IR-Tec WallSenzr BBS-702 series Installation Instructions Manual

OVERVIEW
The BBS-702 series is a member of IR-TEC’s WALLSENZR family of low voltage wall switch sensor designed to fit in a standard NEMA wall box. The sensor combines state-of-the-art passive infrared sensing technology with décor aesthetics to provide optimal energy-saving for the applications.
The model BBS-702S comes with an ambient light sensor (ALS) to inhibit its output if ambient light levels are higher than required. The Accu-Set digital potentiometers make delay time (TIME) and ambient light level (LUX) settings fast, easy and accurate. Isolated dry contact output allows the BBS-702 series to control the load with IR-TEC Power Packs or integrate with BMS/BAS.
INSTALLATION NOTES
SPECIFICATIONS
Low Voltage Wall Switch Sensor
INSTALLATION INSTRUCTIONS
BBS-702 Series
Power input
Current drain
Infrared sensor
Control output
Contact rating
Detectable speed
Mounting height
Ambient light level
Delay time setting
Op. humidity
Op. temperature
Dimensions
Detection coverage
12~24VDC ± 5%
5/20 mA, 24VDC @vacant/occupied
Dual element pyroelectric
Form A dry contact & active low
Max. 2A @30VDC
1~10 ft./sec. (0.3~3 m/sec)
3 ~ 5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft high
Minor motion - 20 ft x 20 ft (W x L) @4 ft high
7 levels, from dark to 24 Hr.
T/1’/3’/5’/10’/20’/30’, T=10 sec. for testing
Max. 95% RH, non-condensate
-40°F ~ 131°F (-40°C ~ 55°C)
4.13”H x 1.77”W x 1.65”D (w/mounting plate)
INDOOR USE ONLY Utilisation a L'interieur Uniquement
AVERTISSEMENT & PRUDENCE
WARNING & CAUTION
DETECTION COVERAGE
Top view
Side view
Minor motion
40’
4’
7’
30’
40’
20’
20’
Major motion
The sensor is more sensitive to the movements “crossing” the detection zones than “toward” or “away” the sensor. To obtain better sensitivity, ensure the sensor to have clear field of view for the occupant’s motion within the desired detection coverage.
The closer the movement is to the sensor, the more sensitive the sensor is.
The sensor should be mounted within the specified mounting height for optimal performance.
Avoid blocking the sensor with any obstacles, such as door, plant, partition or furniture. As a general rule, every occupant within the desired range should be able to clearly see the sensor.
Do NOT mount the sensor directly above or nearby a heat source, or where unintended motion (e.g. hallway traffic) will be “seen” by the sensor.
1.
2.
3.
4.
5.
Turn power OFF at circuit breaker before installing Power Pack or Sensors.
Do NOT touch the square window of infrared sensor under the lens assembly.
Do Not Install To and/or Cover a Junction Box Having Class 1, 3 or Power and Lighting Circuits
Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 1, 3 or Power and Lighting Wiring
Coupez l'alimentation au disjoncteur avant d'installer Power Pack ou capteurs.
Ne PAS toucher la fenêtre carrée de capteur infrarouge sous l'ensemble de l'objectif
Ne pas installer ou couvrir une boîte de jonction ayant les classes 1 et 3 ou circuits de puissance et d'éclairage.
Classe 2 Câblage de périphériques Seulement - Ne PAS reclasser et installer Classe 1, 3 ou alimentation et circuits d'éclairage
P/N: 058-70200-003 Printed in Taiwanwww.irtec.com
This product may be covered by one or more U.S. patents or patent applications. Please visit www.irtec.com for more information.
Black White
Red
Red Black Green White Yellow
Red
Load
Hot 120~277V
Neutral
Hot
Neut Relay Relay
DC24V
GND
Control
Manual
Hold ON
Hold OFF
PPU-300
DC+ GND COM NO OUT+
Red Black Green White Yellow
DC+ GND COM NO OUT+
Red
Black
Blue
Grey
BOS-515
Black White
Red
Red Black Green White Yellow
Red
Load
Hot 120~277V
Neutral
Hot
Neut Relay Relay
DC24V
GND
Control
Manual
Hold ON
Hold OFF
PPU-300
DC+ GND COM NO OUT+
Red Black Green White Yellow
DC+ GND COM NO OUT+
BOS-515
Red
Black
Blue
Grey
Orange
Brown
IR-TEC International Ltd. warranties this product to be free of defects in materials or workmanship for a period of five years from date of shipment. There are no obligations or liabilities on the part of IR-TEC International Ltd. for consequential damages arising out or in connection with the use or performance of this product or other indirect damages with respect to loss of property, revenue, or profit, or cost of removal, installation or reinstallation.
WARRANTY
INSTALLATION
Install the power pack and connect the load according to its instructions.
Connect the low voltage wires of power pack with the respective wires of the sensor according to the diagram of desired control.
Turn ON the line voltage power for the power pack.
Conduct sensor operation test.
Attach the wallplate cover after testing and setting completed.
1.
2.
3.
4.
5.
WIRING DIAGRAM
OPERATION & SETTINGS
DIP Switch Settings
The BBS-702 series low voltage wall switch sensor employs passive infrared (PIR) sensing technology to monitor the occupancy status within its coverage, and provide an isolated dry contact output for the power pack to control the operation of connected load. An independent push-button control output is available to for multi-way manual ON/OFF control.
The BBS-702 features adjustable light-off delay time and ambient light level to inhibit the unnecessary lighting when ambient light is higher than the level set. The time delay (TIME) and ambient light level (LUX) settings can be changed by rotating the respective Accu-Set potentiometer at different position. A 2P DIP switch is available to disable the sensor LED indicator and lower the sensitivity.
The sensor can be applied to provide occupancy sensing control (Auto-ON, Auto-OFF) or vacancy sensing control (Manual-ON, Auto-OFF) through different wiring.
For other control options, please consult a qualified lighting control engineer or contact info@irtec.com for assistance.
This is the delay time that the BBS-702 series sensor will hold the load ON after the last motion detected. The factory setting is 10 minutes, and it can be changed by pointing the arrowhead of potentiometer to the specific position.
TIME - Delay time
This is the threshold of ambient light level that the sensor will inhibit switching on the load. The factory setting is ALS disabled (24 Hr) for test convenience, and it can be changed by pointing the arrowhead of potentiometer to the specific position.
After the sensor installed and wiring completed, sensor operation test can be conducted as instructed below;
LUX – Ambient light level
TESTING
Apply the power to the Power Pack.
Walk within the desired coverage. LED will blink to indicate the motion sensed.
Replace the wall plate cover after completing the sensor test and setting.
1.
2.
3.
NOTE: The connected load will be switched ON as delay time set (factory default 10 minutes) once apply the power. The delay time can be set to the shortest (10 seconds) for ease of testing.
Ensure to set the TIME as desired for optimum operation after testing.
LUX
1 7
2 6
3 5
4
TIME
1 7
2 6
3 5
4
LUX
TIME T
POS. 1 2 3 4 5 6 7
1’ 3’ 5’ 10’ 20’ 30’
5 10 30 50
100 150 24H Factory Set
LENS
PUSH­BUTTON
Occupancy Sensing Control with PPU-300
Vacancy Sensing Control with PPU-300
To change the sensor settings, press the push-button cover and slide it down as shown.
Slide
ON
12
LUX
TIME
Press
&
ON
1 2
LUX TIME
DIP Switch
Enabled
Disabled
ON
OFF
#1 (LED indicator)
Standard
Low
#2 (Sensitivity)
SW