When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnecting the unit connector.
3. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Re-
place the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
FLUORESCENT EMERGENCY BALLAST
4. DO NOT USE OUTDOORS. The I-26-EM-B is for use with grounded, UL Listed, damp location rated, indoor
fixtures. Not for use in heated air outlets or hazardous locations.
5. The I-26-EM-B requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. Do not mount near gas or electric heaters.
7. The I-26-EM-B should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
8. The I-26-EM-B is designed to cold strike and operate one 18W–26W, quad tube compact fluorescent lamp,
two-pin base including integral starter, with a single lampholder per lamp.
9. The I-26-EM-B is for use in fluorescent downlight fixtures.
10. Suitable for use in damp locations and in enclosed and gasketed fixtures.
11. When used in conjunction with enclosed and gasketed fixtures, the I-26-EM-B is suitable for mounting in the
ballast compartment only.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
+ RED
LEAD
WHITE/RED
LEAD
+ RED
CAUTION: Before installing, make certain the A.C. power is off and the
I-26-EM-B unit connector is disconnected.
1. MOUNTING THE I-26-EM-B
Mount the I-26-EM-B in the ballast channel or enclosed wireway so the wire leads are not exposed, at least 1/2″
away from the A.C. ballast(s). Refer to illustrations 1 and 2.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s), ballast and I-26-EM-B. Install
in accordance with the National Electrical Code and local regulations. For additional wiring diagrams not shown,
consult Customer Service.
3. INSTALLING THE CHARGE INDICATOR
Downlight Fixture– Select a convenient location on the fixture so that the Charge Indicator can be seen after in-
stallation. Allow for proper clearance and drill or punch a 1/2″ mounting hole. Disconnect the leads from the Charge Indicator. Push the Charge Indicator into the 1/2″ hole until it is firmly locked into place. Reconnect the leads,
observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Make certain all leads are
enclosed in an appropriate wireway. Refer to Illustrations 1 and 2.
NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-
tion Manual.
4. INSTALLING THE TEST SWITCH
Downlight Fixture– The test switch should be mounted on the fixture to allow access to authorized personnel. Drill
or punch a 1/2″ mounting hole. Make certain all leads are enclosed in an appropriate wireway. Refer to Illustration 1.
Illustration 1
Downlight Fixture
I-26-EM-B
Illustration 2
Charge Indicator
NOTE: Position the Charge Indicator so that
it can be seen after installation.
OBSERVE PROPER POLARITY
Page 2
5. LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for
lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.
6. COMPLETING INSTALLATION
A. When the wiring is complete, the A.C. power is to be turned on permanently, join the unit connector.
B. Replace the ballast cover, fixture lens and other fixture hardware.
C. Refer to the “Operation” section below for proper operation.
OPERATION
General —The I-26-EM-B is a compact fluorescent emergency ballast. The I-26-EM-B is to be used with U.L. Listed
fluorescent fixtures. When used with fluorescent downlight fixtures, the I-26-EM-B will wire in conjunction with the existing lamp(s) to provide the emergency function.
Normal Mode – A.C. power is present. The A.C. ballast(s) operate the fluorescent lamp(s) as intended. The
I-26-EM-B is in the standby charging mode. The Charge Indicator will be lit providing a visual indication that
the battery is being charged.
Emergency Mode – The A.C. power fails. The I-26-EM-B senses the A.C. power failure and automatically switches to
the Emergency Mode. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power
is restored, the I-26-EM-B switches the system back to the Normal Mode and resumes battery charging. See page 1 of
the Instruction Manual.
TESTING & MAINTENANCE
Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour
charge before conducting a one hour test.
The I-26-EM-B is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety
Code, outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. One lamp should operate at reduced output.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 11/2 hour discharge test. The unit should
operate as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
Page 3
BLK (120V)
SWITCHED OR
ONE LAMP MAGNETIC BALLAST
TYPICAL WIRING DIAGRAMS
SWITCHED OR
ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST
BLK (120V)
ONE LAMP ELECTRONIC BALLAST
BLK (120V)
TWO LAMP ELECTRONIC BALLAST
INSTRUCTIONS FOR PROPER POLARITY WIRING.
SWITCHED OR
TWO LAMP PARALLEL MAGNETIC BALLAST
SWITCHED OR
TWO LAMP PARALLEL HIGH POWER FACTOR MAGNETIC BALLAST
SWITCHED OR
TWO LAMP SERIES MAGNETIC BALLAST
SWITCHED OR
TWO LAMP SERIES HIGH POWER FACTOR MAGNETIC BALLAST
For use with 2 pin, 26 watt lamps with integral starter only
Wiring and Troubleshooting Tips are available on-line at http://www.iotaengineering.com/wiringtips.pdf
1. ONE LAMP MAGNETIC BALLAST
UNSWITCHED LINE
COMMON
UNSWITCHED
LINE
TEST
SWITCH
A.C.
BALLAST
BLUEBLACK
ORG (277V)
➀
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
*LAMP
*AC/EMERGENCY LAMP
I-26-EM-B
SERIES D
➀
➁
➂
3. ONE LAMP ELECTRONIC BALLAST
UNSWITCHED LINE
COMMON
WHITE
BLACK
SWITCHED OR
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
TEST
RED
BLUE
*LAMP
➀
ORG (277V)
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
EMERGENCY
I-26-EM-B
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED OR
➂
EMERGENCY
BALLAST
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
BALLAST
RED/BLK (+)
WHT/RED
WHT/BLK
WHT/BLK
RED OR
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
FIXTURE
GROUND
➁
UNIT
CONNECTOR
➂
INDICATOR
➁
UNIT
CONNECTOR
CHARGE
INDICATOR
CHARGE
2. ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST
*LAMP
➀
BLK (120V)
ORG (277V)
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
RED OR
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➁
UNIT
CONNECTOR
➂
CHARGE
INDICATOR
UNSWITCHED LINE
COMMON
WHITE
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
TEST
BLUEBLACK
4. TWO LAMP ELECTRONIC BALLAST
UNSWITCHED LINE
COMMON
WHITE
BLACK
SWITCHED OR
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
WHT
BLACK
TEST
BLACK
WHITE
➀
ORG (277V)
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
*LAMPLAMP
*AC/EMERGENCY LAMP
RED OR
➂
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➁
CONNECTOR
INDICATOR
UNIT
CHARGE
5. TWO LAMP PARALLEL MAGNETIC BALLAST
UNSWITCHED LINE
COMMON
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
RED
TEST
BLUEBLACK
*AC/EMERGENCY LAMP
BLK (120V)
ORG (277V)
➀
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
*LAMPLAMP
7. TWO LAMP SERIES MAGNETIC BALLAST
*LAMPLAMP
➀
BLK (120V)
ORG (277V)
WHITE
BLUE
BLUE/WHT
YELLOW
YEL/BLK
UNSWITCHED LINE
COMMON
BLACK
UNSWITCHED
LINE
A.C.
BALLAST
TEST
SWITCH
BLUE
WHT
*AC/EMERGENCY LAMP
RED OR
➂
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
RED OR
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➁
UNIT
CONNECTOR
➂
➁
CONNECTOR
INDICATOR
INDICATOR
UNIT
CHARGE
CHARGE
6. TWO LAMP PARALLEL HIGH POWER FACTOR MAGNETIC BALLAST
UNSWITCHED LINE
COMMON
WHITE
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
BLUE
TEST
BLUEBLACK
*AC/EMERGENCY LAMP
BLK (120V)
ORG (277V)
➀
WHITE
BLUE/WHT
YELLOW
YEL/BLK
*LAMPLAMP
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
BLUE
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED OR
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➂
CHARGE
INDICATOR
➁
UNIT
CONNECTOR
8. TWO LAMP SERIES HIGH POWER FACTOR MAGNETIC BALLAST
*LAMP
➀
BLK (120V)
ORG (277V)
WHITE
BLUE/WHT
BLUEBLUEBLACK
YELLOW
YEL/BLK
RED OR
➂
EMERGENCY
I-26-EM-B
BALLAST
SERIES D
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
➁
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➂
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➁
UNIT
CONNECTOR
CHARGE
INDICATOR
UNSWITCHED LINE
COMMON
WHITE
UNSWITCHED
LINE
SWITCH
A.C.
BALLAST
RED
TEST
LAMP
*AC/EMERGENCY LAMP
Rev. 071513
68326-202
Page 4
SWITCHED OR
TWO NORMAL POWER FACTOR MAGNETIC BALLASTS
TYPICAL WIRING DIAGRAMS
TWO HIGH POWER FACTOR MAGNETIC BALLASTS
For use with 2 pin, 18 through 26 watt lamps with integral starter only.
Wiring and Troubleshooting Tips are available on-line at http://www.iotaengineering.com/wiringtips.pdf
9. TWO NORMAL POWER FACTOR MAGNETIC BALLASTS
➀
BLK (120V)
ORG (277V)
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
UNSWITCHED
LINE
UNSWITCHED LINE
COMMON
BLACK
A.C.
BALLAST
#1
TEST
SWITCH
BLUE
EMERGENCY
I-26-EM-B
SERIES D
BALLAST
RED OR
RED/BLK (+)
WHT/RED
FIXTURE
GROUND
WHT/BLK
WHT/BLK
➂
CHARGE
INDICATOR
➁
UNIT
CONNECTOR
BLACK
A.C.
BALLAST
#2
BLUE
*LAMPLAMP
➀
➁
➂
10. TWO HIGH POWER FACTOR MAGNETIC BALLASTS
➀
BLK (120V)
ORG (277V)
WHITE
BLUE/WHT
BLUE
YELLOW
YEL/BLK
➀
➁
SWITCHED OR
UNSWITCHED
LINE
UNSWITCHED LINE
COMMON
WHITE
A.C.
BLACK
BALLAST
#1
BLACK
WHITE
A.C.
BALLAST
#2
TEST
SWITCH
BLUE
BLUE
*LAMPLAMP
➂
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED OR
EMERGENCY
I-26-EM-B
SERIES D
BALLAST
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
RED/BLK (+)
WHT/RED
WHT/BLK
WHT/BLK
➂
FIXTURE
GROUND
➁
UNIT
CONNECTOR
CHARGE
INDICATOR
Rev. 071513
68326-202
Page 5