IR TEC RS420900 User Manual

ON-LRD-209S
Line Voltage OS-NET Sensor
INSTALLATION INSTRUCTIONS
Indoor dry location use only Utilisation a L'interieur Uniquement
DIMENSIONS
R5.3mm(0.21”)
11.8mm (0.46”)
42mm (1.65”)
23mm(0.91”)
21mm (0.83”)
80mm (3.15”)
21mm (0.98”)
WARNING & CAUTION
Do NOT touch the square window of infrared sensor under the lens assembly.
Open Type Photoelectric Switches. Install this device in accordance with electrical codes and
protect with circuit breaker. Install the sensor at least 1 ft. away from any occupant.
AVERTISSEMENT & PRUDENCE
Risque de choc électrique - Débranchez l'alimentation avant l'entretien.
Ne PAS toucher la fenêtre carrée de capteur infrarouge sous l'ensemble de l'objectif.
Ouvrir Type commutateurs optoélectroniques.
R2mm(0.08”)
25mm
(thread tip)
This product may be covered by one or more U.S. patents or patent applications. Please visit www.irtec.com for more information.
OVERVIEW
The ON-LRD-209S is a low profile OS-NET Sensor (ONS) packed with multiple sensing control functionalities including occupancy/vacancy sensing, daylight harvesting, bi-level StepDIM or continuous SmartDIM, and wireless mesh networking capability for top-notch intelligent lighting control.
Being a member of Mini ONS, this sensor can be integrated with general office luminaires through a 1” hole. A flat lens provides excellent detection to the office activities within its coverage of 2X mounting height. With ON-LRD-209S, you can effortlessly achieve code-compliant, energy efficient smart lighting control through a wireless sensor mesh network effortlessly deployed while installing the OS-NET enabled luminaires in commercial environments.
APPLICATION NOTES
The sensor is more sensitive to the movements
1. “crossing” the detection zones than “toward” or “away” the sensor unit. To obtain better sensitivity, avoid placing the sensor in line with occupant path.
2.
The closer the movement is to the sensor, the more sensitive the sensor is. The higher the sensor is installed, the larger movement is required to be detected.
Ensure to place the sensor at least at 1.5m (5 ft.) away
3. from air supply ducts as rapid air flow may cause false activations.
4.
The sensor cannot “see” the movements behind obstacles, such as tall furniture, shelf, glass or partitions. Avoid placing the sensor where obstructions may block the sensor’s line of sight.
5.
The partition of workstation could block the sensor view to occupant movements, it is best to place the sensor over the intersection of workstation. For large open office, place multiple sensors so that there is overlap coverage with each adjacent sensor.
6.
To obtain optimal wireless communication range, avoid enveloping the sensor with a metallic enclosure.
Wiring Diagram
DIM
DIM
Line
Neutral
BALLAST LED DRIVER
N
L
Black
L
Red
N
White Violet
DIM
Gray
P/N: 058-60901-001Printed in Taiwanwww.irtec.com
PRELIMINARY
SPECIFICATIONS
Power supply Maximum Load Infrared sensor Dim control HIC protection Wireless protocol Radio frequency Number of Channel Radio range Detectable speed Mounting height Detection range Remote range Op. humidity Op. temperature Dimensions
120/230/277VAC, 50/60Hz Ballast Electronic (LED)-500VA Digital quad-element pyroelectric sensor 0-10V, ±5%, isolated, max 25mA Max. 80A for 16.7msec. Modified Zigbee Light Link (ZLL) 2405~2480MHz 16ch 5 m (16 ft) @ indoor only
0.15 ~ 3 m/sec. (0.5~10 ft./sec.)
2.4~3.6 m (8~12 ft) 2X mounting height Typ. 10 m (33 ft), indoor with no backlight Max. 95% RH
-40°C~70°C (-40°F~158°F) 80x42x34.8mm (3.15”x1.65”x1.37”)
DETECTION PATTERN
3m
Minor Motion
2 mM
TA4 m
6 m
Mounting Height
Coverage Diameter
2.4 m (8 ft) 3.0 m (10 ft)
1.0 m (3 ft)
M
3.0 m (10 ft)
T
5.0 m (16 ft)
A
2.0 m (7 ft)
4.0 m (13 ft)
6.0 m (20 ft)
NOTE:
1.
Use 0/1-10V dimmable driver/ballast to enable dimming control.
Ensure to connect the LINE and NEUTRAL wires
2. correctly. Reverse connection may damage the sensor permanently.
Ensure TOTAL isolation between DIM+/DIM- and
3. GROUND of line voltage to avoid damaging the sensor.
Always conduct factory test with GROUND connected.
4.
M
TAToward
Across
3.6 m (12 ft)
3.0 m (10 ft)
5.0 m (16 ft)
7.0 m (23 ft)
SENSOR MOUNTING
Drop Mount
Sensor assembly hole
25mm (1”)
Arch Panel
Sensor
Spacer
Panel
Nut
Flat Panel
Panel
Nut-Free Mount
Sensor assembly hole
24~25mm (0.094~1”)
28mm (0.11”)
Panel
Sensor
Nut
Screw (recommended screw size Ø2.3x8mm)
23mm (0.09”)
(bracket height subject to fixture design)
Metal bracket
1
2
1
2
SETTING
Programming Guide
All sensor settings can be configured, in individual or group basis, by an OS-NET Remote Programmer SRP-281. Following table highlights the setting items and options available with ON-LRD-209S. For detailed setting operation, please refer to the OS-NET Programming Guide available for download from www.irtec.com.
Settings Description Options (*Denotes factory default)
INDIV-SET To setup an individual device GROUP-SET To setup all devices of the group with same settings CONTROL Control schemes available for OS-NET sensor. ON/OFF, OSO, OSLA, OSLATO*, DSVM, DSC, VSC,
AMBIENT LUX Thresholds of ambient light level for OS-NET sensor to execute the
control.
DELAY Delay time that sensor will turn off or fade down the light. 30 sec./1/3/5/10*/15/20/30/60 min. TIME OFF Delay time that sensor will keep the light at low dim level after the
OFF delay time elapsed.
HIGH DIM High dim is the output level set to control the light during occupancy,
or when ambient light is lower than the threshold if daylight sensing scheme is selected.
LOW DIM/SmartDIM Low dim is the output level set to dim the light when space is vacant
for bi-level control. Low dim setting will become SmartDIM bar if SmartDIM control is selected.
RAMP UP Speed of lighting output increase. INSTANT*/SOFT/SLOW FADE DOWN Speed of lighting output decrease. INSTANT/SOFT*/SLOW VM-TB Time duration BEFORE Virtual Midnight.
Only available if DSVM is selected.
VM-TA Time duration AFTER Virtual Midnight.
Only available if DSVM is selected.
LED INDICATOR Enable or disable the LED indicator of the sensor. ENABLED*/DISABLED SENSITIVITY Sensitivity of occupancy sensor. HIGH*/NORMAL/LOW
OSB, OFF 10/20/40/60/80/200/400/600/1000/2000/DISABLED*/
CURRENT
10/30 sec./3/5/10*/15/20/30/45/60 min.
50/55/60/65/70/80/90/100%* SmartDIM
0/5/10/15/20/25/30*/40%
0.5/1/1.5/2/2.5*/3/3.5/4/4.5/5/5.5/6 hour
0.5/1/1.5/2/2.5/3/3.5/4*/4.5/5/5.5/6 hour
SETTING ACKNOWLEDGEMENT
The sensor will acknowledge setting success or failure with different indications by device LED or connected lighting.
INDICATION ACKNOWLEDGEMENT REMARKS
Device LED fast blinking in GREEN and BLUE. The device is scanning and linking to the network. The fast blinking (on-off per 0.2 second)
Device LED blinks twice every 2-second in
The sensor detects occupant’s motion. GREEN means the device is network linked.
GREEN or BLUE. Device LED blinks twice every 2-second for
5 minutes, and then 15-second after power
The device is set with daylight sensing control. (DSVM or DSC)
applied. Device short beeps twice.
Device beeps one long and two short. The connected lights flash twice.
The connected lights flash twice.
Receiving a single setting or control command.
1. Multiple setting data UPLOAD successful.
2. GROUP LINK successful.
1. Factory default setting resumed.
2. SmartDIM setting completed.
Federal Communication Commission Interference Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
FCC ID: NRIRS420900
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
only appears during network linking.
BLUE means the device is unlinked. GREEN means the device is network linked.
BLUE means the device is unlinked.
Industry Canada statement: IC: 22993-209RS4AC901
This device complies with ISED’s licence-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d’ ISED applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes : (1) le dispositif ne doit pas produire de brouillage préjudiciable, et (2) ce dispositif doit accepter tout brouillage reçu, y compris un brouillage susceptible de provoquer un fonctionnement indésirable.
Radiation Exposure Statement:
This equipment complies with ISED radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with greater than 20cm between the radiator & your body.
Déclaration d'exposition aux radiations:
Cet équipement est conforme aux limites d'exposition aux rayonnements ISED établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé à plus de 20 cm entre le radiateur et votre corps.
CONTROL SCHEME
The ON-LRD-209S series can be programmed to control the connected lighting in one of the schemes as below.
Scheme Description
ON/OFF
OSO
OSLA
OSLATO
DSVM
DSC
VSC
OSB
OFF
This is a typical
occupancy sensing control
scheme. Lighting will be inhibited when the ambient light level is higher than the set threshold, regardless of occupancy or vacancy. When the ambient light level is lower than the set threshold, the controlled light will be automatically turned on once the sensor detects the presence of occupant, and turned off after the delay time elapsed.
NOTE:
This scheme can be used with
This is an
occupancy sensing control
dimmable
or
non-dimmable
lighting, but not for HID lighting.
scheme can be applied in areas that require 24-hour lighting. When space is vacant, the lights will be maintained at Low Dim level. Whenever space is occupied, lighting output will be increased to High Dim level or continuously regulated to maintain within the pre-set range by SmartDIM control.
NOTE:
Do
NOT
This is an
use this scheme to control
occupancy sensing control
non-dimmable
lighting.
scheme can be applied in spaces that require automatic lighting when the ambient light level is lower than the set threshold. Lighting will be inhibited if the ambient light level is higher than the set threshold, regardless of occupancy or vacancy. When the ambient light level is lower than the set threshold, the sensor will automatically control the light at Low Dim level. When sensor detects the presence of an occupant, lighting output will be increased to the High Dim level or continuously regulated within the pre-set range by SmartDIM control. After the delay time elapsed, lighting output will be reduced to Low Dim level or shut off if the ambient light is higher than the set threshold.
NOTE:
Do
NOT
This is an
use this scheme to control
occupancy sensing control
non-dimmable
lighting.
scheme can be applied in spaces that require maintaining Low Dim lighting for a period of time before shutting off. Lighting will be inhibited if the ambient light level is higher than the set threshold, regardless of occupancy or vacancy. When the ambient light level is lower than the set threshold, and any sensor detects the presence of occupant, lighting output will be increased to High Dim level or continuously regulated to maintain overall lighting level within the pre-set range by SmartDIM control. After the delay time elapsed, lighting output will be reduced to Low Dim level for a period of TIME OFF delay before shut off.
NOTE:
This scheme requires
dimmable
lighting to enable dimming control. If lighting is
non-dimmable
, there will be no dim control
and the delay time will be extended with the TIME OFF (TO) delay.
This is a
daylight sensing control
scheme can be applied in spaces that require automatically dimming the lighting output to a low level between a certain time before and after virtual midnight. Lighting will be inhibited if the ambient light level is higher than the set threshold. When the ambient light level is lower than the set threshold, the sensor will turn the light to High Dim level or continuously regulate the output to maintain overall lighting level within the pre-set range by SmartDIM control. Lighting output will be reduced to Low Dim level from a certain time before virtual midnight to a certain time after.
NOTE:
This scheme requires
dimmable
lighting to enable dimming control. If lighting is
non-dimmable
, all lights will remain on
whenever ambient light level is lower than the set threshold. This is a
daylight sensing control
scheme can be applied in spaces that require automatic lighting whenever the ambient light is lower than the set threshold. The sensor will automatically turn on the light to High Dim level or continuously regulate the output to maintain overall lighting level within the pre-set range by SmartDIM control when the ambient light level is lower than the set threshold, and automatically turn off the light when the ambient light level is higher than the set threshold.
NOTE:
This scheme requires
dimmable
lighting to enable dimming control. If lighting is
non-dimmable
, all lights will remain on
whenever ambient light level is lower than the threshold. This is a
vacancy sensing control
scheme can be applied in spaces that require users to manually turn on the light, and have the sensor turn off the light automatically. The occupant would have to press the OS-NET Button to turn on the lighting group assigned. The sensor will control the lights at High Dim level or continuously regulate the output to maintain overall lighting level within the pre-set range by SmartDIM control. The sensor will control the connected lighting as per OSLATO scheme.
NOTE:
This scheme requires
dimmable
lighting to enable dimming control. If lighting is
non-dimmable
, there will be no dim control
and the delay time will be extended with the TIME OFF (TO) delay. This is an advanced
occupancy sensing control
scheme can be applied in open offices to provide background light level before the area of entire lighting group is vacant. Lighting will be inhibited if the ambient light level is higher than the set threshold, regardless of occupancy or vacancy. When the ambient light level is lower than the set threshold and the first occupant is detected by a grouped sensor, the output of sensor connected light will be increased to High Dim level or continuously regulated within the pre-set range by SmartDIM control during occupancy, and the unoccupied areas of entire lighting group will brighten up to Low Dim level as background light. The entire lighting group turns off after the last person leaves and delay time elapsed.
NOTE:
Do
NOT
This is a
use this scheme to control
manual control
scheme can be used when you need the light to be off for a certain period of time.
non-dimmable
lighting.
Once this scheme is set, all OS-NET controlled lighting will remain off until another scheme is selected.
www.irtec.com