IPEX PH422Ex2 User Manual

Doc No: PH422Ex2-UM-001
14 January 2014
USER’S MANUAL
PH422Ex2
#2 RS-422 Serial Port to Ethernet, Terminal Server/Client
IPEX
(IP Electronix)
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
Contents
1. INTRODUCTION ....................................................................................................................................... 3
2. SPECIFICATIONS ...................................................................................................................................... 3
3. PACKAGE CHECKLIST ............................................................................................................................... 4
4. TOP PANEL .............................................................................................................................................. 4
5. FRONT PANEL .......................................................................................................................................... 5
6. RS-422 CONNECTING METHODS .............................................................................................................. 6
7. CONNECTION DIAGRAM .......................................................................................................................... 7
8. DEVICE NETWORK AND SERIAL PORT SETTINGS ...................................................................................... 9
9. NETWORK CONNECTION TESTING ......................................................................................................... 12
10. CONNECTING TO DEVICE VIA TCP SOCKET ......................................................................................... 14
11. INSTALLING THE DRIVER SOFTWARE ................................................................................................. 15
12. SET WINDOWS COM PORTS FOR PORT 1 & PORT2 ............................................................................ 17
13. GUARANTEE ...................................................................................................................................... 21
14. TECHNICAL SUPPORT ........................................................................................................................ 21
Page 2 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
1. Introduction
IPEX PH422Ex2™ bidirectional communication terminal server/client is a simple solution for connecting serial devices to a network which results in having 2 RS-422 (4-Wired RS-485) serial ports over Ethernet network which is compatible with RS-422 standard devices differential Tx+,Tx- & Rx+,Rx- signals. This converter uses transparent communicate protocol, so it is not required to understand complex Ethernet TCP/IP protocol, and no modification in serial programs is needed. It operates as a Real COM, TCP Server or TCP Client Full-Duplex converter and supports bidirectional connection.
PH422Ex2™ is designed for industrial usage and is useful for connecting any device with a serial interface to a computer via Ethernet supported network like LAN, WAN … and can be used in Industrial Automation, Telecommunications, SCADA Systems, and DCS Systems ….
Protection against Surge, ESD and EMI is implemented in its design and it has 3kV isolation between Ethernet and RS-422 sides.
PH422Ex2™ comes complete with drivers for Microsoft Windows XP/CE/2003/2008/7. Its setup file creates 2 virtual COM Port on your Server, PC or Laptop with configurable baud rate, 8 bits data length and 1 stop bit fixed setting.
2. Specifications
Number of Ports: #2 RS-422 Serial Port, #1 Ethernet RJ45 (10/100 Mbps) Port Serial Standard: EIA RS-485, RS-422 Standard, Asynchronous Full-Duplex 4-Wire RS-422 Signals: Tx+, Tx-, Rx+, Rx-, GND RS-422 Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200 and 38400 bps; Selectable RS-422 Parity: Even, Odd, None, Mark and Space; Selectable Supports Point-to-Point and Multidrop Configuration Transmission Medium: Twisted Pair Cable or Shielded Wire Maximum Communication Distance: 1200m (4000 feet) Loading: Supported up to 32 Nodes Network Protocols: ICMP, IP, TCP, UDP, DHCP, Telnet, DNS, SNMP, HTTP, SMTP, ARP Windows Virtual COM Drivers: Windows 95/98/ME/NT/2000, Windows XP/2003/Vista/2008/7 x86/x64, Power (Green) LED Indicator Transmit (Blue) and Receive (Yellow) LED Indicator for All Ports ESD Protection: RS-422 Bus-Pin ESD Protection Exceeds ±15 kV Using Human-Body Model (HBM) Dimensions: 36.41mm x 121.82mm x 140 mm (1.43inch x 4.79inch x 5.51inch) Operating Temperature: -10°C to +70°C (+14°F to +158°F) 1 Year Guarantee and 5 Years Support
Page 3 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
3. Package Checklist
Before installing the PH422Ex2, verify that the package contains the following items:
1) PH422Ex2
2) 220V AC to +6V DC Voltage Adaptor
3) Installation CD-ROM
NOTE: Notify your sales representative if any of the above items is missing or damaged.
4. 0BTop Panel
General Indicators:
POWER LED (Green): It is turned ON, when the power supply connects to +VDC and GND correctly. SERVER LED (Green): It is turned ON if the device is in Server Mode. CLIENT LED (Green): It is turned ON if the device is in Client Mode.
Port Indicators:
TCP LED (Green): It is turned ON if a TCP connection between the device and a remote Server/Client established. PE LED (Red): It is blinking if the device detecting a Parity Error in data. RX LED (Yellow): It is blinking when the device receive data on serial port. TX LED (Green): It is blinking when data is transmitting from the device serial port.
Page 4 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
5. Front Panel
Page 5 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
6. RS-422 Connecting methods
6.1 00BRS-422: Point to Point
6.2 00BRS-422: Multi Drop Network
Page 6 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014
www.ipelectronix.com
IPEX (IP Electronix) PH422Ex2
: User’s Manual
7. Connection Diagram
7.1 PH422Ex2 as a Terminal Server
The below diagram is a typical connection configuration of PH422Ex2. You can connect two devices with a RS­422 serial port to any RS-422 serial port of the PH422Ex2. Then you can connect to the device, behind the network by any application software you want.
There are two methods in order to be connected to the PH422Ex2 COM Ports via Ethernet. As the first way, it is possible to connect to the device by opening a normal COM Port (if you have installed PHEx2.exe software on the PC or Laptop). The second way is connecting to PH422Ex2 by opening a TCP Socket without need of any auxiliary driver.
To configure network settings of PH422Ex2 such as IP Address or Subnet mask, connect a computer with a terminal emulator software (like Hyper Terminal) on it, to the COM1 of PH422Ex2 and restart PH422Ex2 by pressing the Network Config. Button.
Page 7 of 21 Doc No. : PH422Ex2-UM-001 14 January 2014