IR TEC RS330100 User Manual

ON-PPU-301
OS-NET Power Pack & Load Controller
INSTALLATION INSTRUCTIONS
ONLY QUALIFIED ELECTRICIANS SHOULD INSTALL THIS DEVICE.
Indoor dry location use only Utilisation a L'interieur Uniquement
WARNING & CAUTION
TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING THIS DEVICE. Install this device at least 1 ft. away from any occupant. Risk of Electric Shock – More than one disconnect switch may be required to
de-energize the equipment before servicing. Use UL listed wires for all wiring connections. Low voltage wiring connection should
use at least 22 AWG wire. Load switching wiring connection should use at least 12 AWG. AC power line voltage wiring connection should use at least 18 AWG wire. Wire all Class 2 circuits using types CL3, CL3P, CL3R, or equivalent conductors. For plenum return ceilings, use UL listed plenum-approved cables.
Always check national, state and local building codes for necessary compliance. After initial wiring is complete, ensure to verify all the low and high voltage wires are correctly connected before applying the power. Incorrect wiring could possibly cause permanent damage to the power pack, lighting system, occupancy sensors or other control devices.
AVERTISSEMENT & PRUDENCE
COUPER LE COURANT AU DISJONCTEUR AVANT D'INSTALLER BLOCS D’ALIMENTATION.
Risque de choc électrique – Plus d'un interrupteur peut être nécessaire pour mettre hors tension le matériel avant l'entretien.
Utiliser homologation UL fils pour toutes les connections de câblage. Basse tension connection de câblage doit utiliser au moins 22 fils de AWG. Commutation de charges connections de câblage doit utiliser au moins 12 AWG. Tension de la ligne de courante alternative connections de câblage doit utiliser au moins 18 fils de AWG. Brancher tous les circuits de classe 2 à l'aide de types CL3, CL3P, CL3R, ou conducteurs équivalent. Pour les plafonds de retour de plénum, utiliser UL câbles ignifuges approuvés énuméré.
Toujours vérifier les codes de constructions nationaux, étatiques et locales pour le respect nécessaire et conformité. Après le câblage initial est terminé, assurez-vous de vérifier que tous les fils basse et haute tension sont connectés correctement avant d'appliquer la puissance. Un câblage incorrect pourrait causer des dommages permanents à la batterie d'alimentation, système d'éclairage, aux détecteurs de présence ou autres dispositifs de commande.
ENCLOSED ENERGY MANAGEMENT EQUIPMENT 4ZS9
INTRODUCTION
The ON-PPU-301 is an OS-NET enabled power pack and plug load controller featuring wireless mesh network capability to provide top-notch intelligent lighting control. This power pack not only supplies 24 VDC power for IR-TEC’s low voltage occupancy sensors, but also provides load switching up to 20A upon receiving control signals from wired sensors, or wireless commands from networked OS-NET devices of the same group. A unique radio command will be transmitted to other OS-NET devices for executing coordinated group controls whenever ON-PPU-301 receives a control signal from a wired sensor.
This device can be attached to a junction box, cable tray, or fixture through a 1/2 inch knockout with the designed threaded nipple and locknut. Subject to the wiring connection and control setting, the ON-PPU-301 can be programmed to provide occupancy or vacancy sensing control to the connected
Federal Communication Commission Interference Statement FCC ID: NRIRS330100
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
Radiation Exposure Statement: This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
P/N: Z50-00516-000 Printed in Taiwanwww.irtec.com
light or plug load control for codes compliance. Numerous control settings, including burn-in time, delay time, group/ungroup, lock/unlock…etc. can be intuitively configured via a 2-way handheld remote programmer.
With ON-PPU-301, you can easily enable wireless smart lighting control with IR-TEC low voltage occupancy sensors. Zone lighting and plug load control can be easily done at any junction box or fixture.
Combining the ON-PPU-301 with the OS-NET Button gives unparalleled flexibility and ease for room control. Whether it is a new construction or retrofit project, OS-NET will save time in installation, commissioning, and user adoption.
SPECIFICATIONS
Power supply DC power output Maximum load
Control signal Wireless protocol Radio frequency Radio range Remote range Op. humidity Op. temperature Dimensions Purpose of control
Type Action External Pollution
Situation Rated Impulse
Voltage
120/277 VAC, 60 Hz 24 V, 100 mA max.
1 HP @120VAC 1 HP @ 240VAC 20A Resistive @ 120/277VAC 20A Ballast @120/277VAC
Dry contact or active low open collector Modified Zigbee Light Link (ZLL)
2.4 GHz Typical 15 m (50 ft.) @ indoor Typ. 10 m (33 ft), indoor with no backlight Max 95% RH
-20°C ~ 55°C (-4°F ~ 122°F) 111 x 90 x 46 mm (4.37” x 3.54” x 1.80”) Operating Control with Electronic
Independently Mounted Type 1 Pollution Degree 2
4000 V
PRELIMINARY
Programming Guide
SETTING
The ON-PPU-301 can be configured to link with other OS-NET devices wirelessly to execute specific control via SRP-281. For more details about remote operation, please refer to the OS-NET Programming Guide available from www.irtec.com.
Settings Description Options
INDIV-SET To setup an individual device GROUP-SET To setup all devices of the
CONTROL Control schemes
DELAY Delay time that
group with same settings
available for ON-PPU
ON-PPU will turn off load
ON/OFF, VSC, PLC
30 sec./1/3/5/10/15/ 20/30/60 min.
INSTALLATION
Low voltage wires
Line voltage wires
Load switching wires
IMPORTANT!
1.
All line voltage wiring connections should be made inside of junction box.
2.
To obtain optimal wireless communication, avoid placing the device behind a metal mesh/plate.
To enable wireless network control, the
3. ON-PPU-301 must be grouped and linked with the other OS-NET devices. An “ungrouped” ON-PPU-301 with low voltage occupancy sensor connected will only operate in standalone control.
Default
ON/OFF
20 min.
WIRING DIAGRAMS
Line Voltage Wires
Color Description Function Gauge
Neutral
White
Line
Black Red
Relay contacts
Red
Following are basic wiring diagrams for typical controls, consult with an IR-TEC team member for correct wiring diagram if a more complex control is required.
Line voltage
Load switching
Color Description Function Gauge
Red
18 AWG
Black Blue
12 AWG
A. Occupancy/Vacancy Sensing Control
Red (
DC24V)
Black (
DC )
Blue (
Control)
Black (
Line)
White (Neutral) Red (
Relay)
Red (
Relay)
S
OS-NET Sensor OS-NET Button
NOTE: For Vacancy Sensing Control (VSC), at least one OS-NET Button should be installed and grouped with the ON-PPU-301 to enable manual-on control.
B. Plug Load Control
Red (
DC24V)
Black (
DC )
Blue (
Control)
Black (
Line)
White (Neutral) Red (
Relay)
Red (
Relay)
S
OS-NET Sensor OS-NET Button
NOTE: If PLC is selected, the OFF-command from OS-NET Button will be ignored.
B
Low Voltage Wires
DC24V DC-
Control
DC power supply
Sensor signal input
Red
DC+
Black
DC
Green
COM
White
NO
Line 120/277V
Neutral
Load
B
Red
DC+
Black
DC
Green
COM
White
NO
Line 120/277V
Neutral
N L
IR-TEC Low Voltage Occupancy Sensor
IR-TEC Low Voltage Occupancy Sensor
Ground
G
24 AWG Class 2
CONTROL SCHEME
The following schemes can be programmed via CONTROL setting of the SRP-281. Depending on the connection of wired Low Voltage Occupancy Sensor (LVOS) and grouped OS-NET Sensor (ONS)/OS-NET Button (ONB), the ON-PPU may control the load in slightly different patterns.
CONTROL = ON/OFF
The load will be switched ON when ON-PPU receives 1) control signal from a wired LVOS, or 2) wireless command from a grouped ONS/ONB, and switched OFF when programmed delay time elapses or receives the OFF-command from a grouped OSB.
If the load was switched OFF via an OSB, the ON-PPU will operate in Presentation Mode. The load will remain OFF if motion is detected before the delay time elapse. The ON-PPU will resume to auto-ON, auto-OFF control after delay time elapsed.
“√” means “one or more units connected/grouped”
LVOS ONS ONB ON-PPU-301 Operations
Load ON Load OFF -­Delay reset Load ON Load OFF -­Delay reset Load ON Load OFF --
Delay reset Load ON Load OFF ­Delay reset Load ON Load OFF -
Delay reset Load ON Load OFF ­Delay reset Load ON Load OFF Delay reset
Any LVOS detects occupancy Last active LVOS delay elapses Not activated Any ONS detects occupancy ON-PPU delay elapses When ONS detects occupancy Any ONB is pressed ON ON-PPU delay elapses or ONB is pressed OFF When ONB is pressed ON Any LVOS/ONS detects occupancy Both LVOS and ON-PPU delays elapse When ONS detects occupancy Any LVOS detects occupancy or ONB is pressed ON Last LVOS delay elapses or ONB is pressed OFF When ONB is pressed ON Any ONS detects occupancy or ONB is pressed ON ON-PPU delays elapse or ONB is pressed OFF When ONS detects occupancy or ONB is pressed ON Any LVOS/ONS detects occupancy or ONB is pressed ON Both LVOS and ON-PPU delays elapse or ONB is pressed OFF When ONS detects occupancy or ONB is pressed ON
CONTROL = VSC
VSC refers to Vacancy Sensing Control. This control requires user to turn ON the load by pressing a grouped OSB, and the ON-PPU will turn OFF the load when delay time elapses or receives the OFF-command from a grouped OSB.
LVOS ONS ONB ON-PPU-301 Operations
Load ON Load OFF - ­Delay reset Load ON Load OFF ­Delay reset Load ON Load OFF ­Delay reset Load ON Load OFF Delay reset
Any ONB is pressed ON ON-PPU delay elapses When ONB is pressed ON Any ONB is pressed ON Both LVOS and ON-PPU delays elapse or ONB is pressed OFF When ONB is pressed ON Any ONB is pressed ON ON-PPU delays elapse or ONB is pressed OFF When ONS detects occupancy or ONB is pressed ON Any ONB is pressed ON Both LVOS and ON-PPU delays elapse or ONB is pressed OFF When ONS detects occupancy or ONB is pressed ON
CONTROL = PLC
PLC refers to Plug Load Control. The ON-PPU will enable the plug load power when it receives 1) control signal from a wired low voltage occupancy sensor, or 2) wireless command from a grouped OS-NET Sensor/Button, and switch OFF the plug load power after the area is vacant and programmed delay time elapsed.
LVOS ONS ONB ON-PPU-301 Operations
NOTE
The DELAY timer of ON-PPU will only be activated by receiving the wireless command
1. from grouped OS-NET devices.
2.
The ON-PPU will transmit OCC signal wirelessly for group control when wired LVOS detects occupancy.
3.
To prevent unintentionally shutting off the power for plug load control, ensure to set the DELAY of the ON-PPU longer than the setting of grouped ONS.
Under PLC mode, all OFF-command from the OS-NET Button will be ignored.
4.
Same as ON/OFF control-­Same as ON/OFF control-­Load ON Any ONB is pressed ON Load OFF -- ON-PPU delay elapses
Delay reset When ONB is pressed ON Same as ON/OFF Control­Load ON Any LVOS detects occupancy or ONB is pressed ON Load OFF - Last LVOS delay elapses
Delay reset When ONB is pressed ON Load ON -Any ONS detects occupancy or ONB is pressed ON Load OFF ON-PPU delay elapses
Delay reset When ONS detects occupancy or ONB is pressed ON Load ON Any LVOS/ONS detects occupancy or ONB is pressed ON Load OFF Both LVOS and ON-PPU delays elapse Delay reset When ONS detects occupancy or ONB is pressed ON
DEVICE LED ACKNOWLEDGEMENT
The device will acknowledge the setting success or failure with following indications by device LED in BLUE or GREEN. BLUE means the device is unlinked and GREEN means the device is network linked.
DEVICE LED ACKNOWLEDGEMENT
LED on Control scheme is set to ON/OFF sensing control
Slow blinking (on-off per 0.5 second) Control scheme is set to vacancy sensing control (VSC)
Blinks twice every 2-second Control scheme is set to plug load control (PLC)
Blinks irregularly in BLUE or GREEN Receiving commands from the remote
Fast blinking in BLUE and GREEN intermittently
Blinks slow once and fast twice The device is under test mode
Blinks slow once and fast once The device is under burn-in mode Lit for 2 seconds in GREEN Grouping/setting is completed
Scanning for an open network and linking
Loading...