I-42-L
TBTS SERIES AC
10W–42W RAPID START
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
EMERGENCY LIGHTING EQUIPMENT
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – Connect the battery to the unit before applying A.C. power.
2. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
3. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon
necting the unit connector. In addition, the circuit board should be mounted so that no live parts are accessible
dur
ing routine maintenance or relamping.
4. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
5. The I-42-L is for use with grounded, UL Listed, indoor fixtures. The acceptability of the combination must be
determined by Underwriters Laboratories. Refer to the Engineering Considerations section for proper installation.
6. T
he I-42-L and A.C. ballast must be on the same branch circuit.
7. The I-42-L requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.
lead.
8. Do not mount near gas or electric heaters.
9. The I-42-L should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
10. The I-42-L will cold strike and operate one 10W through 42W, or two 10W through 18W, 4-pin Rapid Start
compact fluorescent lamps. Contact Customer Service for additional lamp usage.
11. The I-42-L is for use with unusually shaped fluorescent fixtures such as wall packs, sconces, and recessed
stair fixtures.
12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
13. Do not use this equipment for other than intended use.
14. Install in accordance with the National Electrical Code and local regulations.
15. Installation and servicing should be performed by qualified personnel.
16. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility before
final installation.
4 PIN COMPACT LAMP
-
SAVE THESE INSTRUCTIONS
![](/html/3f/3ff7/3ff757876d71034f8e925340aac8475cd8b440128373a6bee267ec48a539a2d7/bg2.png)
Mounting
Barrier
Leave space
between boards
NOITPOPMALEPYT
YCNEGREME
NOITAREPO
TELOIV
SDAEL
1
2
3
4
10W-18W
26W-42W
18W
One Lamp
One Lamp
Two Lamp
Two Lamp
Compact
Compact
Compact
Compact
Connected
Disconnected
Connected
Disconnected
10W-13W
5
6
7
18W
24W
36W
Long
Compact
Long
Compact
Long
Compact
One Lamp
One Lamp
One Lamp
Connected
Disconnected
Disconnected
ENGINEERING CONSIDERATIONS
Use – For use only in complete equipment or final applications where the acceptability of the combination is deter-
mined by Underwriters Laboratories, Inc.
These components have been judged on the basis of the required spacings in the Standard for Emergency Lighting
and Power Equipment UL 924, Sec. 29, which covers the end use product for which the component was designed.
CONDITIONS OF ACCEPTABILITY
1. Installed in a suitable ultimate enclosure.
2. Used with marked electrical ratings.
3. Provide with proper spacing between live parts and enclosure and/or adjacent devices.
4. Factory wired only (terminations not suitable for field wiring).
5. Temperature tests may have to be repeated where battery temperature exceeds 50° C.
6. Mounted within the end-use product such that the battery is secured and the test switch operates properly
when the end product is fully assembled.
7. End-use products employing one or more of these devices are to be marked in accordance with the Standard
for Emergency Lighting and Power Equipment, UL 924.
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the I-42-L unit connector is disconnected.
1. LAMPS OPERATED
Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in the emergency mode.
If you have any questions regarding specific lamps, contact customer service.
The 6″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads
disconnected and capped. When used with particular lamp types, violet leads should be connected to one another. Refer to chart for lamp selection options.
2. MOUNTING THE I-42-L AND BATTERY
Mount the I-42-L in the ballast channel or enclosed wireway so the wire leads are not exposed, at least 1/2″ away
from the A.C. ballast(s). Mount the I-42-L using the mounting holes provided. The insulating barrier should be
mounted against the fixture wall. Then the main circuit board can be mounted leaving a space between the board
and the mounting barrier as shown in Illustration 1. The circuit board should be placed so that no live parts are accessible during routine maintenance or relamping.
The battery should be at least 1/2″ from the A.C. ballast and other heat sources. Since heat rises, try to mount the
battery as low as possible. CAUTION – Connect the battery to the unit before applying A.C. power.
Illustration 1
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
Page 2
Illustration 2 - TBTS
OBSERVE PROPER
POLARITY