 A total load on the terminals 1, 1G and 3.
• Cable length maximum 30 m for J-Y(ST)Y 0.8 mm
6.1 Terminal assignment
No connector
1
2
No connector
Night/bank
1
3
BA
1
8 – 24 V DC/AC + 5 %
5 7 57a
Pulse
internal
+ 24 V
Signal input
1423141
3
1G
43 3 64 63 62
18k
Pulse
external
0 V
+ 24 V
Signal input
0 V
3
0 V
+ 24 V
COM
NO
NC
0 V
Locking response
Locking relay
max. 1 A/48 V DC/AC
Safety sensor
hinge side
Signal input
Test output
+ 24 V
11517
Connection depends on the
smoke detector
3
0 V
111
Safety sensor
opposite hinge side
Signal input
Test output
+ 24 V
13 3
0 V
20 ISEO
4a
0 V
Shutdown
drive function
1
4
2
1
36
0 V
97 98 9930 31 32 34 33 3335
NC
0 V
Signal input
Partial open
Permanent open
Night/bank
Program
Off
Exit only
Automatic
switch
Open
Status
NO
closed
relay
Max. 1 A/48 V DC/ACCOM
IS 9100
—
7. Commissioning
(also after a reset with factory setting (Fact-Setup))
7.1 Requirements
• The drive unit is completely installed and correctly
connected to the door panel.
• The parts delivered separately such as the program
switch and activator (microwave detector, night/bank
key switch) are installed and connected.
• The motor is cold.
7.2 Commissioning the drive unit
1.
Turn the program switch to the OFF position.
2. Turn on the drive unit using the power switch.
Ź The display shows a sequence of characters that
indicate the current processing status.
The system is being tested.
2 segments in the center moving back and forth
indicate that the control unit is waiting for internal
signals (maximum 1 second).
2 underlines moving up and down indicate the
mounting position can be entered. In case of an
incorrect input, the characters on the display are
upside down.
3. Press the lower pushbutton
(possible only during the initial commissioning).
After leaving the parameterization mode, the
display will show a small, spinning “o“ and “P“.
7.4 Performing a teach-in run
The teach-in run must be carried out while the motor
is cold. The door panel may not be moved manually
and stopped during the teach-in run. The control unit
would otherwise not be able to correctly determine the
parameters.
The safety sensors and activators are shut off during
the teach-in run so that they do not interfere with the
teach-in process.
The smoke detector and the shutdown drive function
are active.
1. Secure the movement range of the door panels.
2. Close the door and turn the program switch to the OFF
position.
A spinning “o“ and “O“ indicate that a teach-in
run is required.
3. Press the pushbutton
Ź The door performs various movements and the display
shows a sequence of characters.
Do not stop the movements of the door panel.
The door is in the 70° position and waiting for the
opening width to be set.
for 3 seconds.
The device identification will “run“ through
the display. IS 9100 and the firmware version
(indicated by XX XX).
A small, spinning “o“ and “P“ indicate that a
further parameterization is required (only during
the initial commissioning or after a reset with
factory setting).
4. Set the following parameters: type of mounting (AS),
lintel depth (rd) and door width (Tb).
For the meaning and the value ranges of the
parameters, please refer to the table on
Even factory setting are the good values, a validation is
necessary.
7.3 Changing the parameters
1. Press the pushbotton for 3 seconds in
order to call up the parameter menu.
2. Press the pushbuttons in order to select
the desired parameter.
3. Press the pushbutton in order to display
the parameter value.
4. Press the pushbutton in order to select
the value for the change.
=> The value flashes.
5. Press the pushbuttons in order to set the
desired value.
6. Press the pushbutton in order to save the
changed value.
7. Press the pushbutton in order to return to
the parameter menu.
8. Press the pushbuttons in order to select
the next parameter.
page 23.
or
or
or
4. Push the door to the desired open position and press
the pushbutton
In case the spring force is too low, the display will
show the small spinning “o“ and “F“.
5. In this case, increase the spring force and restart the
teach-in run.
The door is now operational.
Due to system tolerances, the actual forces on the door
panel have to be measured after the teach-in run and
adjusted, if necessary, in order to comply with the local
standards and regulations.
7.5 Commissioning of a 2-panel system
1. Commssion the active panel.
2. Switch the program switch to PERMANENT OPEN after
the teach-in run.
3. Commission the inactive door panel.
Additional parameterization
• On the active panel:
Set parameter >dL< (door type) to “1“.
Set parameter >Ad< (caster angle) to the set value.
• On the inactive panel:
Set parameter >dL< to “2“.
7.6 Zero point search after mains reset
During the zero point search, the display will show
the small spinning “o“ and “b“.
.
21ISEO
IS 9100
—
8. Installing Upgrade Cards
8.1 Requirements:
• The drive unit is completely installed.
• The teach-in run has been successfully completed.
• The mains voltage is turned on.
• The program switch is in the OFF position.
• The information display indicates an
inactive state.
8.2 Use in 2-panel systems
Full Energy: The Upgrade Card Full Energy can be
installed on 1 or both drive units.
8.3 Installing the Upgrade Card
1. Insert the Upgrade Card into
the slot
(see page 4 position 9).
Ź The yellow LED flashes once
during the insertion.
The following is also to be considered during the installation:
• If the container module is removed, the previously
enabled functions will be deactivated after some time.
• For a new installation of the Upgrade Cards, it is
necessary to carry out an extended factory setting.
• In case the control unit is replaced, the container
module will be taken from the old control unit and
attached to the new one. The new control unit
synchronizes with the container module and all
functions will be available again.
• The Upgrade Card will be rejected if an already
enabled Upgrade Card is attached. This is indicated by
a fast flashing of the yellow LED. The module is then
not devalued.
• If the container module of an external control unit is
inserted, the container module will be rejected. This
is indicated by a fast flashing of the yellow and the
green LED. The module can be synchronized only with
a control unit.
Ź The data are transmitted.
The communication between
the modules is indicated by
a slow flashing of the green
LED.
Ź The corresponding function is now enabled and can be
activated (see page 27, Parameter F1 – F8).
Ź The system is now operational.
Ź The Upgrade Card assumes the function of the
container module.
22 ISEO
IS 9100
—
9. Parameterization/Service
After a completed teach-in run, the drive unit can be operated
with the basic parameters.
The system also offers the option to adapt the moving
parameters to the actual conditions and to activate the enhanced
functions. These parameters should already be set during the
commissioning according to the preferences of the user.
Parameter/displayValue rangeUnit
Assembly type
Lintel depth
Door panel width
Door type
MOUNTING AND DOOR INFORMATIONS
Opening speed
Closing speed
SPEED ADJUSTMENTHOLD-OPEN ADJUSTMENT
Hold-open time
Hold-open time
Night/Bank
Hold-open time in
case of a manual
opening
0 – 2
3 – 30
7 – 11
0 – 4
8 – 50
(in case of low
energy reduced
to a maximum of
27°/sec.)
8 – 50
(in case of low
energy reduced
to a maximum of
27°/sec.)
0 – 30
(in case of low
energy min. 5 s)
0 – 30Seconds10The hold-open time night/bank (key switch button) can be
0 – 30Seconds1The hold-open time after a manual opening is in effect with
Factory
setting = Bold
Degrees/
second
Degrees/
second
Seconds5The hold-open time should be adjusted so that people have
0
1Lintel assembly opposite hinge side, arms push version
2Lintel assembly opposite hinge side, slide channel push
0
10
0
12-panel door, active panel, overlapping door panel
22-panel door, inactive panel, overlapping door panel
32-panel door, active panel, non-rebated door panel
42-panel door, inactive panel, non-rebated door panel
25
25
Explanation
Lintel installation hinge side, slide channel pull version
version
The lintel depth is set in 10 mm steps. The required measure
can be taken from the assembly drawings.
In case the CPD lever is used, 30 mm must be deducted from
the real lintel depth.
The rabbet will be included in the door panel width.
The door width is shown in 100-mm steps.
1-p an el door
The opening speed relates to the automatic mode. Countryspecific limits must be complied with and tested after the
setting. The full setting range is available only if an Upgrade
Card Full Energy has been installed. The speed can be
changed using this parameter. The permissibility of the
setting is checked via internal monitoring. If exceeded, the set
value is shown alternating with the active value.
The closing speed relates to the automatic mode. Countryspecific limits must be complied with and tested after the
setting. The full setting range is available only if an Upgrade
Card Full Energy has been installed. The speed can be
changed using this parameter. The permissibility of the
setting is checked via internal monitoring. If exceeded, the set
value is shown alternating with the active value.
enough time to pass through the door. The hold-open time
starts once the contact/voltage on the activator inputs,
internal, external, safety, Push & Go is opened/drops and the
door is in the open position. The signal can be retriggered. In
the operating mode Low Energy, the hold-open time may not
fall below the minimum hold-open time of 5 s. The values of
0 – 30 seconds can be set in 1 second steps and values over
30 seconds in 5 seconds steps.
set separately. The hold-open time night/bank starts once the
contact on the activator input night/bank is opened and the
door is in the open position. The signal can be retriggered.
any purely manual opening, even in case of an activated
power-assist function and after a stop by the sensor bar.
< 3s Quit
> 3s Reset
<3s
>3s
PRG
>3s
LEARN
>8s
Fact-Setup
23ISEO
IS 9100
—
Parameter/displayValue rangeUnit
Wall suppression BS
Test
Safety sensor
SAFETY SENSORUNLOCKING
Pulse by safety
sensor opposite side
hinge
60 – 99
99 = deactivated
0 – 6
0 – 1
Factory
setting = Bold
Degrees80Once the set angle has been reached, the input signal of the
Explanation
safety sensor hinge side will be ignored. The wall suppression
is required if the door opens against an obstacle. The wider
the detection range of the used safety sensor, the larger the
range has to be within which the detection is ignored. To
protect people, we recommend to minimize this range.
If during the opening of the door the wall suppression angle
is exceeded, a fast flashing point will appear on the top left
on the display of the control unit. This display will disappear
when the angle is smaller.
0
1Test sensor on hinge side - Level High active
2Test sensor on opposite hinge side - Level High active
3Test sensor on hinge side & sensor on opposite hinge side -
4Test sensor on hinge side - Level Low active
5Test sensor on opposite hinge side - Level Low active
6Test sensor on hinge side & sensor on opposite hinge side -
0
1With the door closed, the safety sensor can trigger an
Test off. The safety sensors will not be tested. In combination
with safety sensors according to EN 16005 or DIN 18650,
one of the parameters 1 – 6 must be used. The test level Low
and High active depends on the sensor and must be set on
the sensor to the same value as the drive unit.
Level High active
Level Low active
The input signal of the safety sensors will be ignored as soon
as the door is closed.
opening pulse.
Suppression
safety sensor BS
during initial run
Unlocking time
Unlocking force
PR module test
0 – 10The safety sensor on hinge side is not active during the intial
1
0 – 40100 ms1The unlocking time starts after the pulse. The door will be
0 – 9
0 – 1
0
O
1The test of the PR module is carried out every 24 hours, 10
run (will be suppressed).
The safety sensor on hinge side is active during the intial run.
opended only after the unlocking time has lapsed. When
set to “0“, the pushing will not be carried out before the
unlocking. Depending on the locking device used and in
combination with the response contact, the process will
change.
The unlocking force determines the force with which the door
is pushed in the "CLOSED" direction prior to the opening.
The time is determined by the unlocking time parameter.
The pushing in the “CLOSED“ direction can be practical in
order to relieve a possibly existing e-opener and to ensure its
opening. The higher the value is set, the higher the load on
the arms mounting. In order to have a long service life of the
system, adjust this force only as high as really required.
Test off
minutes after the mains has been turned on. In case of an
error, no more unlockings will be carried out and therefore
also no more automatic door movements will be started.
24 ISEO
IS 9100
—
Parameter/displayValue rangeUnit
Static force in the
opening direction
(basic parameter for
wind load control)
Static force in the
closing direction
STATIC FORCE
(basic parameter for
wind load control)
Latching action
pulse
Latching action
angle
END CLOSING
2 – 15
(reduced in case
of
Low Energy)
2 – 15
(reduced in case
of
Low Energy)
0 – 9
2 – 10Degrees3The door opening angle is determined by the latching action
Factory
setting = Bold
10 N
10 N
Explanation
The forces acting on the closing edge can be changed using
6
6
0
this parameter. The permissibility of the setting is checked
via internal monitoring. If exceeded, the set value is shown
alternating with the active value. Due to system tolerances,
the actual forces on the door panel have to be measured after
the automatic drive teach-in run and adjusted, if necessary, in
order to comply with the local standards and regulations.
The forces acting on the closing edge can be changed using
this parameter. The permissibility of the setting is checked
via internal monitoring. If exceeded, the set value is shown
alternating with the active value. Due to system tolerances,
the actual forces on the door panel have to be measured after
the automatic drive teach-in run and adjusted, if necessary, in
order to comply with the local standards and regulations.
In addition to the mechanical latching action, there is a
motor-driven latching action available for the automatic mode.
The motor-driven latching action allows you to overcome door
seals or locking devices during the closing. Starting with a
small value, the setting is to be increased in order to prevent
damage to the door.
It must be ensured that the door itself and the arm assembly/
slide channel mounting is suitable for the addional and
permanently introduced forces. In case of doubt, we
recommend to select the smallest possible setting.
angle after which the motor-driven latching action pulse is
effective.
Locking force
Push & Go
Program
switch type
Behavior after a
mains reset
PROGRAM SWITCH
Internal program
switch
– switch on delay
0 – 90 = off
1 – 9 = on
0 – 1
0 – 4
0 – 1
0 – 1
0 = off
1 = on
0
1An external program switch with contacts on the connection
2Not applicable
3Not applicable
4Not applicable
0
1In case of a power failure or after a shutdown of the drive
0
1After the switching of the internal program switch, the function will
The locking force will be permanently applied after the
latching action.
This force is to keep the door in the CLOSED position even if
wind pushes against the door.
The locking force can be set between 0 (off) and 9
(maximum).
Once activated, the door will be automatically opened when
the door is manually moved from the “CLOSED“ position by
an angle of 4° into the direction of “OPEN“.
For this function, the value “hd“ must also be set to 0.
The internal program switch is active.
board is connected. The connector of the internal program
switch must be unplugged.
In case of a power failure or after a shutdown of the drive
drive unit, the program switch will be automatically switched
to the last known position once the mains is switched on.
Important: The switching on of the mains may also take place
outside business hours and will therefore affect the insurance
requirements.
unit, the program switch will be automatically switched to the
OFF position when the mains is switched on. This function
should be used if the insurance-company approved lock must
be provided.
The function of the internal program switch will be applied by the
drive unit immediately after the switching.
be applied with a delay of 10 s. This function is practical if the PGS
is to be repositioned and the person must pass the door through the
standard detectors after the switching. An additional pushbutton
night/bank is not required.
25ISEO
IS 9100
—
Parameter/displayValue rangeUnit
Day activation
Status relay
function
Control unit
output 1G, with the
input 4/4a
Cycle counter
Delete error memory
Resetting the
service interval
display (LED yellow)
0 – 1
0 – 60The status relay is deactivated.
0 – 1
0 – 9910.000
0 – 1
0 – 1
Factory
setting =
Bold
0
1In the automatic operating mode, the door will not be locked when
1
2The status relay will be switched as soon as the set OPEN position
3Error
4Door CLOSED and locked.
5Error or information
6The status relay will be switched if the open door exceeds the
0
1The locking output (terminal 1G) switches as soon as the contact 4/4a
Cycles
0
1The error memory will be deleted.
0
1The service cycle and time counter will be reset to the values
Explanation
The door will always be locked when it reaches the CLOSED position.
the CLOSED position is reached. The locking contact is permanent.
This results in a faster opening in combination with motor locks.
When an e-opener is used, this opener must be suitable for a 100 %
switch-on time in order to prevent damage.
The status relay will be switched as soon as the set CLOSED position
has been reached.
has been reached.
All errors that result in a message to the internal display will be
output on the status relay.
All errors or any information that result in a message to the internal
display will be reported through an output on the status relay.
parameter “Status contact angle“. The value of the parameter can be
changed only via the hand terminal.
Output 1G is independent of contact 4/4a.
is opened. The contact switches permanently. Therefore, an e-opener
with a 100% switch-on time is required for the application, e.g. a
closed current contact.
The display takes place in increments of 10,000 cycles.
Example: display 4 = 40,000 cycles, display 53 = 530,000 cycles.
The value 99 on the internal display will therefore mean 990,000 or
higher.
Without function.
The parameter will then be automatically reset to 0.
Without function.
200,000 cycles and 12 months.
Factory setting level1 – 2
INFORMATIONS/UPKEEP
Opening angle
26 ISEO
0 – 110DegreesThe opening angle set during the teach-in run will be
By pressing the Fact-Setup pushbutton on the user interface
> 8 seconds, the drive unit can be reset to the factory setting.
The Sl parameter can be used prior to the factory setting to
determine which data are to be deleted.
1
2Extended factory setting:
Standard factory setting: All paramaters will be reset to the
factory setting. However, the installed Upgrade Cards are kept
and do not have to be reinstalled.
All parameters will be reset to the factory setting. The
installed Upgrade Cards will deleted from the memory of the
control unit. The control unit and Upgrade Card can be used
independently from each other again (delivery state).
displayed here. It can be changed only by performing a teachin run.
Due to assembly and parameter tolerances, the display may
differ from the actual door position.
IS 9100
—
Parameter/displayValue rangeUnit
Door closer/
automatic mode
Power-assiststarting angle
Power-assist
power assistance
POWER ASSIST
Assistance
manual mode in
CLOSED position
Upgrade Cards
0 – 10The automatic mode should be used if the door is preferably opened
1 – 5Degrees3Sets the angle after which the Power-Assist function is to be effective.
0 – 10
0 – 10
0 – 3
Factory
setting =
Bold
Explanation
automatically and if motion sensors are used. In case of blockages during
the closing, the drive will automatically reverse. The movement has been
optimized for a safe closing. The wind load control and the Push & Go
function can be used only in the automatic mode.
1
The door closer mode should be used if the door is opened manually
most of the time and only rarely automatically. In case of blockages
during the closing, the door will remain in the current position. The
movement has been optimized for the manual opening.
The Power-Assist function is to be used only in the door closer mode.
The smaller the value, the more sensitive the response of the PowerAssist function.
0
Sets the Power-Assistance The higher the value, the easier it is to open
the door manually.
At 0, the function is deactivated. The Power-Assist function is available
only in the door closer mode (hd=1). If the assistance has been set too
high, the door can open automatically.
0
Setting of the strength of the Power-Assist in the
CLOSED position. The higher the value, the easier it is to manually
open the door from the CLOSED position. The Power-Assist function is
available only in the door closer mode (hd=1).
0
Upgrade-Card not installed, function not available.
1Upgrade-Card installed, function not activated.
2Upgrade-Card installed, function activated.
3L'Upgrade Card has been removed, function is no longer available.
Upgrade Card Fire
Protection
Upgrade Card
Full Ener gy
Upgrade Card
Professional
Impulse relay
UPGRADE CARDS
Extended
hold-open
time
Nurse beds
Upgrade Card
Handicapped WC
Upgrade Card DCW
0,2,3
0, 2, 3
0, 1, 2, 3
0, 2, 3
0, 1, 2, 3
0, 1, 2, 3
0, 2, 3
Not Available
After the installation of the Upgrade Card, the value 2 will be
automatically activated. The full setting range will be available
for the parameters So, Sc, Fo and Fc after the activation.
Not Available
Not Available
Not Available
Not Available
Not Available
27ISEO
IS 9100
—
Parameter/displayValue rangeUnit
Configuration of the
interface COM1
(upright connector)
Opening dampening
when opened
manually
Door thickness
Shutdown drive
function effective
direction (4,4a)
Night/bank
effective direction
Triggering the
hold-open system
by disengaging the
door panel
Castor angle for
2-panel doors
0 – 1
5 – 40
0 – 990...35...99mmThe door thickness affects the measured door opening angle.
0 – 1
0 – 1
0 – 1
0 – 300...30°Here you can adjust the angle that the active panel has to
Factory
setting = Bold
0
1Not applicable
10°
0
1Normally open contact
0
1Normally closed contact
1
0Function switched off
Explanation
Not applicable
In this case, enter the angle after which the door is braked
when manually opened.
The entered value counts backward from the set opening
angle.
Example: Opening angle: 90°
Parameter bc: 12°
=> opening dampening starts at 78°
If a more accurate resolution is required, you can enter the
actual door width.
Normally closed contact
In case of a normally closed contact, the drive function will be
shut down. This effective direction must be used for door lock
switches which are equipped with a changeover contact or
normally closed contact.
In case of a normally open contact, the drive function will be
shut down. This effective direction must be used for door lock
switches which are equipped with a normally open contact.
Normally open contact
The night/bank function will be triggered in case of a normally
open contact. This effective direction is preferred for a key
switch button or access control.
The night/bank function will be triggered in case of a normally
closed contact.
This effective direction is often used for the connection to a
smoke went and heat exhaust system or building management
system in order to activate doors with a normally closed
contact.
Function switched on
If the drive is operated as a hold-open system, the manual
triggering can be carrried out via the manual closing of the
door panel by 10° (+/– 2°) from the taught hold-open time. A
manual release button is not required.
If the drive is operated as a hold-open system, a manual
release button will be required for the manual activation.
travel before the inactive panel begins to open.
Clearance between
hinges
DOOR PARAMETER
28 ISEO
+ 5 – – 5
3
The clearance between hinges is crucial for the calculated
door angle. It may only have a small effect but it can be
adjusted in extreme cases to increase the accuracy.
The basic setting of the parameter HS is 3, for 30 mm.
In case of center-pivoted doors, the setting must be changed
to the negative. A teach-in run is then required as the system
creates an angle table as a function of the set parameters.
IS 9100
—
10. Diagnosis/Troubleshooting
ISEO drive units meet a high safety standard and comply
with all technical regulations and requirements. Internal as
well as external safety circuits managed by the drive unit will
be periodically monitored.
Information "In"
Information is provided for the easy servicing of the drive
unit and points to both faulty states and operating states
that suppress the automatic operation of the drive unit.
During the operation of the devices, situations may arise that
lead to an error message.
The drive unit tries to determine the cause and react
accordingly. The reaction takes place depending on the
severity of the cause and ranges from an information to the
shutdown of the automatic functions of the drive unit.
In this case, the drive unit switches into the emergency
mode and acts as a door closer.
The door can be manually passed through.
Information “In“ and error messages “E0“ ... “E9“ will be
output on the display of the user interface and the red LED
on the internal program switch.
The output to the LED is coded and can be taken from the
error table.
Error messages “E0“ ... “E9“ will be saved in the error
memory and can be read off the display of the interface.
A current error information will always occupy the error
message memory cell E0. In case of another error or its
acknowledgement, it will be moved to the error message
memory cell E1.
A maximum of 9 errors can be saved in the error memories
E1 – E9. The same error messages occuring successively will
not be saved again.
To call up the error messages E0 ... briefly
press E9.
Example:
In 08 -> Emergency stop is pressed; the drive unit does
not perform automatic functions.
In 01 -> A blocking has been detected; the drive unit
keeps operating.
An information can become an error message in case of a
repeated occurance.
Error messages “E0“ ... “E9“
Error messages indicate a hardware defect. However,
installation errors and the manual operation during safety
tests can also cause error messages, and the system will
switch into the emergency mode. The following options are
available for the reset of error messages:
• Switching the program switch to off or resetting by
pressing the reset button of the user interface with the
casing open.
• Mains reset. Switching off the power switch. Restart
after 10 seconds.
The cause should be analyzed and eliminated before an error
message is acknowledged. The following table will provide
assistance.
ErrorPossible causeRemedy
The door can be passed
only manually or the
door does not open
automatically after an
opening pulse.
Testing of the green LED.
If the green LED is not on, there is a
problem with the power supply.
Testing of the red LED.
If the LED flashes on the power switch,
the control unit found an error and the
emergency mode is activated.
The program switch is in the Off or Exit
only position.
There is a signal from the safety sensor
on the hinge side. This signal prevents
the opening.
The power switch must be switched on.
The power supply must be tested and restored, if
necessary.
If power is supplied but 24 V DC is not available, the
mains adaptor must be replaced.
The troubleshooting is described in the "Information
and error messages" list.
Put the program switch into the Automatic or
Permanent Open position.
The signals of the safety sensors will be displayed for
the diagnosis directly with the 2 decimal
points of the LED display on the user
interface.
In case of a detection, the respective decimal point will
light.
The wiring and function of the system must be tested.
If the LED at the top left flashes, the wall suppression
will be active. There is no error.
29ISEO
IS 9100
—
ErrorPossible causeRemedy
During the installation:
It is difficult to manually
open the door and the
closing movement takes
place at a high speed.
The teach-in run cannot be
started.
The internal/external
program switch does not
work or incorrectly
The door opens
automatically but closes
only after a long time or
not at all.
The speeds differ strongly
from the set parameters.
The connector of the braking circuit is
in the incorrect position.
The program switch is in the incorrect
position.
The signal shutdown
drive function (4/4a) is active.
The parameter program switch type is
incorrectly set.
The cable of the internal program
switch is not attached.
Connection error or switch defect.The wiring and function of the switch must be tested.
The hold-open time is too long.Reduce the hold-open time.
The program switches in the Permanent
Open position.
There is a signal from the safety sensor
on the opposite hinge side and it
prevents the closing.
There is a signal from a connected
activator that prevents the closing.
The teach-in run was performed with a
warm motor and the door panel weight
was therefore incorrectly determined.
The connector must be positioned correctly depending
on the arms assembly used.
See page 17 point 5.9.
Turn the program switch into the "OFF" position.
Test the wiring of the smoke detector or the stop signal
on 4/4a.
The type used must be correctly set as parameter
program switch type.
Test the cable and connect, if necessary.
Switch the program switch.
The signals of the safety sensors will be displayed for
the diagnosis directly with the 2 decimal
points of the LED display on the user
interface.
In case of a detection, the respective
decimal point will light. The wiring and function of
the system must be tested. If the LED at the top left
flashes, the wall suppression will be active. There is no
error.
The wiring of the connected activator must be tested.
A normally open contact is to be used in all cases.
The signal input 57/57a may be operated with external
voltage. Remove the signal lines 35, 57, 42 and 41 one
after another in order to localize the error.
Repeat the teach-in run with the motor cold.
30 ISEO
LED red
LED yellow
Power switch
LED green
IS 9100
—
11. Error messages
Display Display
LED
In 01none
In 08none
In 09none
In 11 The red
LED
lights
In 23none
In 61none
In 72none
In 73none
In 91none
Meaning/causeTroubleshooting
Blockage
The door is blocked due to an obstacle and
the door movement was stopped by the drive
unit.
Shutdown drive function
The contact 4/4a is opened. The drive unit
switches into the emergency mode and only a
manual passage is possible.
Upgrade Card signal error
The installed Upgrade Card was removed or
the intially installed Upgrade Card (container
module) had not been inserted during the
installation of 2 Upgrade Cards.
Resolution hold-open system
The hold-open system was triggered.
Locking alarm
The door is blocked in the CLOSED position.
An opening is not possible.
Communication error in case of a 2-panel
operation
The communciation between the 2 devices is
interrupted.
Current measurement circuit
The periodically performed test of the internal
current measurement circuit could not be
successfully performed.
Braking circuit test
The periodically performed test (every 24 hours)
of the internal braking circuit could not be
successfully performed.
DCW communication
At least 1 registered DCW device is missing.
The door movement should be tested in a deenergized state
and a possibly existing stiffness must be eliminated. The
permanent operation of a defective door may damage the drive
unit. A blocking is also often triggered by people. The reason
for this might be that the detection range of the sensors are
not suitable for the drive unit and that the door will inevitably
be touched during the passage. In this case, the detection
range of the sensors and/or the opening speed of the drive
unit should be increased. The effectiveness is to be verified by
passing through the door.
An emergency command mechanism, a door lock switch or
other safety system may be connected to the input. Either the
system has actually triggered or there is a defect.
The activation must be reset.
The drive unit starts the operation automatically. If this is
not the case, the wiring and the systems causing it must be
tested.
Installed Upgrade Cards must remain permanently in the
control unit and must not be removed. If several Upgrade
Cards are installed, the Upgrade card used first has the
function of a container module and must be the last one to be
attached to the control unit (see chapter Upgrade Card).
In case of a defective container module, a new set of
functional modules must be used.
The hold-open system can be triggered automatically by the
smoke detector and manually by a hand trigger button or by
disengaging the door panel. According to DIN 18263-4, the
recommissioning must be deliberately performed.
Depending on the configuration of the system, this is done by
the manually opening the door up to the taught opening angle,
via the PGS by switching into the OFF position or by a reset via
the pushbuttons
be ensured that the smoke detector has not been triggered. If
a reset has not been successful, there may be a defect on the
smoke detector connection and the system must be inspected
by qualified personnel.
The most frequent cause is a closed door.
The error can be avoided if a door lock switch is installed. The
door lock switch detects the switching state of the deadbolt
and switches the drive unit off, if necessary. A door lock
switch is recommended as the permanent opening against the
closed door may damage the drive unit or the door.
The communication cable between the 2 drive units must
be checked. After a visual inspection, check if the correct
interface on the control unit has been used.
System tolerances and environmental conditions influence
the current measurement. That is why it cannot always be
successfully completed with the first time. The information is
shown in this case This, for example, is the case if the door is
manually passed through during the measurement. The test
will be automatically repeated.
System tolerances and environmentally conditions influence
the braking circuit test. That is why it cannot always be
successfully completed with the first time. The information is
shown in this case This, for example, is the case if the door is
manually passed during the measurement. If the test has been
negative 10 x in a row, the error message E 73 will be output.
Reconnect the corresponding DCW device.
If this is not possible, you must restart the drive unit.
Press simultanuously the pushbuttons
internal user field for a minimum of 3 seconds.
and on the internal user field. It has to
and on the
31ISEO
IS 9100
—
Display Display
E 022 x
E 033 x
E 044 x
E 1212 x
E 1313 x
E 1515 x
E 255 x
E 51
E 52
E 53
E 626 x
E 636 x
E 717 x
E 727 x
E 737 x
LED
flashing
flashing
flashing
flashing
flashing
flashing
flashing
5 x
flashing
flashing
flashing
flashing
flashing
flashing
Meaning/causeTroubleshooting
Locking error
The drive unit tries to open or close a locking
device with a feedback contact or a DCW
locking device. An error occured.
DCW program switch is missing Check and replace, if necessary, the DCW program switch.
Test error safety sensor
The test of the corresponding safety sensors
has not been successful. A test signal is sent to
the corresponding sensor prior to each opening
or closing movement. The drive unit expects a
response within a certain time window.
EEPROM error
The internal memory check could not be
successfuly completed. The drive unit operates
in the closer mode.
Excess current detection
More power is taken from the system than the
mains adaptor can provide.
Faulty teach-in run
The teach-in run could not be completed.
SVP DCW PR module
The test was negative.
Incremental encoder error
The incremental encoder monitoring has
detected a
faulty state.
The second system has an incompatible
firmware version for the 2-panel operation.
The second system has an incompatible fire
protection setting.
System error 1 (2nd Switch-off path
In order to switch off the drive unit always
reliably, several switching elements are used.
They are periodically tested for its functioning.
System error 2 (current measurement circuit)
The current measurement circuit is part of the
safety mechanisms and will be periodically
tested for its functioning. The drive unit
operates in the emergency mode.
System error 3 (braking circuit)
The braking circuit is a safety element in the
closer mode and will be tested every 24 hours.
During the test, the motor is shut down during
the closing movement and the door closes a set
angle in the emergency mode. The test can be
noticed as a short jerk on the door panel and is
no reason for a complaint.
In this case, you have to assume a defect on the locking
device or an error in the wiring. The locking feedback
contact must be tested and replaced, if necessary.
First, it must be checked whether the parameter "Test
safety sensor" is configured accordingly. Then it is to be
checked whether the test has also been activated on the
sensor itself and whether it is operated with the same level.
The test is turned off when the sensors are delivered.
You can try a reinitialization by reloading the current
firmware. If that fails, the control unit must be replaced.
The motor consumes too much power or the control end
stage is defective. In case of recurrence, the components
motor gear unit and/or control unit are to be replaced.
The error can occur if the teach-in run has been
interrupted, e.g. through manipulation of the door during
the process. The teach-in run must be restarted.
Check the wiring and, if necessary, replace the PR module.
In case of an error, the plug connections of the incremental
encoder and the motor as well as the circuit of the locking
device are first to be checked for a short circuit. If no error
can be found, the motor gear unit must be replaced. The
error can be caused by a defective motor or a short circuit
in the electric circuit of the locking device. The motor gear
unit must be replaced in case of a defective motor.
Both control units are to be fitted with the same firmware
version.
In case of 2-panel systems, the Upgrade Card Fire
Protection must be installed in both control units.
If the test is always negative, the control unit must be
replaced.
If the test is always negative, the control unit must be
replaced.
The door closes in the deenergized state too fast
(in under 3 seconds).
Check and reduce, if necessary, the closing speed (see
page 18 point 5.11).
If the test is always negative despite the correctly set
closing speed, the control unit must be replaced.
32 ISEO
Energy management
- 1
The motor is too hot (e.g. due to an excessive
ambient temperature).
- 2The movement dynamics in the OPEN and CLOSED
The system responds automatically.
- 3The system shuts down for 3 minutes
- 4The hold-open time will be extended.
The movement dynamics in the CLOSED direction will be
reduced.
direction will be reduced.
(door closer mode).
IS 9100
—
12. Product operating description
12.1 Function description
The IS 9100 is electromechanical automatic swing door
drive. It automatically open swing doors once an activator
has been activated.
The door closes after the set hold-open time has lapsed.
If a suitable locking device is connected, it will be opened by
the movement of the door.
In case of a power failure, people can pass through the
door at any time; the drive will then work like a normal door
closer.
Functions
The drive features 4 different functions. The functions can
be selected on the program switch.
FunctionMeaning
OFF
AUTOMATIC
PERMANENT
OPEN
EXIT ONLY
12.2 Operating elements
The power switch is always on the door hinge side; the
internal program switch is always on the side of the main
closing edge.
Power switch Internal program switch
The door will be automatically opened once
the activator Night/Bank has been activated.
The door closes when the open-hold time
night/bank has ended.
The door will automatically open once an
activator has been activated.
The door will close again once the set holdopen time has expired.
The door will automatically open and stay
open as long as the function is activated.
The door will automatically open only after
the inside activator or the activator Night/
Bank has been activated.
The door will close again once the set holdopen time has expired.
Internal program switch
In order to select the function, you must set a combination
of both rocker switches on the internal program switch.
OFF
Both switches are set to "0".
AUTOMATIC
The front switch is set "0",
the rear switch is set to "I".
PERMANENT OPEN
The front switch is set to "0",
the rear switch is set to "II".
EXIT ONLY
(only for 1-panel systems)
The front switch is set to "I",
the rear switch is set to "I".
12.3 Activator
Activator, inside outside, night/bank and intercom system
may be connected to the device. The activator inside is
usually found inside a building or room. The activator outside
is found on the outside of a building or room. The activator
night/bank is installed on the outside and often designed as
a card reader or key switch button.
12.4 Manual lock
If the door is closed manually, the drive must be switched to
the function OFF in order to prevent damage to the system.
If a door lock switch is installed, the drive function will
be automatically shut off.
IS 9100 recommends the use of a door lock switch.
12.5 Low/Full Energy mode
Drive IS 9100 can be operated in the low and full energy
mode.
Power switch Internal program switch
Program switch
Use the program switch to select the function. The program
switch can be a 4-digit or 3-digit type.
In case of an internal, 3-digit program switch, the function
EXIT ONLY is not available for 2-panel systems.
Low energy mode
The low speed of the door avoids most of the risk posed by
automatic movements. The door opens very slowly and offers
therefore superior safety.
Full energy mode
The high speed makes it necessary to secure the turning
range of the door with sensors.
Safety sensors mounted to the door panel monitor the
turning range and will prevent people from getting hit by the
door as far as possible.
12.6 Safety sensor s
If the safety sensors on the hinge side detect an obstacle
during the opening, the door will stop.
If the safety sensors on the hinge side detect an obstacle
while the door is closed, the door will remain closed.
If the safety sensors on the opposite hinge side detect an
obstacle during the closing, the door will reverse.
If the safety sensors on the opposite hinge side detect an
obstacle while the door is open, the door will remain in the
open position.
If the monitoring range is free again, the drive will resume its
normal operation.
33ISEO
IS 9100
—
12.7 Maintenance interval display
If the internal 4-digit program switch is used, a service
interval display will be available. A yellow LED will inform
you about required maintenance work.
12.8 Use in a hold-open system
If the drive is used on a smoke control door or fire door,
the drive will usually be operated in a hold-open system in
combination with smoke detectors. The drive of the door will
keep the door open either permanently (PERMANENT OPEN)
or temporarily (AUTOMATIC). However, in case of a fire,
the door must close in order to prevent smoke and fire from
spreading. For this reason, the opening automatic of the
drive will be automatically shut off as soon as a connected
smoke detector detects smoke; this is indicated on the
smoke detector by a red LED. The door can then only be
opened manually. The hold-open function will be canceled
even if the power supply is interrupted.
Manual activation of the hold-open function
In case of danger, the door can also be closed manually either by pushing the optional red pushbutton with the label
"Close door" or by manually moving the door approx. 10-20
cm in the Closed direction.
Recommissioning the drive unit
In order to reestablish the drive function, the hold-open
system must be reset. In accordance with the legal
provisions, this must be carried out manually. The reset can
be carried out in different ways.
Reset via the door position
1. Reset the smoke detector (LED display is green).
2. Completely close the door.
3. Open the door to the adjusted opening width.
4. Release the door.
Reset via the program switch
1. Reset the smoke detector (LED display is green).
2. Program switch in OFF and back.
Smoke control doors and fire doors are important for
your safety. However, this is only the case if the doors
will properly close in the case of danger. Therefore, do
not use additional wedges or objects that could prevent
the closing.
13. Maintenance and care
Maintenance
Maintenance work must be carried out only with the system
de-ernergized (turn off the fuse protection on site).
Acceptance and regular inspection
As the operator of the automatic door, you are responsible for
the regular inspection of the system. An initial inspection is
required before the initial commissioning. The acceptance must
be carried out according to the inspection book by a person
trained by ISEO. The door system is then to be inspected and
maintained, if necessary, at least once a year by a specialist.
All inspections will be documented in the inspection book (from
page 8 in these operating instructions). It serves as proof that
you have fulfilled your obligations and it must be retained.
Have the door system inspected and maintained, if necessary, at
least once a year by a specialist.
The testing and approval must be carried out according to the
inspection book by a person trained by ISEO.
The results are to be documented and to be retained by the
operator for at least 1 year.
The following parts are wear parts and need to be checked at
least once a year and replaced, if necessary (see installation
instructions) :
•Arm assembly
•Sliding piece
•Slide channel
Use only original spare parts.
Care
Turn the program switch during the cleaning to the OFF
position or PERMANENT OPEN position in order to prevent
unintended movements.
Never let water or other liquids enter the drive
unit.
Never insert a metal object into the openings of the drive
unit. Otherwise, there will be the risk of an electrical shock.
Clean the drive with a moist cloth and common cleaning agents.
Do not use any scrubbing agents as they might damage the
surface.
Do not start the device before the surfaces are dry.
14. Maintenance by ISEO
A regular maintenance of your system will pay off :
weak spots are detected and eliminated early, the service life will
be increased.
ISEO and its authorized partners offers a premium maintenance
service for automatic doors and catching devices, whereby the
offcial seal of approval provides the operators of the building with
reliable safety. If not all door systems are properly tested, the
building operator will be liable for property damage and physical
injuries in case of an accident. Irrespective of safety aspects,
a regular maintenance makes also sense from an economic
point of view. This allows you to detect and eliminate possible
damage or wear early on. The risk of unforeseeable costs due to,
for example, high repair costs can be minimized – and we will
help you keeping an eye on your budget. The goal is always to
increase the service life of your door systems.
ISEO will assume the complete organization and execution of
the maintenance. Your benefits: all installations will be tested
by trained experts in regular intervals - even systems from other
manufacturers. The building operator does not have to take care
of anything; legal requirements will be met in a reliable manner.
34 ISEO
A maintenance contract for the door will ensure the tested
reliability according to a premium standard.
IS 9100
—
15. Troubleshooting
Functional errors may have many causes.
The errors are often caused by environmental conditions and
the drive unit will therefore try to detect and to react to them
accordingly. The drive unit stops the current function and
starts again after a waiting period or a new pulse. If it does
not work, the automatic function will be shut off and an error
message will be output.
This is indicated by a red LED on the program switch.
The display flashes or lights permanently and indicates an
error that need to be eliminated by the ISEO Service.
The following options are available to reset error messages:
1. Switch the program switch to the OFF position.
2. Mains reset. Switch off the power switch.
Restart after 10 seconds.
The cause should be analyzed and eliminated before an error
message is acknowledged.
Self-help in case of errors
In case errors occur during the operation
please check the following:
• Mains voltage available?
• Is the power switch on?
• Can the door be freely moved?
• Is the door manually locked, shutdown
(lock switch) activated?
• Has the correct function been selected with the
program switch?
• Is the turning range of the door free from obstacles?
• Has the hold-open system been triggered?
Please contact the Service Department if these points are
okay and the doors system still does not work.
16. Disassembly, recycling and disposal
17. EC Declaration of conformity
ISEO Serrature s.p.a.
Via San Girolamo 13
25055 Pisogne (BS)
Italy
hereby declares that the products
IS9100
comply with the provisions of the named EC Directive(s) and
that the standards and/or technical specifications referred to
in the following have been applied.
Directive:2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic
compatibility
Harmonized European standard, national rule:
EN 13849-1 EN ISO 12100-1 EN ISO 14121-1
BGR 232 EN 61000 - 6 - 2 EN 61000 - 6 - 3
EN 61000 - 3 - 2 EN 61000 - 3 - 3 EN 55022
EN 60335 - 1 EN 60950 - 1
18. EC Declaration of incorporation
ISEO Serrature s.p.a.
Via San Girolamo 13
25055 Pisogne (BS)
Italy
hereby declares that the incomplete machine
IS9100
complies with the following basic requirements of the
Machine Directive (2006/42/EC)- Appendix I, Article:
The incomplete machine also complies with all relevant
provisions of the directives 2006/95/EC und 2004/108/EC.
It may be installed and operated in automatic door
systems in accordance with the Machine Directive if the
manufacturer of the system ensures that all requirements
of the Machine Directive are complied with and if the
manufacturer issues a EC Declaration of conformity.
The disassembly is carried out in the reverse order of the
installation manual and must be carried out by qualified
personnel.
De-energize the door system before disassembling the
door system.
Dispose the product in an environmentally friendly
manner. Electronic parts and batteries may not be
disposed via the general trash.
Take them to an appropriate collection point for
disposal.
Always comply with the applicable national legal provisions.
35ISEO
R
Internal program switch
In order to select the function, you must set a combination
of both rocker switches on the internal program switch.
OFF
Both switches are set to "0".
AUTOMATIC
The front switch is set "0",
the rear switch is set to "I".
PERMANENT OPEN
The front switch is set to "0",
the rear switch is set to "II".
EXIT ONLY
(only for 1-panel systems)
The front switch is set to "I",
the rear switch is set to "I".
ISEO Serrature s.p.a.
Via San Girolamo 13
25055 Pisogne (BS)
Italy
Tel. : +39 0364 8821
Fax : +39 0364 882263
iseo@iseo.eu
059130-45532, 09/16, Subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.