IOTA I-13-EM-A User Manual

I-13-EM-A
SERIES D
COMPACT LAMP
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon necting the unit connector.
3. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
EMERGENCY
LIGHTING EQUIPMENT
-
4. DO NOT USE OUTDOORS. The I-13-EM-A is for use with grounded, UL Listed, damp location rated, indoor fixtures. Not for use in heated air outlets or hazardous locations.
5. The I-13-EM-A requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6. The I-13-EM-A and A.C. ballast must be on the same branch circuit.
7. Do not mount near gas or electric heaters.
8. The I-13-EM-A should be mounted in locations and at heights where it will not readily be subjected to tamper ing by unauthorized personnel.
9. The I-13-EM-A will cold strike and operate one 5W, 7W, or 9W, twin tube, double twin tube, 180ma or 13W twin tube, double twin tube, 285ma fluorescent lamp, each with a single lampholder per lamp.
10. The I-13-EM-A is for use with fluorescent downlight fixtures.
11. Suitable for use in damp locations.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void warranty, and result in non-compliance with UL specifications.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before final installation.
-
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
FLEX “A”
JUNCTION
BOX
CEILING
TILE
A.C. BALLAST & LAMP SOCKET COMPARTMENT
FLEX “B”
SWITCH BOX
TEST SWITCH
CHARGE LIGHT
CAUTION: Before installing, make certain the A.C. power is off and the I-13-EM-A unit connector is disconnected.
1. MOUNTING THE I-13-EM-A
When used with ceiling mounted downlight fixtures, the I-13-EM-A should be mounted on the fixture above the
ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction box on the fixture which allows access to the ballast/lamp connections. Refer to Illustration 1 for typical mounting.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
2. MOUNTING THE TEST SWITCH AND CHARGE INDICATOR LIGHT
Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the I-13-EM-A flex
marked “B”. After mounting the switch box, connect flex “B” to the box and route all leads inside the box. Refer to Illustration 1 for typical mounting. Connect the leads to the components as follows:
Red/Black or Red lead w/connector (+) Charge light terminal
Wht/Red lead (–) Charge light terminal White Test switch *Wht/Blk lead Unit connector White/Black *Wht/Blk lead Unit connector
* To prevent electrical shock and unintentional battery discharge, do not join the unit connector until the installation
is complete.
NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-
tion Manual.
3. WIRING
A. The I-13-EM-A and A.C. ballast must be on the same branch circuit.
B. The I-13-EM-A requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used
Illustration 1
Downlight Fixture
I-13-EM-A
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.