IPM balancedpower plus Installation And Operation Manual

INSTALLATION
and
OPERATION MANUAL
for
International Power Machines
®
BalancedPower Plus
10-300 kVA
(UPS)
SAVE THESE IMPORTA NT
SAFE TY I NS T RUCTIONS
This manual contains important safety instructions that should be followed during installation and maintenance of the UPS and Battery Cabinets.
International Power Machines® 10451 Brockwood Road Dallas, Texas 75238-1641 Phone: (214) 342-6100
Service Hotline (800) 777-8922
IPM at your service
International Power Machines Corporation considers prompt customer service to be an integral pa rt of its produ ct. Ou r Fi eld S ervi c e D ep artm e nt i s accessible by telephon e 24 hours a day, seven d ays a week to im plement timely servicing of our equipment.
IPM 24-HOUR SERVICE HOTLINE:
Phone: (800) 777-8922
Outside US.: (919) 871-1800
Fax: (214) 342-6115
When calling for service assistance, have the following information and a rec ord of r eadi ngs a nd al arm ligh ts fr om the m achi ne’s m on itor panel available for the IPM service dispatcher:
Serial Number:
(On label inside machine’s front door.)
Input Output Voltage Frequency (Hz) Model No. Monitor
International Power Machines
10451 Brockwood Road
Dallas, Texas 75238-1641 U.S.A.
800-527-1208
Important No tice
The manufacturer recommends that the monitor panel be inspected visually every eight-hour shift to see that lights are operat­ing and no alarm conditions exist. If any unusual conditions exist, call facility mainte­nance personnel or IPM/LorTec Service Hotline:
(800/777-8922)
TABLE OF CONTENTS
Section I
Theory of Operation
1.1 General............................................................................................... Page 1.1
1.2 Rectifier/Charger.........................................................................................1.1
1.3 Inverter........................................................................................................1.2
1.4 Static Bypass Switch....................................................................................1.2
1.5 Batteries ......................................................................................................1.2
1.6 Control Logic and Control Circuitry ............................................................1.3
1.7 Digital Monitoring Panel.............................................................................. 1.3
1.8 Multi-Level Passwords................................................................................1.4
1.9 Phone Home Alarm Reporting.....................................................................1.5
1.10 Dial-Back Security......................................................................................1.5
Section II
Installation
2.1 General................................................................................................... Page 2.1
2.2 Mechanical Preparation of UPS.......................................................................2.1
Figure 2-1 Casters and Leveling Feet..................................................................2.3
2.3 Mechanical Preparation of the Battery Cabinet(s)............................................2.4
2.4 Signal Wiring..................................................................................................2.5
2.4.1 Remote Control (TB 1)...........................................................................2.5
2.4.2 Optional Remote Status Panel (TB2).......................................................2.6
2.4.3 Optional RS232 Communication (J6-J9).................................................2.6
2.4.4 Optional Modem Connection (J10-J13)...................................................2.6
2.4.5 Optional Site Interface Assembly (A26)..................................................2.7
2.4.6 Optional User Specified Alarm (A33).....................................................2.7
2.5 Power Wiring - UPS to Battery Cabinet...........................................................2.7
2.6 Connecting the Cabinets..................................................................................2.8
Figure 2.2 Bolting Battery Cabinet to UPS.........................................................2.8
2.7 Re-assembly....................................................................................................2.8
2.8 AC Power Connection.....................................................................................2.9
2.9 Activating the Battery Cabinet(s).....................................................................2.11
2.9.1 Battery Cabinet #1...................................................................................2.12
2.9.2 Battery Cabinet #2...................................................................................2.13
2.9.3 Battery Cabinets #3 and #4 ......................................................................2.14
2.9.4 Final Battery Cabinet Connections...........................................................2.14
Figure 2-3 Battery Interconnections ....................................................................2.15
Installation Dr awings
BP+15-150,2.9X
5/95
Page i
Table of Contents
Section III Operation
3.1 General...................................................................................................Page 3.1
3.2 Safety Considerations ......................................................................................3.1
3.2.1 Cleanliness ...............................................................................................3.1
3.2.2 Fire........................................................................................................... 3.1
3.2.3 Security/Personnel....................................................................................3.2
3.3 Radio Frequency Energy Hazard .....................................................................3.2
3.4 Digital Monitoring Panel................................................................................. 3.3
Figure 3.1 Digital Monitoring Panel................................................................... 3.3
3.4.1 Indicator Lights.........................................................................................3.4
3.4.2 Message Screens........................................................................................3.5
3.4.3 Display Select Pushbuttons........................................................................3.9
3.4.4 Parameter Adjust Pushbuttons ...................................................................3.9
3.4.5 Alarm Silence Pushbutton..........................................................................3.9
3.4.6 Emergency Power Off Pushbutton.............................................................3.10
3.5 System Controls..............................................................................................3.10
3.6 UPS Operating Procedures..............................................................................3.11
3.6.1 System Startup Procedure..........................................................................3.11
3.6.2 Alarm Identity/History...............................................................................3.14
Table 3-1, Typical Alarm History Screens..........................................................3.15
Table 3-2, Alarm Identity/History Messages....................................................... 3.16
3.6.3 UPS Maintenance Menu............................................................................3.25
Bypass/Shutdown Procedure .....................................................................3.29
Manual Transfer to Bypass ......................................................................3.31
3.6.4 System Shutdown......................................................................................3.47
3.6.5 CPU Fault..................................................................................................3.47
4.1 General...................................................................................................Page 4.1
4.2 Safety Precautions...........................................................................................4.1
4.3 Preventive (Periodic) Maintenance.................................................................. 4.2
4.3.1 Air Filters.................................................................................................. 4.2
4.3.2 Cable Connections.....................................................................................4.3
4.4 Remedial Maintenance (Troubleshooting) .......................................................4.3
4.4.1 General ......................................................................................................4.3
BP+15-150,2.9X
5/95
Section IV
Maintenance
(continued)
Page ii
Table of Contents
Secti on IV, Mainte nance
(continued)
4.4.2 Status/Alarm Indicators............................................................................... 4.4
4.5 Fuses.............................................................................................................. 4.5
4.6 Battery Maintenance....................................................................................... 4.5
4.6.1 Safety Precautions............................................................................... 4.5
4.6.2 Maintenance Shutdown of Battery Pack.............................................. 4.6
4.6.3 Inspection and Periodic Maintenance................................................... 4.7
4.6.4 Battery Test......................................................................................... 4.8
4.6.5 Battery Replacement........................................................................... 4.10
4.6.6 Reactivating the Battery...................................................................... 4.11
Figures 4-1 and 4-2 Battery Interconnections............................................... 4.11
Battery Manufacturer’s Torque Specifications.............................................. 4.12
Section V
Spares, Training, Maintenance
5.1 Spare Parts Page 5.1
Level “A” Spares......................................................................................... 5.2
Level “B” Spares......................................................................................... 5.3
Level “C” Spares......................................................................................... 5.4
5.2 Training....................................................................................................... 5.5
5.3 Continuing Maintenance .............................................................................. 5.5
Section VI
Glossary
Glossary........................................................................................................Page 6.1
Section VII
Remote Video Term inal
7.1 General.................................................................................................Page 7.1
7.2 RS232 Interface............................................................................................ 7.1
7.3 UPS Maintenance Menu............................................................................... 7.3
7.4 Alarm History Screen................................................................................... 7.3
7.5 P-Record...................................................................................................... 7.4
INFORMATION CONTAINED HEREIN IS THE PROPERTY OF INTERNATIONAL POWER
MACHINES CORPORATION, IS PROP RIETARY, CONFIDENTIAL AND NOT TO BE DIS
CLOSED, DISSEMINATED NOR USED EXCEPT FOR THE PURPOSE PROVIDED BY
INTERNATIONAL POWER MACHINES CORPORATION.
BP+15-150,2.9X
5/95
Page iii
HOW TO USE THIS MANUAL
A proper understanding and use of this operating and maintenance manual will enhance UPS system reliability. Therefore, the manual should be given equal status with the tools and equipment used to align and maintain the system. Conversely, improper understanding or application of the principles set forth can result in impaired system op er at io n, l os s of p ow er t o cr it ic al e qu ip me nt l oa ds , in ju ry t o pe rs on ne l an d/ or damage to the UPS.
The following guidelines will assist in the understanding and use of this manual.
1. Become fa miliar w ith the Table of Content s. It is here th at the u ser can first determine where in th e manual req uired info rmation or guidance can be found.
2. Read through the entire manual so as to become familiar with its style and general contents.
3. Know the manual’s limitations. It is not the intent of this manual to give a detaile d th eo ry o f op er at io n of t he U PS s ys te m. Tro ub le sh oo ti ng i s li mi te d to t he isolation and correction of problems that are signaled by the Control! Monitoring/Alarm Panel.
4. Be thorou ghly fam iliar wi th the saf ety prec aution s outl ined i n Sect ions II and IV of the manual.
5. Do not take short cuts when operating the UPS or performing mainte­nance on the system. A slower, more deliberate pace will give better results beca use it elimi nate s conf usio n and an y fals e conc lusi ons whic h may be reached by skipping steps. Careful adherence to step sequences presented herein is, more often than not, the fastest way to achieve desired results.
6. This manual is written based on the assumption that maintenance personnel will be fully knowledgeable in electronics and aware of the hazards of working with high voltage equipment. Always remember that voltages may be present even when the system has been fully shut down. Use a voltmeter to check terminals to ground. There is no substitute for common sense.
7. Do n’t gues s! If you do n’t know , ask some one who do es.
8. Remembe r that the Interna tional Pow er Machine s Service St aff is alway s available to answer your questions or provide helpful advice about your UPS system. Call them on our Service Hot Line:
BP+15-150,2.9X
5/95
Telephone: (800) 777-8922
Page iv
Handling and Unpacking Instructions
Handling Instructions:
1. Cabinets should always be stored in an upright position. Failure to observe this precaution can cause serious damage and cancellati on of war ranty.
2. Cabinets should be forklifted only at appropriate lifting points. Make sure that forks are long enough to go entirely under the unit and protrude from the oth er side. Be careful not to pun c t ure another unit beyond the one being lifted.
3. Chains, cables, ropes or oth er retaining devices sh ould not be wr apped around a cabin et. The weight of th e system is great enough to cause collapse of the cabinet when lifted by these means.
4. Pa dding mus t be us ed when transporting the system s o a s to help prevent damage to the cabi n ets.
Inspection and Unpack ing Instructions:
The uninterruptible power system (UPS), battery pack cabinet and/or power distribution unit (PDU) is thoroughly checked, both electrically and mechanically, before shipment from the factory. With the exten sive protection provided in packaging the unit for shipm ent, it shoul d be in proper cond ition upon recei pt. However, there i s a possibility that the unit might have been damaged in tran sit so a complet e inspection of th e equipment shoul d be made before si gning receipt . As a minimum, the foll owing insp ection pr oc edures should be e xecut e d as soon as possible after delivery.
Receiving / Unpacking lnspection Checklist
5. Each palletized unit is designed for forklift or lift gate handling. It is recommended that all packaging be left intact until the unit is in close proximity to its final location to prevent incidental damage during movement.
6. Inspect th e exterior packaging for obvious damage such as punctures or gashes th at are indicative of da mage to the unit. If eviden ce of dama ge exist s, save th e packag ing materia l for insp ecti on by th e carr ier when a cl ai m is fil ed. Requ est for in sp ection should be made immediately.
7. Strapping should be cut and the corrugated cap and/or sleeve carefully removed. Remove padding and plastic sheeting. The cabinet then may be unbolted from the shipping pallet.
8. Inspect each cabinet: check all exterior surfaces for scratches, chips, cracks and/or indentations. Check monitoring panels carefully.
9. If door key is needed, locate key envelope taped to rear of cabinet. Open each door, checking for damage.
10. A label on the outside of the UPS tells the location of the Operations & Maintenance (O & M) Manuals.
11. Remove any internal padding/packaging, checking carefully for parts, documentation, etc., that might have been shipped inside the cabi net. If foam
12. blocks are inside the battery trays, leave them in place. The are to keep small batteries from moving around inside the trays.
Damage Documentation
It is the responsibility of the recipient to file claim with the carrier for damages to the equipment or notify IPM, depending on t he f.o.b. poin t. Any and all damage noted upon recei pt of th e UPS, bat tery pa ck and/ or PDU sh ould be cl earl y identi fied in detai l on th e Bill of Lading. Carrier’s claim procedures should be initiated promptly. In the event damage is found after delivery, it should be reported as soon as possible (normally, there is a 15 day time limit on reporting damages incurred in shipment).
Additional information may be obtained by contacting: Manager, Qualit y Assurance International Power Machines Phone: (214) 342-6100 10451 Brockwood Road Fax (214) 342-6116 Dallas, Texas 75238-1641
BP+15-150,2.9X
5/95
Page v
3-phase UPS
Warranty
BP+15-150,2.9X
5/95
Page vi
International Power Machines
THREE-PHASE UPS WARRANTY
International Power Machines’ (IPM) uninterruptible power systems (UPS) are warranted to be free from defect s in d esign, ma teria l and work mansh ip under normal use and servi ce. Should any such system be found defective, IPM will furnish the necessary parts, labor and expenses to corr ect such defects (wit h in th e 48 contiguou s Unit ed St ates ) for twel ve (12 ) m onth s from th e date of equipment start-up at the job site, or eighteen (18) months from the date of shipment, whichever occurs first. Coverage work is performed 8:00 a.m. to 5:00 p.m. Monday through Friday (excluding holidays). For all three-phase products installed in Alaska and Hawaii, travel time is billable at the applicable field service rate in effect at the time of travel, and travel expense is billable at cost. For units outside the United States, please contact IPM for details. This warranty is subject to the following conditions:
A. Initial start-up and necessary UPS adjustments at the customer’s site shall be performed by IPM or
an IPM auth orized servi ce represen tative to en sure that the s ystem is proper ly started an d tested prior to use.
B. Purcha ser shall not opera te the system outs ide the speci fication s as stated in th e system man ual,
and shall follow all operating instructions therein.
C. An y necessary repairs made during the period of this warranty shall be made by IPM or by others
with IPM’s written concurrence.
D. All parts or d evi ces repla ced by IPM shall become th e property of IPM.
E. This warranty will not apply to repair of damage caused by accident, neglect, misuse,
misapplication, incorrect installation and repair or alteration not authorized by IPM.
F. The cust omer/user sh all be liable for th e cost of any war ranty call found to be due to oper ator
error, in whole or in part.
G. Bat tery cells are excluded from system warranty; see below.
INTERNATIONAL POWER MACHINES PROVIDES WARRANTY WITH RESPECT TO BATTERY, PERIPHERAL DEVICE, ATTACHMENT OR APPARATUS EMPLOYED WHICH IS NOT MANUFACTURED BY IPM TO THE EXTENT THAT IPM WILL ASSIGN TO THE PURCHASER ITS RIGHTS UNDER SUCH WARRANTIES AS THE MANUFACTURER OF THE PARTICULAR BATFERY, PERIPHERAL DEVICE, AT FACHMENT OR APPARATUS PROVIDES TO IPM WHEN THE PARTICULAR BATTERY, PERIPHERAL DEVICE, ATFACHMENT OR APPARATUS IS SUPPLIED BY IPM. FOR SPECIFIC CONDITIONS RELATED TO WARRANTY CONSULT THE MANUFACTURER’S DOCUMENTATI ON.
IN NO EVENT WILL IPM BE LIABLE FOR CONSEQUENTIAL DAMAGES EVEN IF IPM HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESSED OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS, AND ANY OTHER OBLIGATION ON THE PART OF IPM.
mc: warranty
BP+15-150,2.9X
5/95
Page vii
SECTION I
Theory of Operation
1.1 General
The BalancedPower Plus® (BP+) Uninterruptible Power System (UPS) presented in this manual is a solid state, o n-line system designed to provide high quality, continuously filtered and conditioned ac power to computers, their peripherals and/or other critical equipment loads. Most commonly, the UPS is configured as a single, stand-alone unit. Fi fteen (15) power ratings are available from 10 to 300 kVA. Information contained herein is applicable to all power ratings except where specified otherwise.
A single UPS is comprised of the following basic components:
Input transformer Rectifier/Charger Inverter Static Bypass Switch Bypass Breaker Output Transformer System Control Logic and Circuitry Digital Monitoring Panel Battery DC Disconnect
A one-line diagram in Section II shows the relationship of these various components.
1.2 Rectifier/Charger
The UPS input voltage from the utility is fed into the rectifier/charger (usually referred to as the rectifier) which converts the ac to filtered, regulated dc voltage. The dc is used to power the inverter and to recharge the batteries as necessary. The assembly consists of an input circuit breaker, a transformer, and a solid-state three-phase rectifier designed t o eliminate e ven ordered harmonics. An optional input filter reduces harmonics caused by rectifier switching. This prevents the harmonics from affecting utility distribution.
BP+ 10-150 2/95
Page 1.1
SECTION I
Theory of Operation
1.3 Inverter
The inverter changes dc voltage to precision ac voltage through pulse width modulation (PWM) inversion. Output isolation transformers and an output filter provide “clean”, computer grade ac which is then sent to the critical load. When utility power is available, the rectifier supplies power t o the inverter. Should the utility power fail, the inverter is powered by the batteries for a predetermined length of time.
1.4 Static Bypass Switch
The static bypass switch connects the UPS bypass input to the load in the event of the loss of the inverter output or an overload condition. Du ring normal conditions, the static bypass switch is in the open or disconnected m ode which isolates the bypass input from the load.
If the inverter output becomes unavailable or exceeds its specified tolerance, the static bypass switch will close and transfer the load directly to ac power without interruption. This transfer is automatically inhibited in the event the UP S bypass input is not within specified tolerance.
As soon as the inverter becomes available, returns to within tolerance or the overload clears, the static bypass switch will disconnect and retransfer the load to the inverter. Note, however, that so long as the inverter is out of sp ecification, the static bypass switch will automatically inhibit retransfer of the load.
1.5 Batteries
The optional battery pack supplies 216 VDC (10-30 kVA) or 360 VDC (37.5­150 kVA) nominal. It can be attached to the UPS module t o form a sing le unit or may stand alone to accommodate space restrictions. It is the energy reservoir of the UPS and provides dc power to the inverter in case of loss of UPS input power or rectifier malfunction. The DC Disconnect (Battery) Circuit Breaker electrically isolates the battery pack from the UPS module for maintenance purposes and provides overcurrent protection at the battery output.
BP+ 10-150 2/95
Page 1.2
SECTION I
Theory of Operation
1.5 Batteries (continued)
The rectifier/charger normally provides a maintaining or “float” charge to the batteries. Following periods of discharge when the batteries have supplied power to the inverter, the rectifier/charger increases power to the batteries in order to recharge them.
1.6 Control Logic and Control Circuitry
The control logic and circuitry of the UPS p rovide the operating logic and system control for all functions ranging from limiting the rectifier/c harger inrush current by “walking” it in, to maintaining t he inverter output voltage within rigid specifications, to determining whether or no t the static bypass switch should be activated. The control logic is, for all practical purposes, the brain of the UPS.
1.7 Digital Monit oring Panel
The UPS is equipped with a standard Digital Monitoring Panel which selectively monitors critical parameters of the UPS, using bright, easy-to-read digital LED displays. In addition, detailed instructions guide the operator through the UPS startup sequences. An alarm history can be called up on these digital displays when desired.
In the event of an abnormal condition, an au dible alarm sounds and the corresponding red LED illuminates to identify the condition so that corrective action can be taken. Alarm Silence and Emergency Power Off pushbuttons are provided.
This panel is discussed in greater detail in Section III.
BP+ 10-150 2/95
Page 1.3
SECTION I
Theory of Operation
1.8 Multi-Level Passwords
A password is required to access and make use of the UPS Maintenance Menu, described in Section 3.6.3. This menu, with five subsections, makes
possible the performance of a variety of maintenance functions including transfer and retransfer to bypass, password changes and adjustment of time and date.
All passwords may be changed by a person who already kno ws either the password in question or a higher level password.
Passwords consist of a minimum of 4 characters and a maximum of 9 characters. The numerals 0 through 9 and letters A through F may be employed.
The first character of the password indicates the privilege level of the password. The higher the privilege level, the more capabi lities that password can access.
Privilege level 0: No password. Used for the front panel display of
voltages, currents, etc. only. Does not permit any
menus to be accessed. Privilege level 1: Reserved for future development. Privilege level 2: Remote operator password. Used to monitor the UPS,
but not to affect transfers and retransfers. Privilege level 3: Reserved for future development. Privilege level 4: Operator password. Monitors the UPS as well as
allowing transfers, retransfers, transfer enables,
retransfer enables, reset faults, etc.
BP+ 10-150 2/95
Page 1.4
SECTION I
Theory of Operation
1.9 Phone Home Alarm Reporting
When this UPS is activated for phone home operation and the UPS sense s
one of several pre-selected alarm conditions, the UPS automatically dials IPM’s Field Service computer without human assistance and notifies IPM’s Field Service personnel of a system problem requiring attention.
Important information downloaded during each phone home event includ es:
1) UPS name, ID and serial number, 2) customer ID and phone number and 3) list of active alarms. You obtain the following benefits from this feature:
a. Immediate field service notification of site power or UPS problems,
even when the UPS is unattended.
b. Increased availability due to reduced mean-time-to-repair with
automatic notification and complete remote diagnostic capabilities.
c. 24-hours per day, 7 days per week monitoring of unmanned facilities
and locations where operators are unfamiliar with the UPS. Often, service personnel can take steps to solve a UPS problem remotely before the user is aware that there is a problem.
An internal modem and a dedicated telephone line are required. Phone
Home Alarm Reporting can be activated only with a Field Service level of password. It is normally done at the time of startup by our Customer Engineer.
1.10 Dial-Back Security
This security feature is provided to insure system integrity. It prevents
“hackers” or other unauthorized persons from intentiona11y or unin­tentionally accessing the UPS database. Anyone calling the UPS must
establish authority through the use of a dial-back password. The unit will validate this password against up to four passwords stored in non-volatile memory. One of the passwords will allow direct communication to commence with the UPS. The other three passwords will have associated telephone numbers. If one of these three passwords rec eives validation, the UPS logic will hang up and dial back the phone number associated with that password . When connection is made, the remote operator must enter the normal privilege level password for access to the corresponding level of monitoring diagnostics and
BP+ 10-150 2/95
Page 1.5
SECTION I
Theory of Operation
1.10 Dial-Back Security (continued)
controls. In this way high level security is provided since the remote operator must know the dial-back and access passwords and be calling from the proper associated phone number.
An internal modem and a dedicated telephone line are req uired. Dial-B ack
Security can be activated only with a Field Service level of password. It is normally done at the time of startup by our Customer Engineer. Phone Home Alarm Reporting and Dial-Back Security can share the same modem and telephone line.
BP+ 10-150 2/95
Page 1.6
SECTION II Installation
2.1 General
Your International Power Machines BalancedPower Plus UPS is UL-listed
and designed for installation on the compute r room floor. Its attractive computer­like appearance and quiet operation eliminate any necessity of creating special facilities to house the UPS and its battery component. Since all modern computer rooms utilize environmentally controlled conditions, installation in such a locale will normally suffice to meet the needs of the UPS.
In the event that computer room installation is not practical, the selection of
a location for the UPS is critical to the per formance of the system and to the life expectancy of its components. Failure to select a site which meets all requirements specified in this section can result in excessive maintenance problems. For environmental considerations, please see the Installation Information at the end of this section.
Operating temperature range for batteries is 0°C to 40°C (32°F to 104°F).
Battery warranty is conditional upon application at or below 25°C (75°F). Continuous operation above 25°C may reduce or void battery warranty.
The BalancedPower Plus battery pack supplied by International Power
Machines is listed by Underwriters Laboratories only for use with the BalancedPower Plus UPS.
2.2 Mechanical Preparation of UPS
The UPS can be fully accessed from the front for operation and mainte-
nance. However, during installation the UPS and any accompanying battery cabinets should be left at least two feet (61 cm) from the wall to allow access to the rear. If optional top cable entry has been p urchased, an area of at l east three fe et (91 cm) is required at the right side for installation.
The following steps should be taken, in the order indicated:
BP+10-150 12/95
Page 2.1
SECTION II Installation
2.2 Mechanical Preparation of UPS (continued)
1. Insure that all packing, both external and internal, has been
removed from the UPS.
2. Open right-hand front door of the UPS.
3. For standard bottom cable entry, unscrew scr ews holding the panel
around the circuit breakers and remove the panel. Then, remove the cable access panel on the bottom of the UPS by removing six (6) screws.
4. For optional top cable entry, remove the right side cover by removing
two (2) screws at the bottom (inside front and back) and lift the cover. Drill holes in the appropriate conduit plate of suitable size for the cables to be inserted throu gh it, and replace the plate.
5. Fasten leveling feet (packed inside) to the four bottom corners of th e
UPS cabinet. Access to the inside of the cabinet is not required. Refer to Figure 2-1. (An optional pedestal mount may replace leveling feet and casters.)
a. First screw the leveling foot screw through the leveling plate. b. Use two sets of 114-20 x 1” screw, flat washe r and lock washer to
fasten the leveling plate to the bottom of the cabinet. Two threaded holes are in the floor of the cabinet to receive them.
c. Screw in each leveling foot until it is a min imum of 0.75 in (1.9 cm)
above the floor level. Tighten locking nut to keep it there.
6. If an IPM battery pack is to be attached to the left sid e of the
UPS, perform this sequence. If the battery cabinet is not to be attac hed to the le ft side of the UPS, skip Step 6.
a. Open the left-hand front door of the UPS. Remove eight (8) screws
from the lower metal cover to remove the cover. When the three-(3) upper screws are removed, the clear plastic guard above will also come off.
BP+10-150 12/95
Page 2.2
SECTION II Installation
2.2 Mechanical Preparation of UPS (continued)
b. DO NOT REMOVE THE RED GLASTIC GUARD PANEL FROM
THE LEFT SIDE OF THE UPS.
BP+10-150 12/95
Page 2.3
SECTION II Installation
2.3 Mechanical Preparation of the Battery Cabinet(s)
If batteries are not provided in IPM cabinets, see Disconnect Installation
Drawing at the back of this section for wiring of separat e circuit bre aker and ski p this Section 2.3. For battery preparation refer to the battery manufacturer’s manual.
IPM battery trays are shipped screwed to the shelf supports and should be
left fastened down.
1. Fasten leveling feet (packed inside) to the four bottom corners of the
battery cabinet. Access to the inside of the cabinet is not required. Refer to Fig ure 2-1. (An optional pedestal mount may replace leveling feet and casters.)
a. First screw the leveling foot screw through the leveling plate. b. Use two sets of 1/4-20 x 1” screw, flat washer and lock washer to
fasten the leveling plate to the bottom of the cabinet. Two threaded holes are in the floor of the cabinet to receive them.
c. Screw in each leveling foot until it is a min imum of 0.75 in (1.9 cm)
above the floor level. Tighten locking nut to keep it there.
2. If an IPM battery cabinet is to be attach ed to the left side of the UPS,
remove the fiberboard shipping panels from t he left side of the UPS a nd the right side of the battery cabinet by forcing out the fasteners. Leave the red glastic panel attached. It is recommended that the battery cabinet not be attached to the
right side of the UPS.
a. If more than one battery cabine t is used, the one with a disconnect
circuit breaker should go adjacent to the UPS. This is Battery Cabinet #1.
3. Remove each left battery cabinet cover by removing screws from the
inside front. Be very careful not to touch the screwdriv er against t he battery terminals. Then pull side panel forward and lift to remove.
4. In each battery cabinet, cut the straps holding the top tray of batteries If
foam blocks are inside the battery trays, leave them in place. They are to keep small batteries from moving around inside the trays.
BP+10-150 12/95
Page 2.4
SECTION II Installation
2.3 Mechanical Prep ar ation of the Batt er y C abi n ets (co nti n ue d)
5. If Battery Cabinet #1 is to be fastened to the left side of the UPS,
place it adjacent to the UPS, but don’t bolt them together. If additional battery cabinets are to be fastened together to the left of Cabin et #1, place them adjacen t to #1 and each other, but don’t bolt them together.
CAUTION: Do not connect the battery trays to each other until
instructed in this manual.
6. Remove the cable entry panel located on the top (or bottom) of
Battery Cabinet #1. Drill conduit holes in this panel of suitable size for the cables to be inserted through it. Replace panel.
2.4 Signal Wiring
NOTE: Class 1 wiring method must be used for field wiring
connections.
Make connections for all optional equipment to the terminal blocks on the
lower front or right side of the UPS (see installation drawings).
Electrical connections should now be made b etween the UPS and Battery
Cabinet #1. There is a wiring harness with a connector coiled on the left side of the UPS. This connector plugs into a matching connector on a wiring harness coiled in the lower right corner of Battery Cabinet #1.
If battery cabinet is not to be attached to the UPS, run wiring out through
UPS access panel at the bottom or top to the battery cabinet, following information on the installation drawings at the end of this section.
Connections for the following functions are located on the Customer
Interface Board:
2.4.1 Remote Control (TB1):
a. Remote EPO Switch
1. 24 Vdc lamp supply, 0.25 amp max.
2. Isolated contact closure causes EPO.
BP+10-150 12/95
Page 2.5
2.4 Signal Wiring (continued)
2.4.1 Remote Control (TB1) (continued)
b. Battery Trip and Position
1. 24 Vdc UVR control for battery disconnect, 0.6 amp max.
2. Contact indicates position of battery disconnect. c. Remote On-Generator Condition Isolated contact closure signals
UPS logic that a generator is supplying UPS input power.
d. Summary Alarm (NO/NC)
1. 120 Vac—0.5 amps ac max.
2. 28 Vdc 1 amp ac max.
SECTION II Installation
Terminal wire sizing : #22-#12 AWG
2.4.2 Optional Remote Status Panel (TB2)
Ten position terminal for direct connection between UPS a nd TB1 in the
Remote Status Panel. Terminal wire size #22-#14 AWG (recommended: #16 AWG).
2.4.3 Optional RS232 Communication (J6-J9)
25 Pin D-Sub Receptacles (male), DTE and DCE are provided for COM Ports 1 and 2. Communication shall be selectable from either standard ANSI
terminal format or P-Record protocol.
2.4.4 Optional Modem Connection (J1O-J13)
Two modem port line and two modem port phone connections are included.
Accepts standard RJ11 plugs. Communication shall be selectable from either standard ANSI terminal format or P-Record protocol.
BP+10-150 12/95
Page 2.6
SECTION II Installation
2.4 Signal Wiring (continued)
2.4.5 Optional Site Interface Assembly (A26)
This board mounts on top of the Customer Interface Board. The following
connections are available from this interface:
a. Computer Shutdown Interface (AS400) 9 pin D-sub plug. b. System 38 BNC connector (jack). c. 12 sets of NO and NC contacts are provided for monitoring UPS
status and alarm conditions. Connector wire size #22-#12 AWG.
2.4.6 Optional User Specified Alarm (A23)
This board mounts on top of the Customer Interface Board. Three sets of
NO contact inputs can be connected for UPS monitoring of external alarms. Connector wire size #22-#12 AWG.
2.5 Power Wiring - UPS to Battery Cabinet
Use separate conduits for power and signal wiring. When the battery cabinet is attached to the left side of the UPS, there is a
power cable with a connector on the left side of the UPS. This connector plugs into a matching connector on the right side of Battery Cabinet running from the circuit breaker.
If additional battery cabinets are to be used, additional cables and wiring
harnesses of varying lengths are coiled in B attery Cabinet #1. These must be fed through one or more battery cabinets to connect to matching plugs similarly numbered.
If battery cabinet is not attached to the UPS, run wiring out through UPS
access panel at the bottom or top of the battery cabinet, following information on the installation drawings at the end of this section.
BP+10-150 12/95
Page 2.7
2.6 Connecting the Cabinets
1. If Battery Cabinet #1 is to be attached
to the left side of the UPS, fasten the two cabinets together using the four (4) 5/16” x 1” bolts, nuts and washers packed with the leveling feet (see Figure 2-2).
2. If two or more battery cabinets are to
be installed, remove the left-hand fiberboard shipping panel of the first cabinet and the right­hand cover of the second cabinet in the same way. Plug the power and signal wire electrical connectors together. Bolt the two cabinets together as described. Repeat for any additional battery packs.
SECTION II Installation
2.7 Re-assembly
1. Replace side cover(s) of battery cabinets, attaching screws on inside
(removed in Paragraph 2.3, Step 3). Be very careful not to touch screwdriver
against the battery terminals.
2. Replace the clear plastic guard and metal cover on the front of th e UPS
(removed in Paragraph 2.2, Step 6a).
3. The complete assembly, UPS and battery cabinet(s), can now be rolled on
its casters back to eliminate the work area behind it. When it is in its final location, lower the leveling feet to stabilize and level the cabinets. Tighten locking nuts.
NOTE: For proper maintenance access and ventilation, a clear area thr ee
feet (91 cm) in front of the UPS and one foot (30.5 cm) above it is recommended.
BP+10-150 12/95
Page 2.8
SECTION II Installation
2.8 AC Power Connection
1. Make sure that all circuit breakers and the battery DC
disconnect are open.
2. Solderless compression type lugs are provided for cable connections.
All power connections to the UPS terminal blocks must be torqued in a ccordance with the table below.
WARNING
Verify that power cabling is
de-energized befo re pr oceedi ng.
TIGHTENING TORQUE FOR PRESSURE WIRE CONNECTORS
Size of Wire Used Torque Spec ification AWG/kcmil (mm
6-4 (13.3-21.2) 110 (12.4) 3 (26.7) 150 (16.9) 2 (33.6) 150 (16.9) 1 (42.4) 150 (16.9) 1/0-2/0 (53.5-67.4) 180 (20.3) 3/0-4/0 (85.0-107.2) 250 (28.2) 250-350 (127-177) 325 (36.7) 400 (203) 325 (36.7) 500 (253) 375 (42.4)
3. UPS Input Voltage Configuration. Run cables for UPS input through the access panel of the UPS and connect
to terminal block as shown in installation drawings in this section.
a. On a single input UPS, when input voltage equals output voltage
-3-phase, 4-wire plus ground.
2
) lb-in (N-m)
BP+10-150 12/95
Page 2.9
SECTION II Installation
2.8 AC Power Connection (continued)
3. a. UPS Input Voltage Configuration (continued) Note: When connecting the UPS to a 3-phase, 3-wire supply, the supply
transformer must be a 3-phase, center grounded WYE and the ground conductor must be connected to the UPS ground terminal. The neutral must be gro unded and the UPS can only supply power to 3-phase, 3-wire loads. No single-phase loads can be connected to the UPS. For any other configurations consult IPM Application Engineering.
b. On a single input UPS, when input voltage does not equal output
voltage and on a dual input UPS 3-phase, 3-wire plus ground.
Note: The UPS 3-phase, 3-wire supply transformer must be a 3-phase,
center grounded WYE with neutral grounded. The ground connector must be connected to the UPS ground terminal. For any other configurations, c onsult IPM Applications Engineering.
4. UPS Output Voltage Configuration. Referring to the installation drawings in th is section, connect UPS o utput
terminals to the equipment to be protected, running the cables out through the access panel.
a. On a single input U PS, when input voltage equals output voltage,
and on a dual input UPS 3-phase, 4-wire plus ground can feed WYE-connected or DELTA-connected loads (see Note at 3,a, above).
b. On a single input UPS, when input voltage does not equal output
voltage 3-phase, 4-wire plus ground; can feed WYE-connected or DELTA­connected loads.
Note: This configuration provides a separately de rived source. UPS output
neutral has been factory connected to system ground. UPS output circuit protection is required.
BP+10-150 12/95
Page 2.10
SECTION II Installation
2.8 Power Connections (continued)
5. Bypass Input Voltage Configuration (Dual Input UPS) Bypass input voltage configuration must be the same voltage, frequency,
phase sequence and configuration as the UPS ac voltage configuration, i.e., 3­phase, 4-wire plus ground. The UPS output can feed WYE (4-wire) loads or DELTA (3-wire) loads: WYE systems require neutral connections for both bypass input and UPS output; DELTA or 3-wire systems require neutral connection for bypass input only.
6. Ground Connections Two 3/8-16 x 1.0 LG ground studs are provid ed for connection to syste m
ground. Ground studs are welded to the cabi net frame and are located near the cable entry points or power terminal.
7. Replace the panel around the circuit breakers (removed in Paragraph
2.2, Step 3). (With top cable entry option, replace right side panel removed in Paragraph 2.2, Step 4.)
2.9 Activating the Battery Cabinet(s)
WARNING
This procedure should be performed only by qualified electrical personnel Due to potential for arcing, safety equipment such as face shield or eye goggles and gloves must be worn at all times. All tools must be insulated. There will be high voltages present and failure to follow this procedure exactly may lead to injury or death.
Make sure that all elec tri cal power has been removed from the
UPS and batter y cabinets.
Make sure that battery tray cables are not plugged together.
BP+10-150 12/95
Page 2.11
SECTION II Installation
2.9 Activating the Battery Cabinet(s) (continued)
Make sure that all packing material and shipping straps have been
removed from the battery cabinets.
Make sure that the electrical signal and power connections have
been made between Battery Cabinet #1 and any additional cabinets.
Make sure that the electrical signal and power connections have
been made between Battery Cabinet #1 and the UPS.
Make sure that the mechanical connections have been made
between the battery cabinets.
2.9.1 Battery Cabinet #1
1. Open the front doors of Battery Cabinet #1.
2. Using an ohmmeter, measure from each pole on both the top and the
bottom of the battery disconnect circuit bre aker to frame ground. Verify that no short circuits exist to frame ground. There may be a high impedance between the two cables connecting to the UPS cabinet and frame groun d, but no sho rt circuit should exist.
3. Using an ohmmeter, measure between each combination of two poles (A
to B, A to C and B to C) on the top of the battery disconnect circuit breaker. Verify that no short circuit exists between any two poles.
4. Using an ohmmeter, measure between each combination of two poles (A
to B, A to C and B to C) on the bottom of the battery disc onnect circu it breaker. Verify that no short circuit exists between any two poles. NOTE: There will be a
capacitor action between the two cables connecting to the UPS cabinet, but no short circuit should exist.
5. In Battery Cabinet #1, connect the battery trays to each other as shown
in Figure 2-3. The two connectors to be attached at each tray are similarly numbered.
BP+10-150 12/95
Page 2.12
SECTION II Installation
2.9 Activating the Battery Cabinet(s) (continued)
2.9.1 Batt ery Cabinet #1 (c on ti nu ed )
6. Using a dc voltmeter, carefully measure the dc voltage at the top of the
battery disconnect circuit breaker. The voltage should be slightly above the nominal battery voltage (for example: 380 volts dc for a nominal 360 volt battery cabinet; 230 volts for a nominal 216 vdc). R ecord the vo ltage. The polarity should have the positive on the left-hand pole (Pha se A) and the negative on the right­hand pole (Phase C) when you are facing the battery disconnect circuit breaker. Verify that the polarity is correct. If it is not, locate and correct the problem.
7. When the polarity is correct, disconnect the top right-hand tray
connection to the tray immediately below. Verify there is no voltage present between the left and right poles at the top of the battery disconnect circuit breaker.
2.9.2 Battery Cabinet #2
8. Open the front doors of Battery Cabinet #2 (the one next to Battery
Cabinet #1). Connect the battery trays in the cabinet to each other a s shown in Figure 2-3. The two connectors to be attached at each tray are similarly numbered.
9. Using a dc voltmeter, carefully measure the dc voltage at the top of the
battery disconnect circuit breaker in Battery Cabinet #1. The voltage should be slightly above the nominal battery voltage (for example: 380 volts dc for a nominal 360 volt battery cabinet; 230 volts for a nominal 216 vdc). Record the voltage. The polarity should have the positive on the lef t-hand pole (Phase A) and the negativ e on the right-hand pole (Phase C) when you are facing the battery disconnect circuit breaker. Verify that the polarity is correct. If it is not, locate and correct the problem.
10.When the polarity is correct, disconnect the top right-hand tray connec-
tion to the tray immediately below in Battery Cabinet #2. Verify there is no voltage present between the left and right poles at the top of the battery disconnect circuit breaker.
BP+10-150 12/95
Page 2.13
SECTION II Installation
2.9 Activating the Battery Cabinet(s) (continued)
2.9.3 Battery Cabinets #3 and #4
11. Repeat Steps 8, 9 and 10 for the additional battery cabinet(s).
2.9.4 Final Battery Cabinet Connections
12. When connections and polarity have been checked on each additional
battery cabinet, verify that there is one connection left unplugged i n each cabinet (Steps 7 and 10). In Battery Cabinet #1, reconnect the to p right-hand tray to the tray immediately below.
13. Move to Battery Cabinet #2.
WARNING
Before reconnecting the top right-hand tray to the tray immediately below in Battery Cabinet #2, measure the voltage between these un­plugged connectors with a dc voltmeter. It is expected that this voltage reading will be small. In no case should the connection be made if there is more than 5 volts difference.
14. If there is less than 5 volts between the connectors, plug them together.
15. Repeat Steps 13 and 14 for each additional battery cabinet, making
sure to measure the voltage between the unplugged connectors each time.
The uninterruptible power system is now ready for startup. See Section III,
Operation.
WARNING: Do not close the battery circuit breaker until instructed to do so in the startup procedure.
BP+10-150 12/95
Page 2.14
SECTION II Installation
2.9 Activating the Battery Cabinet(s) (continued)
6 battery trays
Figure 2-3
10 battery tray s
BP+10-150 12/95
Page 2.15
SECTION III
Operation
3.1 General
This section contains safety considerations, UPS operational procedures,
and an overview of the monitoring panel and operating controls for th e system. Prior to operation, ensure that the UPS has been installed correctly as outlined i n Section II of this manual. Ensure that correct input/out put phase rotation and battery polarities have been observed. Failure to do so can result i n damage to the UPS and/or injury to personnel. Operators should be thoroughly familiar with the contents of this manual and with the location an d function o f all system controls and indicators.
3.2 Safety Considerations
Safety considerations are divided into several areas which are discussed
below. Refer also to Section IV of this manual, Maintenance, for safety precautions to be taken whenever operating or working on the UPS.
3.2.1 Cleanliness
Litter or trash of any sort should not be allowed to accumulate in or around
the UPS. Liquid spills or metal objects carelessly dropped or placed can cause shorts and damage to the system as well as possible injury to personnel. Dirt and dust accumulating in the UPS air filters can impede air f low, thereby decreasing the cooling effectiveness of the blowers and possibly resulting in an overtempera­ture shutdown of the system.
3.2.2 Fire
In order to minimize the possibility of a fire and to reduce the extent of any
damage resulting from such an incident, the walls, ceiling and floor of the UPS room should be constructed of noncombustible materials. A portable carbon dioxide extinguisher should be located in the UPS room. Personnel involved in operating and/or maintaining the UPS should be familiar with Class C hazard fires.
BP+2.9X 11/95
Page 3.1
SECTION III
Operation
3.2 Safety Considerations (continued)
3.2.3 Security/Personnel
Access to the UPS should be limited to a minimum of perso nnel. Module
doors should be kept locked. All personnel who operate or maintain the UPS should be proficient in normal and emergency operational procedures. A refresher briefing or test at specific intervals is rec ommended to maintain this proficiency. New personnel should be trained and tested p rior to operating the equipment. A thorough knowledge of first aid procedures, especially those pertaining to electrical shock or bums, and the use of carbon dioxide fire extinguishers should be mandatory.
3.3 Radio Frequency Energy Hazard
WARNING: This equipment generates, uses and can radiate radio
frequency and if not installed and used in accordance with instructions may cause interference to radio communications. It has been designed to comply with the limits for Class A computing devices pursuant to Subpart J or Part 15 of FCC Rules, which are designed to provide reasonable protection against such inter­ference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be necessary t o correct such interference.
CAUTION
Always be aware that hazardous voltages may be present with in the
UPS even when the system is not operating.
BP+2.9X 11/95
Page 3.2
SECTION III
Operation
3.4 Digital Monit oring Panel
The Digital Alarm Panel consists of eight (8) L ED Indicator Lights, one (1)
LCD message screen, two Display Select pushbuttons, three (3) Paramete r Adjust pushbuttons, an ALARM SILENCE pushbutton and an EMERGENCY POWER OFF (EPO) pushbutton. The Display Select butt ons provide access to the various data and messages which are displayed on the Message Scr een. These include detailed instructions for startup sequence, alarm parameters, available battery run time and alarm conditions.
Figure 3.1
BP+2.9X 11/95
Digital Monitoring Panel
Page 3.3
SECTION III
Operation
3.4 Digital Monit oring Panel (continued)
3.4.1 Indicator Lights
The Indicator Lights (LED’s), located in the upper part of the panel, are:
UPS Normal (green) - This indicates that the critical load is being powered
from the inverter. The LED normally is on and, when this is the only L ED lighted on the panel, it represents a fully normal condition. Other LED’s may also be lighted simultaneously indicating a problem with the UPS. When this occurs, first record the alarm(s). Then, depress the ALARM SILENCE button to reset the alarm circuitry. Any alarm LED’s will go out when the alarm condition is corrected. See Paragraph 3.4.5 for more details.
If “UPS Normal” flashes slowly, this indicates that a non-critical alarm is
present, and that message will appear on the message screen. Check Alarm History (Paragraph 3.6.2) to identify the alarm.
AC Input Failure (red) -The UPS input power has been disrupted or gone
out of specification limits. The system goes to battery power and the alarm sounds, alerting the operator to a brownout or power failure. When the batteries run down, the critical load will shut off unless steps are taken to correct the situation or another source of input power is provided.
Low Battery Voltage (red) - When the system is operating on battery
power, this LED illuminates to show approxima tely five minutes remains before the UPS system shuts down. A message screen (shown on Pa ge 3.6) displ ays the amount of battery run time left. Also, the link (battery) voltage maybe monitored (See Paragraph 3.4.2.6). Shutdown occurs when the link voltage drops to 178VDC (15-30kVA) or 297VDC (37.5-300kVA). If utility power can not be restored or an auxiliary power source be activated, the critical load sh ould be shut down in an orderly procedure.
UPS Overload (red) - The load on the UPS output is in excess of 105% of
rated load. If the condition exists for more than a few seconds, enough of the critical load should be powered down or remo ved to make the indicator go out. Otherwise, the UPS will shut down and/or transfer to bypass within 15 minutes. If the indicators are set to latch, the ALARM S ILENCE button must be depressed twice to clear it.
BP+2.9X 11/95
Page 3.4
SECTION III
Operation
3.4 Digital Monit oring Panel (continued)
3.4.1 Indicator Lights (continued)
This condition may occur when the UPS is loaded close to 100% and a large
disk drive or other motor load is started. These loads draw currents many times their normal level for a few seconds when first started. The UPS is designed to handle this short overload condition.
• Transferred to Bypass (red) - An indication that the critical load is being
powered directly from the UPS bypass power source. This situation is created when maintenance personnel want to bypass the UPS throug h the static bypass switch for routine maintenance or when an abnormal condition exists in the inverter, such as failure or extended overload. When in this operational mode, the critical load does not have UPS protection.
• Transfer Not Available (red) - An indication that transfer to the static
bypass switch is not possible. This may be caused by the UPS bypass input power source being out of specification or a power outage.
• Battery Not Available (red) - The battery’s DC Disconnect (circuit breaker)
is open or a battery cabinet fuse is blown. The battery is not available to power the inverter if needed.
• Retransfer Inhibited (red) - An indication that the inverter is out of
specification or has lost phase lock with the bypass power source. Wh en active in conjunction with the Transferred to Bypass indicator, power can not be retransferred from the static bypass switch back to the inverter.
3.4 .2 Message Screens
Message screens display the status of the UPS. To scroll through these
screens, depress or buttons beneath DISPLAY SELECT.
Following are the legends that appear in
this area while the UPS is running normally. To display these in this order, start with the screen at right and depress the button to show each screen in turn.
UPS
Operating
Normally
BP+2.9X 11/95
Page 3.5
SECTION III
3.4 Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
If the UPS is operating on battery power,
this screen will appear instead. It can be monitored to determine the battery run time remaining during a power outage. Voltage shown is link voltage.
3.4.2.1 Alarm History
Voltage XXX.X VDC
Operation
Time Left
hhH mmM ssS
This is a sequence of entries showing as
many as the last 1500 alarm and status condi­tions that have occurred. To see them all, scroll through the list depressing the or button successively (see paragraph 3.6.2).
On this screen the letters are read as
follows:
xx = month yy = day of the month zz = year uu = hour (on the 24-hour clock) vv = minutes of the hour ww = seconds aa = cycles b = 1/4 cycles tttt = alarm sequence number. 0 is most recent. Pre ss -to scroll from a
higher number to 0 or press -to scroll from 0 to a higher number.
3.4.2.2 Input Voltage:
This is a readout of input voltage between
phases.
-and-
Xx/yy/zz tttt
uu :vv.ww.aab
Alarm identity
Input Vab Input Vbc Input Vca
This is a readout of input volt age phase
to neutral.
BP+2.9X 11/95
Input Van Input Vbn Input Vcn
Page 3.6
SECTION III
3.4 Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
3.4.2.3 Input Current:
Operation
This is a readout of the input current,
measured in amps per phase.
3.4.2.4 Bypass Voltage
This is a readout of the bypass voltage betw een
phases.
3.4.2.5 Frequencies/Temperature
A readout of the input and output frequency
(Hz) and the inlet temperature (°C).
3.4.2.6 Link Voltage:
A display of the DC link (battery) voltage, battery current and maximum
output crest factor of the load on the UPS.
Link voltage - 243 (405)* VDC ±10%. If there is an increase to about 246 (410) VDC, it indicates the batteries are being charged. If the voltage goes above 256(426) VDC, the rectifier will shut down. (These values are subject to change according to battery type.)
Battery Amps - A positive number indicates battery charging; a negative number indicates discharging (possibly because UPS is operating on battery power).
Max Out CF - Displays maximum output crest factor of the load on the UPS
* Numbers in parenthesis are for 37.5-300 kVA; without parenthesis for 15-30 kVA.
Input Van Input Vbn Input Vcn
Bypass Vab Bypass Vbc Bypass Vca
Input Freq
Output Freq
Inlet Temp
Link Voltage
Battery Amps
Max Out CF
BP+2.9X 11/95
Page 3.7
SECTION III
3.4 Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
3.4.2.7 Output Power
Operation
A readout of the output kVA, kW and
power factor.
3.4.2.8 Output Voltage:
A readout of output voltage phase to
neutral. There normally is up to ±5% variance between phases.
3.4.2.9 Output Current:
A readout of the output current,
measured in amperes per phase.
3.4.2.10 Date
Displays today’s date.
Output KW
Output KVA
Output PF
Output Van Output Vbn
Output Vcn
Output Van Output Vbn
Output Vcn
Date
Actual Date
3.4.2.11 Time
A readout of the current time.
3.4.2.12 UPS Maintenance Menu
This screen allows entrance into the UPS
Maintenance Menu described in Paragraph
3.6.3. A password is required to use this menu.
BP+2.9X 11/95
Time
HH:MM:SS
UPS
Maintenance
Menu
Page 3.8
SECTION III
Operation
3.4 Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
The next message is “UPS Operating Normally.”
3.4.2.13 Other Messages
Under certain conditions other messages may appear on the message
screens.
3.4.3 Display Select Pushbuttons
The and pushbuttons are used to select th e desired display on the
Message Screen, as described in Paragraph 3.4.2. (See Page 3.3 regarding arrows.)
3.4.4 Param et er Adju st P us hbut to n s
These pushbuttons, labeled , and , are used with Alarm Ident ity/
History procedures (Paragraph 3.6.2) and to set or alter the parameters of the UPS. (See Page 3.3 regarding arrows.)
3.4.5 Alarm Silence Pushbutton
Whenever an alarm condition exists, an audible alarm sounds calling
attention to the situation. If set for non-latching alarms, the audible alarm is silenced by depressing the ALARM SILENCE pushbutton once. If set for latching alarms, pressing the ALARM SILENCE pushbutton a second time resets the alarm circuit. Any indicator LED’s that remain illuminated represent active alarm conditions that may require immediate action . (See Paragr aph 3.6.3.4, Step 4 for selecting “latching” or “non-latching.”)
BP+2.9X 11/95
Page 3.9
SECTION III
Operation
3.4 Digital Monit oring Panel (continued)
3.4.6 Emergency Power Off Pushbutton
To be used only for emergency conditions whe re instant shutdown of the
UPS is required. The red EPO pushbutton is normally illuminated so th at it may be located easily, even in the dark. Depressing the EMERGENCY POWER OFF (EPO) pushbutton results in immediate shutdown of operations, opening all UPS breakers and the DC (battery) disconnect, the audible alarm sounds and all power to the critical load is shut off. Once the EPO has been activated, the UPS must be manually restarted. (The EPO also may be activated remotely by a contact closure.)
CAUTION
Any time the UPS has been shut down by using the EPO, the system should be carefully checked by trained facilities personnel before restarting.
3.5 System Controls
Controls for the UPS, with the exception of the pushbuttons located on the
face of the UPS module indicator panel, are situated inside the right-hand door of the module cabinet. Since the cabinet is routinely kept locked, this provides some degree of security from tampering with the system.
UPS CONTROL switch: This switch is rotated clockwise to energize the
power supply to turn on the system logic or Digital Signal Processor logic.
INPUT CIRCUIT BREAKER: When closed, allows UPS input power to
supply the rectifier and SBS input on units having a single input.
BP+2.9X 11/95
Page 3.10
SECTION III
Operation
3.5 System Controls (continued)
BYPASS CIRCUIT BREAKER: Used primarily for ma intenance purposes.
When closed, it enables the UPS to be de-energized for ma intenance procedures while continuing to supply power to the critical load.
STATIC SWITCH BYPASS CIRCUIT BREAKER: (On dual input units
only.) When closed, allows reserve input to supply power to the Static Switch.
OUTPUT SWITCH: When closed, connects the cri tical load to the inverter
and static bypass switch.
3.6 UPS Operating Procedures
It is important for saf ety and the protection and perf ormance of the UPS that
the step-by-step instructions for each procedure be followed in the sequence given.
3.6.1 System Startup Procedure
Before initiating UPS startup, make sure that:
• All circuit breakers/switches are OFF (open).
• The DC (Battery) disconnect switch on the battery pack is OFF (open). Then --
Each of the following steps must be completed before going to the
next step. Failure to do so may result in interruption of power to the critical load.
1. Rotate UPS CONTROL switch
knob clockwise to ON to energize the system or DSP logic. If this screen appears, the UPS is not in operable condition. Phone Customer Service at (800) 777-8922 for assistance.
Checksum Bad
Service
Required
BP+2.9X 11/95
Page 3.11
SECTION III
Operation
3.6 UPS Operating Procedures (continued)
3.6.1 System Startup Procedure (continued)
Normally, turning on the UPS CONTROL switch should illuminate the
following LED’s:
AC Input Failure Transfer Not Available Retransfer Inhibited Battery Not Available
Checksum
… and this screen which will be
displayed for a short time,
Good
. . . . . then –
2. When this instruction appears on the
Message Screen, close BYPASS CIRCUIT BREAKER. The same LED’s should remain lighted. Power is available now on the UPS output.
3. When this instruction appears on
the Message Screen, close the I NPUT CIRCUIT
BREAKER.
Close
BYPASS
CKT. BREAKER
Close
INPUT
CKT. BREAKER
BP+2.9X 11/95
Page 3.12
SECTION III
Operation
3.6 UPS Operating Procedures (conti nued)
3.6.1 System Startup Procedure (continued)
4..This screen will appear for a short
time, then --
When this instruction appears on the
Message Screen, close the DC (Battery) Dis­connect switch. Depress the ALARM SILENCE pushbutton twice to turn off some of the LED’s. Now, only the Transfer Not Available LED should be lit.
5. When this instruction appears on
the Message Screen, close the Output Switch or Circuit Breaker. (When input voltage does not equal output voltage, this is a rotary switch.) This should light the following LED’s:
Transferred to Bypass Retransfer Inhibited
Waiting
DC Link =
XXX.X VDC
Close
BATTERY
CKT BREAKER
Close
OUTPUT
SWITCH OR BKR
6. On dual input UPS only, when
this instruction appears on the Message Screen, close STATIC SWITCH BYPASS CIRCUIT BREAKER. The same LED’s should remain lighted.
7. When this instruction appears on
the Message Screen, open the BYPASS CIRCUIT BREAKER. Within approximately 2 minutes the audible alarm will sound. Depress the ALARM SILENCE pushbutton, silencing the alarm, turning off the two lighted LED’s and lighting the UPS Normal LED.
BP+2.9X 11/95
Close
SBS INPUT
CKT. BREAKER
Open
BYPASS
CKT. BREAKER
Page 3.13
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.1System Startup Procedure (continued)
8. This screen will show for a short time.
9. Then this screen will appear, indicat-
ing that the UPS is now in normal operation.
3.6.2 Alarm Identity/History
As described in Paragraph 3.4.2.1 this is
the first Alarm History screen. It can be dis­played by pressing the or button, going through the sequence of screens described in Paragraph 3.4.2 until this screen appears.
Wait
Retransfer
Pending
UPS
Operating
Normally
xx/yy/zz tttt
uu:vv:ww.aab
Alarm identity
xx = month yy = day of the month zz = year uu = hour (on the 24-hour clock) vv = minutes of the hour ww = second aa = cycles b = 114 cycles tttt = alarm sequence number. 0 is most recent. Pre ss - to scroll from a higher number to or press to scroll from 0 to a higher number.
* The identity of the alarm is abbreviated on the screen. The full identification of each and corrective action are given in Table 3-2.
BP+2.9X 11/95
Page 3.14
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.2 Alarm Identity/History (continued)
The principal use of the Alarm History scree n is to identify the source of
audible alarms so that corrective action can be taken. When the audible alarm sounds, press or until this Alarm History screen ap pears. You ma y depress the ALARM SILENCE button once to silence the alarm.
You may find it advantageous to leave the message screen on Alarm History
during normal operations. Then, if an alarm sounds, its identity will be seen immediately.
It may be helpful to view the Alarm History a s a list of a larms, ordere d by
date and time. Whenever the Alarm History screen is first selected, th e first entry shown on the screen is the latest entry on t he list. Pres sing moves you toward the top of the list and pressing - moves you toward the bottom of the list. See an example below.
Table 3-1
Typical Alarm History Screens
Following is the beginning of a typical list of messages from the Alarm
History screen as the startup procedure is begun. The date, time and alarm identity are shown on the screen in the first Alarm History screen after system startup. By depressing you can scroll the screen up one message at a time to the oldest (earliest) message. Thinking of the Alarm History screens as part of a list will help you visualize what is happening.
Date Time I Alarm Screen Message 01/01/90 08:30:00.000 CPU Restarted CPU Restart 01/01/90 08:35:09.452 Input Circuit Breaker Closed inp bkr clsd 01/01/90 08:35:10.000 Input Voltage Normal inp vol norm 01/01/90 08:36:00.000 DC Voltage Normal dc volt norm
BP+2.9X 11/95
Page 3.15
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.2 Alarm Identity/History (continued)
Table 3-2
Screen Message Description Correctiv e Action inp bkr open Input Circuit Breaker open Follow System St artup pr oc edur e to
close Input Circ . Br k r.
inp bkr clsd* Input Cir c uit Breaker closed Verifies that Input Cir c uit Br k r. is closed
bat bkr open Battery (DC Disconnect) switch
open
bat bkr clsd* B attery (DC Disconnect) switc h
closed
inp vlt high Input voltage too high Verify corr ect UP S inputvoltage.
inp vlt low Input voltage too low Verify correct UPS input voltage.
inp vlt norm* Input volt age normal No action requir ed
inp freq hi ‘
inp freq low ‘
inp frq norm* Input frequency normal No action required
inp cur high Input current t oo high Reduce load on UPS output.
inp cur imbl I nput current out of balance Verify correct UPS input v olt-age and
Input frequency too high Verify correct UPS input frequency.
Input frequency too low Verify correct UPS input frequency.
Follow System St artup pr oc edur e to close Battery (DC Disconnect) switch
Verifies that Battery (DC Disconnect) switch is closed
Decrease if necessary.
Increase if necessary.
current.
inp cur normA Input current norm al No action requir ed
dc volt high DC (battery) voltage
dc volt low DC (battery) voltage
BP+2.9X 11/95
too high
too low
Verify corr ect batt er y v oltage. Decrease if necessary.
UPS is operating off battery.
Page 3.16
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Description Correctiv e Action
dc volt norm* DC (battery) voltage normal No action required
rct fus norm* Rectifier fuses normal No action requir ed
rct bin fusA Rectifier fuse A blown Test/replac e r ectifier fuses on Al power
assembly.
rct bIn fusB Rectifier fuse B blown Test/replace rectifier fuses on A2 power
assembly.
rd bin fusC Rectifier fuse C blown Test/replace rectifier fuses on A3 power
assembly.
rct pwr fail Rectifier power supply failure Test/replace rectifier drive board on Al,
A2 and A3 power assemblies.
rct pwr norm* Rectifier power normal No action requi r ed
rct lock* Rectifier phase locked No action requir ed
rct not lock Rec tifier not phase locked Verify UPS input voltage and frequency.
rct cur limt Rectifier current limit Reduce load on UPS output.
rct cur aval* Rectifier current not available No action required
rct on gen* Rectifier on generator No action required
rct in rechg* Rectifi er in recharge mode
(battery being r ec har ged)
rct in float* Rectifier in floa t (battery is
recharged)
bat volt low Battery voltage low (LED warning
also)
inv fus norm* I nverter fuse normal No action requir ed
inv bln fusA Inverter fuse A blown Test/replace inverter fuses on A1 power
No action requir ed
No action requir ed
UPS will shut down in a few minutes. Initiat e shutdown of critical loads
assembly
BP+2.9X 11/95
Page 3.17
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Description Correctiv e Action
inv bIn fusB Inverter fuse B blown Test/r eplace inverter fuses on A2 power
assembly.
inv bIn fusC Inverter f use C blown Test/replace inverter fuses on A3 power
assembly.
inv PS fail Power supply failure Test/replace inver ter drive boards on A1,
A2and A3 power assemblies.
inv PS norml* Power supply norm al No act ion required
inv Iocked* lnverter phase locked No action required
inv not lock Inverter not phase locked Verify UPS input voltage and frequency .
inv ovr tmpA Inverter ov er tem per ature. phaseAVerify cooling fans are operating on A1
power assembly .
inv ovr tmpB Inverter ov er tem per ature, phaseBVerify cooling fans are operating on A2
power assembly .
inv ovr tmpC Inverter over temperature, phaseCVerify cooling fans are operating on A3
power assembly .
inv norm tmp* I nverter temp. normal No action required
inv cur norm* Inv erter current normal No ac tion required
inv OC shtdn Inverter shut down -over current Remov e some of the load
inv OT shtdn Inverter shut down -over
temperature
inv cur limt I nverter current limit Reduce load on UF’S
xfer enabled* Transfer enabled No action required
Rexfr enabled* Retransfer enabled No action requir ed
Room is too not or fan fail ur e
* Not an alarm condition.
BP+2.9X 11/95
Page 3.18
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Descript ion Corrective Action maint by fIt Maintenance bypass fault Maintenance bypass breaker is closed
with inverter operating. Follow Startup procedure to open bypass breaker .
dc hi shtdn’ Rectifier shutdown due to dc
output overvolt age
mv mnl strt* Inverter manual start No action required
mv mnl stop* Inverter m anual stop No action required
mv mnl xfer* Inverter manual transfer No action required
inverter on* Inverter on No action requir ed
inverter off Invert er off Follow Startup procedure to restart
Verify that rectif ier automatically restarts
UPS.
mv fan fail Inverter fan failure Verify all cooling fans are operating.
mv fan norm* Inverter fan normal No action requi r ed
dc low shtdn UP S shutdown - DC (battery)
voltage low
mv phrt nml* Inverter phase rot ation normal No action requi r ed
out volt hi Output voltage hi gh Verify UPS output voltage. Decrease if
out volt low Output voltage l ow V er ify UPS output voltage. Inc r ease if
out volt nml* Output voltage normal No action required
out frq high Output frequency high Verif y UP S output frequency.
out frq low Output frequency low Verify UPS output frequency.
out frq normal* Output frequency normal No ac tion required
Batteries are di scharged.
necessary.
necessary.
* Not an alarm condition.
BP+2.9X 11/95
Page 3.19
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Descri ption Correctiv e Action out cur high Output current high Reduc e load on the UPS
out cur norm* Output current normal No action required
out bkr open UPS Output Circuit Break er
(Switch) open
out bkr clsd* UP S Output Circuit
Breaker_(Switch)_closed
sbs pwr norm* Static Bypass Switch
power normal
sbs pwr f alA Static Bypass Switch
power supply failure – Phase A
sbs pwr f aIB Static Bypass Swi tch
power supply failure – Phase B
sbs pwr f aIC Static Bypass Switc h
power supply failure ­Phase C
bypass open* Bypass Cir c uit Breaker Open No act ion required
bypass clsed Bypass Circuit Breaker closed Follow Startup pro-cedure to open
sbs on Static Bypass Switc h on ( cl osed) Follow Startup procedure t o retur n to
Follow Startup procedure to close
No action requir ed
No action requir ed
Test/replace SBS drive board on Al
power assembly .
Test/replace SBS drive board on A2
power assembly .
Test/replace SBS drive board on A3
power assembly .
Normal.
sbs oft* Static Bypass Switc h off ( open) No action requir ed
sbs disabled Static Bypass Swit c h disabled Enter S B S Maint enanc e M enu and
sbs enabled* Static Bypass Switch enabled No action required
ups amb high UP S ambient temp. high Room is too hot. Lower temperatur e
ups amb norm UPS ambient temp. normal No ac tion required
* Not an alarm condition.
BP+2.9X 11/95
enable transf er (S tep 6)
Page 3.20
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Description Corrective Action ups amb shdn UPS ambient temp. shutdown Room is too hot. Lower temperature.
byp volt hi Static Bypass Switch by-pass
voltage high
byp volt low S tatic Bypass Switch by-pass
voltage low
byp volt nml* Static Bypass Switch by-pass
voltage norm al
byp freq. hi Static Bypass Switch by-pass
frequency high
byp freq. low Static Bypass Switch by - pass
frequency low
byp f req. nml* Static Bypass Switc h by - pass
frequency normal
rct summary Rectifier summary alarm Review other rectifier alarms for
rct inhibit Rectifier inhibit ed Review other rectifier alarms for
rct normal* Rectifier normal No action requir ed
dc low shtdn UPS dc link low shutdown Complet e UP S restart procedure is
Verify SBS input v oltage. Decrease if necessary.
Verify SBS input v oltage. crease if necessary.
No action requir ed
Verify SBS input Frequency.
Verify SBS input frequency.
No action requir ed
cause
cause
required
dc link norm* UPS dc link normal No action requir ed
mv summary Inverter summar y alarm Review other invert er al arms for
mv inhibit Inverter inhibited Review other invert er al arms for
mv normal* Inverter normal No acti on requi r ed
sbs summ ary Static Bypass Switch summa ry
* Not an alarm condition.
BP+2.9X 11/95
cause
cause
Review other SBS alarms for cause
alarm
Page 3.21
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Description Correctiv e Action sbs inhibit Static Bypass Switch inhibited Review other SBS alarms for
cause
sbs normal* Static Bypass Switch normal No action required
ups summary UPS summary alarm Review all alarms for cause
ups inhibit UPS inhibit ed Review all alarms for cause
ups normal* UPS in normal condition No action requi r ed
CPU normal* UPS processor normal No act ion required
UPS Powerup* UPS processor initiali z ed No action required
EPO btn pshd EP O pushbutton pressed Complete UPS restart
procedure_is_required
EPO btn rlsd EPO pushbutton r eleased Complete UPS restart
procedure_is_required
ctl pwr on~ Control power on No action requir ed
ctl pwr off Contr ol power off Turn on Cont r ol P ower switch
rd wdog f It Rect ifier watchdog fault Call Customer Service
rct hi shtdn Rect ifier high shutdown Call Customer Service
dr rd wdog* Rectifier watchdog fault cleared No action requir ed
pwrsply fail Power supply failure Call Customer Serv ic e
pwrsply nrml * Power supply normal No act ion required
ps inp fail Power supply input failure Call Custom er Serv ic e
* Not an alarm condition.
BP+2.9X 11/95
Page 3.22
SECTION III
Operation
Table 3.2 (conti nue d)
Screen Message Descripti on Correctiv e Action PS inp normal* Power supply input normal No action required
bat vlt nrml* B attery voltage normal No act ion required
sbs scr normal* Static bypass switch ----normal No action required
rct on util* Rectifier served by utility power No acti on required
sbs inp open Static bypass switch breaker open Follow Startup procedur e to close
circuit breaker
sbs inp closed* Stati c by pass input swit c h or ci r c uit
breaker closed
sbs out open St atic bypass output switch is open Follow Startup procedur e to close
sbs out clsd* St atic bypass output switch is cl osed No action requir ed
xfer dsabld* Retransfer disabled No action required
inv no ovrld* Inverter driv e no ov erl oad No action required
trnsnt overl d lnverter drive transient overload Decrease load
lnv Overload Inverter drive overload Decr ease load
ram normal* RAM is normal No acti on requi r ed
ph dial* Phone home dialout No action required
ph connect* P hone home connection establi shed No action required
No action requir ed
switch
ph test Phone home test performed No action required
* Not an alarm condition.
BP+2.9X 11/95
Page 3.23
SECTION III
Operation
Screen Message Descripti on Correctiv e Action ph fail* ‘
Phone home connection attempt failed No action requir ed
out overload The load on the UPS has
exceeded 100%
load normal * The load on the UPS is < or = 100% No action requir ed
bln trap fuse The input trap fuse has blown Call Customer Service
trap fuse ok* The fuse on the input filter is normal No action required
inp 5th high The 5th harmonic content of the input
current is too hi gh
inp 5th norm* The 5th harmonic content of the input
current is at an acceptable level
unused* Unused al arm appears when
alarm history is cleared
Reduce the load
Perform bypass shutdown and call Customer Serv ic e
No action requir ed
No action requir ed
* Not an alarm condition.
NOTE: If a message requires action you can not p erform, call Factory
Customer Service (800) 777-8922.
2. Depress to display the next most recent alarm. You can repeatedly
depress to review past alarms in receding order. Continue as long as desired. After you have started this repeated depressing of , depressing will display more recent alarms back to the current alarm.
3. To exit Alarm History, depress or .
BP+2.9X 11/95
Page 3.24
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu
The UPS Maintenance Menu performs a variety of maintenance functions
including password changes and adjustment of date and time. It is divided into the following secondary menus in the order stated. The detailed instructi ons for each are given on the following subparagraphs.
3.6.3.1 Rectifier Maintenance Menu
3.6.3.2 Inverter Maintenance Menu
3.6.3. 3 SBS Maintenan ce Menu
3.6.3.4 System Maintenance Menu
3.6.3.5 Password Maintenance Menu
1. To bring the UPS Maintenance Menu
to the screen, depress the pushbutton as many times as necessary until the screen reads like this.
2. Press This will display –
NOTE:There is a further discussion of
multi-level passwords in Section 1.8.
3. The UPS is shipped with the password
4F00. To enter this password, depress or to change the first digit to “4”. is the shortest way to get to the “4” the first time. The screen will now look like this.
UPS
Maintenance
Menu
Enter Pa ssword
0
Enter Pa ssword
4
BP+2.9X 11/95
Page 3.25
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenan ce Menu (continued)
4. Now depress to activate the second
digit. Press or until the “F” shows, like this:
5. Depress to activate the third digit.
The screen will show:
6. Depress again to activate the fourth
digit to obtain:
7. Depress
secondary menus. Depress to bring up the other four Maintenance Menus in turn. Some­times it will be faster to depress to obtain the desired menu.
to bring up the first of the
Enter Pa ssword
4F
Enter Pa ssword
4F0
Enter Pa ssword
4F00
Rectifier
Maintenance
Menu
3.6.3.1 Rectifier Maintenance Menu
To be used only when advised by
qualified service personnel
1. When in the Rectifier Maintenance
Menu, depress displayed, press to reset the faults.
BP+2.9X 11/95
When this screen is
.
Page 3.26
Reset Rect Faults
UP = Reset
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.1 Rectifier Maintenance Menu (continued)
2. This message will appear on the
screen. To confirm the previous action, press again,
- returning the screen to –
3. Press to obtain this screen:
4. Press to return to the Rectifier
Maintenance Menu.
Confirm
Yes =UP No=DN
Reset Rect Faults
UP = Reset
Return to
Previous Menu
Rectifier
Maintenance
Menu
3.6.3.2 Inverter Maintenance Menu
1. Press to advance to the Inverter
Maintenance Menu.
BP+2.9X 11/95
Inverter
Maintenance
Menu
Page 3.27
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.2 Inverter Maintenance Menu (continued)
2 Press to obtain this screen. The
crest factors shown here are for information only. No adjustments can be made.
3. Press to obtain this screen.
Steps 4, 5, and 6 should only be per-
formed when advised by qualified service personnel.
4. Press to reset the inverter faults.
5. This screen will ask you to confirm
that you wish to reset inverter faults.
Output CF A B C
XX.X XX.X XX.X
Reset Inv Faults (UP)
Ready to Start
Confirm
Yes=UP No=DN
6. Press again to return to this screen.
7. Press to obtain –
BP+2.9X 11/95
Reset Inv Faults (UP)
Ready to Start
Return to
Previous Menu
Page 3.28
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.2 Inverter Maintenance Menu (continued)
8. Press to return to the Inverter
Maintenance Menu.
3.6.3. 3 SBS Maintenan ce Menu
1. Press to advance to the SBS
Maintenance Menu.
Bypass/Shutdown Procedure
2. Press to obtain this screen. Press ^
to begin the Bypass/Shutdown Procedure. Retransfers are disabled by this procedure.
To Skip Bypass/Shutdown procedure
and go directly to Manual Transfer to Bypass (Step 12) press instead of .
Inverter
Maintenance
Menu
SBS
Maintenance
Menu
Bypass/Shutdown UPS
UP=Bypass
3. Press to continue the Bypass
Shutdown procedure.
Warning: Bypass/Shutdown procedure may
not be exited without performing all steps in the order shown.
4. When this message appears, close the
BYPASS CIRCUIT BREAKER.
BP+2.9X 11/95
Confirm
Yes=UP No=DN
Menu
Close
Bypass
Breaker
Page 3.29
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3. 3 SBS Maintenan ce Menu (continued)
5. When this message appears, open the
OUTPUT SWITCH or CIRCUIT BREAKER. [On single-input UPS, when the inpu t voltage does not equal the output voltage, place the rotary switch in “maintenance” (open) position.]
Warning: With rotating Output Switch,
output transformer (T2) is energized in Maintenance Bypass mode.
Open
Output
Breaker
6. When this message appears, open the
BATTERY CIRCUIT BREAKER.
7. On dual input UPS only – when this
message appears, open SBS INPUT CIRCUIT
BREAKER.
8. When this message appears, open the
INPUT CIRCUIT BREAKER.
9. While this message is on the screen,
the link voltage will be gradually decreasing. XXX.X represents the actual voltage as dis­played. When the link voltage h as decreased to the proper value, the following screen message will appear.
Open
Battery
Breaker
Open SBS
Input
Breaker
Open
Input
Breaker
Waiting…
DC Link=
XXX.X Vdc
BP+2.9X 11/95
Page 3.30
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3. 3 SBS Maintenan ce Menu (continued)
10. This message indicates that the
Maintenance Bypass Shutdown procedure is complete.
11. You may turn off the UPS CONTROL
switch. This message appears briefly.
Manual Transfer to Bypass
12. Press and to obtain this screen.
13. Press to obtain this screen.
Bypass/
Shutdown
Complete
You may
turn off
UPS contro l
Man Transfer
/Retransfer
Inv Running
Confirm
Yes=UP No=DN
14. Press to manually transfer input to
reserve power source. This will inhibit retransfer and light the Transferred to Bypass and Retransfer Inhibited LED’s. It will also change the “Inv Running” on the screen to “Wait Rexfr.”
BP+2.9X 11/95
Man Transfer
/Retransfer
Inv Running
Page 3.31
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3. 3 SBS Maintenan ce Menu (continued)
15. If it is desired to manually retransfer
to primary UPS input, press and wait 10 seconds for this screen to appear. This will turn off all the LED’s except UPS Normal.
16. Normally, the system will be left so
that transfer and retransfer are enabled. Following Step 11 of this subsection press once or twice to obtain this screen with either “transfers” or “retransfers” on the top line. Pressing or will change between “enable d” and “disabled” on the bottom line.
Man Transfer
/Retransfer
Inv Running
Retransfers
Enabled
17. Press to obtain –
18. Press to return to the SBS
Maintenance Menu.
3.6.3.4 System Maintenance Menu
1. Press to advance to the System
Maintenance Menu.
Return to
Previous
Menu
SBS
Maintenance
Menu
System
Maintenance
Menu
BP+2.9X 11/95
Page 3.32
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4 System Maintenance Menu (continued)
2. Press to obtain this screen. The
“X.XX” represents the latest software release number.
3. Pressing the key will obtain this
screen. Press to execute the LED/lamp test. All of the LED’s will light and a test patter n will be displayed for 3 seconds in b oth the text and numerical display areas.
NOTE: This test can be performed only from
the front panel display.
4. Press to obtain this message. This is
the beginning of a procedure to change the language on the monitor panel, if desired. To leave it in English, press . This will skip to Step 7, below.
5. Pressing in the step above will bring
out this screen. If you wish to change the language, it is necessary to confirm by pres sing UP again.
Software Rev.
Level
X.XX 60 Hz
LED/Lamp
Test
UP = Test
Language
English
Confirm
Yes=UP No=DN
6. Pressing the second time changed
the language and obtained this message (example shown in German).
WARNING: If you don’t speak German, don’t
perform this step. You may get lost trying to get back to English.
BP+2.9X 11/95
Sprache Deutsch
Page 3.33
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4 System Maintenance Menu (continued)
7. Press to obtain this message in the
language displayed in Step 6. The message screens will now all be in that language. Press to confirm that this is the desired language. Press DOWN to change the language. Refer to the manual written in the appropriate language for screen messages and instructions.
Yes=UP No=DN
Confirm
8. Press to obtain this screen. This is
the start of the procedure if it is necessary to change the date setting.
9 Press . The screen will ask you to
confirm that you want to reset the date. If you do not wish to reset the date, press .
10. Press to obtain this screen. If
desired, press or to change the year. Press
. Then, if desired, press or to change the month. Then press . If desired, press or to change the day.
11. Press . This will display the new
month/day/year you have set.
Date
mm/dd/yy
Confirm
Yes=UP No=DN
Enter Date
mm/dd/yy
(actual date)
Date
mm/dd/yy
12. Press to obtain this screen. This is the start of the procedure to change the time setting. (Time readings are based on a 24 ho ur clock.)
BP+2.9X 11/95
Time
(actual time)
Page 3.34
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4 System Maintenance Menu (continued)
13. Press . The screen will ask you to confirm that you want to reset the time. If you do not wish to reset the time, press .
14. If you press , you will obtain this screen. If desired, press or to change the second. Press . Then, if desired, press or to change the hour. Then press . If desired, press or to change the minute.
15. Press . This will display the new time you have set.
16. This sequence is only for those units with LCD display screens. The screen may be tilted up and down to give persons of different height a better view of the messages. Press or
to increase or decrease the reference number. A higher number tilts the screen down; a low er number tilts it up. When finished, press .
Confirm
Yes=UP No=DN
Enter Time
hh:mm:ss
(actual time)
Time
(actual time)
LCD display
view angle
XX
17. Press to obtain this screen. Pressing will save all the changes to the menu made before this.
18. Pressing in the step above will bring out this screen. It is necessary to co nfirm by pressing again.
BP+2.9X 11/95
Save
Personality
UP=Save
Confirm
Yes=UP No=DN
Page 3.35
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4 System Maintenance Menu (continued)
19. Pressing or will return to this screen.
3.6.3.4.1 Alarm Configuration Menu
20. Press to obtain this screen, beginning the Alarm Configuration Menu.
21. Press to obtain this screen. CAUTION: Pressing will clear the Alarm
History records.
3.6.3.4.2 Latching Alarms Menu
The purpose of this procedure is to allow the user to set the various alarms as latching or non-latching. Pressing successively through this section will leave all the settings as they are.
Save
Personality
UP=Save
Alarm
Configuration
Menu
Clear Alarm
History?
UP = Clear
22. Press to obtain this screen,
beginning the procedure.
23. Press to obtain this screen.
24. If you press , this screen will appear
to confirm that you wish to latch all alarms.
BP+2.9X 11/95
Latching
Alarms
Menu
Set all alarms latc hing
UP = Yes
Confirm
Yes = UP No = DN
Page 3.36
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.2 Latching Alarms Menu (continued)
25. If you press after step 23, you will obtain this screen. Pressing will ask you to confirm that you wish to clear all latched alarms. Pressing will obtain the following screen.
26. If you have cleared all latched alarms in Step 25, this will read “Non-latching.” If you wish to change the latching instructions on any of the screens from Step 26 through Step 32, press , change the latching instructions, confirm and press . To go from step 26 to step
Set all alarms latc hing
Transfer to
UP = Yes
Bypass
Latching
27 without making a change, press .
27. Press to go to the following screen.
28. Press to go to the following screen.
29. Press to go to the following screen.
30. Press to go to the following screen.
31. Press to go to the following screen.
Transfer not
Available
Latching
Battery not
Available
Latching
Retransfer
Inhibited Latching
Low Battery
Voltage
Latching
AC Input
Failure
Latching
BP+2.9X 11/95
Page 3.37
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.2 Latching Alarms Menu (continued)
32. Press to go to the following screen.
33. Press and to proceed.
3.6.3.4.3 Communications Menu
34. Press to obtain this screen.
35. Press to obtain this screen.
UPS Overload
Latching
Return to
Previous
Menu
Communications
Menu
COM1 Menu
36. Press to obtain this screen. Pressing at this point will reset the optional
COM1 serial port. (See NOTE 1.)
NOTE 1: The last display line shows the present state of the COM port.
Following is a list of valid messages:
BP+2.9X 11/95
COM1 Device
UP to reset
Power Up Init
Power Up Init Wait on call Get Password Dev. Online Dev. Offline LogOut Resetting
Page 3.38
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.3 Communications Menu (continued)
NOTE 2: COM1 and COM2 in some of the following displays will apply only to an
optional modem or RS232 customer interface described ful ly in Section VII. They can be skipped by pressing until you get to step 48.
37. Press once to obtain one of the “Com 1 Display screens. Press or to obtain another of these three screens, as desired. Pressing will display the “Save Changes?”
screen. User Interface enables the UPS to communicate in a standard ANSI terminal format (VT100 emulation or equivalent). P-Rec Proto allows computer to computer communications with user developed software per the protocol provided in section VII or optional Windows based UPS Manager Plus ™ software. BCM Proto enables communications with optional Onlinet® network power management software.
COM1 Display
User Interface
COM1 Display
P-Rec Prot o
COM1 Display
BCM Proto
38. Pressing will select the desired program and will bring back the previous COM1 screen.
39. Press once to get to this screen. If you wish to change the Com 1 baud rate, press
to increase baud rate from 2400 to 9600, or press to decrease from 9600 to 2400. Pressing will display the “Save Changes?”
screen.
UPS Manager Plus™ is a trademark of International Power Machines. Onlinet® is a registered trademark of Exide Electronics Group.
BP+2.9X 11/95
Save Changes?
Yes = UP No = DN
COM1 Baud Rate
2400
Page 3.39
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.3 Communications Menu (continued)
40. Pressing ^ will select the desired baud rate and will bring back the previous COM1 screen.
41. Press and to proceed.
42. Press to obtain this screen.
43. Press to obtain this screen. Pressing at this point will reset the optional
COM2 serial port. (See NOTE 1.)
44. Press once to obtain one of the “Com 2 Display screens. Press or to obtain another of these three screens, as desired. Pressing will display the “Save Changes?”
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
COM2 Menu
COM2 Device
UP to reset
Power Up Init
COM2 Display
User Interface
screen. User Interface enables the UPS to communicate in a standard ANSI terminal format (VT100 emulation or equivalent). P-Rec Proto allows computer to computer communications with user developed software per the protocol provided in section VII or optional Windows based UPS Manager Plus ™ software. BCM Proto enables communications with optional Onlinet® network power management software.
BP+2.9X 11/95
COM2 Display
P-Rec Prot o
COM2 Display
BCM Proto
Page 3.40
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.3 Communications Menu (continued)
45. Pressing will select the desired program and will bring back the previous COM2 screen.
46. Press once to get to this screen. If you wish to change the Com 2 baud rate, press
to increase baud rate from 2400 to 9600, or press to decrease from 9600 to 2400. Pressing will display the “Save Changes?”
screen.
47. Pressing ^ will select the desired baud rate and will bring back the previous COM1 screen.
48. Press and to proceed.
Save Changes?
Yes = UP No = DN
COM1 Baud Rate
2400
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
3.6.3.4.4 UPS Identification Menu
49. Press to obtain this screen.
50. Press to obtain this screen.
BP+2.9X 11/95
UPS
Identification
Menu
UPS Name
Page 3.41
SECTION III
_
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.4 UPS Identification Menu (continued)
51. Press and this confirmation screen will appear asking whether you want to enter a name.
52. Press again if you wish to enter a name. This screen will appear.
Notice the blinking cursor at the bottom lin e. Pressing or will change the character under the cursor (originally a space). You can move through the available characters faster by holding down the ALARM SILENCE button while pressing or . To move the cursor to the right, press ; to move to the left press
.
53. When all characters have been
entered, the screen will look like this. Press X.
54. Press to save the changes.
Yes = UP No = DN
ABC COMPANY
Yes = UP No = DN
Confirm
Enter Name
Enter Name
Save Changes?
55. Press to obtain this screen.
56. Press and this confirmation screen will appear asking whether you want to enter a unit identification.
BP+2.9X 11/95
UPS Unit ID
Confirm
Yes = UP No = DN
Page 3.42
SECTION III
_
_
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.4 UPS Identification Menu (continued)
57. Press again if you do wish to enter a unit identification. This screen will appear:
Notice the blinking cursor at the bottom lin e. Pressing or will change the character under the cursor (originally a space). You can move through the available characters faster by holding down the ALARM SILENCE button while pressing or . To move the cursor to the right, press ; to move to the left press
.
58. Press to save the changes.
59. If “Phone Home” feature is being used, the UPS modem phone number must be entered. Press once to obtain this screen. If you wish to skip this sequence, press twice to go to step 59.
Enter unit ID:
Save Changes?
Yes = UP No = DN
UPS Phone
Number
60. Pressing and this confirmation screen will appear asking whether you want to enter a phone number.
61. Press again if you do wish to enter a phone number. This screen will appear.
BP+2.9X 11/95
Confirm
Yes = UP No = DN
Enter Phone Number:
Page 3.43
SECTION III
_
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.4 UPS Identification Menu (continued)
Notice the blinking cursor at the bottom lin e. Pressing or will change the character under the cursor (originally a space). You can move through the available characters faster by holding down the ALARM SILENCE button while pressing or . To move the cursor to the right, press ; to move to the left press
.
62. When all characters have been
entered, the screen will look like this. Press .
63. Press to save the changes.
64. This sequence is for entering a 24 hour telephone number which can be called b y Factory Field Service personnel to tell you that your UPS has reported an alarm condition via its Phone Home capability. Press once to obtain this screen. If you wish to skip this sequence, press twice to go to step 64.
65. Press and this confirmation screen will appear asking whether you want to enter a phone number.
Enter Phone Number:
XXXXXXXXXX
Save Changes?
Yes = UP No = DN
24 Hr. Voice Phone
Number:
Confirm
Yes = UP No = DN
66. Press again if you do wish to enter a phone number. This screen will appear.
BP+2.9X 11/95
Enter Phone Number:
Page 3.44
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.4.4 UPS Identification Menu (continued)
Notice the blinking cursor at the bottom lin e. Pressing or will change the character under the cursor (originally a space). You can move through the available characters faster by holding down the ALARM SILENCE button while pressing or . To move the cursor to the right, press ; to move to the left press
.
67. When all characters have been
entered, the screen will look like this: Press .
68. Press to save the changes.
69. Press to obtain this screen.
70. Press to return to the System
Maintenance Menu.
3.6.3.5 Password Maintenance Menu
Enter Phone Number:
XXXXXXXXXX
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
System
Maintenance
Menu
1. Press to advance to the Password
Maintenance Menu.
BP+2.9X 11/95
Password
Maintenance
Menu
Page 3.45
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.5 Password Maintenance Menu (continued)
2. Press to obtain this screen. There
are four (4) levels of passwords. Press as often as necessary to reach the desired level. The number in the lower left will ch ange, indicat ing the level attained. (NOTE: You can not go beyond the level for which the system is set when you start.)
3. Press . The system will ask you to
confirm the password level.
4. Press as requested in the previous message. You are now ready to modify the password. Follow the procedure you used in steps 3 through 6, pages 3.25 a nd 3.26 to g et into the UPS Maintenance Menu. When you have finished, press .
5. You will see this message briefly flashed on the screen –
No Password
Password
Menu
Confirm
Yes = UP No = DN
Enter
Password
0
Verify
Password
6. Then this message will appear again. It is necessary to repeat step 4, entering the new password again. Then press .
7. Press to save the new password.
BP+2.9X 11/95
Enter
Password
0
Save Changes?
Yes = UP No = DN
Page 3.46
SECTION III
Operation
3.6 UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.5 Password Maintenance Menu (continued)
8. Press to obtain this screen.
9. Press to return to the Password Maintenance Menu.
10. Depress to return to Previous Menu.
11. Depress to leave UPS Maintenance Menu.
3.6.4 System Shutdown
1. Perform the Bypass/Shutdown procedure (Paragraph 3.6.3.3).
NOTE: This leaves the critical load powered by the utility power source
through the bypass.
Return to
Previous
Menu
Password
Maintenance
Menu
2. To remove all power to the load, open the BYPASS CIRCUIT BREAKER.
3.6.5.CPU Fault
If this message should appear on the screen, the UPS is transferred to bypass. Call Service Hotline at (800) 777-8922.
BP+2.9X 11/95
Page 3.47
SECTION IV
Maintenance
4.1 General
Proper maintenance, both preventive and remedial, is the key to optimal operation of the UPS and will ensure a long and useflil life of the equipment. Preventive maintenance includes regularly performed procedures designed to prevent system malfunction and obtain maximum operational efficiency. Re­medial maintenance consists of troubleshooting the system in order to effect repairs. Troubleshooting the UPS involves following a logical sequence of steps which will determine the cause of an alarm and/or malfunction within the shortest time frame safely possible so as to expedite the repair and return of the equipment to normal service.
The manufacturer recommends that the monitor panel be inspected visually every eight-hour shift to see that lights are operating and no alarm conditions exist. The Alarm History should be checked at this time (see Paragraph 3.6.2) to determine if any recent alarms have gone un-noticed. If any unusual conditions exist, call facility maintenance p ersonnel or Service Hotline: 800-777-8922 or (outside U.S.) 919-871-1800.
4.2 Safety Precautions
For safe and successful maintenance on the system, certain basic safety precautions must be observed, necessary tools and test equipment must be available, and properly trained maintenance personnel must be involved.
The following basic safety practices should always be observed:
1. Always be aware that hazardous voltages a re p resent within the UP S even when the system is not operating.
WARNING
On a single-input UPS, when input voltage does not equal output voltage, output transformer (T2) is energized in Maintenance Bypass Mode.
2. Ensure that UPS operating and maintenance personnel are thoroughl y familiar with the equipment and with the contents of this manual.
BP+2.9X 11/95
Page 4.1
SECTION IV
Maintenance
4.2 Safety Precautions (continued)
3. Never wear metal jewelry such as rings or wrist watches when workin g on the UPS equipment.
4. Keep cabinet doors closed and secured during normal operation.
5. Never guess about safety procedures. If any doubt exists, ask someone who knows.
6. Always be aware of the presence of high voltage within the UPS.
Check with a voltmeter to make sure power is off and conditions are safe before attempting to make repairs, adjustments, etc. within the unit.
7. Above all, always USE COMMON SENSE!
4.3 Preventive (Periodic) Maintenance
The following paragraphs describe preventive maintenance procedures
which, when followed, will increase the reliability and efficiency of the UPS
system operations.
4.3.1 Air Filters
Filters, installed in the bottom of the cabinet, eliminate particles from the air which is used to cool the UPS. In time, particle accumulation in the filters will reduce airflow through the system causing a rise in operating temperatures, triggering an alarm condition and resulting in shut down of the UPS. Filters should be checked and cleaned or replaced at least every 30 days in a clean environment, and no more than 7 days in a dirty environment.
Models of 125 and 150 kVA have two filters; other models have only one. Loosening a clip beneath the UPS near the front allows the filter to drop down and you can slide it out. Insert new filter and twist clip to secure it in place.
Filters are standard fiberglass furnace filters of the following sizes:
10-100 kVA UPS - 16" x 25" x 1" 125-150 kVA UPS - 14" x 25" x 1"
BP+2.9X 11/95
Page 4.2
SECTION IV
Maintenance
4.3 Preventive Maintenance (continued)
4.3.2 Cable Connections
Cable connections to circuit breaker and switch terminals should be checked whenever the system is powered down and at least annually. This necessitates removal of the circuit breaker panel to gain access.
WARNING
Be aware of the presence of high voltages within the UPS! When the system is shut down, wait at least five (5) minutes after all panel lights go out before proceeding. Then check for the p resence of power with a voltmeter across the input and output terminals.
4.4 Remedial Mainte nance (Troubleshooting)
Remember the International Power Machines 24-Hour Hot Line:
Phone: 800-777-8922; (outside U.S.) 214-272-8000
is always available to provide advice and assistance on your UPS.
4.4.1 General
When properly installed, operated and maintained your International P ower Machines BalancedPower Plus UPS will provide long, reliable power protection with little need of remedial or corrective maintenance actions. However, this section contains information as to problem isolation techniques and recommended actions to be taken so as to effect repairs on the UPS.
BP+2.9X 11/95
Page 4.3
SECTION IV
Maintenance
4.4 Remedial Mainte nance (continued)
4.4.1 Gener al (c o nti nu ed )
Because of the modular design o f the BalancedPower Plus UPS, corrective action in many instances requires replacement of a major assembly or subassembly. For this reason, troubleshooting information as containe d herein is generally limited to immediate action that may be taken on site to correct a specific alarm condition. If such immediate action does not remedy the situation, contact the 1PM 24-Hour Hotline for assistance.
In general the BalancedPower Plus UPS is designed so that the operator should not find it necessary to have access to any area of the equipment except the Digital Monitor Panel and the circuit breake rs, switch and fuses inside the right­hand door.
WARNING
Do not remove front plastic shield, front panel around the circuit breakers or either side panel unless all power to the UPS is OFF. Only trained maintenance personnel should remove any of these panels.
4.4.2 Status/Alarm Indicators
The LED status/alarm indicators on the monitor panel are described in Paragraph 3.4.1. Specific action that may be taken in case of alarm c onditions is described in Table 3-2, a part of Paragraph 3.6.2.
BP+2.9X 11/95
Page 4.4
SECTION IV
Maintenance
4.5 Fuses
There are four (4) fuses adjacent to the UPS CONTROL switch inside the front door. If one of these fuses is blown, the control logic will not become energized at startup. Once the UPS is started, it will operate even though one o r more of the fuses is blown.
In case a fuse blows, replace it with a fuse of the same make and size.
These are the only fuses available to the user unless he or she has had authorized factory training.
4.6 Battery Maintenance
4.6.1 Safety Precautions
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and the following type of batteries: sealed lead acid. All batteries in a cabinet should be from the same
manufacturer and of the same part number.
CAUTION: Do not dispose of battery or batteries in a fire. The battery
may explode.
CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working on batteries:
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
BP+2.9X 11/95
Page 4.5
4.6 Battery Maintenance (continued)
4.6.1 Safety Precautions (continued)
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Open DC Disconnect switch prior to connecting or disconnecting battery terminals.
6. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such a shock will be reduced if such grounds are removed during installation and maintenance.
SECTION IV
Maintenance
4.6.2 Maintenance Shutdown of Battery Pack
This procedure is for shutting down the IPM battery pack. It does not require that the protected load be removed from the UPS.
Perform the following steps in the order presented:
1. Verify that each UPS attached to the battery pack is running on UPS input ac pow er by noting the dc link voltage. Depress or beneath DISPLAY SELECT to obtain the Link Voltage message on the screen. Voltage should be 234 VDC (10-30 kVA) or 390 VDC (37.5-150 kVA) or greater.
Do not proceed if battery system is sup plying p ower to any protected
equipment.
2. Shut off DC Disconnect switch. This will illuminate the Battery Not
Available LED .
3. A general alarm will appear at each UPS as the Disconnect device is opened. This is normal. Depress the ALARM SILENCE button once to turn off the audible alarm.
Link Voltage
Battery Amps
Max Out CF
BP+2.9X 11/95
Page 4.6
4.6 Battery Maintenance (continued)
4.6.3 Inspection and Periodic Maintenance
This procedure should be performed annually or whenever batteries need to
be replaced.
1. Place the battery pack in Maintenance Shutdown condition (Para­graph 4.6.2).
2. Open the front doors of each battery pack and visuall y inspect the inside of the cabinet for:
a. Leaking acid. b. Corrosion on frame and electrical parts. c. Loose or discolored electrical connections, especially around
the cable connections.
SECTION IV
Maintenance
3. Disconnect all the battery cable connectors.
4. Each battery tray is held in place by two bolts that fasten it to a slide.
Remove the bolts from one tray at a time and very carefully pull the tray forward. Care should be taken that the tray doesn't come all the way out. The tray is heavy weighing as much as 200 pounds (91 kg) or more.
5. Use a lift hand truck to remove the tray completely from its slide.
CAUTIO N
The battery tray weighs as much as 200 lbs (91 kg). Use lift hand truck to remove it.
6. Inspect each battery post for corrosion or discoloration. If post is discolored or corroded remove battery cable and clean the post and cable connector shiny bright. Replace cable, torque cable connector bolt to the battery manufacturer's recommended torque*, and apply a generous amount of grease (Dow Corning silicone grease or equal) to the battery posts and connectors.
* Tor que s p ecif icati on s ma y be fou nd o n th e bat ter y its elf or in sp ecifi ca ti ons at th e end of this
section.
BP+2.9X 11/95
Page 4.7
SECTION IV
Maintenance
4.6 Battery Maintenance (continued)
4.6.3 Inspection and Periodic Maintenance (continued)
7. If not removed and cleaned, torque all cable connector bolts to battery manufacturer's retorquing specifications.
8. Repeat until all battery trays have been inspected, cleaned and gr eased. Do one tray at a time and be sure to return tray to its original location. Bolt in place. Trays are numbered in accordance with Figure 4-1 or 4-2 on Page 4.11.
9. Retighten power cable connections between the DC Disconnect switch and the UPS. Refer to torque table in Paragraph 2.7, AC Power Connection.
10. Reconnect the battery trays to each other as described in Paragraph 2.8, Activating the Battery Pack. Close the battery pack door.
4.6.4 Batt ery Test
Batteries should be tested whenever a batter y-related problem is susp ected or at annual intervals. The procedure described is for individual batteries and requires the use of a Balkamp 700-112 Battery Tester or equivalent. The Balkamp unit is available at most NAPA auto parts stores or from IPM.
The tester is rated for 100 amps, 12 vdc. It checks voltage under load.
Batteries should be tested in their fully-charged state, but not within 24 hours of having been equalized (recharged). Batteries should be left in their trays during testing.
1. Perform Maintenance Shutdown procedure (Paragraph 4.6.2).
2. Remove two bolts and slide out the desire d battery tray onto a lift hand
truck.
CAUTIO N
The battery tray weighs as much as 200 lbs (91 kg). Use lift hand truck to remove it.
BP+2.9X 11/95
Page 4.8
SECTION IV
Maintenance
4.6 Battery Maintenance (continued)
4.6.4 Battery Test (con ti nu ed )
3. Test each battery separately.
4. Using a digital voltmeter which can be read to 0.01 vdc, check the voltage across the posts of the batteries, one at a time. Record the voltage readings for each battery. If the voltage does not read at least 12.40 vdc, the battery probably should be replaced. You may try to recharge the battery, but it probably won't hold a charge. For replacement procedure see Paragraph 4.6.5.
5. If the battery's voltage is satisfactory, use the battery tester. Attach the red battery tester cable to the positive (+) battery pole; attach the black cable to the negative (-) battery pole.
6. Press the LOAD switch. (If using a brand of tester other than the Balkamp, follow the tester's operating instructions.)
7. In approximately 10 seconds, the tester n eedle should be in the "good" (green) area. If not, the battery should be replaced.
8. Perform the same tests on all batteries i n the cabinet . (Allow the tester to cool between tests.)
9. For proper operation, each battery in the cabinet should show voltage readings within ±0.10 vdc of their average. If full agreement of battery voltages cannot be obtained, contact Service Hotline 800-777-8922.
10. Return the battery trays to their normal position. When each tray is fully back, replace the two bolts that fasten it to the slide. Reconnect the battery tra y cables.
BP+2.9X 11/95
Page 4.9
SECTION IV
Maintenance
4.6 Battery Maintenance (continued)
4.6.5 Battery Replacement
1. Perform Maintenance Shutdown procedure (Paragraph 4.6.2).
2. Disconnect the desired battery tray, unbolt it from its slide and slide it out onto a lift hand truck.
CAUTIO N
The battery tray weighs as much as 200 lbs (91 kg). Use lift hand truck to remove it.
3. Disconnect battery and remove it from the tray. Note battery polarity.
4. Mount new battery in tray, clean the posts and cable l ugs and connect cables, observing polarity (see Figure 4-1 or 4-2 on next page).
5. Torque cable connector bolts to battery manufacturer's specifications.
6. Using a digital voltmeter which can be re ad to 0.01 vdc, check voltage across the poles of the new battery. Voltage should be at least 12.40 vdc.
7. Apply a generous amount of grease (Dow Corning silicone grease or equal) to the battery posts and connectors.
8. Push battery tray back to its original position. When the tray is fully back, replace the two bolts that fasten it to the slide.
9. Reconnect the battery tray cables.
4.6.6 Reactivating the Battery Pack
1. After all battery trays and their batteries are in place and reconn ected, close the battery pack doors.
2. Verify UPS rectifier DC link voltage is at proper value (234VDC for 10­3OkVA; 39OVDC for 37.5-300kVA).
3. Close the DC Disconnect switch only if link voltage is correct.
BP+2.9X 11/95
Page 4.10
4.6 Battery Maintenance (contin ued)
4.6.6 Reactivating the Battery Pack (continued)
SECTION IV
Maintenance
6 battery trays
Figure 4-1
BP+2.9X 11/95
10 battery trays
Figure 4-2
Polarity of Batteries in Tray
Page 4.11
SECTION IV
Maintenance
Battery Manufacturers' Torque Specifications
Johnson Controls:
Item Bolt
Size
UPS 12-140FR 1/4 7/16 40 lb-in 30 lb-in UPS 12-170FR 1/4 7/16 40 lb-in 30 lb-in UPS 12-270FR 1/4 7/16 40 lb-in 30 lb-in UPS 12-310FR 1/4 7/16 65 lb-in 50 lb-in UPS 12-370FR 1/4 7/16 65 lb-in 50 lb-in UPS 12-475FR 1/4 7/16 110 lb-in 60 lb-in
Wrench
Size
Initial
Torque
Retorque
Power Batteries:
Recommended torque is on label on top of each battery.
GNB
100 lb-in
C&D
100 lb-in
Annual
NOTE: To obtain N-m, multiply in/lb by 0.113.
BP+2.9X 11/95
Page 4.12
SECTION V
Spares, Training Maintenance
5.1 Spare Parts
To facilitate service on the BalancedPower Plus UPS, it is recommended that a spare parts stock be maintained on site. Investment in a spares stock ensures immediate parts availability when required, thereby providing for faster service and greater protection from costly system downtime.
International Power Machines can supply any of several recommended Spares Levels to meet differing requirements. The desired Mean-Time-To-Repair and the travel time from IPM's nearest Service Center would normally determine the approximate level of spares to be stocked.
This section lists typical spare parts for a UPS of the size shown on the cover page of this manual. It is not applicable to other size UPS.
For further information concerning the stocking of spare parts, or to order replacement parts, please contact:
Customer Services Representative International Power Machines Worldwide Services Group, IPRC 2708 Discovery Drive Raleigh, NC 27604
Domestic: Phone: (919) 981-8127
Fax: (919) 981-8150
Outside U.S.: Phone: (919) 870-3208
Fax: (919) 870-3300
BP+2.9X 11/95
Page 5.1
SECTION V
Spares, Training Maintenance
5.2 Training
To insure that our customers derive maximum benefit from their UPS and related equipment, IPM offers a variety of training classes tailored to specific interests and requirements. These courses include a one-day Operator Seminar, a Basic Maintenance class for facilities perso nnel and spec ialized trai ning for uniq ue equipment configurations. Most classes can be presented either at our Training and Support Center or at the customer's site.
Additional information and rates may be obtained from:
WSG Training and Support Center
International Power Machines
3401 Spring Forest Road
Raleigh, NC 27604
Phone: (919) 871-1812
Fax:(919)871-1822
5.3 Continu ing Maint enance Program
We consider regular maintenance of your UPS to be insurance for your equipment investment. We have, therefore, developed a continuing maintenance program, available throughout the 50 states, that can go into effect upon the expiration of the standard warranty on new equipment. Basically, the program provides for one preventive maintenance call per year, plus unlimited remedial maintenance calls as required, with all parts, labor and expenses included. Similar battery maintenance programs are available.
Additional information and prices may be obtained from:
Worldwide Services Group
International Power Machines
Maintenance Sales Department
10451 Brockwood Road
Dallas, Texas 75238-1641
Phone: (214) 342-6104
Fax: (214) 214-342-6115
BP+2.9X 11/95
Page 5.2
SECTION VI
Glossary
AC­Alternating current (normally "AC").
AC POWER ­AC input to the UPS. Also identified as "UPS Input."
ALARM ­An abnormal condition within the UPS.
ALARM SIGNAL ­A loud piercing electronic tone signaling an alarm condition.
APPARENT POWER (kVA) ­The product of voltage and current. This is used to state the maximum rating of power generating devices.
AUTO RETRANSFER ­A feature which allows the Static Bypass Switch to place the UPS back on line without manual intervention.
CIRCUIT BREAKER PANEL ­That portion of the cabinet behind the right-hand door, containing th e UPS Input Circuit Breaker, Static Bypass Circuit Breaker, Bypass Circuit Breaker and Output Circuit Breaker.
CURRENT LIMIT ­Electronically governing the maximum current output from the rectifier and/or the inverter.
DC­Direct current (normally "DC").
DC LINK­DC voltage output of the rectifier and input to the inverter. Is maintained by a battery bank during a power outage.
DIGITAL SIGNALPROCESSOR (DSP) ­The "brain" of the control logic system.. Receives and an alyzes data, and provides control and monitoring for the UPS.
BP+2.9X 11/95
Page 6.1
SECTION VI
Glossary
EMERGENCY POWER OFF (EPO) ­A means of cutting power from the UPS in emergency situations. The EPO switch is located on the Monitor Panel.
EQUALIZE ­See RECHARGE.
FLOAT CHARGE ­A dc voltage applied to a battery at a level which mainta ins the battery in a fully­charged state.
HERTZ (Hz) ­The measure of electrical frequency in cycles per second.
INVERTER ­A major component of the UPS. Its primary function is to change DC to AC.
LED­Light-emitting diode. A semiconductor that give off light when it is energized.
LOGIC CIRCUIT ­A network of electronic components that performs a specific function.
OUTAGE ­Loss of UPS input or bypass power.
PHASE LOCK ­A condition in which the inverter output is frequency and phase synchronous with the utility ac source.
PHASE SEQUENCE ­The order in which the fundamental components of a poly-phase set of voltages/currents reach a particular value.
POWER FACTOR ­The ratio of real power to apparent power. Equal to the cosine of the phase angle between the current and voltage for sinusoidal voltages and currents.
BP+2.9X 11/95
Page 6.2
SECTION VI
Glossary
REAL POWER (kW) ­The portion of apparent power which actually performs work or generates heat.
RECHARGE ­A dc voltage applied to a battery for a given period of time which will equalize unevenly charged cells. After an emergency discharge, it will restore the batteries to full charge.
RECTIFIER/CHARGER ­A major component of the UPS. Its primary function is to change AC to DC for the inverter input. It also supplies current to recharge or m aintain the charge of the batteries.
REMOTE ALARM CONTACTS ­Relay switch! contact arrangement which opens or closes in response to an alarm condition within the UPS. The contacts are connected to terminals which are easily accessible to the customer. They provide the ability to remotely sense an alarm condition.
STATIC BYPASS SWITCH (SBS) ­A major component of the UPS. Connects the U PS Input to the load if th e rectifier and/or the inverter become unavailable or unacceptable.
TRANSFER ­A static bypass switch operation which exchanges load power sources from the UPS to utility power.
UPS­Uninterruptible power system. UPS are on-line units which deliver power to the critical load from the inverter on a full-time basis. A power outage does not require load switching manually since the battery in stantaneousl y takes over to supply dc power to the inverter. Due to the ac to dc t o ac conversi on, most UPS units offer superior ac transient noise suppression.
WYE OUTPUT ­A wiring configuration. Wye utilizes four wires to furnis h a neutral. The output of the UPS is a WYE configuration.
BP+2.9X 11/95
Page 6.3
SECTION VII
Remote Video Terminal
7.1 General
An optional remote video terminal, supplied by LorTec or by the customer, is plugged into the optional RS232 communicati on or telepho ne modem port. If this port was not purchased, this section does not apply to your UPS.
The remote monitor is to be a video display terminal capable of emulating a VT100 or equivalent.
7.2 RS232 Interlace
When COM1 or COM2 user interface is selected, the basic CRT Menu Screen looks like this during normal UPS operation. A valid password must be entered to access this screen.
[*] UPS Normal [ ] Tran sferred to Bypass [ ] AC Input Failure [ ] Transfer not Available [ ] Low Battery Voltage [ ] Battery Not Available [ ] UPS Overloaded [ ] Retr ansfer Inhibited
UPS Maintenance Input Van 121.1 Link Voltage 400.1 Menu Input Vbn 121.8 Battery Amps -7.2
Input Vcn 121.0 Max Out CF 1.86
UPS Input Ia 62.7 Output KW 0.0 Operating Input Ib 62.5 Output KVA 1.0 Normally Input Ic 62.6 Output PF 0.00
08/30/9 5 Bypass Va b 216.2 Output Van 120.1 10:07:0 1. 31 4 Bypass Vbc 215.6 Output Vbn 120.3 ups norma l Bypass Vc a 224.7 Output Vcn 119.9
Input Vab 210.1 Input Freq 60.00 Output Ia 3.3 Input Vbc 209.2 Output Freq 60.00 Output Ib 3.3 Input Vca 210.4 Inlet Temp 19.9 Output Ic 3.3
[N]ext [P ]r ev ious [S]il en ce [U]p [D]own [E] nte r [ ^R]efres h [H ]i story
The top segment represents the LED's on the front of the UPS monitor panel. The four-column segment represents the messages which ap pear on the monitor panel's message screen. (Numbers are typical; actual values will appear.)
BP+2.9X 11/95
Page 7.1
SECTION VII
Remote Video Terminal
7.2 RS232 Interface (continued)
The lower segment shows the keyboard keys to be used to change the message screens (in place of the pushbutton s on the monitor panel). Briefly, the functions of these keys are as follows:
Key Function
[N]ext Scrolls data up the display area.
Displays next item in a submenu list.
[P]revious Scrolls data down the display area.
Displays previous item in a submenu list. [S]ilence Alarm silence. [U]p Displays next alarm entry in Alarm History when Alarm
History is active.
Increment displayed value of modifiable elements. [D]own Displays previous alarm entry in Alarm History when Alarm
History is active.
Decrement displayed value of modifiable elements. [E]nter Select the menu displayed in active area.
Save changes of modifiable elements. [^R]efresh (Press Control R.) Clears the screen and redraws it. [H]istory Full screen alarm history display. [LO]g out (Not shown on screen.) Disconnects the modem. The upper left-hand message is the only one that is active at any given time,
On the sample CRT screen "UPS Maintenance Me nu" is in the active area. Other message screens can be brought into this active area by depressing [N]ext or [P]revious on the keyboard, causing the messages to rotate. Do this as often as necessary until the desired message is in the upper left-hand corner.
BP+2.9X 11/95
Page 7.2
SECTION VII
Remote Video Terminal
7.3 UPS Maintenance Menu
The description given in Section 3.6.3 for the UPS Maintenance Menu
applies equally to its use from a remote terminal. Make sure that "UPS Maintenance Menu" is in the upper left-hand area of the CRT screen. Then use the keys that correspond to the pushbuttons described in this manual. You will need to use the operator password (level 4) in order to obtain access to the UPS Maintenance Menu. The various screen messages will appear on t he CRT also in the upper left-hand area.
7.4 Alarm History Screen
Below is a typical Alarm History screen. The alarms are displayed in
date/time order with the most recent alarm at the bottom of the screen.
Mo/Dy/Yr Hr:Mn:Sc :Cy:Q A larm (U=U p D=Dn += PgUp -=PgD n T=Top B =Bot M=Mo nitor) 09/20/91 14:59:27 .07.0 sb s output breaker c losed 09/20/91 14:59:27 .07.0 in v not pha se locked 09/20/91 14:59:27 .07.0 in v transfe r enabled 09/20/91 14:59:27 .07.0 in v retrans fer enabl ed 09/20/91 14:59:27 .07.0 in v fan nor mal 09/20/91 14:59:27 .08.0 in put frequ ency norm al 09/20/91 14:59:27 .08.0 sb s bypass frequency normal 09/20/91 14:59:27 .10.0 sb s bypass voltage l ow 09/20/91 14:59:28 .41.0 rc t phase l ocked 09/20/91 14:59:28 .42.0 in put volta ge low 09/20/91 14:59:32 .23.0 in put volta ge normal 09/20/91 14:59:32 .23.0 sb s bypass voltage n ormal 09/20/91 14:59:32 .23.0 in v phase r otation n ormal 09/20/91 14:59:32 .23.0 re ctifier n ormal 09/20/91 14:59:37 .07.1 in v normal temperatu re 09/20/91 14:59:37 .08.0 in v fuse no rmal 09/20/91 14:59:37 .08.0 in v power s upply nor mal 09/20/91 14:59:37 .18.0 in v current normal 09/20/91 14:59:37 .18.0 ou tput volt age low 09/20/91 14:59:37 .18.0 in verter of f 09120/91 14:59:37 .18.0 sb s off 09/20/91 14:59:39 .09.0 in v phase l ocked 09/20/91 14:59:47 .33.0 dc voltage normal
A convenient way of viewing the Alarm Histor y screen is t o use the com mands at the top of this screen:
U Scrolls up one alarm T Goes to the top of the alarm history buffer D Scrolls down one alarm B Goes to the bottom of the alarm history buffer + Scrolls up one page M Monitors the occurrence of alarms. All new
- Scrolls down one page alarms are added to the bottom of the screen.
BP+2.9X 11/95
Page 7.3
SECTION VII
Remote Video Terminal
7.5 P-Record
P-Record format is for users who need to query the UPS periodically for
information as to its status or develop cust om monitoring software. It is used also when the "phone home" capability is enabled.
For additional information on the P-Record protocol, refer to document
950-010-A416, Revision C, UPS Remote Monitor Protocol.
BP+2.9X 11/95
Page 7.4
Loading...