4. TOP PANEL .............................................................................................................................................. 5
5. POWER SUPPLY ....................................................................................................................................... 5
Page 3 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
www.ipelectronix.com
IPEX (IP Electronix) PH485REPi
: User’s Manual
1 Introduction
IPEXPH485REPi™ is a RS-485 Repeater and Amplifier. If it is needed to have RS-485 network with more than
1200m length or to have more than 32 nodes, using a PH485REPi™ helps you to increase the network length up
to 2400m and also to have up to 64 devices connected to it. PH485REPi™ is compatible with RS-485 standard
devices differential Data+ & Data- signals and is fully Plug & Play. It works with a wide range of +10V up to +30V
DC power supply with low (about 40mA) consumption. PH485REPi™ is designed for industrial usage and is
useful for Industrial Automation, Telecommunications, SCADA Systems, and DCS Systems …
Protection against Surge, ESD and EMI is considered in its design and also has 3kV isolation between RS-485
sides. Since RS-485 is a Half-Duplex standard, switching between transmit and receive is done automatically and
no further signal (such as RTS) is required. PH485REPi™ supports Point-to-Point and Point-to-Multi Point Party
Line network topologies.
2 Specifications
RS-485 Bidirectional Repeater and Amplifier
Fully Plug & Play
RS-485 Signal: Data+, Data-, GND
Baud Rate Type: Auto Switching Baud Rate
Serial Transmission Speed Up to 230.4 kbps
Maximum Communication Distance: 2400m (8000 feet) – 1200m for each side
Loading: Supported up to 64 Nodes – 32 Nodes for each side
Isolation Protection: 3kV Instantaneous, 500V DC continuous
Power (Green) LED Indicator
Transmit (Blue) and Receive (Yellow) LED Indicator
Power Supply Input Voltage: +10VDC to +30VDC
1 Year Guarantee and 5 Years Support
Operating Temperature: -10°C to +70°C (+14°F to +158°F)
Page 4 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
www.ipelectronix.com
IPEX (IP Electronix) PH485REPi
: User’s Manual
3 Package Checklist
Before installing the PH485REPi, verify that the package contains the following items:
1) PH485REPi
2) Installation CD-ROM
3) #2 Phonix 7Pin Green terminals
NOTE: Notify your sales representative if any of the above items is missing or damaged.
4 Top Panel
Green LED: It is turned ON, when the power supply connects to +VS and GND correctly.
Yellow LED: It is blinking if there is a data stream from right to left side of the repeater.
Blue LED: It is blinking if there is a data stream from left to right side of the repeater.
5 Power Supply
Connect a DC voltage in range of +10V to +30V, between +VS and GND terminals. If the power supply connects
correctly, the Green LED should be ON.
NOTE: It is not required to connect GND signal from one side to GND signal of other side.
Page 5 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
www.ipelectronix.com
IPEX (IP Electronix) PH485REPi
: User’s Manual
7 RS-485 Connecting Methods
7.1 RS-485: Point to Point Connection (without Repeater)
7.2 RS-485: Point to Point Connection (with a Repeater)
Page 6 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
www.ipelectronix.com
IPEX (IP Electronix) PH485REPi
: User’s Manual
7.3 RS-485: Multipoint Network (Without Repeater)
7.4 RS-485: Multipoint Network (With a Repeater)
Page 7 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
www.ipelectronix.com
IPEX (IP Electronix) PH485REPi
: User’s Manual
8 Guarantee
All products manufactured by IPEX are under warranty regarding defective materials for a period of one year
from the date of delivery to the original purchaser.
9 Technical Support
If you have any technical question or need any technical support, please contact us using this Email address:
support@ipelectronix.com
.
Page 8 of 8 Doc No. : PH485REPi-UM-001
15 August 2013
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.