This manual contains important safety instructions
that should be followed during installation and
maintenance of the UPS and Battery Cabinets.
International Power Machines®
10451 Brockwood Road
Dallas, Texas 75238-1641
Phone: (214) 342-6100
Service Hotline (800) 777-8922
IPM at your service
International Power Machines Corporation considers prompt customer
service to be an integral pa rt of its produ ct. Ou r Fi eld S ervi c e D ep artm e nt i s
accessible by telephon e 24 hours a day, seven d ays a week to im plement
timely servicing of our equipment.
IPM 24-HOUR SERVICE HOTLINE:
Phone: (800) 777-8922
Outside US.: (919) 871-1800
Fax: (214) 342-6115
When calling for service assistance, have the following information
and a rec ord of r eadi ngs a nd al arm ligh ts fr om the m achi ne’s m on itor
panel available for the IPM service dispatcher:
Serial Number:
(On label inside machine’s front door.)
InputOutput
Voltage
Frequency (Hz)
Model No.Monitor
International Power Machines
10451 Brockwood Road
Dallas, Texas 75238-1641 U.S.A.
800-527-1208
Important No tice
The manufacturer recommends that the
monitor panel be inspected visually every
eight-hour shift to see that lights are operating and no alarm conditions exist. If any
unusual conditions exist, call facility maintenance personnel or IPM/LorTec Service
Hotline:
INFORMATION CONTAINED HEREIN IS THE PROPERTY OF INTERNATIONAL POWER
MACHINES CORPORATION, IS PROP RIETARY, CONFIDENTIAL AND NOT TO BE DIS
CLOSED, DISSEMINATED NOR USED EXCEPT FOR THE PURPOSE PROVIDED BY
INTERNATIONALPOWERMACHINESCORPORATION.
BP+15-150,2.9X
5/95
Page iii
HOW TO USE THIS MANUAL
A proper understanding and use of this operating and maintenance manual will
enhance UPS system reliability. Therefore, the manual should be given equal status
with the tools and equipment used to align and maintain the system. Conversely,
improper understanding or application of the principles set forth can result in impaired
system op er at io n, l os s of p ow er t o cr it ic al e qu ip me nt l oa ds , in ju ry t o pe rs on ne l an d/ or
damage to the UPS.
The following guidelines will assist in the understanding and use of this manual.
1.Become fa miliar w ith the Table of Content s. It is here th at the u ser can
first determine where in th e manual req uired info rmation or guidance can be
found.
2.Read through the entire manual so as to become familiar with its style and
general contents.
3.Know the manual’s limitations. It is not the intent of this manual to give a
detaile d th eo ry o f op er at io n of t he U PS s ys te m. Tro ub le sh oo ti ng i s li mi te d to t he
isolation and correction of problems that are signaled by the Control!
Monitoring/Alarm Panel.
4.Be thorou ghly fam iliar wi th the saf ety prec aution s outl ined i n Sect ions II
and IV of the manual.
5.Do not take short cuts when operating the UPS or performing maintenance on the system. A slower, more deliberate pace will give better results
beca use it elimi nate s conf usio n and an y fals e conc lusi ons whic h may be reached
by skipping steps. Careful adherence to step sequences presented herein is, more
often than not, the fastest way to achieve desired results.
6.This manual is written based on the assumption that maintenance
personnel will be fully knowledgeable in electronics and aware of the hazards of
working with high voltage equipment. Always remember that voltages may bepresent even when the system has been fully shut down. Use a voltmeter to check
terminals to ground. There is no substitute for common sense.
7.Do n’t gues s! If you do n’t know , ask some one who do es.
8.Remembe r that the Interna tional Pow er Machine s Service St aff is alway s
available to answer your questions or provide helpful advice about your UPS
system. Call them on our Service Hot Line:
BP+15-150,2.9X
5/95
Telephone: (800) 777-8922
Page iv
Handling and Unpacking Instructions
Handling Instructions:
1.Cabinets should always be stored in an upright position. Failure to observe this precaution can cause serious damage and
cancellati on of war ranty.
2.Cabinets should be forklifted only at appropriate lifting points. Make sure that forks are long enough to go entirely under the unit
and protrude from the oth er side. Be careful not to pun c t ure another unit beyond the one being lifted.
3.Chains, cables, ropes or oth er retaining devices sh ould not be wr apped around a cabin et. The weight of th e system is great
enough to cause collapse of the cabinet when lifted by these means.
4.Pa dding mus t be us ed when transporting the system s o a s to help prevent damage to the cabi n ets.
Inspection and Unpack ing Instructions:
The uninterruptible power system (UPS), battery pack cabinet and/or power distribution unit (PDU) is thoroughly checked, both
electrically and mechanically, before shipment from the factory. With the exten sive protection provided in packaging the unit for
shipm ent, it shoul d be in proper cond ition upon recei pt. However, there i s a possibility that the unit might have been damaged in
tran sit so a complet e inspection of th e equipment shoul d be made before si gning receipt . As a minimum, the foll owing insp ection
pr oc edures should be e xecut e d as soon as possible after delivery.
Receiving / Unpacking lnspection Checklist
5.Each palletized unit is designed for forklift or lift gate handling. It is recommended that all packaging be left intact until the unit
is in close proximity to its final location to prevent incidental damage during movement.
6.Inspect th e exterior packaging for obvious damage such as punctures or gashes th at are indicative of da mage to the unit. If
eviden ce of dama ge exist s, save th e packag ing materia l for insp ecti on by th e carr ier when a cl ai m is fil ed. Requ est for in sp ection
should be made immediately.
7.Strapping should be cut and the corrugated cap and/or sleeve carefully removed. Remove padding and plastic sheeting. The
cabinet then may be unbolted from the shipping pallet.
8.Inspect each cabinet: check all exterior surfaces for scratches, chips, cracks and/or indentations. Check monitoring panels
carefully.
9.If door key is needed, locate key envelope taped to rear of cabinet. Open each door, checking for damage.
10. A label on the outside of the UPS tells the location of the Operations & Maintenance (O & M) Manuals.
11. Remove any internal padding/packaging, checking carefully for parts, documentation, etc., that might have been shipped inside
the cabi net. If foam
12. blocks are inside the battery trays, leave them in place. The are to keep small batteries from moving around inside the trays.
Damage Documentation
It is the responsibility of the recipient to file claim with the carrier for damages to the equipment or notify IPM, depending on t he
f.o.b. poin t. Any and all damage noted upon recei pt of th e UPS, bat tery pa ck and/ or PDU sh ould be cl earl y identi fied in detai l on th e
Bill of Lading. Carrier’s claim procedures should be initiated promptly. In the event damage is found after delivery, it should be
reported as soon as possible (normally, there is a 15 day time limit on reporting damages incurred in shipment).
Additional information may be obtained by contacting:
Manager, Qualit y Assurance
International Power MachinesPhone: (214) 342-6100
10451 Brockwood RoadFax (214) 342-6116
Dallas, Texas 75238-1641
BP+15-150,2.9X
5/95
Page v
3-phase UPS
Warranty
BP+15-150,2.9X
5/95
Page vi
International Power Machines
THREE-PHASE UPS WARRANTY
International Power Machines’ (IPM) uninterruptible power systems (UPS) are warranted to be
free from defect s in d esign, ma teria l and work mansh ip under normal use and servi ce. Should any
such system be found defective, IPM will furnish the necessary parts, labor and expenses to
corr ect such defects (wit h in th e 48 contiguou s Unit ed St ates ) for twel ve (12 ) m onth s from th e date
of equipment start-up at the job site, or eighteen (18) months from the date of shipment, whichever
occurs first. Coverage work is performed 8:00 a.m. to 5:00 p.m. Monday through Friday
(excluding holidays). For all three-phase products installed in Alaska and Hawaii, travel time is
billable at the applicable field service rate in effect at the time of travel, and travel expense is
billable at cost. For units outside the United States, please contact IPM for details. This warranty is
subject to the following conditions:
A.Initial start-up and necessary UPS adjustments at the customer’s site shall be performed by IPM or
an IPM auth orized servi ce represen tative to en sure that the s ystem is proper ly started an d tested
prior to use.
B.Purcha ser shall not opera te the system outs ide the speci fication s as stated in th e system man ual,
and shall follow all operating instructions therein.
C.An y necessary repairs made during the period of this warranty shall be made by IPM or by others
with IPM’s written concurrence.
D.All parts or d evi ces repla ced by IPM shall become th e property of IPM.
E.This warranty will not apply to repair of damage caused by accident, neglect, misuse,
misapplication, incorrect installation and repair or alteration not authorized by IPM.
F.The cust omer/user sh all be liable for th e cost of any war ranty call found to be due to oper ator
error, in whole or in part.
G.Bat tery cells are excluded from system warranty; see below.
INTERNATIONAL POWER MACHINES PROVIDES WARRANTY WITH RESPECT TO
BATTERY, PERIPHERAL DEVICE, ATTACHMENT OR APPARATUS EMPLOYED WHICH
IS NOT MANUFACTURED BY IPM TO THE EXTENT THAT IPM WILL ASSIGN TO THE
PURCHASER ITS RIGHTS UNDER SUCH WARRANTIES AS THE MANUFACTURER OF
THE PARTICULAR BATFERY, PERIPHERAL DEVICE, AT FACHMENT OR APPARATUS
PROVIDES TO IPM WHEN THE PARTICULAR BATTERY, PERIPHERAL DEVICE,
ATFACHMENT OR APPARATUS IS SUPPLIED BY IPM. FOR SPECIFIC CONDITIONS
RELATED TO WARRANTY CONSULT THE MANUFACTURER’S DOCUMENTATI ON.
IN NO EVENT WILL IPM BE LIABLE FOR CONSEQUENTIAL DAMAGES EVEN IF IPM
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THIS WARRANTY IS
EXPRESSLY IN LIEU OF ANY OTHER EXPRESSED OR IMPLIED WARRANTIES,
INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS, AND
ANY OTHER OBLIGATION ON THE PART OF IPM.
mc: warranty
BP+15-150,2.9X
5/95
Page vii
SECTION I
Theory of Operation
1.1General
The BalancedPower Plus® (BP+) Uninterruptible Power System (UPS)
presented in this manual is a solid state, o n-line system designed to provide high
quality, continuously filtered and conditioned ac power to computers, their
peripherals and/or other critical equipment loads. Most commonly, the UPS is
configured as a single, stand-alone unit. Fi fteen (15) power ratings are available
from 10 to 300 kVA. Information contained herein is applicable to all power ratings
except where specified otherwise.
A single UPS is comprised of the following basic components:
Input transformer
Rectifier/Charger
Inverter
Static Bypass Switch
Bypass Breaker
Output Transformer
System Control Logic and Circuitry
Digital Monitoring Panel
Battery
DC Disconnect
A one-line diagram in Section II shows the relationship of these various
components.
1.2Rectifier/Charger
The UPS input voltage from the utility is fed into the rectifier/charger
(usually referred to as the rectifier) which converts the ac to filtered, regulated dc
voltage. The dc is used to power the inverter and to recharge the batteries as
necessary. The assembly consists of an input circuit breaker, a transformer, and a
solid-state three-phase rectifier designed t o eliminate e ven ordered harmonics. An
optional input filter reduces harmonics caused by rectifier switching. This prevents
the harmonics from affecting utility distribution.
BP+ 10-150
2/95
Page 1.1
SECTION I
Theory of Operation
1.3 Inverter
The inverter changes dc voltage to precision ac voltage through pulse width
modulation (PWM) inversion. Output isolation transformers and an output filter
provide “clean”, computer grade ac which is then sent to the critical load. When
utility power is available, the rectifier supplies power t o the inverter. Should the
utility power fail, the inverter is powered by the batteries for a predetermined length
of time.
1.4 Static Bypass Switch
The static bypass switch connects the UPS bypass input to the load in the
event of the loss of the inverter output or an overload condition. Du ring normal
conditions, the static bypass switch is in the open or disconnected m ode which
isolates the bypass input from the load.
If the inverter output becomes unavailable or exceeds its specified tolerance,
the static bypass switch will close and transfer the load directly to ac power
without interruption. This transfer is automatically inhibited in the event the UP S
bypass input is not within specified tolerance.
As soon as the inverter becomes available, returns to within tolerance or the
overload clears, the static bypass switch will disconnect and retransfer the load to
the inverter. Note, however, that so long as the inverter is out of sp ecification, the
static bypass switch will automatically inhibit retransfer of the load.
1.5Batteries
The optional battery pack supplies 216 VDC (10-30 kVA) or 360 VDC (37.5150 kVA) nominal. It can be attached to the UPS module t o form a sing le unit or
may stand alone to accommodate space restrictions. It is the energy reservoir of the
UPS and provides dc power to the inverter in case of loss of UPS input power or
rectifier malfunction. The DC Disconnect (Battery) Circuit Breaker electrically
isolates the battery pack from the UPS module for maintenance purposes and
provides overcurrent protection at the battery output.
BP+ 10-150
2/95
Page 1.2
SECTION I
Theory of Operation
1.5Batteries (continued)
The rectifier/charger normally provides a maintaining or “float” charge to
the batteries. Following periods of discharge when the batteries have supplied
power to the inverter, the rectifier/charger increases power to the batteries in order
to recharge them.
1.6Control Logic and Control Circuitry
The control logic and circuitry of the UPS p rovide the operating logic and
system control for all functions ranging from limiting the rectifier/c harger inrush
current by “walking” it in, to maintaining t he inverter output voltage within rigid
specifications, to determining whether or no t the static bypass switch should be
activated. The control logic is, for all practical purposes, the brain of the UPS.
1.7Digital Monit oring Panel
The UPS is equipped with a standard Digital Monitoring Panel which
selectively monitors critical parameters of the UPS, using bright, easy-to-read
digital LED displays. In addition, detailed instructions guide the operator through
the UPS startup sequences. An alarm history can be called up on these digital
displays when desired.
In the event of an abnormal condition, an au dible alarm sounds and the
corresponding red LED illuminates to identify the condition so that corrective
action can be taken. Alarm Silence and Emergency Power Off pushbuttons are
provided.
This panel is discussed in greater detail in Section III.
BP+ 10-150
2/95
Page 1.3
SECTION I
Theory of Operation
1.8Multi-Level Passwords
A password is required to access and make use of the UPS Maintenance
Menu, described in Section 3.6.3. This menu, with five subsections, makes
possible the performance of a variety of maintenance functions including transfer
and retransfer to bypass, password changes and adjustment of time and date.
All passwords may be changed by a person who already kno ws either the
password in question or a higher level password.
Passwords consist of a minimum of 4 characters and a maximum of 9
characters. The numerals 0 through 9 and letters A through F may be employed.
The first character of the password indicates the privilege level of the
password. The higher the privilege level, the more capabi lities that password can
access.
Privilege level 0:No password. Used for the front panel display of
voltages, currents, etc. only. Does not permit any
menus to be accessed.
Privilege level 1:Reserved for future development.
Privilege level 2:Remote operator password. Used to monitor the UPS,
but not to affect transfers and retransfers.
Privilege level 3:Reserved for future development.
Privilege level 4:Operator password. Monitors the UPS as well as
allowing transfers, retransfers, transfer enables,
retransfer enables, reset faults, etc.
BP+ 10-150
2/95
Page 1.4
SECTION I
Theory of Operation
1.9Phone Home Alarm Reporting
When this UPS is activated for phone home operation and the UPS sense s
one of several pre-selected alarm conditions, the UPS automatically dials IPM’s
Field Service computer without human assistance and notifies IPM’s Field Service
personnel of a system problem requiring attention.
Important information downloaded during each phone home event includ es:
1) UPS name, ID and serial number, 2) customer ID and phone number and 3)
list of active alarms. You obtain the following benefits from this feature:
a.Immediate field service notification of site power or UPS problems,
even when the UPS is unattended.
b.Increased availability due to reduced mean-time-to-repair with
automatic notification and complete remote diagnostic capabilities.
c.24-hours per day, 7 days per week monitoring of unmanned facilities
and locations where operators are unfamiliar with the UPS. Often,
service personnel can take steps to solve a UPS problem remotely
before the user is aware that there is a problem.
An internal modem and a dedicated telephone line are required. Phone
Home Alarm Reporting can be activated only with a Field Service level of password.
It is normally done at the time of startup by our Customer Engineer.
1.10 Dial-Back Security
This security feature is provided to insure system integrity. It prevents
“hackers” or other unauthorized persons from intentiona11y or unintentionally accessing the UPS database. Anyone calling the UPS must
establish authority through the use of a dial-back password. The unit will
validate this password against up to four passwords stored in non-volatile
memory. One of the passwords will allow direct communication to commence
with the UPS. The other three passwords will have associated telephone
numbers. If one of these three passwords rec eives validation, the UPS logic will
hang up and dial back the phone number associated with that password . When
connection is made, the remote operator must enter the normal privilege level
password for access to the corresponding level of monitoring diagnostics and
BP+ 10-150
2/95
Page 1.5
SECTION I
Theory of Operation
1.10 Dial-Back Security (continued)
controls. In this way high level security is provided since the remote operator must
know the dial-back and access passwords and be calling from the proper
associated phone number.
An internal modem and a dedicated telephone line are req uired. Dial-B ack
Security can be activated only with a Field Service level of password. It is normally
done at the time of startup by our Customer Engineer. Phone Home Alarm
Reporting and Dial-Back Security can share the same modem and telephone line.
BP+ 10-150
2/95
Page 1.6
SECTION II
Installation
2.1General
Your International Power Machines BalancedPower Plus UPS is UL-listed
and designed for installation on the compute r room floor. Its attractive computerlike appearance and quiet operation eliminate any necessity of creating special
facilities to house the UPS and its battery component. Since all modern computer
rooms utilize environmentally controlled conditions, installation in such a locale
will normally suffice to meet the needs of the UPS.
In the event that computer room installation is not practical, the selection of
a location for the UPS is critical to the per formance of the system and to the life
expectancy of its components. Failure to select a site which meets all requirements
specified in this section can result in excessive maintenance problems. For
environmental considerations, please see the Installation Information at the end of
this section.
Operating temperature range for batteries is 0°C to 40°C (32°F to 104°F).
Battery warranty is conditional upon application at or below 25°C (75°F).
Continuous operation above 25°C may reduce or void battery warranty.
The BalancedPower Plus battery pack supplied by International Power
Machines is listed by Underwriters Laboratories only for use with the
BalancedPowerPlus UPS.
2.2Mechanical Preparation of UPS
The UPS can be fully accessed from the front for operation and mainte-
nance. However, during installation the UPS and any accompanying battery
cabinets should be left at least two feet (61 cm) from the wall to allow access to the
rear. If optional top cable entry has been p urchased, an area of at l east three fe et
(91 cm) is required at the right side for installation.
The following steps should be taken, in the order indicated:
BP+10-150
12/95
Page 2.1
SECTION II
Installation
2.2Mechanical Preparation of UPS (continued)
1.Insure that all packing, both external and internal, has been
removed from the UPS.
2.Open right-hand front door of the UPS.
3.For standard bottom cable entry, unscrew scr ews holding the panel
around the circuit breakers and remove the panel. Then, remove the cable access
panel on the bottom of the UPS by removing six (6) screws.
4.For optional top cable entry, remove the right side cover by removing
two (2) screws at the bottom (inside front and back) and lift the cover. Drill holes in
the appropriate conduit plate of suitable size for the cables to be inserted throu gh
it, and replace the plate.
5.Fasten leveling feet (packed inside) to the four bottom corners of th e
UPS cabinet. Access to the inside of the cabinet is not required. Refer to Figure 2-1.
(An optional pedestal mount may replace leveling feet and casters.)
a.First screw the leveling foot screw through the leveling plate.
b.Use two sets of 114-20 x 1” screw, flat washe r and lock washer to
fasten the leveling plate to the bottom of the cabinet. Two threaded holes are in the
floor of the cabinet to receive them.
c.Screw in each leveling foot until it is a min imum of 0.75 in (1.9 cm)
above the floor level. Tighten locking nut to keep it there.
6.If an IPM battery pack is to be attached to the left sid e of the
UPS, perform this sequence. If the battery cabinet is not to be attac hed to the le ft
side of the UPS, skip Step 6.
a.Open the left-hand front door of the UPS. Remove eight (8) screws
from the lower metal cover to remove the cover. When the three-(3) upper screws
are removed, the clear plastic guard above will also come off.
BP+10-150
12/95
Page 2.2
SECTION II
Installation
2.2Mechanical Preparation of UPS (continued)
b. DO NOT REMOVE THE RED GLASTIC GUARD PANEL FROM
THE LEFT SIDE OF THE UPS.
BP+10-150
12/95
Page 2.3
SECTION II
Installation
2.3Mechanical Preparation of the Battery Cabinet(s)
If batteries are not provided in IPM cabinets, see Disconnect Installation
Drawing at the back of this section for wiring of separat e circuit bre aker and ski p
this Section 2.3. For battery preparation refer to the battery manufacturer’s
manual.
IPM battery trays are shipped screwed to the shelf supports and should be
left fastened down.
1. Fasten leveling feet (packed inside) to the four bottom corners of the
battery cabinet. Access to the inside of the cabinet is not required. Refer to Fig ure
2-1. (An optional pedestal mount may replace leveling feet and casters.)
a.First screw the leveling foot screw through the leveling plate.
b.Use two sets of 1/4-20 x 1” screw, flat washer and lock washer to
fasten the leveling plate to the bottom of the cabinet. Two threaded holes are in the
floor of the cabinet to receive them.
c.Screw in each leveling foot until it is a min imum of 0.75 in (1.9 cm)
above the floor level. Tighten locking nut to keep it there.
2. If an IPM battery cabinet is to be attach ed to the left side of the UPS,
remove the fiberboard shipping panels from t he left side of the UPS a nd the right
side of the battery cabinet by forcing out the fasteners. Leave the red glastic panel
attached. It is recommended that the battery cabinet not be attached to the
right side of the UPS.
a.If more than one battery cabine t is used, the one with a disconnect
circuit breaker should go adjacent to the UPS. This is Battery Cabinet #1.
3. Remove each left battery cabinet cover by removing screws from the
inside front. Be very careful not to touch the screwdriv er against t he batteryterminals. Then pull side panel forward and lift to remove.
4. In each battery cabinet, cut the straps holding the top tray of batteries If
foam blocks are inside the battery trays, leave them in place. They are to keep
small batteries from moving around inside the trays.
BP+10-150
12/95
Page 2.4
SECTION II
Installation
2.3Mechanical Prep ar ation of the Batt er y C abi n ets (co nti n ue d)
5.If Battery Cabinet #1 is to be fastened to the left side of the UPS,
place it adjacent to the UPS, but don’t bolt them together. If additional battery
cabinets are to be fastened together to the left of Cabin et #1, place them adjacen t
to #1 and each other, but don’t bolt them together.
CAUTION:Do not connect the battery trays to each other until
instructed in this manual.
6.Remove the cable entry panel located on the top (or bottom) of
Battery Cabinet #1. Drill conduit holes in this panel of suitable size for the cables to
be inserted through it. Replace panel.
2.4Signal Wiring
NOTE:Class 1 wiring method must be used for field wiring
connections.
Make connections for all optional equipment to the terminal blocks on the
lower front or right side of the UPS (see installation drawings).
Electrical connections should now be made b etween the UPS and Battery
Cabinet #1. There is a wiring harness with a connector coiled on the left side of the
UPS. This connector plugs into a matching connector on a wiring harness coiled in
the lower right corner of Battery Cabinet #1.
If battery cabinet is not to be attached to the UPS, run wiring out through
UPS access panel at the bottom or top to the battery cabinet, following information
on the installation drawings at the end of this section.
Connections for the following functions are located on the Customer
Interface Board:
2.4.1 Remote Control (TB1):
a.Remote EPO Switch
1.24 Vdc lamp supply, 0.25 amp max.
2.Isolated contact closure causes EPO.
BP+10-150
12/95
Page 2.5
2.4Signal Wiring (continued)
2.4.1 Remote Control (TB1) (continued)
b.Battery Trip and Position
1.24 Vdc UVR control for battery disconnect, 0.6 amp max.
2.Contact indicates position of battery disconnect.
c.Remote On-Generator Condition — Isolated contact closure signals
UPS logic that a generator is supplying UPS input power.
d.Summary Alarm (NO/NC)
1.120 Vac—0.5 amps ac max.
2.28 Vdc — 1 amp ac max.
SECTION II
Installation
Terminal wire sizing : #22-#12 AWG
2.4.2 Optional Remote Status Panel (TB2)
Ten position terminal for direct connection between UPS a nd TB1 in the
25 Pin D-Sub Receptacles (male), DTE and DCE are provided for COM Ports
1 and 2. Communication shall be selectable from either standard ANSI
terminal format or P-Record protocol.
2.4.4 Optional Modem Connection (J1O-J13)
Two modem port line and two modem port phone connections are included.
Accepts standard RJ11 plugs. Communication shall be selectable from either
standard ANSI terminal format or P-Record protocol.
BP+10-150
12/95
Page 2.6
SECTION II
Installation
2.4Signal Wiring (continued)
2.4.5 Optional Site Interface Assembly (A26)
This board mounts on top of the Customer Interface Board. The following
connections are available from this interface:
a.Computer Shutdown Interface (AS400) 9 pin D-sub plug.
b.System 38 BNC connector (jack).
c.12 sets of NO and NC contacts are provided for monitoring UPS
status and alarm conditions. Connector wire size #22-#12 AWG.
2.4.6 Optional User Specified Alarm (A23)
This board mounts on top of the Customer Interface Board. Three sets of
NO contact inputs can be connected for UPS monitoring of external alarms.
Connector wire size #22-#12 AWG.
2.5Power Wiring - UPS to Battery Cabinet
Use separate conduits for power and signal wiring.
When the battery cabinet is attached to the left side of the UPS, there is a
power cable with a connector on the left side of the UPS. This connector plugs into
a matching connector on the right side of Battery Cabinet running from the circuit
breaker.
If additional battery cabinets are to be used, additional cables and wiring
harnesses of varying lengths are coiled in B attery Cabinet #1. These must be fed
through one or more battery cabinets to connect to matching plugs similarly
numbered.
If battery cabinet is not attached to the UPS, run wiring out through UPS
access panel at the bottom or top of the battery cabinet, following information on
the installation drawings at the end of this section.
BP+10-150
12/95
Page 2.7
2.6Connecting the Cabinets
1. If Battery Cabinet #1 is to be attached
to the left side of the UPS, fasten the two
cabinets together using the four (4) 5/16” x 1”
bolts, nuts and washers packed with the
leveling feet (see Figure 2-2).
2. If two or more battery cabinets are to
be installed, remove the left-hand fiberboard
shipping panel of the first cabinet and the righthand cover of the second cabinet in the same
way. Plug the power and signal wire electrical
connectors together. Bolt the two cabinets
together as described. Repeat for any additional
battery packs.
SECTION II
Installation
2.7Re-assembly
1. Replace side cover(s) of battery cabinets, attaching screws on inside
(removed in Paragraph 2.3, Step 3). Be very careful not to touch screwdriver
against the battery terminals.
2. Replace the clear plastic guard and metal cover on the front of th e UPS
(removed in Paragraph 2.2, Step 6a).
3. The complete assembly, UPS and battery cabinet(s), can now be rolled on
its casters back to eliminate the work area behind it. When it is in its final location,
lower the leveling feet to stabilize and level the cabinets. Tighten locking nuts.
NOTE: For proper maintenance access and ventilation, a clear area thr ee
feet (91 cm) in front of the UPS and one foot (30.5 cm) above it is recommended.
BP+10-150
12/95
Page 2.8
SECTION II
Installation
2.8 AC Power Connection
1.Make sure that all circuit breakers and the battery DC
disconnect are open.
2.Solderless compression type lugs are provided for cable connections.
All power connections to the UPS terminal blocks must be torqued in a ccordance
with the table below.
WARNING
Verify that power cabling is
de-energized befo re pr oceedi ng.
TIGHTENING TORQUE FOR PRESSURE WIRE CONNECTORS
Size of Wire UsedTorque Spec ification
AWG/kcmil(mm
3.UPS Input Voltage Configuration.
Run cables for UPS input through the access panel of the UPS and connect
to terminal block as shown in installation drawings in this section.
a.On a single input UPS, when input voltage equals output voltage
-3-phase, 4-wire plus ground.
2
)lb-in(N-m)
BP+10-150
12/95
Page 2.9
SECTION II
Installation
2.8AC Power Connection (continued)
3. a.UPS Input Voltage Configuration (continued)
Note: When connecting the UPS to a 3-phase, 3-wire supply, the supply
transformer must be a 3-phase, center grounded WYE and the ground conductor
must be connected to the UPS ground terminal. The neutral must be gro unded
and the UPS can only supply power to 3-phase, 3-wire loads. No single-phase
loads can be connected to the UPS. For any other configurations consult IPM
Application Engineering.
b.On a single input UPS, when input voltage does not equal output
voltage and on a dual input UPS — 3-phase, 3-wire plus ground.
Note: The UPS 3-phase, 3-wire supply transformer must be a 3-phase,
center grounded WYE with neutral grounded. The ground connector must be
connected to the UPS ground terminal. For any other configurations, c onsult IPM
Applications Engineering.
4. UPS Output Voltage Configuration.
Referring to the installation drawings in th is section, connect UPS o utput
terminals to the equipment to be protected, running the cables out through the
access panel.
a.On a single input U PS, when input voltage equals output voltage,
and on a dual input UPS — 3-phase, 4-wire plus ground can feed WYE-connected or
DELTA-connected loads (see Note at 3,a, above).
b.On a single input UPS, when input voltage does not equal output
voltage — 3-phase, 4-wire plus ground; can feed WYE-connected or DELTAconnected loads.
Note: This configuration provides a separately de rived source. UPS output
neutral has been factory connected to system ground. UPS output circuit
protection is required.
BP+10-150
12/95
Page 2.10
SECTION II
Installation
2.8Power Connections (continued)
5.Bypass Input Voltage Configuration (Dual Input UPS)
Bypass input voltage configuration must be the same voltage, frequency,
phase sequence and configuration as the UPS ac voltage configuration, i.e., 3phase, 4-wire plus ground. The UPS output can feed WYE (4-wire) loads or DELTA
(3-wire) loads: WYE systems require neutral connections for both bypass input and
UPS output; DELTA or 3-wire systems require neutral connection for bypass input
only.
6.Ground Connections
Two 3/8-16 x 1.0 LG ground studs are provid ed for connection to syste m
ground. Ground studs are welded to the cabi net frame and are located near the
cable entry points or power terminal.
7.Replace the panel around the circuit breakers (removed in Paragraph
2.2,Step 3). (With top cable entry option, replace right side panel removed in
Paragraph 2.2, Step 4.)
2.9Activating the Battery Cabinet(s)
WARNING
This procedure should be performed only by
qualified electrical personnel Due to potential
for arcing, safety equipment such as face shield
or eye goggles and gloves must be worn at all
times. All tools must be insulated. There will be
high voltages present and failure to follow this
procedure exactly may lead to injury or death.
•Make sure that all elec tri cal power has been removed from the
UPS and batter y cabinets.
•Make sure that battery tray cables are not plugged together.
BP+10-150
12/95
Page 2.11
SECTION II
Installation
2.9Activating the Battery Cabinet(s) (continued)
•Make sure that all packing material and shipping straps have been
removed from the battery cabinets.
•Make sure that the electrical signal and power connections have
been made between Battery Cabinet #1 and any additional cabinets.
•Make sure that the electrical signal and power connections have
been made between Battery Cabinet #1 and the UPS.
•Make sure that the mechanical connections have been made
between the battery cabinets.
2.9.1 Battery Cabinet #1
1.Open the front doors of Battery Cabinet #1.
2. Using an ohmmeter, measure from each pole on both the top and the
bottom of the battery disconnect circuit bre aker to frame ground. Verify that no
short circuits exist to frame ground. There may be a high impedance between the
two cables connecting to the UPS cabinet and frame groun d, but no sho rt circuit
should exist.
3. Using an ohmmeter, measure between each combination of two poles (A
to B, A to C and B to C) on the top of the battery disconnect circuit breaker. Verify
that no short circuit exists between any two poles.
4. Using an ohmmeter, measure between each combination of two poles (A
to B, A to C and B to C) on the bottom of the battery disc onnect circu it breaker.
Verify that no short circuit exists between any two poles. NOTE: There will be a
capacitor action between the two cables connecting to the UPS cabinet, but
no short circuit should exist.
5. In Battery Cabinet #1, connect the battery trays to each other as shown
in Figure 2-3. The two connectors to be attached at each tray are similarly
numbered.
BP+10-150
12/95
Page 2.12
SECTION II
Installation
2.9Activating the Battery Cabinet(s) (continued)
2.9.1 Batt ery Cabinet #1 (c on ti nu ed )
6. Using a dc voltmeter, carefully measure the dc voltage at the top of the
battery disconnect circuit breaker. The voltage should be slightly above the
nominal battery voltage (for example: 380 volts dc for a nominal 360 volt battery
cabinet; 230 volts for a nominal 216 vdc). R ecord the vo ltage. The polarity should
have the positive on the left-hand pole (Pha se A) and the negative on the righthand pole (Phase C) when you are facing the battery disconnect circuit breaker.
Verify that the polarity is correct. If it is not, locate and correct the problem.
7. When the polarity is correct, disconnect the top right-hand tray
connection to the tray immediately below. Verify there is no voltage present
between the left and right poles at the top of the battery disconnect circuit breaker.
2.9.2 Battery Cabinet #2
8. Open the front doors of Battery Cabinet #2 (the one next to Battery
Cabinet #1). Connect the battery trays in the cabinet to each other a s shown in
Figure 2-3. The two connectors to be attached at each tray are similarly numbered.
9. Using a dc voltmeter, carefully measure the dc voltage at the top of the
battery disconnect circuit breaker in Battery Cabinet #1. The voltage should be
slightly above the nominal battery voltage (for example: 380 volts dc for a nominal
360 volt battery cabinet; 230 volts for a nominal 216 vdc). Record the voltage. The
polarity should have the positive on the lef t-hand pole (Phase A) and the negativ e
on the right-hand pole (Phase C) when you are facing the battery disconnect circuit
breaker. Verify that the polarity is correct. If it is not, locate and correct the
problem.
10.When the polarity is correct, disconnect the top right-hand tray connec-
tion to the tray immediately below in Battery Cabinet #2. Verify there is no voltage
present between the left and right poles at the top of the battery disconnect circuit
breaker.
BP+10-150
12/95
Page 2.13
SECTION II
Installation
2.9Activating the Battery Cabinet(s) (continued)
2.9.3 Battery Cabinets #3 and #4
11. Repeat Steps 8, 9 and 10 for the additional battery cabinet(s).
2.9.4 Final Battery Cabinet Connections
12. When connections and polarity have been checked on each additional
battery cabinet, verify that there is one connection left unplugged i n each cabinet
(Steps 7 and 10). In Battery Cabinet #1, reconnect the to p right-hand tray to the
tray immediately below.
13. Move to Battery Cabinet #2.
WARNING
Before reconnecting the top right-hand tray to the
tray immediately below in Battery Cabinet
#2, measure the voltage between these unplugged connectors with a dc voltmeter. It is
expected that this voltage reading will be small. In
no case should the connection be made if there is
more than 5 volts difference.
14. If there is less than 5 volts between the connectors, plug them together.
15. Repeat Steps 13 and 14 for each additional battery cabinet, making
sure to measure the voltage between the unplugged connectors each time.
The uninterruptible power system is now ready for startup. See Section III,
Operation.
WARNING: Do not close the battery circuit breaker until
instructed to do so in the startup procedure.
BP+10-150
12/95
Page 2.14
SECTION II
Installation
2.9Activating the Battery Cabinet(s) (continued)
6 battery trays
Figure 2-3
10 battery tray s
BP+10-150
12/95
Page 2.15
SECTION III
Operation
3.1General
This section contains safety considerations, UPS operational procedures,
and an overview of the monitoring panel and operating controls for th e system.
Prior to operation, ensure that the UPS has been installed correctly as outlined i n
Section II of this manual. Ensure that correct input/out put phase rotation and
battery polarities have been observed. Failure to do so can result i n damage tothe UPS and/or injury to personnel. Operators should be thoroughly familiar
with the contents of this manual and with the location an d function o f all system
controls and indicators.
3.2Safety Considerations
Safety considerations are divided into several areas which are discussed
below. Refer also to Section IV of this manual, Maintenance, for safety precautions
to be taken whenever operating or working on the UPS.
3.2.1 Cleanliness
Litter or trash of any sort should not be allowed to accumulate in or around
the UPS. Liquid spills or metal objects carelessly dropped or placed can cause
shorts and damage to the system as well as possible injury to personnel. Dirt and
dust accumulating in the UPS air filters can impede air f low, thereby decreasing
the cooling effectiveness of the blowers and possibly resulting in an overtemperature shutdown of the system.
3.2.2 Fire
In order to minimize the possibility of a fire and to reduce the extent of any
damage resulting from such an incident, the walls, ceiling and floor of the UPS
room should be constructed of noncombustible materials. A portable carbon
dioxide extinguisher should be located in the UPS room. Personnel involved in
operating and/or maintaining the UPS should be familiar with Class C hazard
fires.
BP+2.9X
11/95
Page 3.1
SECTION III
Operation
3.2Safety Considerations (continued)
3.2.3 Security/Personnel
Access to the UPS should be limited to a minimum of perso nnel. Module
doors should be kept locked. All personnel who operate or maintain the UPS
should be proficient in normal and emergency operational procedures. A refresher
briefing or test at specific intervals is rec ommended to maintain this proficiency.
New personnel should be trained and tested p rior to operating the equipment. A
thorough knowledge of first aid procedures, especially those pertaining to electrical
shock or bums, and the use of carbon dioxide fire extinguishers should be
mandatory.
3.3Radio Frequency Energy Hazard
WARNING:This equipment generates, uses and can radiate radio
frequency and if not installed and used in accordance with instructions may cause
interference to radio communications. It has been designed to comply with the
limits for Class A computing devices pursuant to Subpart J or Part 15 of FCC
Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment
in a residential area is likely to cause interference in which case the user at his own
expense will be required to take whatever measures may be necessary t o correct
such interference.
CAUTION
Always be aware that hazardous
voltages may be present with in the
UPS even when the system is
not operating.
BP+2.9X
11/95
Page 3.2
SECTION III
Operation
3.4Digital Monit oring Panel
The Digital Alarm Panel consists of eight (8) L ED Indicator Lights, one (1)
LCD message screen, two Display Select pushbuttons, three (3) Paramete r Adjust
pushbuttons, an ALARM SILENCE pushbutton and an EMERGENCY POWER
OFF (EPO) pushbutton. The Display Select butt ons provide access to the various
data and messages which are displayed on the Message Scr een. These include
detailed instructions for startup sequence, alarm parameters, available battery run
time and alarm conditions.
Figure 3.1
BP+2.9X
11/95
Digital Monitoring Panel
Page 3.3
SECTION III
Operation
3.4Digital Monit oring Panel (continued)
3.4.1 Indicator Lights
The Indicator Lights (LED’s), located in the upper part of the panel, are:
• UPS Normal (green) - This indicates that the critical load is being powered
from the inverter. The LED normally is on and, when this is the only L ED lighted
on the panel, it represents a fully normal condition. Other LED’s may also be
lighted simultaneously indicating a problem with the UPS. When this occurs, first
record the alarm(s). Then, depress the ALARM SILENCE button to reset the alarm
circuitry. Any alarm LED’s will go out when the alarm condition is corrected. See
Paragraph 3.4.5 for more details.
If “UPS Normal” flashes slowly, this indicates that a non-critical alarm is
present, and that message will appear on the message screen. Check Alarm
History (Paragraph 3.6.2) to identify the alarm.
• AC Input Failure (red) -The UPS input power has been disrupted or gone
out of specification limits. The system goes to battery power and the alarm sounds,
alerting the operator to a brownout or power failure. When the batteries run down,
the critical load will shut off unless steps are taken to correct the situation or
another source of input power is provided.
• Low Battery Voltage (red) - When the system is operating on battery
power, this LED illuminates to show approxima tely five minutes remains before
the UPS system shuts down. A message screen (shown on Pa ge 3.6) displ ays the
amount of battery run time left. Also, the link (battery) voltage maybe monitored
(See Paragraph 3.4.2.6). Shutdown occurs when the link voltage drops to 178VDC
(15-30kVA) or 297VDC (37.5-300kVA). If utility power can not be restored or an
auxiliary power source be activated, the critical load sh ould be shut down in an
orderly procedure.
• UPS Overload (red) - The load on the UPS output is in excess of 105% of
rated load. If the condition exists for more than a few seconds, enough of the
critical load should be powered down or remo ved to make the indicator go out.
Otherwise, the UPS will shut down and/or transfer to bypass within 15 minutes. If
the indicators are set to latch, the ALARM S ILENCE button must be depressed
twice to clear it.
BP+2.9X
11/95
Page 3.4
SECTION III
Operation
3.4Digital Monit oring Panel (continued)
3.4.1 Indicator Lights (continued)
This condition may occur when the UPS is loaded close to 100% and a large
disk drive or other motor load is started. These loads draw currents many times
their normal level for a few seconds when first started. The UPS is designed to
handle this short overload condition.
• Transferred to Bypass (red) - An indication that the critical load is being
powered directly from the UPS bypass power source. This situation is created
when maintenance personnel want to bypass the UPS throug h the static bypass
switch for routine maintenance or when an abnormal condition exists in the
inverter, such as failure or extended overload. When in this operational mode, the
critical load does not have UPS protection.
• Transfer Not Available (red) - An indication that transfer to the static
bypass switch is not possible. This may be caused by the UPS bypass input power
source being out of specification or a power outage.
• Battery Not Available (red) - The battery’s DC Disconnect (circuit breaker)
is open or a battery cabinet fuse is blown. The battery is not available to power the
inverter if needed.
• Retransfer Inhibited (red) - An indication that the inverter is out of
specification or has lost phase lock with the bypass power source. Wh en active in
conjunction with the Transferred to Bypass indicator, power can not be
retransferred from the static bypass switch back to the inverter.
3.4 .2 Message Screens
Message screens display the status of the UPS. To scroll through these
screens, depress or buttons beneath DISPLAY SELECT.
Following are the legends that appear in
this area while the UPS is running normally. To
display these in this order, start with the screen
at right and depress the button to show each
screen in turn.
UPS
Operating
Normally
BP+2.9X
11/95
Page 3.5
SECTION III
3.4Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
If the UPS is operating on battery power,
this screen will appear instead. It can be
monitored to determine the battery run time
remaining during a power outage. Voltage
shown is link voltage.
3.4.2.1 Alarm History
Voltage XXX.X VDC
Operation
Time Left
hhH mmM ssS
This is a sequence of entries showing as
many as the last 1500 alarm and status conditions that have occurred. To see them all, scroll
through the list depressing the or button
successively (see paragraph 3.6.2).
On this screen the letters are read as
follows:
xx = monthyy = day of the monthzz = year
uu = hour (on the 24-hour clock) vv = minutes of the hour
ww = secondsaa = cyclesb = 1/4 cycles
tttt =alarm sequence number. 0 is most recent. Pre ss -to scroll from a
higher number to 0 or press -to scroll from 0 to a higher number.
3.4.2.2Input Voltage:
This is a readout of input voltage between
phases.
-and-
Xx/yy/zz tttt
uu :vv.ww.aab
Alarm identity
Input Vab
Input Vbc
Input Vca
This is a readout of input volt age phase
to neutral.
BP+2.9X
11/95
Input Van
Input Vbn
Input Vcn
Page 3.6
SECTION III
3.4Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
3.4.2.3Input Current:
Operation
This is a readout of the input current,
measured in amps per phase.
3.4.2.4Bypass Voltage
This is a readout of the bypass voltage betw een
phases.
3.4.2.5Frequencies/Temperature
A readout of the input and output frequency
(Hz) and the inlet temperature (°C).
3.4.2.6Link Voltage:
A display of the DC link (battery) voltage, battery current and maximum
output crest factor of the load on the UPS.
•Link voltage - 243 (405)* VDC ±10%. If there is an increase to about 246
(410) VDC, it indicates the batteries are being charged. If the voltage goes
above 256(426) VDC, the rectifier will shut down. (These values are subject
to change according to battery type.)
•Battery Amps - A positive number
indicates battery charging; a negative
number indicates discharging (possibly
because UPS is operating on battery
power).
•Max Out CF - Displays maximum output crest factor of the load on the UPS
* Numbers in parenthesis are for 37.5-300 kVA; without parenthesis for 15-30 kVA.
Input Van
Input Vbn
Input Vcn
Bypass Vab
Bypass Vbc
Bypass Vca
Input Freq
Output Freq
Inlet Temp
Link Voltage
Battery Amps
Max Out CF
BP+2.9X
11/95
Page 3.7
SECTION III
3.4Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
3.4.2.7Output Power
Operation
A readout of the output kVA, kW and
power factor.
3.4.2.8Output Voltage:
A readout of output voltage phase to
neutral. There normally is up to ±5% variance
between phases.
3.4.2.9Output Current:
A readout of the output current,
measured in amperes per phase.
3.4.2.10Date
Displays today’s date.
Output KW
Output KVA
Output PF
Output Van
Output Vbn
Output Vcn
Output Van
Output Vbn
Output Vcn
Date
Actual Date
3.4.2.11Time
A readout of the current time.
3.4.2.12UPS Maintenance Menu
This screen allows entrance into the UPS
Maintenance Menu described in Paragraph
3.6.3. A password is required to use this menu.
BP+2.9X
11/95
Time
HH:MM:SS
UPS
Maintenance
Menu
Page 3.8
SECTION III
Operation
3.4Digital Monit oring Panel (continued)
3.4.2 Message Screens (continued)
The next message is “UPS Operating Normally.”
3.4.2.13Other Messages
Under certain conditions other messages may appear on the message
screens.
3.4.3 Display Select Pushbuttons
The and pushbuttons are used to select th e desired display on the
Message Screen, as described in Paragraph 3.4.2. (See Page 3.3 regarding arrows.)
3.4.4 Param et er Adju st P us hbut to n s
These pushbuttons, labeled , and , are used with Alarm Ident ity/
History procedures (Paragraph 3.6.2) and to set or alter the parameters of theUPS. (See Page3.3 regarding arrows.)
3.4.5 Alarm Silence Pushbutton
Whenever an alarm condition exists, an audible alarm sounds calling
attention to the situation. If set for non-latching alarms, the audible alarm is
silenced by depressing the ALARM SILENCE pushbutton once. If set for latching
alarms, pressing the ALARM SILENCE pushbutton a second time resets the alarm
circuit. Any indicator LED’s that remain illuminated represent active alarm
conditions that may require immediate action . (See Paragr aph 3.6.3.4, Step 4 for
selecting “latching” or “non-latching.”)
BP+2.9X
11/95
Page 3.9
SECTION III
Operation
3.4Digital Monit oring Panel (continued)
3.4.6 Emergency Power Off Pushbutton
To be used only for emergency conditions whe re instant shutdown of the
UPS is required. The red EPO pushbutton is normally illuminated so th at it may
be located easily, even in the dark. Depressing the EMERGENCY POWER OFF
(EPO) pushbutton results in immediate shutdown of operations, opening all UPS
breakers and the DC (battery) disconnect, the audible alarm sounds and all power
to the critical load is shut off. Once the EPO has been activated, the UPS must be
manually restarted. (The EPO also may be activated remotely by a contact closure.)
CAUTION
Any time the UPS has been shut down by using the EPO,
the system should be carefully checked by trained facilities
personnel before restarting.
3.5System Controls
Controls for the UPS, with the exception of the pushbuttons located on the
face of the UPS module indicator panel, are situated inside the right-hand door of
the module cabinet. Since the cabinet is routinely kept locked, this provides some
degree of security from tampering with the system.
UPS CONTROL switch: This switch is rotated clockwise to energize the
power supply to turn on the system logic or Digital Signal Processor logic.
INPUT CIRCUIT BREAKER: When closed, allows UPS input power to
supply the rectifier and SBS input on units having a single input.
BP+2.9X
11/95
Page 3.10
SECTION III
Operation
3.5System Controls (continued)
BYPASS CIRCUIT BREAKER: Used primarily for ma intenance purposes.
When closed, it enables the UPS to be de-energized for ma intenance procedures
while continuing to supply power to the critical load.
STATIC SWITCH BYPASS CIRCUIT BREAKER: (On dual input units
only.) When closed, allows reserve input to supply power to the Static Switch.
OUTPUT SWITCH: When closed, connects the cri tical load to the inverter
and static bypass switch.
3.6UPS Operating Procedures
It is important for saf ety and the protection and perf ormance of the UPS that
the step-by-step instructions for each procedure be followed in the sequence given.
3.6.1 System Startup Procedure
Before initiating UPS startup, make sure that:
• All circuit breakers/switches are OFF (open).
• The DC (Battery) disconnect switch on the battery pack is OFF (open).
Then --
Each of the following steps must be completed before going to the
next step. Failure to do so may result in interruption of power to the
critical load.
1.Rotate UPS CONTROL switch
knob clockwise to ON to energize the system or
DSP logic. If this screen appears, the UPS is not
in operable condition. Phone Customer Service
at (800) 777-8922 for assistance.
Checksum Bad
Service
Required
BP+2.9X
11/95
Page 3.11
SECTION III
Operation
3.6UPS Operating Procedures (continued)
3.6.1 System Startup Procedure (continued)
Normally, turning on the UPS CONTROL switch should illuminate the
following LED’s:
AC Input Failure Transfer Not Available
Retransfer InhibitedBattery Not Available
Checksum
… and this screen which will be
displayed for a short time,
Good
. . . . . then –
2. When this instruction appears on the
Message Screen, close BYPASS CIRCUITBREAKER. The same LED’s should remain
lighted. Power is available now on the UPS
output.
3.When this instruction appears on
the Message Screen, close the I NPUT CIRCUIT
BREAKER.
Close
BYPASS
CKT. BREAKER
Close
INPUT
CKT. BREAKER
BP+2.9X
11/95
Page 3.12
SECTION III
Operation
3.6 UPS Operating Procedures (conti nued)
3.6.1 System Startup Procedure (continued)
4..This screen will appear for a short
time, then --
When this instruction appears on the
Message Screen, close the DC (Battery) Disconnect switch. Depress the ALARM SILENCE
pushbutton twice to turn off some of the LED’s.
Now, only the Transfer Not Available LED
should be lit.
5.When this instruction appears on
the Message Screen, close the Output Switch or
Circuit Breaker. (When input voltage does not
equal output voltage, this is a rotary switch.)
This should light the following LED’s:
Transferred to Bypass
Retransfer Inhibited
Waiting
DC Link =
XXX.X VDC
Close
BATTERY
CKT BREAKER
Close
OUTPUT
SWITCH OR BKR
6.On dual input UPS only, when
this instruction appears on the Message Screen,
close STATIC SWITCH BYPASS CIRCUITBREAKER. The same LED’s should remain
lighted.
7.When this instruction appears on
the Message Screen, open the BYPASS CIRCUIT
BREAKER. Within approximately 2 minutes the
audible alarm will sound. Depress the ALARM
SILENCE pushbutton, silencing the alarm,
turning off the two lighted LED’s and lighting
the UPS Normal LED.
BP+2.9X
11/95
Close
SBS INPUT
CKT. BREAKER
Open
BYPASS
CKT. BREAKER
Page 3.13
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.1System Startup Procedure (continued)
8. This screen will show for a short time.
9. Then this screen will appear, indicat-
ing that the UPS is now in normal operation.
3.6.2 Alarm Identity/History
As described in Paragraph 3.4.2.1 this is
the first Alarm History screen. It can be displayed by pressing the or button, going
through the sequence of screens described in
Paragraph 3.4.2 until this screen appears.
Wait
Retransfer
Pending
UPS
Operating
Normally
xx/yy/zztttt
uu:vv:ww.aab
Alarm identity
xx = month yy = day of the monthzz = year
uu = hour (on the 24-hour clock)vv = minutes of the hour
ww = secondaa = cyclesb = 114 cycles
tttt =alarm sequence number. 0 is most recent. Pre ss - to scroll from a
higher number to or press to scroll from 0 to a higher number.
* The identity of the alarm is abbreviated on the screen. The full
identification of each and corrective action are given in Table 3-2.
BP+2.9X
11/95
Page 3.14
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.2 Alarm Identity/History (continued)
The principal use of the Alarm History scree n is to identify the source of
audible alarms so that corrective action can be taken. When the audible alarm
sounds, press or until this Alarm History screen ap pears. You ma y depress
the ALARM SILENCE button once to silence the alarm.
You may find it advantageous to leave the message screen on Alarm History
during normal operations. Then, if an alarm sounds, its identity will be seen
immediately.
It may be helpful to view the Alarm History a s a list of a larms, ordere d by
date and time. Whenever the Alarm History screen is first selected, th e first entry
shown on the screen is the latest entry on t he list. Pres sing moves you toward
the top of the list and pressing - moves you toward the bottom of the list. See an
example below.
Table 3-1
Typical Alarm History Screens
Following is the beginning of a typical list of messages from the Alarm
History screen as the startup procedure is begun. The date, time and alarm
identity are shown on the screen in the first Alarm History screen after system
startup. By depressing you can scroll the screen up one message at a time to the
oldest (earliest) message. Thinking of the Alarm History screens as part of a list will
help you visualize what is happening.
DateTime IAlarmScreen Message
01/01/9008:30:00.000CPU RestartedCPU Restart
01/01/9008:35:09.452Input Circuit Breaker Closedinp bkr clsd
01/01/9008:35:10.000Input Voltage Normalinp vol norm
01/01/9008:36:00.000DC Voltage Normaldc volt norm
BP+2.9X
11/95
Page 3.15
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.2 Alarm Identity/History (continued)
Table 3-2
Screen MessageDescriptionCorrectiv e Action
inp bkr openInput Circuit Breaker openFollow System St artup pr oc edur e to
close Input Circ . Br k r.
inp bkr clsd*Input Cir c uit Breaker closedVerifies that Input Cir c uit Br k r. is closed
bat bkr openBattery (DC Disconnect) switch
open
bat bkr clsd*B attery (DC Disconnect) switc h
closed
inp vlt highInput voltage too highVerify corr ect UP S inputvoltage.
inp vlt lowInput voltage too lowVerify correct UPS input voltage.
inp vlt norm*Input volt age normalNo action requir ed
inp freq hi
‘
inp freq low
‘
inp frq norm*Input frequency normalNo action required
inp cur highInput current t oo highReduce load on UPS output.
inp cur imblI nput current out of balanceVerify correct UPS input v olt-age and
Input frequency too highVerify correct UPS input frequency.
Input frequency too lowVerify correct UPS input frequency.
Follow System St artup pr oc edur e to
close Battery (DC Disconnect) switch
Verifies that Battery (DC Disconnect)
switch is closed
Decrease if necessary.
Increase if necessary.
current.
inp cur normAInput current norm alNo action requir ed
dc volt highDC (battery) voltage
dc volt lowDC (battery) voltage
BP+2.9X
11/95
too high
too low
Verify corr ect batt er y v oltage. Decrease
if necessary.
UPS is operating off battery.
Page 3.16
SECTION III
Operation
Table 3.2 (conti nue d)
Screen MessageDescriptionCorrectiv e Action
dc volt norm*DC (battery) voltage normalNo action required
rct fus norm*Rectifier fuses normalNo action requir ed
rct bin fusARectifier fuse A blownTest/replac e r ectifier fuses on Al power
assembly.
rct bIn fusBRectifier fuse B blownTest/replace rectifier fuses on A2 power
assembly.
rd bin fusCRectifier fuse C blownTest/replace rectifier fuses on A3 power
assembly.
rct pwr failRectifier power supply failureTest/replace rectifier drive board on Al,
A2 and A3 power assemblies.
rct pwr norm*Rectifier power normalNo action requi r ed
rct lock*Rectifier phase lockedNo action requir ed
rct not lockRec tifier not phase lockedVerify UPS input voltage and frequency.
rct cur limtRectifier current limitReduce load on UPS output.
rct cur aval*Rectifier current not availableNo action required
rct on gen*Rectifier on generatorNo action required
rct in rechg*Rectifi er in recharge mode
(battery being r ec har ged)
rct in float*Rectifier in floa t (battery is
recharged)
bat volt lowBattery voltage low (LED warning
also)
inv fus norm*I nverter fuse normalNo action requir ed
inv bln fusAInverter fuse A blownTest/replace inverter fuses on A1 power
No action requir ed
No action requir ed
UPS will shut down in a few minutes.
Initiat e shutdown of critical loads
assembly
BP+2.9X
11/95
Page 3.17
SECTION III
Operation
Table 3.2 (conti nue d)
Screen MessageDescriptionCorrectiv e Action
inv bIn fusBInverter fuse B blownTest/r eplace inverter fuses on A2 power
assembly.
inv bIn fusCInverter f use C blownTest/replace inverter fuses on A3 power
assembly.
inv PS failPower supply failureTest/replace inver ter drive boards on A1,
A2and A3 power assemblies.
inv PS norml*Power supply norm alNo act ion required
ph connect*P hone home connection establi shedNo action required
No action requir ed
switch
ph testPhone home test performedNo action required
* Not an alarm condition.
BP+2.9X
11/95
Page 3.23
SECTION III
Operation
Screen MessageDescripti onCorrectiv e Action
ph fail*
‘
Phone home connection attempt failedNo action requir ed
out overloadThe load on the UPS has
exceeded 100%
load normal *The load on the UPS is < or = 100%No action requir ed
bln trap fuseThe input trap fuse has blownCall Customer Service
trap fuse ok*The fuse on the input filter is normalNo action required
inp 5th highThe 5th harmonic content of the input
current is too hi gh
inp 5th norm*The 5th harmonic content of the input
current is at an acceptable level
unused*Unused al arm appears when
alarm history is cleared
Reduce the load
Perform bypass shutdown and
call Customer Serv ic e
No action requir ed
No action requir ed
* Not an alarm condition.
NOTE: If a message requires action you can not p erform, call Factory
Customer Service — (800) 777-8922.
2. Depress to display the next most recent alarm. You can repeatedly
depress to review past alarms in receding order. Continue as long as desired.
After you have started this repeated depressing of , depressing will display
more recent alarms back to the current alarm.
3. To exit Alarm History, depress or .
BP+2.9X
11/95
Page 3.24
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu
The UPS Maintenance Menu performs a variety of maintenance functions
including password changes and adjustment of date and time. It is divided into the
following secondary menus in the order stated. The detailed instructi ons for each
are given on the following subparagraphs.
3.6.3.1Rectifier Maintenance Menu
3.6.3.2Inverter Maintenance Menu
3.6.3. 3SBS Maintenan ce Menu
3.6.3.4System Maintenance Menu
3.6.3.5Password Maintenance Menu
1. To bring the UPS Maintenance Menu
to the screen, depress the pushbutton as
many times as necessary until the screen reads
like this.
2. Press This will display –
NOTE:There is a further discussion of
multi-level passwords in Section 1.8.
3. The UPS is shipped with the password
4F00. To enter this password, depress or to
change the first digit to “4”. is the shortest
way to get to the “4” the first time. The screen
will now look like this.
UPS
Maintenance
Menu
Enter Pa ssword
0
Enter Pa ssword
4
BP+2.9X
11/95
Page 3.25
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenan ce Menu (continued)
4. Now depress to activate the second
digit. Press or until the “F” shows, like this:
5. Depress to activate the third digit.
The screen will show:
6. Depress again to activate the fourth
digit to obtain:
7. Depress
secondary menus. Depress to bring up the
other four Maintenance Menus in turn. Sometimes it will be faster to depress to obtain the
desired menu.
to bring up the first of the
Enter Pa ssword
4F
Enter Pa ssword
4F0
Enter Pa ssword
4F00
Rectifier
Maintenance
Menu
3.6.3.1Rectifier Maintenance Menu
To be used only when advised by
qualified service personnel
1.When in the Rectifier Maintenance
Menu, depress
displayed, press to reset the faults.
BP+2.9X
11/95
When this screen is
.
Page 3.26
Reset Rect Faults
UP = Reset
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.1Rectifier Maintenance Menu (continued)
2. This message will appear on the
screen. To confirm the previous action, press
again,
- returning the screen to –
3. Press to obtain this screen:
4. Press to return to the Rectifier
Maintenance Menu.
Confirm
Yes =UP No=DN
Reset Rect Faults
UP = Reset
Return to
Previous Menu
Rectifier
Maintenance
Menu
3.6.3.2Inverter Maintenance Menu
1. Press to advance to the Inverter
Maintenance Menu.
BP+2.9X
11/95
Inverter
Maintenance
Menu
Page 3.27
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.2Inverter Maintenance Menu (continued)
2 Press to obtain this screen. The
crest factors shown here are for information
only. No adjustments can be made.
3. Press to obtain this screen.
Steps 4, 5, and 6 should only be per-
formed when advised by qualified service
personnel.
4. Press to reset the inverter faults.
5. This screen will ask you to confirm
that you wish to reset inverter faults.
Output CF A B C
XX.X XX.X XX.X
Reset Inv Faults (UP)
Ready to Start
Confirm
Yes=UP No=DN
6. Press again to return to this screen.
7. Press to obtain –
BP+2.9X
11/95
Reset Inv Faults (UP)
Ready to Start
Return to
Previous Menu
Page 3.28
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.2Inverter Maintenance Menu (continued)
8. Press to return to the Inverter
Maintenance Menu.
3.6.3. 3SBS Maintenan ce Menu
1. Press to advance to the SBS
Maintenance Menu.
Bypass/Shutdown Procedure
2. Press to obtain this screen. Press ^
to begin the Bypass/Shutdown Procedure.
Retransfers are disabled by this procedure.
To Skip Bypass/Shutdown procedure
and go directly to Manual Transfer to Bypass
(Step 12) press instead of .
Inverter
Maintenance
Menu
SBS
Maintenance
Menu
Bypass/Shutdown UPS
UP=Bypass
3. Press to continue the Bypass
Shutdown procedure.
Warning: Bypass/Shutdown procedure may
not be exited without performing all
steps in the order shown.
4. When this message appears, close the
BYPASS CIRCUIT BREAKER.
BP+2.9X
11/95
Confirm
Yes=UP No=DN
Menu
Close
Bypass
Breaker
Page 3.29
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3. 3SBS Maintenan ce Menu (continued)
5. When this message appears, open the
OUTPUT SWITCH or CIRCUIT BREAKER. [On
single-input UPS, when the inpu t voltage does
not equal the output voltage, place the rotary
switch in “maintenance” (open) position.]
Warning: With rotating Output Switch,
output transformer (T2) is
energized in Maintenance Bypass
mode.
Open
Output
Breaker
6. When this message appears, open the
BATTERY CIRCUIT BREAKER.
7. On dual input UPS only – when this
message appears, open SBS INPUT CIRCUIT
BREAKER.
8. When this message appears, open the
INPUT CIRCUIT BREAKER.
9. While this message is on the screen,
the link voltage will be gradually decreasing.
XXX.X represents the actual voltage as displayed. When the link voltage h as decreased to
the proper value, the following screen message
will appear.
Open
Battery
Breaker
Open SBS
Input
Breaker
Open
Input
Breaker
Waiting…
DC Link=
XXX.X Vdc
BP+2.9X
11/95
Page 3.30
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3. 3SBS Maintenan ce Menu (continued)
10. This message indicates that the
Maintenance Bypass Shutdown procedure is
complete.
11. You may turn off the UPS CONTROL
switch. This message appears briefly.
Manual Transfer to Bypass
12. Press and to obtain this screen.
13. Press to obtain this screen.
Bypass/
Shutdown
Complete
You may
turn off
UPS contro l
Man Transfer
/Retransfer
Inv Running
Confirm
Yes=UP No=DN
14. Press to manually transfer input to
reserve power source. This will inhibit retransfer
and light the Transferred to Bypass and
Retransfer Inhibited LED’s. It will also change
the “Inv Running” on the screen to “Wait Rexfr.”
BP+2.9X
11/95
Man Transfer
/Retransfer
Inv Running
Page 3.31
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3. 3SBS Maintenan ce Menu (continued)
15. If it is desired to manually retransfer
to primary UPS input, press and wait 10
seconds for this screen to appear. This will turn
off all the LED’s except UPS Normal.
16. Normally, the system will be left so
that transfer and retransfer are enabled.
Following Step 11 of this subsection press
once or twice to obtain this screen with either
“transfers” or “retransfers” on the top line.
Pressing or will change between “enable d”
and “disabled” on the bottom line.
Man Transfer
/Retransfer
Inv Running
Retransfers
Enabled
17. Press to obtain –
18. Press to return to the SBS
Maintenance Menu.
3.6.3.4System Maintenance Menu
1. Press to advance to the System
Maintenance Menu.
Return to
Previous
Menu
SBS
Maintenance
Menu
System
Maintenance
Menu
BP+2.9X
11/95
Page 3.32
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4System Maintenance Menu (continued)
2. Press to obtain this screen. The
“X.XX” represents the latest software release
number.
3. Pressing the key will obtain this
screen. Press to execute the LED/lamp test.
All of the LED’s will light and a test patter n will
be displayed for 3 seconds in b oth the text and
numerical display areas.
NOTE: This test can be performed only from
the front panel display.
4. Press to obtain this message. This is
the beginning of a procedure to change the
language on the monitor panel, if desired. To
leave it in English, press . This will skip to
Step 7, below.
5. Pressing in the step above will bring
out this screen. If you wish to change the
language, it is necessary to confirm by pres sing
UP again.
Software Rev.
Level
X.XX 60 Hz
LED/Lamp
Test
UP = Test
Language
English
Confirm
Yes=UP No=DN
6. Pressing the second time changed
the language and obtained this message
(example shown in German).
WARNING: If you don’t speak German, don’t
perform this step. You may get
lost trying to get back to English.
BP+2.9X
11/95
Sprache
Deutsch
Page 3.33
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4System Maintenance Menu (continued)
7. Press to obtain this message in the
language displayed in Step 6. The message
screens will now all be in that language. Press
to confirm that this is the desired language.
Press DOWN to change the language. Refer to
the manual written in the appropriate language
for screen messages and instructions.
Yes=UP No=DN
Confirm
8. Press to obtain this screen. This is
the start of the procedure if it is necessary to
change the date setting.
9 Press . The screen will ask you to
confirm that you want to reset the date. If you
do not wish to reset the date, press .
10. Press to obtain this screen. If
desired, press or to change the year. Press
. Then, if desired, press or to change the
month. Then press . If desired, press or
to change the day.
11. Press . This will display the new
month/day/year you have set.
Date
mm/dd/yy
Confirm
Yes=UP No=DN
Enter Date
mm/dd/yy
(actual date)
Date
mm/dd/yy
12. Press to obtain this screen. This is
the start of the procedure to change the time
setting. (Time readings are based on a 24 ho ur
clock.)
BP+2.9X
11/95
Time
(actual time)
Page 3.34
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4System Maintenance Menu (continued)
13. Press . The screen will ask you to
confirm that you want to reset the time. If you
do not wish to reset the time, press .
14. If you press , you will obtain this
screen. If desired, press or to change the
second. Press . Then, if desired, press or
to change the hour. Then press . If desired,
press or to change the minute.
15. Press . This will display the new
time you have set.
16. This sequence is only for those units
with LCD display screens. The screen may be
tilted up and down to give persons of different
height a better view of the messages. Press or
to increase or decrease the reference number.
A higher number tilts the screen down; a low er
number tilts it up. When finished, press .
Confirm
Yes=UP No=DN
Enter Time
hh:mm:ss
(actual time)
Time
(actual time)
LCD display
view angle
XX
17. Press to obtain this screen.
Pressing will save all the changes to the menu
made before this.
18. Pressing in the step above will
bring out this screen. It is necessary to co nfirm
by pressing again.
BP+2.9X
11/95
Save
Personality
UP=Save
Confirm
Yes=UP No=DN
Page 3.35
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4System Maintenance Menu (continued)
19. Pressing or will return to this
screen.
3.6.3.4.1Alarm Configuration Menu
20. Press to obtain this screen,
beginning the Alarm Configuration Menu.
21. Press to obtain this screen.
CAUTION: Pressing will clear the Alarm
History records.
3.6.3.4.2Latching Alarms Menu
The purpose of this procedure is to allow the user to set the various alarms
as latching or non-latching. Pressing successively through this section will leave
all the settings as they are.
Save
Personality
UP=Save
Alarm
Configuration
Menu
Clear Alarm
History?
UP = Clear
22. Press to obtain this screen,
beginning the procedure.
23. Press to obtain this screen.
24. If you press , this screen will appear
to confirm that you wish to latch all alarms.
BP+2.9X
11/95
Latching
Alarms
Menu
Set all alarms latc hing
UP = Yes
Confirm
Yes = UP No = DN
Page 3.36
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.2Latching Alarms Menu (continued)
25. If you press after step 23, you will
obtain this screen. Pressing will ask you to
confirm that you wish to clear all latched
alarms. Pressing will obtain the following
screen.
26. If you have cleared all latched alarms
in Step 25, this will read “Non-latching.” If you
wish to change the latching instructions on any
of the screens from Step 26 through Step 32,
press , change the latching instructions,
confirm and press . To go from step 26 to step
Set all alarms latc hing
Transfer to
UP = Yes
Bypass
Latching
27 without making a change, press .
27. Press to go to the following screen.
28. Press to go to the following screen.
29. Press to go to the following screen.
30. Press to go to the following screen.
31. Press to go to the following screen.
Transfer not
Available
Latching
Battery not
Available
Latching
Retransfer
Inhibited
Latching
Low Battery
Voltage
Latching
AC Input
Failure
Latching
BP+2.9X
11/95
Page 3.37
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.2Latching Alarms Menu (continued)
32. Press to go to the following screen.
33. Press and to proceed.
3.6.3.4.3Communications Menu
34. Press to obtain this screen.
35. Press to obtain this screen.
UPS Overload
Latching
Return to
Previous
Menu
Communications
Menu
COM1 Menu
36. Press to obtain this screen.
Pressing at this point will reset the optional
COM1 serial port. (See NOTE 1.)
NOTE 1: The last display line shows the present state of the COM port.
Following is a list of valid messages:
BP+2.9X
11/95
COM1 Device
UP to reset
Power Up Init
Power Up Init
Wait on call
Get Password
Dev. Online
Dev. Offline
LogOut
Resetting
Page 3.38
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.3Communications Menu (continued)
NOTE 2: COM1 and COM2 in some of the following displays will apply only to an
optional modem or RS232 customer interface described ful ly in Section
VII. They can be skipped by pressing until you get to step 48.
37. Press once to obtain one of the
“Com 1 Display screens. Press or to obtain
another of these three screens, as desired.
Pressing will display the “Save Changes?”
screen. User Interface enables the UPS to
communicate in a standard ANSI terminal
format (VT100 emulation or equivalent). P-Rec
Proto allows computer to computer
communications with user developed software
per the protocol provided in section VII or
optional Windows based UPS Manager Plus ™
software. BCM Proto enables communications
with optional Onlinet® network power
management software.
COM1 Display
User Interface
COM1 Display
P-Rec Prot o
COM1 Display
BCM Proto
38. Pressing will select the desired
program and will bring back the previous COM1
screen.
39. Press once to get to this screen. If
you wish to change the Com 1 baud rate, press
to increase baud rate from 2400 to 9600, or
press to decrease from 9600 to 2400.
Pressing will display the “Save Changes?”
screen.
UPS Manager Plus™ is a trademark of International Power Machines.
Onlinet® is a registered trademark of Exide Electronics Group.
BP+2.9X
11/95
Save Changes?
Yes = UP No = DN
COM1 Baud Rate
2400
Page 3.39
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.3Communications Menu (continued)
40. Pressing ^ will select the desired
baud rate and will bring back the previous
COM1 screen.
41. Press and to proceed.
42. Press to obtain this screen.
43. Press to obtain this screen.
Pressing at this point will reset the optional
COM2 serial port. (See NOTE 1.)
44. Press once to obtain one of the
“Com 2 Display screens. Press or to obtain
another of these three screens, as desired.
Pressing will display the “Save Changes?”
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
COM2 Menu
COM2 Device
UP to reset
Power Up Init
COM2 Display
User Interface
screen. User Interface enables the UPS to
communicate in a standard ANSI terminal
format (VT100 emulation or equivalent). P-Rec
Proto allows computer to computer
communications with user developed software
per the protocol provided in section VII or
optional Windows based UPS Manager Plus ™
software. BCM Proto enables communications
with optional Onlinet® network power
management software.
BP+2.9X
11/95
COM2 Display
P-Rec Prot o
COM2 Display
BCM Proto
Page 3.40
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.3Communications Menu (continued)
45. Pressing will select the desired
program and will bring back the previous COM2
screen.
46. Press once to get to this screen. If
you wish to change the Com 2 baud rate, press
to increase baud rate from 2400 to 9600, or
press to decrease from 9600 to 2400.
Pressing will display the “Save Changes?”
screen.
47. Pressing ^ will select the desired
baud rate and will bring back the previous
COM1 screen.
48. Press and to proceed.
Save Changes?
Yes = UP No = DN
COM1 Baud Rate
2400
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
3.6.3.4.4UPS Identification Menu
49. Press to obtain this screen.
50. Press to obtain this screen.
BP+2.9X
11/95
UPS
Identification
Menu
UPS Name
Page 3.41
SECTION III
_
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.4UPS Identification Menu (continued)
51. Press and this confirmation screen
will appear asking whether you want to enter a
name.
52. Press again if you wish to enter a
name. This screen will appear.
Notice the blinking cursor at the bottom lin e. Pressing or will change
the character under the cursor (originally a space). You can move through the
available characters faster by holding down the ALARM SILENCE button while
pressing or . To move the cursor to the right, press ; to move to the left press
.
53. When all characters have been
entered, the screen will look like this. Press X.
54. Press to save the changes.
Yes = UP No = DN
ABC COMPANY
Yes = UP No = DN
Confirm
Enter Name
Enter Name
Save Changes?
55. Press to obtain this screen.
56. Press and this confirmation screen
will appear asking whether you want to enter a
unit identification.
BP+2.9X
11/95
UPS Unit ID
Confirm
Yes = UP No = DN
Page 3.42
SECTION III
_
_
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.4UPS Identification Menu (continued)
57. Press again if you do wish to enter
a unit identification. This screen will appear:
Notice the blinking cursor at the bottom lin e. Pressing or will change
the character under the cursor (originally a space). You can move through the
available characters faster by holding down the ALARM SILENCE button while
pressing or . To move the cursor to the right, press ; to move to the left press
.
58. Press to save the changes.
59. If “Phone Home” feature is being
used, the UPS modem phone number must be
entered. Press once to obtain this screen. If
you wish to skip this sequence, press twice to
go to step 59.
Enter unit ID:
Save Changes?
Yes = UP No = DN
UPS Phone
Number
60. Pressing and this confirmation
screen will appear asking whether you want to
enter a phone number.
61. Press again if you do wish to enter
a phone number. This screen will appear.
BP+2.9X
11/95
Confirm
Yes = UP No = DN
Enter Phone Number:
Page 3.43
SECTION III
_
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.4UPS Identification Menu (continued)
Notice the blinking cursor at the bottom lin e. Pressing or will change
the character under the cursor (originally a space). You can move through the
available characters faster by holding down the ALARM SILENCE button while
pressing or . To move the cursor to the right, press ; to move to the left press
.
62. When all characters have been
entered, the screen will look like this. Press .
63. Press to save the changes.
64. This sequence is for entering a 24
hour telephone number which can be called b y
Factory Field Service personnel to tell you that
your UPS has reported an alarm condition via
its Phone Home capability. Press once to
obtain this screen. If you wish to skip this
sequence, press twice to go to step 64.
65. Press and this confirmation screen
will appear asking whether you want to enter a
phone number.
Enter Phone Number:
XXXXXXXXXX
Save Changes?
Yes = UP No = DN
24 Hr. Voice Phone
Number:
Confirm
Yes = UP No = DN
66. Press again if you do wish to enter
a phone number. This screen will appear.
BP+2.9X
11/95
Enter Phone Number:
Page 3.44
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.4.4UPS Identification Menu (continued)
Notice the blinking cursor at the bottom lin e. Pressing or will change
the character under the cursor (originally a space). You can move through the
available characters faster by holding down the ALARM SILENCE button while
pressing or . To move the cursor to the right, press ; to move to the left press
.
67. When all characters have been
entered, the screen will look like this: Press .
68. Press to save the changes.
69. Press to obtain this screen.
70. Press to return to the System
Maintenance Menu.
3.6.3.5Password Maintenance Menu
Enter Phone Number:
XXXXXXXXXX
Save Changes?
Yes = UP No = DN
Return to
Previous
Menu
System
Maintenance
Menu
1. Press to advance to the Password
Maintenance Menu.
BP+2.9X
11/95
Password
Maintenance
Menu
Page 3.45
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.5Password Maintenance Menu (continued)
2. Press to obtain this screen. There
are four (4) levels of passwords. Press as often
as necessary to reach the desired level. The
number in the lower left will ch ange, indicat ing
the level attained. (NOTE: You can not go
beyond the level for which the system is set
when you start.)
3. Press . The system will ask you to
confirm the password level.
4. Press as requested in the previous
message. You are now ready to modify the
password. Follow the procedure you used in
steps 3 through 6, pages 3.25 a nd 3.26 to g et
into the UPS Maintenance Menu. When you
have finished, press .
5. You will see this message briefly
flashed on the screen –
No Password
Password
Menu
Confirm
Yes = UP No = DN
Enter
Password
0
Verify
Password
6. Then this message will appear again. It
is necessary to repeat step 4, entering the new
password again. Then press .
7. Press to save the new password.
BP+2.9X
11/95
Enter
Password
0
Save Changes?
Yes = UP No = DN
Page 3.46
SECTION III
Operation
3.6UPS Operatin g Procedures (continued)
3.6.3UPS Maintenance Menu (continued)
3.6.3.5Password Maintenance Menu (continued)
8. Press to obtain this screen.
9. Press to return to the Password
Maintenance Menu.
10. Depress to return to Previous Menu.
11. Depress to leave UPS Maintenance Menu.
3.6.4 System Shutdown
1. Perform the Bypass/Shutdown procedure (Paragraph 3.6.3.3).
NOTE: This leaves the critical load powered by the utility power source
through the bypass.
Return to
Previous
Menu
Password
Maintenance
Menu
2. To remove all power to the load, open the BYPASS CIRCUIT BREAKER.
3.6.5.CPU Fault
If this message should appear on the
screen, the UPS is transferred to bypass. Call
Service Hotline at (800) 777-8922.
BP+2.9X
11/95
Page 3.47
SECTION IV
Maintenance
4.1General
Proper maintenance, both preventive and remedial, is the key to optimal
operation of the UPS and will ensure a long and useflil life of the equipment.
Preventive maintenance includes regularly performed procedures designed to
prevent system malfunction and obtain maximum operational efficiency. Remedial maintenance consists of troubleshooting the system in order to effect
repairs. Troubleshooting the UPS involves following a logical sequence of steps
which will determine the cause of an alarm and/or malfunction within the shortest
time frame safely possible so as to expedite the repair and return of the equipment
to normal service.
The manufacturer recommends that the monitor panel be inspected
visually every eight-hour shift to see that lights are operating and no alarm
conditions exist. The Alarm History should be checked at this time (see
Paragraph 3.6.2) to determine if any recent alarms have gone un-noticed. If
any unusual conditions exist, call facility maintenance p ersonnel or Service
Hotline: 800-777-8922 or (outside U.S.) 919-871-1800.
4.2Safety Precautions
For safe and successful maintenance on the system, certain basic safety
precautions must be observed, necessary tools and test equipment must be
available, and properly trained maintenance personnel must be involved.
The following basic safety practices should always be observed:
1. Always be aware that hazardous voltages a re p resent within the UP S even
when the system is not operating.
WARNING
On a single-input UPS, when input voltage does
not equal output voltage, output transformer
(T2) is energized in Maintenance Bypass Mode.
2. Ensure that UPS operating and maintenance personnel are thoroughl y familiar
with the equipment and with the contents of this manual.
BP+2.9X
11/95
Page 4.1
SECTION IV
Maintenance
4.2 Safety Precautions (continued)
3. Never wear metal jewelry such as rings or wrist watches when workin g on the
UPS equipment.
4. Keep cabinet doors closed and secured during normal operation.
5. Never guess about safety procedures. If any doubt exists, ask someone who
knows.
6. Always be aware of the presence of high voltage within the UPS.
Check with a voltmeter to make sure power is off and conditions are safe before
attempting to make repairs, adjustments, etc. within the unit.
7. Above all, always USE COMMON SENSE!
4.3 Preventive (Periodic) Maintenance
The following paragraphs describe preventive maintenance procedures
which, when followed, will increase the reliability and efficiency of the UPS
system operations.
4.3.1 Air Filters
Filters, installed in the bottom of the cabinet, eliminate particles from the air
which is used to cool the UPS. In time, particle accumulation in the filters will
reduce airflow through the system causing a rise in operating temperatures,
triggering an alarm condition and resulting in shut down of the UPS. Filters should
be checked and cleaned or replaced at least every 30 days in a clean environment,
and no more than 7 days in a dirty environment.
Models of 125 and 150 kVA have two filters; other models have only one.
Loosening a clip beneath the UPS near the front allows the filter to drop down and
you can slide it out. Insert new filter and twist clip to secure it in place.
Filters are standard fiberglass furnace filters of the following sizes:
10-100 kVA UPS - 16" x 25" x 1" 125-150 kVA UPS - 14" x 25" x 1"
BP+2.9X
11/95
Page 4.2
SECTION IV
Maintenance
4.3Preventive Maintenance (continued)
4.3.2 Cable Connections
Cable connections to circuit breaker and switch terminals should be
checked whenever the system is powered down and at least annually. This
necessitates removal of the circuit breaker panel to gain access.
WARNING
Be aware of the presence of high voltages within the
UPS! When the system is shut down, wait at least
five (5) minutes after all panel lights go out before
proceeding. Then check for the p resence of power
with a voltmeter across the input and output
terminals.
4.4Remedial Mainte nance (Troubleshooting)
Remember the International Power Machines 24-Hour Hot Line:
Phone: 800-777-8922; (outside U.S.) 214-272-8000
is always available to provide advice and assistance on your UPS.
4.4.1 General
When properly installed, operated and maintained your International P ower
Machines BalancedPower Plus UPS will provide long, reliable power protection
with little need of remedial or corrective maintenance actions. However, this section
contains information as to problem isolation techniques and recommended actions
to be taken so as to effect repairs on the UPS.
BP+2.9X
11/95
Page 4.3
SECTION IV
Maintenance
4.4Remedial Mainte nance (continued)
4.4.1 Gener al (c o nti nu ed )
Because of the modular design o f the BalancedPower Plus UPS, corrective
action in many instances requires replacement of a major assembly or
subassembly. For this reason, troubleshooting information as containe d herein is
generally limited to immediate action that may be taken on site to correct a specific
alarm condition. If such immediate action does not remedy the situation, contact
the 1PM 24-Hour Hotline for assistance.
In general the BalancedPower Plus UPS is designed so that the operator
should not find it necessary to have access to any area of the equipment except the
Digital Monitor Panel and the circuit breake rs, switch and fuses inside the righthand door.
WARNING
Do not remove front plastic shield,
front panel around the circuit breakers
or either side panel unless
all power to the UPS is OFF. Only
trained maintenance personnel should
remove any of these panels.
4.4.2 Status/Alarm Indicators
The LED status/alarm indicators on the monitor panel are described in
Paragraph 3.4.1. Specific action that may be taken in case of alarm c onditions is
described in Table 3-2, a part of Paragraph 3.6.2.
BP+2.9X
11/95
Page 4.4
SECTION IV
Maintenance
4.5Fuses
There are four (4) fuses adjacent to the UPS CONTROL switch inside the
front door. If one of these fuses is blown, the control logic will not become energized
at startup. Once the UPS is started, it will operate even though one o r more of the
fuses is blown.
In case a fuse blows, replace it with a fuse of the same make and size.
These are the only fuses available to the user unless he or she has had
authorized factory training.
4.6Battery Maintenance
4.6.1Safety Precautions
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
When replacing batteries, use the same number and the following type of
batteries: sealed lead acid. All batteries in a cabinet should be from the same
manufacturer and of the same part number.
CAUTION:Do not dispose of battery or batteries in a fire. The battery
may explode.
CAUTION:Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
CAUTION:A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working
on batteries:
1.Remove watches, rings or other metal objects.
2.Use tools with insulated handles.
BP+2.9X
11/95
Page 4.5
4.6Battery Maintenance (continued)
4.6.1Safety Precautions (continued)
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Open DC Disconnect switch prior to connecting or
disconnecting battery terminals.
6. Determine if the battery is inadvertently grounded. If
inadvertently grounded, remove the source of the ground.
Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such a shock will be
reduced if such grounds are removed during installation
and maintenance.
SECTION IV
Maintenance
4.6.2Maintenance Shutdown of Battery Pack
This procedure is for shutting down the IPM battery pack. It does not
require that the protected load be removed from the UPS.
Perform the following steps in the order presented:
1. Verify that each UPS attached to the
battery pack is running on UPS input ac pow er
by noting the dc link voltage. Depress or
beneath DISPLAY SELECT to obtain the Link
Voltage message on the screen. Voltage should
be 234 VDC (10-30 kVA) or 390 VDC (37.5-150 kVA) or greater.
Do not proceed if battery system is sup plying p ower to any protected
equipment.
2. Shut off DC Disconnect switch. This will illuminate the Battery Not
Available LED .
3. A general alarm will appear at each UPS as the Disconnect device is
opened. This is normal. Depress the ALARM SILENCE button once to turn off the
audible alarm.
Link Voltage
Battery Amps
Max Out CF
BP+2.9X
11/95
Page 4.6
4.6Battery Maintenance (continued)
4.6.3Inspection and Periodic Maintenance
This procedure should be performed annually or whenever batteries need to
be replaced.
1. Place the battery pack in Maintenance Shutdown condition (Paragraph 4.6.2).
2. Open the front doors of each battery pack and visuall y inspect the inside
of the cabinet for:
a.Leaking acid.
b.Corrosion on frame and electrical parts.
c.Loose or discolored electrical connections, especially around
the cable connections.
SECTION IV
Maintenance
3.Disconnect all the battery cable connectors.
4.Each battery tray is held in place by two bolts that fasten it to a slide.
Remove the bolts from one tray at a time and very carefully pull the tray
forward. Care should be taken that the tray doesn't come all the way out.
The tray is heavy weighing as much as 200 pounds (91 kg) or more.
5. Use a lift hand truck to remove the tray completely from its slide.
CAUTIO N
The battery tray weighs as much as
200 lbs (91 kg). Use lift hand truck to remove it.
6. Inspect each battery post for corrosion or discoloration. If post is
discolored or corroded remove battery cable and clean the post and cable connector
shiny bright. Replace cable, torque cable connector bolt to the battery
manufacturer's recommended torque*, and apply a generous amount of grease
(Dow Corning silicone grease or equal) to the battery posts and connectors.
* Tor que s p ecif icati on s ma y be fou nd o n th e bat ter y its elf or in sp ecifi ca ti ons at th e end of this
section.
BP+2.9X
11/95
Page 4.7
SECTION IV
Maintenance
4.6Battery Maintenance (continued)
4.6.3Inspection and Periodic Maintenance (continued)
7. If not removed and cleaned, torque all cable connector bolts to battery
manufacturer's retorquing specifications.
8. Repeat until all battery trays have been inspected, cleaned and gr eased.
Do one tray at a time and be sure to return tray to its original location. Bolt in place.
Trays are numbered in accordance with Figure 4-1 or 4-2 on Page 4.11.
9. Retighten power cable connections between the DC Disconnect switch
and the UPS. Refer to torque table in Paragraph 2.7, AC Power Connection.
10. Reconnect the battery trays to each other as described in Paragraph 2.8,
Activating the Battery Pack. Close the battery pack door.
4.6.4Batt ery Test
Batteries should be tested whenever a batter y-related problem is susp ected
or at annual intervals. The procedure described is for individual batteries and
requires the use of a Balkamp 700-112 Battery Tester or equivalent. The Balkamp
unit is available at most NAPA auto parts stores or from IPM.
The tester is rated for 100 amps, 12 vdc. It checks voltage under load.
Batteries should be tested in their fully-charged state, but not within 24
hours of having been equalized (recharged). Batteries should be left in their trays
during testing.
2. Remove two bolts and slide out the desire d battery tray onto a lift hand
truck.
CAUTIO N
The battery tray weighs as much as
200 lbs (91 kg). Use lift hand truck to remove it.
BP+2.9X
11/95
Page 4.8
SECTION IV
Maintenance
4.6Battery Maintenance (continued)
4.6.4Battery Test (con ti nu ed )
3. Test each battery separately.
4. Using a digital voltmeter which can be read to 0.01 vdc, check the voltage
across the posts of the batteries, one at a time. Record the voltage readings for each
battery. If the voltage does not read at least 12.40 vdc, the battery probably should
be replaced. You may try to recharge the battery, but it probably won't hold a
charge. For replacement procedure see Paragraph 4.6.5.
5. If the battery's voltage is satisfactory, use the battery tester. Attach the red
battery tester cable to the positive (+) battery pole; attach the black cable to the
negative (-) battery pole.
6. Press the LOAD switch. (If using a brand of tester other than the Balkamp,
follow the tester's operating instructions.)
7. In approximately 10 seconds, the tester n eedle should be in the "good"
(green) area. If not, the battery should be replaced.
8. Perform the same tests on all batteries i n the cabinet . (Allow the tester to
cool between tests.)
9. For proper operation, each battery in the cabinet should show voltage
readings within ±0.10 vdc of their average. If full agreement of battery voltages
cannot be obtained, contact Service Hotline 800-777-8922.
10. Return the battery trays to their normal position. When each tray is fully
back, replace the two bolts that fasten it to the slide. Reconnect the battery tra y
cables.
Recommended torque is on label on top of each battery.
GNB
100 lb-in
C&D
100 lb-in
Annual
NOTE: To obtain N-m, multiply in/lb by 0.113.
BP+2.9X
11/95
Page 4.12
SECTION V
Spares, Training Maintenance
5.1Spare Parts
To facilitate service on the BalancedPower PlusUPS, it is recommended
that a spare parts stock be maintained on site. Investment in a spares stock
ensures immediate parts availability when required, thereby providing for faster
service and greater protection from costly system downtime.
International Power Machines can supply any of several recommended
Spares Levels to meet differing requirements. The desired Mean-Time-To-Repair
and the travel time from IPM's nearest Service Center would normally determine the
approximate level of spares to be stocked.
This section lists typical spare parts for a UPS of the size shown on the cover
page of this manual. It is not applicable to other size UPS.
For further information concerning the stocking of spare parts, or to order
replacement parts, please contact:
Customer Services Representative
International Power Machines
Worldwide Services Group, IPRC
2708 Discovery Drive
Raleigh, NC 27604
Domestic: Phone: (919) 981-8127
Fax: (919) 981-8150
Outside U.S.: Phone: (919) 870-3208
Fax: (919) 870-3300
BP+2.9X
11/95
Page 5.1
SECTION V
Spares, Training Maintenance
5.2Training
To insure that our customers derive maximum benefit from their UPS and
related equipment, IPM offers a variety of training classes tailored to specific
interests and requirements. These courses include a one-day Operator Seminar, a
Basic Maintenance class for facilities perso nnel and spec ialized trai ning for uniq ue
equipment configurations. Most classes can be presented either at our Training and
Support Center or at the customer's site.
Additional information and rates may be obtained from:
WSG Training and Support Center
International Power Machines
3401 Spring Forest Road
Raleigh, NC 27604
Phone: (919) 871-1812
Fax:(919)871-1822
5.3Continu ing Maint enance Program
We consider regular maintenance of your UPS to be insurance for your
equipment investment. We have, therefore, developed a continuing maintenance
program, available throughout the 50 states, that can go into effect upon the
expiration of the standard warranty on new equipment. Basically, the program
provides for one preventive maintenance call per year, plus unlimited remedial
maintenance calls as required, with all parts, labor and expenses included. Similar
battery maintenance programs are available.
Additional information and prices may be obtained from:
Worldwide Services Group
International Power Machines
Maintenance Sales Department
10451 Brockwood Road
Dallas, Texas 75238-1641
Phone: (214) 342-6104
Fax: (214) 214-342-6115
BP+2.9X
11/95
Page 5.2
SECTION VI
Glossary
ACAlternating current (normally "AC").
AC POWER AC input to the UPS. Also identified as "UPS Input."
ALARM An abnormal condition within the UPS.
ALARM SIGNAL A loud piercing electronic tone signaling an alarm condition.
APPARENT POWER (kVA) The product of voltage and current. This is used to state the maximum rating of
power generating devices.
AUTO RETRANSFER A feature which allows the Static Bypass Switch to place the UPS back on line
without manual intervention.
CIRCUIT BREAKER PANEL That portion of the cabinet behind the right-hand door, containing th e UPS Input
Circuit Breaker, Static Bypass Circuit Breaker, Bypass Circuit Breaker and Output
Circuit Breaker.
CURRENT LIMIT Electronically governing the maximum current output from the rectifier and/or the
inverter.
DCDirect current (normally "DC").
DC LINKDC voltage output of the rectifier and input to the inverter. Is maintained by a
battery bank during a power outage.
DIGITAL SIGNALPROCESSOR (DSP) The "brain" of the control logic system.. Receives and an alyzes data, and provides
control and monitoring for the UPS.
BP+2.9X
11/95
Page 6.1
SECTION VI
Glossary
EMERGENCY POWER OFF (EPO) A means of cutting power from the UPS in emergency situations. The EPO switch is
located on the Monitor Panel.
EQUALIZE See RECHARGE.
FLOAT CHARGE A dc voltage applied to a battery at a level which mainta ins the battery in a fullycharged state.
HERTZ (Hz) The measure of electrical frequency in cycles per second.
INVERTER A major component of the UPS. Its primary function is to change DC to AC.
LEDLight-emitting diode. A semiconductor that give off light when it is energized.
LOGIC CIRCUIT A network of electronic components that performs a specific function.
OUTAGE Loss of UPS input or bypass power.
PHASE LOCK A condition in which the inverter output is frequency and phase synchronous with
the utility ac source.
PHASE SEQUENCE The order in which the fundamental components of a poly-phase set of
voltages/currents reach a particular value.
POWER FACTOR The ratio of real power to apparent power. Equal to the cosine of the phase angle
between the current and voltage for sinusoidal voltages and currents.
BP+2.9X
11/95
Page 6.2
SECTION VI
Glossary
REAL POWER (kW) The portion of apparent power which actually performs work or generates heat.
RECHARGE A dc voltage applied to a battery for a given period of time which will equalize
unevenly charged cells. After an emergency discharge, it will restore the batteries to
full charge.
RECTIFIER/CHARGER A major component of the UPS. Its primary function is to change AC to DC for the
inverter input. It also supplies current to recharge or m aintain the charge of the
batteries.
REMOTE ALARM CONTACTS Relay switch! contact arrangement which opens or closes in response to an alarm
condition within the UPS. The contacts are connected to terminals which are easily
accessible to the customer. They provide the ability to remotely sense an alarm
condition.
STATIC BYPASS SWITCH (SBS) A major component of the UPS. Connects the U PS Input to the load if th e rectifier
and/or the inverter become unavailable or unacceptable.
TRANSFER A static bypass switch operation which exchanges load power sources from the UPS
to utility power.
UPSUninterruptible power system. UPS are on-line units which deliver power to the
critical load from the inverter on a full-time basis. A power outage does not require
load switching manually since the battery in stantaneousl y takes over to supply dc
power to the inverter. Due to the ac to dc t o ac conversi on, most UPS units offer
superior ac transient noise suppression.
WYE OUTPUT A wiring configuration. Wye utilizes four wires to furnis h a neutral. The output of
the UPS is a WYE configuration.
BP+2.9X
11/95
Page 6.3
SECTION VII
Remote Video Terminal
7.1General
An optional remote video terminal, supplied by LorTec or by the customer, is
plugged into the optional RS232 communicati on or telepho ne modem port. If this
port was not purchased, this section does not apply to your UPS.
The remote monitor is to be a video display terminal capable of emulating a
VT100 or equivalent.
7.2RS232 Interlace
When COM1 or COM2 user interface is selected, the basic CRT Menu
Screen looks like this during normal UPS operation. A valid password must be
entered to access this screen.
[*] UPS Normal[ ] Tran sferred to Bypass
[ ] AC Input Failure[ ] Transfer not Available
[ ] Low Battery Voltage[ ] Battery Not Available
[ ] UPS Overloaded[ ] Retr ansfer Inhibited
[N]ext [P ]r ev ious [S]il en ce [U]p [D]own [E] nte r [ ^R]efres h [H ]i story
The top segment represents the LED's on the front of the UPS monitor panel.
The four-column segment represents the messages which ap pear on the monitor
panel's message screen. (Numbers are typical; actual values will appear.)
BP+2.9X
11/95
Page 7.1
SECTION VII
Remote Video Terminal
7.2RS232 Interface (continued)
The lower segment shows the keyboard keys to be used to change the
message screens (in place of the pushbutton s on the monitor panel). Briefly, the
functions of these keys are as follows:
KeyFunction
[N]extScrolls data up the display area.
Displays next item in a submenu list.
[P]revious Scrolls data down the display area.
Displays previous item in a submenu list.
[S]ilenceAlarm silence.
[U]pDisplays next alarm entry in Alarm History when Alarm
History is active.
Increment displayed value of modifiable elements.
[D]ownDisplays previous alarm entry in Alarm History when Alarm
History is active.
Decrement displayed value of modifiable elements.
[E]nterSelect the menu displayed in active area.
Save changes of modifiable elements.
[^R]efresh(Press Control R.) Clears the screen and redraws it.
[H]istoryFull screen alarm history display.
[LO]g out(Not shown on screen.) Disconnects the modem.
The upper left-hand message is the only one that is active at any given time,
On the sample CRT screen "UPS Maintenance Me nu" is in the active area. Other
message screens can be brought into this active area by depressing [N]ext or
[P]revious on the keyboard, causing the messages to rotate. Do this as often as
necessary until the desired message is in the upper left-hand corner.
BP+2.9X
11/95
Page 7.2
SECTION VII
Remote Video Terminal
7.3UPS Maintenance Menu
The description given in Section 3.6.3 for the UPS Maintenance Menu
applies equally to its use from a remote terminal. Make sure that "UPS Maintenance
Menu" is in the upper left-hand area of the CRT screen. Then use the keys that
correspond to the pushbuttons described in this manual. You will need to use the
operator password (level 4) in order to obtain access to the UPS Maintenance Menu.
The various screen messages will appear on t he CRT also in the upper left-hand
area.
7.4Alarm History Screen
Below is a typical Alarm History screen. The alarms are displayed in
date/time order with the most recent alarm at the bottom of the screen.
Mo/Dy/Yr Hr:Mn:Sc:Cy:Q Alarm (U=Up D=Dn +=PgUp -=PgDn T=Top B=Bot M=Monitor)09/20/91 14:59:27.07.0 sbs output breaker closed09/20/91 14:59:27.07.0 inv not phase locked09/20/91 14:59:27.07.0 inv transfer enabled09/20/91 14:59:27.07.0 inv retransfer enabled09/20/91 14:59:27.07.0 inv fan normal09/20/91 14:59:27.08.0 input frequency normal09/20/91 14:59:27.08.0 sbs bypass frequency normal09/20/91 14:59:27.10.0 sbs bypass voltage low09/20/91 14:59:28.41.0 rct phase locked09/20/91 14:59:28.42.0 input voltage low09/20/91 14:59:32.23.0 input voltage normal09/20/91 14:59:32.23.0 sbs bypass voltage normal09/20/91 14:59:32.23.0 inv phase rotation normal09/20/91 14:59:32.23.0 rectifier normal09/20/91 14:59:37.07.1 inv normal temperature09/20/91 14:59:37.08.0 inv fuse normal09/20/91 14:59:37.08.0 inv power supply normal09/20/91 14:59:37.18.0 inv current normal09/20/91 14:59:37.18.0 output voltage low09/20/91 14:59:37.18.0 inverter off09120/91 14:59:37.18.0 sbs off09/20/91 14:59:39.09.0 inv phase locked09/20/91 14:59:47.33.0 dc voltage normal
A convenient way of viewing the Alarm Histor y screen is t o use the com mands at
the top of this screen:
U Scrolls up one alarmT Goes to the top of the alarm history buffer
D Scrolls down one alarmB Goes to the bottom of the alarm history buffer
+ Scrolls up one pageM Monitors the occurrence of alarms. All new
- Scrolls down one pagealarms are added to the bottom of the screen.
BP+2.9X
11/95
Page 7.3
SECTION VII
Remote Video Terminal
7.5P-Record
P-Record format is for users who need to query the UPS periodically for
information as to its status or develop cust om monitoring software. It is used also
when the "phone home" capability is enabled.
For additional information on the P-Record protocol, refer to document