IR-Tec WallSenzr BDT-700 Series Installation Instructions And Operators Manual

P/N: 058-70007-001 Printed in Taiwanwww.irtec.com
This product may be covered by one or more U.S. patents or patent applications. Please visit www.irtec.com for more information.
OVERVIEW
The BDT-700 series is a 2-pole dual technology low voltage wall switch sensor designed to fit in a standard NEMA wall box for automatic lighting control. This state-of-the-art wall switch sensor combines digital Passive Infrared (PIR) and advanced High Frequency Doppler (HFD) sensing technologies into an aesthetically pleasing housing to provide excellent occupancy/vacancy sensing performance within its 180° field of view detection range.
The BDT-700Sx contains two isolated dry contacts, and two push buttons, for controlling two lighting loads or circuits independently via the connected Power Packs or BMS. A dual color LED indicates the status of sensor detection, GREEN for PIR and BLUE for HFD. Pressing the push-button will change the state of relay contacts manually. The sensor provides typical occupancy sensing (Auto-ON, Auto-OFF) control on pole-1 and vacancy sensing (Manual-ON, Auto-OFF) control on pole-2. Different control modes of each pole can be programmed via DIP switch settings. Presentation Mode (PM) allows the occupant to switch off the load as desired by pressing the specific push-button. The load will remain off if motion is detected before the time delay elapses. Pressing the push-button again will turn the load back ON and the sensor will operate as per sensor setting. If no motion has been detected and the time delay expires, sensor will return to normal operation and turn on the load with the next sensed motion.
INSTALLATION NOTES
SPECIFICATIONS
Low Voltage Dual-Tech Wall Switch
INSTALLATION INSTRUCTIONS
BDT-700 Series
Power input
Current drain
Sensing technology
Control output
Contact rating
Detectable speed
Mounting height
Ambient light level
Delay time setting
Op. humidity
Op. temperature
Dimensions
Detection coverage
12~24VDC ± 5%
10/40 mA, 24VDC @vacant/occupied
Digital PIR & High Frequency Doppler
2 x form A relay, isolated dry contact
Max. 2A @30VDC, isolated
1~10 ft./sec. (0.3~3 m/sec)
3 ~ 5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft high
Minor motion - 20 ft x 20 ft (W x L) @4 ft high
7 levels, from dark to 24 Hr. (ALS disabled)
T/1’/3’/5’/10’/20’/30’, T=10 sec. for testing
Max. 95% RH, non-condensate
-40°F ~ 131°F (-40°C ~ 55°C)
4.13”H x 1.77”W x 1.65”D (w/mounting plate)
INDOOR USE ONLY Utilisation a L'interieur Uniquement
The PIR sensor is more sensitive to the movements “crossing” the detection zones than “toward” or “away” it. To obtain better sensitivity, ensure the sensor to have clear field of view for the occupant’s motion within the desired detection coverage.
In general, the HFD sensor has better sensitivity to the minor motions than the PIR sensor. The HFD sensor could possibly detect the movements out of sight through non-metallic partition or enclosure. If so, reduce the HFD sensitivity to prevent unwanted triggering.
The sensor should be mounted within the specified mounting height to achieve optimal performance.
Do NOT mount the sensor directly above or nearby a heat source, or where unintended motion (e.g. hallway traffic) will be “seen” by the sensor.
1.
2.
3.
4.
DETECTION COVERAGE
40’
Top view
Side view
4’
7’
30’
40’
Minor motion
20’
20’
Major motion
180°, 30 ft x 40 ft (W x L)
Turn power OFF at circuit breaker before installing Power Pack or Sensors.
Do NOT touch the square window of infrared sensor under the lens assembly.
WARNING: Do Not Install To and/or Cover a Junction Box Having Class 1, 3 or Power and Lighting Circuits
Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 1, 3 or Power and Lighting Wiring
Coupez l'alimentation au disjoncteur avant d'installer Power Pack ou capteurs.
Ne PAS toucher la fenêtre carrée de capteur infrarouge sous l'ensemble de l'objectif
AVERTISSEMENT : Classe 2 Câblage de périphériques Seulement - Ne PAS reclasser et installer Classe 1, 3 ou alimentation et circuits d'éclairage
WARNING & CAUTION
AVERTISSEMENT & PRUDENCE
INSTALLATION
WIRING DIAGRAM
Sensor control ON/OFF
(PPU-300/301)
The sensor may be available with other control options, consult a qualified electrician or contact info@irtec.com for assistance.
Hot
Black White
Red Red
Neut Relay Relay
DC24V
GND
Control
Manual
Hold ON
Hold OFF
Load
Hot 120~277V
Neutral
Hot
Black White
Red Red
Neut Relay Relay
DC24V
GND
Control
Manual
Hold ON
Hold OFF
Load
Hot 120~277V
Neutral
Circuit 1
Circuit 2
Red
Black
Green
Green White
White
Red
Black
Blue
DC+ GND
COM NO
COM NO
Circuit 1
Circuit 2
Black
PPU-300/301
PPU-300/301
Install the power pack and connect the load according to its instructions.
Connect the low voltage wires of power pack with the respective wires of the sensor according to the diagram of desired control.
Turn on the line voltage power for the power pack.
Conduct sensor operation test.
Attach the wallplate cover after testing and setting completed.
1.
2.
3.
4.
5.
LENS
POLE-2 PUSH-BUTTON
POLE-1 PUSH-BUTTON
TIME setting determines the delay time that the sensor will hold the load ON after the last motion detected. Factory setting is 10 minutes, and it can be changed by pointing the arrowhead of potentiometer to the specific position.
TIME - Delay time
LUX setting determines the threshold of ambient light level that the sensor will inhibit switching on the load. The factory setting is ALS disabled (24 Hr) for testing convenience, and it can be changed by pointing the arrowhead of potentiometer to the specific position.
LUX – Ambient light level
TESTING
Restore the line power for sensor operation and wait for the sensor to warm-up (GREEN LED will blink during the warm-up period).
Move within the desired range and observe the sensor detection. BLUE blink indicates the PIR sensor detected, and GREEN blink indicates the HFD sensor detected. Move outside of the desired range and observe if the HFD sensor can detect. If GREEN LED blinks, reducing the HFD sensitivity accordingly.
Replace the wall plate cover after sensor testing and setting completed.
1.
2.
3.
NOTE: The connected load will be switched ON as delay time set (factory default 10 minutes) after the power applied. The delay time can be set to the shortest (10 seconds) for test convenience. Ensure to set the TIME back to the desired
delay for optimum operation after test.
To program the sensor control mode or change the settings, press the push-button cover and slide it down as shown.
The combinations of DIP switch 1 and 2 determine the sensitivity of HFD sensor.
SETTING DIP Switch
HFD Sensitivity
- SW1 & 2
- SW3
- SW4
- SW5
DIP switch 3 changes the operating sensor. If necessary, the BDT-700 can be programmed as a single HFD wall switch sensor.
Sensor will turn ON the load of pole-1 when it detects the presence of occupant, and turn OFF automatically if no occupant motion is detected before the time delay elapses. The ambient light sensor (ALS) will inhibit switching ON the load if ambient light level is higher than the set threshold.
VSOC requires occupant to press the pole-2 push-button to turn ON the connected load of pole-2, and sensor will automatically switch OFF the load if no occupant motion is detected before the time delay elapses.
NOTE: The sensor will automatically turn ON the light if it detects occupant activity within 30 seconds after time delay elapsed.
Sensor will control the load of pole-1 as in OSAC, but with ALS and Presentation Mode (PM) both active.
Operating Sensor
Pole-1 Control Mode
Occupancy Sensing with ALS Control (OSAC)
Vacancy Sensing Only Control (VSOC)
The sensor will automatically turn ON the connected load of pole-2 when ambient light is lower than the LUX level set, and turn OFF the load automatically when ambient light is higher than the threshold set.
Ambient Light Sensing Only (ALSO)
The sensor will control the load of pole-2 as per pole-1 is set, but with an Extended Delay for 5 minutes.
Pole One with Extended Delay (POED)
Occupancy Sensing with ALS & PM (OSAP)
Pole-2 Control Mode
Slide
ON
12
3 4 5
TIME
LUX
Press
&
DIP Switch
ON
1 2
3 4 5
TIME
LUX
ON
1 2
3 4 5
ON
1 2
3 4 5
ON
1 2
3 4 5
ON
1 2
3 4 5
PIR & HFD
HFD only
ON
1 2
3 4 5
ON
1 2
3 4 5
SW5=ON
ON
1
SW5
2
3 4 5
SW5=OFF
SW4=ON
ON
1
SW5
2
3 4 5
SW4
SW5=OFF
SW4=OFF
ON
1
SW5
2
3 4 5
SW4
SW4=ON
ON
1
SW4
2
3 4 5
SW4=OFF
ON
1
SW4
2
3 4 5
LUX
1 7
2 6
3 5
4
TIME
1 7
2 6
3 5
4
LUX
TIME T
POS. 1 2 3 4 5 6 7
1’ 3’ 5’ 10’ 20’ 30’
10 20 35 50
100 150 24H
Factory Set
Loading...