IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnecting the unit connector.
3. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Re-
place the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
FLUORESCENT EMERGENCY BALLAST
4. DO NOT USE OUTDOORS. The I-26-EM-B is for use with grounded, UL Listed, damp location rated, indoor
fixtures. Not for use in heated air outlets or hazardous locations.
5. The I-26-EM-B requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. Do not mount near gas or electric heaters.
7. The I-26-EM-B should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
8. The I-26-EM-B is designed to cold strike and operate one 18W–26W, quad tube compact fluorescent lamp,
two-pin base including integral starter, with a single lampholder per lamp.
9. The I-26-EM-B is for use in fluorescent downlight fixtures.
10. Suitable for use in damp locations and in enclosed and gasketed fixtures.
11. When used in conjunction with enclosed and gasketed fixtures, the I-26-EM-B is suitable for mounting in the
ballast compartment only.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
![](/html/93/931c/931cbf4330514e5218ac97d2e8c5952117767f4d0f547e9218d0865fb3395d2b/bg2.png)
INSTALLATION INSTRUCTIONS
+ RED
LEAD
WHITE/RED
LEAD
+ RED
CAUTION: Before installing, make certain the A.C. power is off and the
I-26-EM-B unit connector is disconnected.
1. MOUNTING THE I-26-EM-B
Mount the I-26-EM-B in the ballast channel or enclosed wireway so the wire leads are not exposed, at least 1/2″
away from the A.C. ballast(s). Refer to illustrations 1 and 2.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s), ballast and I-26-EM-B. Install
in accordance with the National Electrical Code and local regulations. For additional wiring diagrams not shown,
consult Customer Service.
3. INSTALLING THE CHARGE INDICATOR
Downlight Fixture– Select a convenient location on the fixture so that the Charge Indicator can be seen after in-
stallation. Allow for proper clearance and drill or punch a 1/2″ mounting hole. Disconnect the leads from the Charge
Indicator. Push the Charge Indicator into the 1/2″ hole until it is firmly locked into place. Reconnect the leads,
observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Make certain all leads are
enclosed in an appropriate wireway. Refer to Illustrations 1 and 2.
NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-
tion Manual.
4. INSTALLING THE TEST SWITCH
Downlight Fixture– The test switch should be mounted on the fixture to allow access to authorized personnel. Drill
or punch a 1/2″ mounting hole. Make certain all leads are enclosed in an appropriate wireway. Refer to Illustration 1.
Illustration 1
Downlight Fixture
I-26-EM-B
Illustration 2
Charge Indicator
NOTE: Position the Charge Indicator so that
it can be seen after installation.
OBSERVE PROPER POLARITY