![](/html/4f/4f59/4f59cf457e7b8e33f60773881132eb6ef4a7627e4a8360e27dfbf5d27f00bcd8/bg1.png)
PRODUCT SPECIFICATION SHEET
SELF-DIAGNOSTIC
AUTOMATIC MONTHLY & ANNUAL TESTING
Certified in CA TITLE 20
Appliance Efficiency Database -
Battery Charger
DESCRIPTION
The ILBLP CP10 HE SD from IOTA is a UL Listed LED emergency driver that allows the same LED
xture to be used for both normal and emergency operation. In the event of a power failure,
the ILBLP CP10 HE SD switches power from the normal AC Driver and operates the xture
for 90 minutes in the emergency mode from the unit’s battery supply. The unit contains a
battery, charger, and converter circuit is available in exed or non-ex mounting congurations for individual xture requirements. The ILBLP CP10 HE SD will operate an LED load at
10 watts with constant power at a rated output voltage of 15V-55V. The Constant Power design
of the ILBLP CP10 HE SD maintains the output wattage to the LED array even as the system voltage diminishes, providing a consistent illumination level for the full 90-minute runtime. Features
lithium battery technology for signicantly decreased form factor and includes automatic
monthly and annual self-testing features as standard.
SPECIFICATIONS
Input Voltage ..................................................................(Universal) 120-277VAC, 50/60Hz
Input Rating ..................................................................................................... .053A (max)
Output Voltage1 .................................................................... 15-55VDC Class 2 Compliant
Output Current ......................................................... 0.67A (@15VDC) - 0.18A (@55VDC)
Output Power ........................................................................................ 10 Watts (constant)
Max. AC Driver Output Current ................................................................................... 3Adc
Surge Protection ............................................................ Meets ANSI/IEEE C62.41.2-2002
Emergency Operation ....................................................................................... 90 minutes
Operating Temp ................................................................................................. 0° to 55° C
EMI ........................................................................... Complies to FCC Commercial Limits
Battery ........................................................................................... Lithium Iron-Phosphate
24 Hour Recharge
5-7 Year Life Expectancy
Weight (Conguration) ...................................................................................... 2.5 lbs. (A)
1.5 lbs (B)
Certications ..................................................... UL Listed for factory and eld installation
CA T20 Appliance Eciency Database
1
Max. output voltage in emergency mode is 58.5 VDC
with a + tolerance of 1.5 volts
DIMENSIONS
10.48″ x 2.34″ x 1.18″ (mounting center 9.92 x 1.1″)
ILBLP CP10 HE SD
Constant Power Emergency LED Driver
MODEL NO:
TYPE:
PROJECT:
COMMENTS:
LUMEN PERFORMANCE
Fixture Ecacy
100 lm/W
110 lm/W
120 lm/W
130 lm/W
PRODUCT ADVANTAGES
Constant Power Performance
Constant wattage delivery maintains illumination for the
full emergency runtime with no degradation
Minimum Mounting Footprint
Lithium battery technology signicantly decreases space
requirements without sacricing output performance
Self-Diagnostic / Self-Testing
Monthly and annual self-testing feature satises the
periodic testing requirements in accordance with NFPA
101 while the on-board diagnostics provides system
readiness with visual indicators.
Listed for Field or Factory Installation
UL Listed for both eld or factory installation in
United States and Canada
FEATURES
UL 924 Listed, UL Listed and Classied to FTBV
Auto-Sense 15-55VDC output is UL 1310 Certied,
Output Class 2 Compliant
AC-Activate circuity simplies wiring by
eliminating the need for manual battery connection
during installation
Galvanized steel case
Includes single-piece TBTS test switch and charge
indicator accessory kit
For use with switched or unswitched xtures
5-Year Warranty
Meets or exceeds all NEC, IBC, and Life Safety Code
Emergency Lighting Requirements
Certied to CA Title 20 and registered in the Modernized Appliance Eciency Database (MAEDBS)
Suitable for use in Plenum, Damp Location, and
Recessed Type IC Luminaires
RoHS Compliant
Minute 1
1000
1100
1200
1300
Minute 45
1000
1100
1200
1300
Minute 90
LED
1000
1100
1200
1300
LENGTH 10.48
1.1
MOUNTING CENTER
IOTA REV 021821
IOTA Emergency Lighting 1361 E. Wieding Road, Tucson, AZ 85706 Phone: 1-800-866-4682 E-mail: techsupport@iotaengineering.com Web: www.iotaengineering.com © 2019 Acuity Brands Lighting, Inc.
9.92
Patented. See www.iotaengineering.com/patents for details.
WIDTH 2.34
HEIGHT
1.18
Product specications are subject to change without notice
![](/html/4f/4f59/4f59cf457e7b8e33f60773881132eb6ef4a7627e4a8360e27dfbf5d27f00bcd8/bg2.png)
ILBLP CP10 HE SD
Constant Power Emergency LED Driver
ORDERING GUIDE
ILBLP CP10
Understanding Your IOTA Driver Model:
ILBLP = IOTA Emergency LED Driver with Lithium Battery Technology
CP** = Constant Power Performance at the rated wattage
HE = High eciency charging control for CA Title 20 requirements
SD = Self-diagnostic capability
HE SD
A (Dual Flex)
B (Integral Non-Flex)
FLEXIBLE CONDUIT TO
FIXTURE (24")
WIRING TO FIXTURE AND
TEST ACCESSORIES
ILBLP CP10 HE SD A
ILBLP CP10 HE SD B
FLEXIBLE CONDUIT TO
TEST ACCESSORIES (24")
ILBLP CP10 HE SD Sample Specication
Supply and install IOTA ILBLP CP10 HE SD Constant Power emergency LED driver system as indicated on the plans. The emergency driver shall be designed for [select “internal” or
“external”] mounting to the luminaire including a self-contained, high-temperature, sealed, maintenance-free lithium iron-phosphate battery rated for a 5 to 7-year service life. The
unit shall be provided complete with an illuminated push to test switch. The emergency driver system shall be UL class 2 certied in accordance with UL 1310 and shall be UL listed
for use in damp locations xtures with a temperature range of 0° to 55° C.
The AC input shall be a two-wire, universal voltage capable 120 thru 277 VAC, 50/60 Hz and be UL Listed to Category Control Number (CCN) FTBR, Emergency Lighting and Power
Equipment, and FTBV, Emergency Light-Emitting-Diode Drivers for eld installation. Maximum input power of the emergency driver shall be 0.053A.
The unit charger shall consist of a two-stage charging system which samples the battery in relation to its temperature, state of charge and input voltage uctuations. The charger
shall be current limited, temperature compensated, short-circuit protected with reverse polarity protection. A low voltage battery disconnect (LVD) circuit shall be provided and will
disconnect the load and circuitry from the battery when it reaches approximately 80 to 85% of its nominal terminal voltage, preventing a non-recoverable, deep-discharge condition
as well as equipment initialization failure when utility power is restored. The unit shall achieve a full recharge in 24-hours.
The unit shall be designed to automatically test the emergency lighting capability for no less than 30 seconds monthly and 90 minutes annually, and shall monitor battery charge and
battery discharge current and load performance. A dual-color light-emitting LED shall be provided to indicate test results and charge status.
The emergency driver shall accommodate an LED load with a forward voltage requirement ranging from 15 to 55VDC. The output voltage sensing shall be automatic and instantaneous
with a resulting, inversely-proportional current to maintain constant power to the LED array with an output tolerance of +/- 5%. The unit shall supply the rated load for a minimum of
1 1/2 hours or to 87 1/2% of rated battery terminal voltage. The output power to the LED load during emergency operation shall be held constant 10 watts from minute one throughout
the entire emergency run time resulting in no loss or degradation of the light source during emergency operation.
The unit shall be furnished with an electronic, AC-lockout circuit which will connect the battery when the branch circuit is energized, and an electronic brownout circuit which will
enable a transfer to emergency operation when utility power dips below an acceptable level.
Emergency Lumen Performance - ILBLP CP10 HE SD
Approx. Luminaire Ecacy
100 lm/W
110 lm/W
120 lm/W
130 lm/W
Minute 1
1000
1100
1200
1300
Minute 45
1000
1100
1200
1300
Minute 90
1000
1100
1200
1300
DIAGNOSTIC CODES
The charge indicator (TBTS) LED will ash RED when charging and remain lit solid GREEN
when fully charged and in the standby mode. The TBTS will ash GREEN when self-testing.
If a problem is encountered during the test cycle, the TBTS will ash RED, according to the
diagnostic codes below:
CONDITIONSTATUS INDICATION
STEADY GREEN NORMAL MODE
STEADY RED BATTERY IS CHARGING
FLASHING GREEN SELF-TESTING
OFF EMERGENCY MODE
FLASHING RED/GREEN INSUFFICIENT CHARGE
1 RED FLASH BATTERY PACK FAILURE
2 RED FLASHES EMERGENCY LAMP FAILURE
3 RED FLASHES FIXTURE DIAGNOSTIC FAILURE DETECTED
Attention: Refer to the IATA website at https://www.iata.org for air transporation requirements and
restrictions for lithium batteries and products containing lithium batteries.
Contact IOTA Customer Service to learn more about IOTA standards and best practices for the shipping, handling, and storage of IOTA lithium battery products.
The ILBLP CP10 HE SD is UL Listed and Classied for
Field Inst allation. Refe r to the “CP Series Compatibil-
ity and Suitability of Use Guidelines” addendum for
complete project installation requirements.
Warranty: 5-Year Limited Warranty
Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
IOTA REV 021821
IOTA Emergency Lighting 1361 E. Wieding Road, Tucson, AZ 85706 Phone: 1-800-866-4682 E-mail: techsupport@iotaengineering.com Web: www.iotaengineering.com © 2019 Acuity Brands Lighting, Inc.
Patented. See www.iotaengineering.com/patents for details.