LC-730S/730T I/M Eng. V4.0 99-07. U.S.A Patent No: 5,557,173. EUROPEAN Patent No:0760498, Taiwan Patent Pending.
SOLO
Energy Saving Auto-Switch
LC-730S / 730T
Installation Instructions
DETECTION PATTERN
Top View 140°, 10 x 10m (at 25°C)
10m
140
1.0
I
1.4m
Side View
WIRING DIAGRAM
A. LC-730S single control
Live
Neutral
Load
AC
MAINS
B. For heavy load or non-applicable PL lamp
Live
Neutral
Load
AC
MAINS
220K
AC Relay
C. LC-730T Two-way parallel control
AC
MAINS
Load
LC-730T
LC-730T
LC-730T is available
for incandescent only
INSTALLATION
Important !
Ceiling mounted
1. Do not install SOLO behind the opened door,
curtain or any objects may block the sensor.
2. Do not place the front cover up side down. Note
the “UP” mark inside the front cover.
TEST & ADJUSTMENTS
1. Apply AC power and the light will be switched
on about 30 seconds for SOLO to warm up.
2. Walk across within the detection range, light will
be switched on whenever motion is detected.
3. Adjust the TIME and LUX controllers to set the
desired light-on threshold and delay time.
TIME
Light-on delay time can be set from approximate 8
seconds to 6 minutes. Further detection during delay
time will reset the timer.
8''
2'
3'
4'
6'
8''
2'
3'
4'
6'
8''
2'
3'
4'
6'
About 8 sec. About 3 min. About 6 min.
LUX
A built-in CdS photocell determines the operation of
by sensing the ambient light level.
Night Dusk Day & Night
(2 ~ 4 lux) (10 ~ 20 lux) (24 hours)
SPECIFICATIONS
Detection method Passive Infrared (PIR)
Infrared sensor Dual element, low noise
Power supply 120 VAC, 60 Hz
Detection range
140°, 10m at 25°C
Delay time 8 sec. ~ 6 min.
Load capacity Max. 120V, 300W ( Resistive)
Screw pitch 83.50mm
Mounting height 1.0 ~ 1.4m (3.3 ~ 4.6 ft)
Temperature
-20° ~ +50°C (-4° ~ +122°F)
Dimensions 120 x 70 x 50 mm
Unit weight 130 gram