IPS RTS-ON-3k0-2U-LCD-6x, RTS-ON-10k0-6U-LCD-16x9, RTS-ON-2k0-2U-LCD-BC48, RTS-ON-3k0-2U-LCD-BC72, RTS-ON-6k0-3U-LCD-BC192 User Manual

...
RTS-ON-user-manual_ENG-R1t
USER MANUAL
Thanks for using our products Please strictly obey all the instructions in this manual and pay attention to all the warning and operation
information. It is not advisable to install or operate the machine before reading this manual.
manual_ENG-R1
1
1. Safety instructions
1.1 UPS safety instructions
●Before applying the UPS system, Please read through all safety information and operating instructions carefully.
It’s recommended to save this manual properly for future reading.
●Do not install the UPS system near the water or in moist environments.
●Do not install the UPS system where it would be exposed to direct sunlight or near the heater.
●Place the UPS staying away from the wall for some distances, ensure enough space on each side of UPS, do
not block ventilation holes in the UPS housing. Install it by following the instructions in the manual.
Please do not open the UPS case as you will, there is a high risk of electric shocks inside.
●Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the UPS.
●Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended.
Attention:
UPS has high voltage inside, for personal safety, please do not repair by yourself. If any questions, please contact local service center or dealer.
1.2 Battery safety instructions
●Battery life cycle will be shortened as environment temperature rise. Replacing battery periodically can help to keep UPS in normal state and assure backup time required.
●Battery replacement should be done by authorized technician. If you want to replace the battery cable, please purchase it from our local service center or distributors to avoid fever and lighter which can cause fire from inadequate power capacity.
●Batteries may cause electric shocks and have a high short-circuit current, for human being safety, please follow
the specifications as below when replace the batteries:
A. Remove wristwatches, rings and other metal objects B. Use only tools with insulated grips and handles C. Wear insulated shoes and gloves D. Do not put the metal tools or parts on the battery E. Before disconnecting the terminals on battery, please cut off all the loads to battery first.
●Do not dispose of the batteries with fire so as to avoid explosion.
●Don’t open the battery, electrolyte inside will do harm to eyes and skin. Please use plenty of clean water to wash
if touching and go to see a doctor.
●Do not connect the positive pole and negative pole directly, otherwise it cause electric shocks or will be on fire.
manual_ENG-R1
2
●The battery circuit is not isolated from the input voltage, high voltage may occur between the battery terminals
and ground, before touching, please verify no voltage is present.
2. Features
2.1 Unpacking inspection
●Open the UPS package, please check the enclosed accessories including a user manual, communication cable,
support feet, CD-ROM. The long-back model also includes the cable for connection to battery bank.
Check the UPS if any damage in transport. If find its damaged or parts missing, do not power on, please turn to
the carrier and dealer.
To determine whether this UPS is the model you want to buy. Check the model name showed both on the front
panel and rear panel of UPS to confirm.
Model
Type
RTS-ON-1k0-2U-LCD-2x9
1KVA RT Standard model
RTS-ON-2k0-2U-LCD-4x9
2KVA RT Standard model
RTS-ON-3k0-2U-LCD-6x9
3KVA RT Standard model
RTS-ON-6k0-6U-LCD-16x7
6KVA RT Standard model
RTS-ON-10k0-6U-LCD-16x9
10KVA RT Standard model
RTS-ON-1k0-2U-LCD-BC24
1KVA RT Long backup model
RTS-ON-2k0-2U-LCD-BC48
2KVA RT Long backup model
RTS-ON-3k0-2U-LCD-BC72
3KVA RT Long backup model
RTS-ON-6k0-3U-LCD-BC192
6KVA RT Long backup model
RTS-ON-10k0-3U-LCD-BC192
10KVA RT Long backup model
Note:
Please save the packaging box and packaging materials for future transport use. As a heavy product, please transit the UPS with care.
2.2 UPS rear panel view
2.2.1 The type of 120V (output could be 100V, 110V, 115V, 120V, 127V)
AStandard model
manual_ENG-R1
3
USB
TEL/MODEM/FAX
IN
OUT
-+-
+
24VDC 40A
EXT.BATTERY
RESET
FUSE 125VAC,15A
INPUT
EPO
RS232
OUTPUT SOCKET
R
E
S
E
T
R
E
S
E
T
T
O
INTELLIGENT SLOT
1
2
4
5
6
3
7
10
9
8
INTELLIGENT SLOT
RS232
EPO
TEL/MODEM/FAX
IN
OUT
USB
INTELLIGENT SLOT
5
6
4
8
7
INPUT
-+-
+
FUSE 125VAC 25A
RESET
48VDC 40A
EXT.BATTERY
OUTPUT SOCKET
OUTPUT
N L
R
E
S
E
T
R
E
S
E
T
T
O
1
2
9
11
10
15A
20A
a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA&3KVA RT rear panel
BLong-run model
USB
TEL/MODEM/FAX
IN
OUT
-+-
+
24VDC 40A
EXT.BATTERY
RESET
FUSE 125VAC,15A
INPUT
EPO
RS232
OUTPUT SOCKET
R
E
S
E
T
R
E
S
E
T
T
O
INTELLIGENT SLOT
1
2
4
5
6
3
7
10
9
8
INPUT
-+-
+
FUSE 125VAC 25A
RESET
48VDC 40A
EXT.BATTERY
OUTPUT SOCKET
OUTPUT
N L
R
E
S
E
T
R
E
S
E
T
T
O
TEL/MODEM/FAX
IN
OUT
EPO
USB
RS232
INTELLIGENT SLOT
2
4
6
10
1
5
7
8
9
11
15A
20A
a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel
EPO
USB
RS232
TEL/MODEM/FAX
IN
OUT
INTELLIGENT SLOT
5
7
8
9
11
2
4
6
10 3
INPUT
-+ -+
FUSE 125VAC 25A
RESET
48VDC 40A
EXT.BATTERY
OUTPUT SOCKET
OUTPUT
N L
R
E
S
E
T
R
E
S
E
T
T
O
1
20A
15A
+ -
DC OUTPUT
+ -
DC OUTPUT
72VDC 72VDC
9
9
c. 0.9PF 3KVA RT rear panel d. 0.9PF Battery Pack rear panel
2.2.2 The type of 220V (output could be 208V, 210V, 220V, 230V, 240V)
AStandard model
USB
TEL/MODEM/FAX
IN
OUT
-+-
+
24VDC 40A
EXT.BATTERY
RESET
FUSE 250VAC,8A
INPUT
OUTPUT SOCKET
INTELLIGENT SLOT
EPO
RS232
R
E
S
E
T
R
E
S
E
T
T
O
9
1
7
8
6
10
2
3
5
4
-+ -+
48VDC 40A
R
E
S
E
T
R
E
S
E
T
T
O
TEL/MODEM/FAX
INOUT
OUTPUT SOCKET
INTELLIGENT SLOT
USB
EPO
RS232
2
13
56 4
8
7
10
9
RESET
FUSE 250VAC,20AINPUT
----
EXT.BATTERY
a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel
-+ -+
72VDC 40A
R
E
S
E
T
R
E
S
E
T
T
O
OUTPUT SOCKET
USB
EPO
TEL/MODEM/FAX
IN
OUT
-+ -+
EXT.BATTERY
RESET
FUSE 250VAC,20A
INPUT
RS232
USB
EPO
INTELLIGENT SLOT
56 4
10
9
2
1
3
8
7
OUTPUT
L N
INPUT
L N
ON
OFF
RS232
USB
EPO
RS232
2
3
9
7
4
5
6
8
11
12
c. 0.9PF 3KVA RT rear panel d. 0.9PF 6/10KVA RT rear panel
manual_ENG-R1
4
BLong-run model
USB
TEL/MODEM/FAX
IN
OUT
-+-
+
24VDC 40A
EXT.BATTERY
RESET
FUSE 250VAC,8A
INPUT
OUTPUT SOCKET
INTELLIGENT SLOT
EPO
RS232
R
E
S
E
T
R
E
S
E
T
T
O
9
1
7
8
6
10
2
3
5
4
RESET
FUSE 250VAC,15A INPUT
OUTPUT SOCKET
EPO
USB
RS232
INTELLIGENT SLOT
R
E
S
E
T
R
E
S
E
T
T
O
-+ -+
48VDC 40A
EXT.BATTERY
TEL/MODEM/FAX
IN OUT
9 10
2 1
8
4
5 7
6
a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel
RESET
FUSE 250VAC,20A
INPUT
-+-
+
72VDC 40A
EXT.BATTERY
OUTPUT SOCKET
EPO
USB
TEL/MODEM/FAX
IN
OUT
INTELLIGENT
SLOT
R
E
S
E
T
R
E
S
E
T
T
O
RS232
2 1
4
6
9
10
8
5
7
3
OUTPUT
L N
INPUT
L N
ON
OFF
RS232
USB
EPO
RS232
2
3
9
7
4
5
6
8
11
12
c. 0.9PF 3KVA RT rear panel d. 0.9PF 6/10KVA RT rear panel
Input Power Terminals Over Current Protector Fan USB Emergency Power Off RS232 Communication Interface Intelligent Slot Surge Protection for Network/Fax/Modem Battery Slot Output Socket Terminal Block
Parallel Port.
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
1
Note: Diagrams take the type of 0.9PF for example, the type of 0.8PF is similar. Due to the technology upgrading and development, goods and diagrams might have some differences.
3. Installation instructions
3.1 Attention items of installation
The UPS installation environment must be with good ventilation, away from water, flammable gases and corrosive entities.
Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake hole will be unobstructed.
●The peripheral environment temperature around the UPS should be within 0 ~ 40 .
If dismantling the machine at low temperatures, there may be condensation droplets, users can not install or
operate it before UPS completely got dry both inside and outside, otherwise there will be danger of electric shocks.
Place the UPS near the mains socket so that can cut off AC mains without any delay at any emergent case.
Make sure the load connect to the UPS is off when users connect the load to UPS, and then turn on the load one
by one later.
●Please connect the UPS with the socket which is over-current protected. Do not connect the UPS with the socket which rated current is less than the Maximum input current of the UPS.
●All the power socket should be configured with earthing device for safety.
●UPS could be electrified or powered no matter the input power cable is tied or not, even when the UPS is off. The
only way to cut off the output is switching off the UPS and disconnecting the mains power supply.
●For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the AC mains power energizes the UPS, it will automatically charge the battery. Without prior charging, UPS output remains as usual but with shorter back-up time than normal.
●When connected to motor, display equipment, laser printer etc, UPS power selection should be based on the
startup power of the load which is usually twice as rated power.
●When wiring, please ensure input cables and output cables are connected firmly.
If install a leakage current protective switch, please install it on output cable.
For EA900II 6-10K Series UPS, before installing, prepare wires for terminal block of the UPS based on the
following table.
Model
Wiring spec(AWG)
Input
Output
Battery
Non-isolated Neutral
Ground
6KVA S
6mm2
6mm2
6mm2
6mm2
6mm2
6KVA H
6mm2
6mm2
6mm2
6mm2
6mm2
10KVA S
10mm2
10mm2
10mm2
10mm2
10mm2
10KVA H
10mm2
10mm2
10mm2
10mm2
10mm2
3.2 1-10K Single UPS installation and output connection
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
2
3.2.1 Tower installation
The UPS system is packaged with feet and extensions, those can be used to install tower UPS model.
Take out two groups of feet and extensions from package, assemble by embedding them with each other
as shown in step1, Place the two support feet in parallel on horizontal surface, and then put the machine into two support feet carefully as shown in step2 and step3. Make sure the mains power is off when you move it.
The battery pack and the UPS unit can be put together, install as the following steps, please do not install
the UPS upside down.
The UPS unit and the battery pack also can be placed horizontally without support feet, remember that
put the battery pack under the UPS unit. The battery pack is heavy, be careful when you move it.
3.2.2 Rack installation
Please follow below steps to install the UPS unit into the rack mount enclosure.
Attach mounting ears to the side mounting holes of UPS by using
screws, and the ears should face forward, please refer to the
diagrams.
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
3
Slide the UPS unit into the rack mount enclosure, attach the UPS to the rack with screws.
3.2.2 Single UPS output connection
Normally, output connection of 1~10KVA type is configured with sockets or terminal blocks, users can plug the load cable into the UPS socket to energize the load as following pictures. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
Note: For the type of 6-10KVA, do not use the wall receptacle as the input power source for the UPS, which rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
RESET
FUSE 125VAC,20A
-+ -+
48VDC 40A
EXT.BATTERY
OUTPUT SOCKET
/MODEM/
IN
OUT
R
E
S
E
T
R
E
S
E
T
T
O
LOAD
OUTPUT
L N
INPUT
L N
ON
OFF
Input
output
Battery
Protector
Over Current
OUTPUT
L N N L
INPUT
Protector
Over Current
Battery
Input
output
3.3 Parallel system of 6-10K UPS installation and output connection
Only 6-10K UPS and containing parallel ports can do parallel operation, other types is not supported. N+X parallel structure is the most reliable power supply structure at present, N stands for the minimum number of
UPS for the load, X stands for the number of redundant UPSX absolutely means how many UPS could be malfunctioning at the same time and the parallel UPS system is still steady. The larger X is, the system is more reliable. N+X is the best method for high reliability. Just install a little more simple accessories, at most 8 UPS could work together to form a flexible parallel system.
This structure of power supply system increases the power safety and reliability. For example, two single UPS make up a parallel system to load averagely, when one is malfunctioning, another one can take the whole load independently. It allows isolation repairs for malfunctioning UPS, and according to users own different requirements, every single UPS could install manual maintenance bypass switch.
3.3.1 Parallel system installation
The function of parallel operation is an optional function of UPS, users can purchase parallel function parts (including parallel card and parallel wire) and contact service personnel to install. At most 8 UPS work together by using parallel wires to form a flexible parallel system. Each UPS should be equipped individual battery pack.
Parallel system installation requirement:
●Install parallel wire, users need to purchase a specific parallel wire from our company, it’s not recommended to
use other type parallel wires. There are 2m length and 5m length to be chosen.
Prepare wires for terminal block of the UPS based on the wiring spec table above in attention items.
●Each UPS input wiring please comply with the requirements of single UPS wiring.
●Every UPS is recommended to connect together to one common utility power terminal block.
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
4
The output cables of each UPS are recommended to connect together on a common terminal block, then output
to the load.
●Each UPS should be equipped individual battery pack.
Wiring installation for parallel UPS system please refer to the wiring diagrams are given below, switches of 6KVA
should withstand more than 40A/250VAC, and switches of 10KVA should withstand more than 63A/250VAC.
●Output wiring length requirements: when the distance between the load and each UPS is less than 20 meters, the
length difference of cables to the load should be less than 20%; when the distance between the load and each UPS is more than 20 meters, the length difference of cables to the load should be less than 10%.
Installation procedure:
Install parallel wires. Two UPS to form an UPS parallel system, in order to ensure the reliability of the parallel system, there is only one way to wire two UPS, use two parallel wires to connect two UPS like the diagram showing below, connection looks like a circle. If three or more than three UPS are needed, the connection is similar, you can refer to the diagram as below. How many UPS unit, how many parallel wires you need.
OUTPUT
L
N
INPUT
L
N
OUTPUT
L N
INPUT
L N
OUTPUT
L N
INPUT
L N
OUTPUT
L N
INPUT
L N
OUTPUT
L N
INPUT
L N
Parallel system of two UPS wiring Parallel system of three UPS wiring
Attention: For three UPS parallel system or more than three unites system type, please remove the short pin
CN3 on the parallel card as following pictures, Only keep the first unit and the last unit short pin(CN3) connected
and remove the rest ones. Open the UPS cover, find the parallel card, it’s installed on the rear panel. Take off the short pin CN3, then screw the cover back. It’s advisable to contact to local dealer to operate, if you have to operate
by yourself, please be sure that you have cut off all the electrical connection, be careful the electric shocks from the UPS inside.
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
5
Connect output cables of all UPS together to a common terminal block. Connect input cables of all UPS together to one common utility power terminal block.
I nput common termi nal bl ock
Uti l i ty power suppl y
Out put common termi nal bl ock
Load
Load
Load
...
Parallel UPS system view
Short Pin
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
6
N
L N
L
Input
Output
N
L N
L
Wiring diagram for two UPS parallel system
Input
Output
N
L
N
L N
L N
L
N
L N
L
Wiring diagram for three UPS parallel system
If the UPS is the standard type, each UPS has batteries inside already. If the UPS is the long-run type, each UPS should be equipped a individual battery pack.
After installation, check all the wiring carefully, be sure to confirm correct, then can operate the system.
3.3.2 Parallel system operation and maintenance
General operation of parallel system, please refer to the operation instruction of single UPS. Before starting the system, need to set up different ID for each UPS, specific settings please refer to the instruction of ID setting which is given in single UPS panel function setting.
Turn on the parallel system
Start the system with mains power: After inputting the mains powerturn on any one UPS of system, others will
start by themselves at same time. All UPS will enter into Line mode.
●Start the system without mains power: Make sure the battery pack is connected well and the breaker is in “ON”
position. There are two ways to start the UPS parallel system without utility power supply: A: Press the key on each UPS, make each LCD of each UPS light up, then turn on any one UPS of system,
others will start by themselves at same time. All UPS will enter into BAT mode. B: Turn on UPS one by one.
RACK TOWER ONLINE UPS
4.011.2017 RTS-ON-user-manual_ENG-R1
7
Turn off the parallel system
Hold on the OFF KEY of any one UPS of system for more than 4 seconds, it would turn off the whole parallel system. Hold on the OFF KEY of any one UPS of system for more than 1 second(less than 4 seconds), it would turn off single UPS you choose, of course if you need to turn on it again or turn on any other single UPS of the system, just press ON KEY of that UPS to start it.
Parallel system maintenance
●Parallel system maintenance please follow the maintenance of single UPS.
If one UPS of parallel system is malfunctioning, first of all, turn off the malfunctioning UPS, then cut off the input
power to the faulty UPS and disconnect the output of faulty UPS to the parallel system, make sure that there is no electrical connection with malfunctioning UPS, after all of those, it’s safe to do operation.
3.4 External battery connection procedure for long back up type
●For different UPS type, users are instructed to configure different battery voltage as below sheet. More or less
units are forbidden, or else something abnormal or faulty will appear.
Type
Battery Quantity
(unit)
Battery Voltage
(volt)
1KVA
2/3
24/36
1.5KVA 4 48
2KVA
4/6
48/72
3KVA
6/8
72/96
6KVA
16
192
10KVA
16
192
●One end of battery cable is for UPS terminals while the other end with triple cables is for battery terminals. Correct
installation procedure is highly vital or else probable electric shock will arise. Users are strictly required to follow the below procedure.
●Connect battery in correct way and make sure the total battery voltage is available for UPS.
●Correctly connect the long battery cable to battery terminals first, red wire is to positive plate while black is to
negative. If users connect the UPS first, electric shock or other danger could not be avoided.
●Before connecting load after UPS, users should supply main power to UPS and energize it.
●Connect long battery cable to UPS terminals with correct poles link (red is for “+”, black is for“-”), UPS will start the
charging work automatically.
RESET
FUSE 125VAC,20A
-+-
+
48VDC 40A
EXT.BATTERY
OUTPUT
R
E
S
E
T
R
E
S
E
T
T
O
Battery
OUTPUT
L N N L
INPUT
RED
BLACK
-
+
-
+
-
+
-
+
-
+
-
+