2. Risk of electrical shock. Connect only to a properly grounded, three pronged grounding type receptacle. Under any circumstances, do not remove the grounding prong from the power cord.
3. Do not smoke, use sparkable electrical devices
or open ame when working on this unit!
4. Do not install Unit in locations classied as hazardous per N.E.C., ANSI/NFPA 70 - 2014.
FAILURE TO HEED ABOVE CAUTIONS COULD RESULT IN INJURY OR DEATH.
The Sumpro® is designed to operate a load up to 12 Amps. If operating more than one pump, the combined FLA cannot exceed 12 Amps.
Important Safety Instructions
Reasonable care and safe methods should be practiced. Check local codes and requirements before installation. This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for continued safe product use.
Note: This manual covers the installation of the inverter, regardless of what pump, switch or controller combination is included in the system you purchased. For more detailed installation information and troubleshooting regarding the pump, switch or controller, please refer to their individual manuals.
DO NOT THROW AWAY OR LOSE THIS MANUAL. Keep it in a safe place so that you may refer to it when needed.
Warning
WARNING: Always disconnect the Unit from
the receptacle power source and battery before handling or making any adjustments to the system.
Battery Backup Warning:
1. Risk of electrical shock this Unit has not been investigated for use in outdoor areas.
Before proceeding further, please review the safety instructions carefully.
General Precautions:
• Before using the inverter read all instructions and caution markings on the inverter, the batteries & all appropriate sections of this instruction manual.
• Do not expose the inverter to any type of chemicals. The inverter is designed for interior use only.
• Do not disassemble the inverter; contact Metropolitan Industries Wholesale Customer Support at (800) 323-1665 when service or
repair is required. Opening by unqualied personnel can lead to electrical shock or re
hazard and void the warranty.
• To reduce risk of electric shock, disconnect all wiring before cleaning.
WARNING: Avoid exposing the inverter or
batteries to any type of explosive gases, as batteries generate explosive gases during normal operation. Install the batteries in a well ventilated area.
To reduce the risk of battery explosion, follow all the instructions of the battery supplier or any equipment you intend to use in the vicinity of batteries.
www.ionproducts.net
Page 2
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 2 of 12
• Use the correct insulated tools to make AC/DC wiring connections.
• Do not install this inverter on or near ammable materials (plywood, chemicals, gas line etc.)
CAUTION: Personal Precautions:
• Someone should be within the range of your voice to come to your aid when you work near batteries.
• Have plenty of fresh water and soap nearby in the event that battery acid contacts skin, clothing or eyes.
• Wear complete eye, skin and clothing protection.
• Avoid touching eyes while working near batteries. Wash your hands when done.
• If battery acid comes in contact with skin or clothing, wash immediately with soap and water.
Knowing Your Inverter
CAUTION: The electrolyte is a dilute sulfuric
acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures should be observed:
a. If electrolyte contacts the skin, wash it o󰀨
immediately.
b. If electrolyte contacts the eyes, ush
thoroughly and immediately with water. Seek medical attention.
c. Spilled electrolyte should be washed down
with a suitable acid neutralizing agent. A common practice is to use a solution of approximately one pound (500 grams) bicarbonate of soda to approximately one gallon (4 liters) of water. The bicarbonate of soda solution should be added until the evidence of reaction (foaming) has ceased.
The resulting liquid should be ushed with
water and the area dried.
CAUTION: Do not reverse the battery
connections, as it will blow the battery fuse. A power cord has been provided to connect the inverter to incoming AC wall outlet.
In its most basic form, an Inverter transforms Direct Current (DC) to Alternating Current (AC). The battery pack acts as reserve power to ensure continuous supply of power whenever electrical supply from utility power is not available. The inverter is used to charge the batteries when normal utility power is available and converts the battery’s DC to AC voltage to run the pump when utility power is lost.
Battery Safety
CAUTION: Do not dispose of batteries in a
re. The battery may explode.
CAUTION: A battery can present a risk of
severe burn and injury from high short circuit current. The following precautions should be observed when working on batteries.
CAUTION: Do not open or mutilate the
battery. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Battery Requirements
Your Unit operates on 24 volt DC battery power when in the power fail mode. Two UL recognized deep cycle marine batteries should be used. There are two principal types of batteries: starting and deep
cycle. There are several di󰀨erent types of battery
constitutions including liquid lead acid, nickel iron, nickel cadmium, alkaline and maintenance free. Batteries are sealed or vented.
NOTE: All batteries must be the same make, model, and age for the inverter to function properly.
Starting Batteries (NOT RECOMMENDED)
Starting batteries are designed for high cranking power but not deep cycling. DO NOT use them with
your inverter. They do not a󰀨ect the inverter, but they
will simply not last long in a deep cycle application. They use a lot of thin plates to maximize the surface area of the battery. This allows very high starting current but less run time when the battery is cycled.
www.ionproducts.net
Page 3
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 3 of 12
Deep Cycle Batteries (RECOMMENDED)
Deep Cycle batteries, also known as marine batteries, are best suited for use with the inverter. They are designed to have the majority of their capacity used before recharge. Available in many sizes and types, be sure to use at least a 100 AH battery.
BATTERIES NOT INCLUDED
Tools Needed
An insulated adjustable wrench will be needed.
Installation
The Sumpro® unit is packaged in two separate cartons containing one complete unit and a fuse link. Below are the contents.
Fuse Link
PN: A0000702i7
reach of the power cord. When fully assembled, the head unit with batteries weighs appoximately 200 lbs. It is recommended to use the optional Sumpro®
stand to keep the unit o󰀨 the oor. A dedicated 15A
receptacle circuit is recommended.
3. Assembly
Set the battery box in place, making sure that the openings will be facing the back of the head unit. Once in place, place the head unit in front of the battery box feeding the battery leads through the large holes in the front of the battery box.
4. Battery Installation
Now that the unit has been properly assembled and in its permanent location the batteries can be installed.
Note: If the battery post conguration di󰀨ers from that
shown on Page 4, Figure A, additional post adapters may be required.
CAUTION: Important Safety Instructions
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries.
Sumpro® Head Unit
PN: iS20281
®
Sumpro
See accompanying unit assembly drawings.
1. Unpack The Sumpro
Your Sumpro® auxiliary power supply should be in two separate containers. Remove the contents from the containers. They should include the head unit, the battery box and the fuse link (located inside the battery box).
Open the lid on the battery enclosure and remove the fuse link from inside.
2. Location
Find a suitable place to set the unit (when it is assembled). Keep in mind that the unit should be placed in an area where water and moisture will not splash or drip on the unit, the fan inlet on the front of the head unit will not be obstructed, and where a properly grounded three prong receptacle is within
Battery Box
PN: iB20386
®
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal objects on top of batteries.
4. Wear safety goggles and a face shield.
After taking the above precautions, secure the battery box to the head unit using the screws provided. Lower the two 12V batteries into the battery box with the terminals facing each other. At this time check the polarity of your batteries. Facing the front of the Sumpro® unit, the left battery terminal should be positive, and the right negative (See Page 4, Figure A). If this is not the case, DO NOT continue until the proper batteries can be obtained.
5. CONNECTING BATTERIES
Now that the batteries have been installed, and the polarity conforms to the Sumpro®, connect the fuse link across the back battery terminals (See Page 4, Detail A). Remove the protective cover from the negative (-) battery lead (black) then connect it to the negative (-) post of the battery. Screw down bolt tightly.
www.ionproducts.net
Page 4
Figure A
Ion Technologies Sumpro
Battery Back-Up
BATTERY BOX
MOUNTING SCREWS
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 4 of 12
ALTERNATIVE DC INPUT ACCESS COVER
POSITIVE BATTERY LEAD AND TERMINAL
FUSE LINK
NEGATIVE BATTERY
LEAD AND TERMINAL
Detail A
POSITIVE TERMINAL
A
NEGATIVE TERMINAL
www.ionproducts.net
Page 5
Ion Technologies Sumpro
Battery Back-Up
Figure B
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 5 of 12
BATTERY BOX LID SCREW ONE THIS SIDE AND ONE OPPOSITE SIDE
Figure C
DC1 TERMINALS DC2 TERMINALS 6P6C/RJ11 JACK
REMOVE KNOCKOUT
INSTALL FLEXIBLE
METAL CONDUIT
Plug the Sumpro® unit into the designated 115V AC outlet.
6. Within 30 seconds, remove the protective cover from the positive (+) red battery lead then connect it to the positive (+) post.
Note: Make sure all battery connections are properly tightened to 75 pound inches.
7. Close Unit
instructions in the controller manual. The controller will be plugged into the Sumpro® instead of the wall outlet.
If connecting a home alarm system to the Sumpro®, make the connection to the 6P6C/RJ11 jack labeled “ALARM CONTACT”. The center most pins (#3 and
4) are used for this circuit, and are normally closed (N/C) under normal conditions. These pins electrically open in a Sumpro® alarm condition.
Close and secure the battery enclosure lid using the screws provided, so that children cannot tamper with the unit (See Page 5, Figure B).
8. Plug In The Pump
At this time you may plug your 115V pump into your Sumpro® unit, not exceeding the load limit of 12 amps or 1440 watts at any one time.
Note: If connecting a pump controller, such as the Ion Genesis or Ion Endeavor, follow the installation
www.ionproducts.net
Alternative DC Input Connections
The alternative DC inputs provide an alternate means of charging the batteries via power source(s), not included. When an alternative DC source is connected to the Sumpro, it will charge the batteries if the generated power is greater than the battery voltage, whether or not AC power is available. If two alternative DC power sources are connected at the same time, the Sumpro utilizes the one generating the most power.
Page 6
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 6 of 12
Please read the following instructions carefully before attempting to connect an alternative DC source.
1. There are two sets of alternative DC input terminals located on the top left side of the Sumpro, DC1 and DC2. Open access cover and remove the conduit knockout that corresponds to the terminals you are going to connect to (See Page 5, Figure C).
2. Connect conduit to the head unit (See Page 5, Figure C). Check local codes for conduit requirements.
3. Run the wires from the alternative DC source and connect the positive (+) wire to the positive (+) DC terminal and the negative (-) wire to the negative (-) DC terminal.
NOTE: It doesn’t matter which DC input is utilized, but insure that the positive (+) and negative (-) wires from the alternative DC source are connected to the same set of DC terminals, i.e., if using DC2 terminals, the positive and negative wires from the alternative DC source must be connected to the positive and negative terminals of DC2.
4. Put access cover back on the head unit.
a. Blinks when alarm condition occurs and
silence has NOT been pressed
b. Solid when alarm condition occurs and
silence has been pressed c. O󰀨 when no alarm condition is present d. Alarm Contact – NC dry contact
i. Opens when either the Inverter LED or
Alarm LED are blinking
4. LCD Display - Displays all info that pertains to current operating condition of the unit
Testing the System
To test the Sumpro®, simply unplug it from the 115V AC power to run your pump on battery power for a short time. You can repeat this if you wish, but it is not necessary. If your Sumpro time it is sure to work time and time again. Be sure
that you remember to plug the unit back into the receptacle after you have completed the test.
Note: New batteries are rarely fully charged.
Depending on the charge condition of the batteries and the voltage from the utility company, it may take up to 7 days for the batteries to be fully charged.
®
unit works the rst
Light and Relay Functions
After you have your Sumpro® unit in operation, you can check its status by looking at the system lights. They should tell you everything you need to know about the status of the unit.
1. Power – Green LED a. Solid when AC Line In Voltage is deemed
present.
b. O󰀨 when AC Line In fault occurs.
2. Inverter – Red LED a. Blinks when unit is running o󰀨 inverter and
silence has NOT been pressed.
b. Solid when unit is running o󰀨 inverter and
silence has been pressed.
c. O󰀨 when unit is operating o󰀨 of AC Line
3. Alarm – Red LED
Sumpro® Maintenance
Your Sumpro® unit has been designed to be virtually maintenance free. Just make sure it is kept clean and dry and that the unit is periodically tested in the auxiliary mode.
Battery Maintenance
If you are using AGM maintenance free batteries, you should visually inspect the batteries every six months for swelling or leakage. For all other batteries, refer to the manufacturer recommended battery maintenance section of the battery being used.
Maintenance or replacement of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
www.ionproducts.net
Page 7
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 7 of 12
Replacing Batteries
Wear full eye protection and protective clothing. When replacing the batteries, use the same type and
size batteries. See battery requirements (Page 2).
CAUTION: The electrolyte is a dilute sulfuric
acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures should be observed:
• Do not lay tools or metal objects on top of the
batteries
• Use tools with insulated handles
1. Unplug the unit from the wall.
2. Follow the Installation Instructions found on page 3 of this manual, starting with step 8 and working back to step 1.
3. Remove and safely dispose of old batteries.
4. Install new batteries per the installation instructions on page 3.
100
90
80
70
60
50
40
30
20
10
Duty Cycle (% of time running)
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 20 25 30
Reserve Power (total hours of operation)
Performance curve results using a 3/4 HP pump with a 7.5 FLA and (2) Metropolitan Power Plus model 31P-36 batteries.
Warranty Is Void If...
1. Power cord has been cut or the grounding prong has been removed.
2. Unit has been used in an outdoor application.
3. Batteries not meeting the above specications have been used.
4. Unit has been submerged in water.
Technical Specifications
Model 100
A.C. Lower Voltage Limit 98 VAC ± 5V
Output Voltage with Full Load 85-135V ± 10V
Maximum Output Current 12 FLA
Battery Lower Voltage Limit 18.5V ± 0.3V
Main Output Frequency 60 Hz
Overload 125 ± 3% (With Auto
Reset Function)
Alarm Contact RJ11 Connection,
Normally Closed Dry Contact
Alternative DC Inputs 24VDC, 20A max
5. Unit has been tampered with in any manner not described in the above instructions.
6. Unit has been disassembled by the customer.
7. Unit has been applied to products exceeding the maximum capacity of the Unit, i.e., a pump other than the one supplied with the unit or more than one pump.
8. Unit has been applied to the wrong voltage.
9. Any labels or cord tags have been removed.
www.ionproducts.net
Page 8
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 8 of 12
Troubleshooting
Please read the following before calling in for technical support as these are the most common, and easiest to rectify, issues that may occur with your Sumpro® unit.
System says that the batteries are too low
1. Check the age of the batteries. a. We recommend that batteries be
replaced every 3 years to insure optimum performance
b. Batteries must be the same age, make and
model in order for the Sumpro® to function properly.
2. If using a wet battery, check water levels.
Normal Operation LCD Displays
LCD Display Description Remedy
1
Sumpro Status
The unit is operating o󰀨 of AC Line
power and is functioning normally.
NORMAL
3. Clean all battery connections and leads with a wire brush or sand paper. Even new batteries could have a slight coating on the connections that could cause issues. Ensure that battery terminal screws are tightened to 75 pound inches.
4. Check fuse link for blown fuses.
The system is stuck in a fault that won’t clear
1. Reboot the system
a. While in AC mode, disconnect the positive
(+) red wire from the battery terminal b. Unplug the Sumpro® from the wall outlet c. Wait a few minutes and plug the Sumpro®
back into the wall outlet d. Within 30 seconds, reconnect the positive
(+) red wire to the battery terminal
Normal
2
Sumpro Status
The unit is in DC mode and running
o󰀨 of power provided by attached
batteries.
Normal
BATTERY BACKUP
3
The unit is charging the batteries. Normal
Sumpro Status
BATTERY CHARGING
4
Input Voltage
The input voltage when running o󰀨
of AC power from the utility.
Normal
120V
5
Battery Current
Current going to the batteries during charging.
Normal
15.0 A
6
Output Current
Current going to the connected load while in DC mode.
Normal
5.0 A
www.ionproducts.net
Page 9
Ion Technologies Sumpro
Battery Back-Up
LCD Display Description Remedy
7
Battery Voltage
26.7 V
®
Battery voltage when batteries are deemed present.
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 9 of 12
Normal
8
Battery Capacity
91%
Battery capacity when batteries are deemed present. Capacity is calculated based on battery voltage alone. While inverting, the battery capacity can drop 15-20% when load is connected and running.
Normal
Alarm & Fault Code LCD Displays
Below are the most common alarms and faults. For a complete list of LCD display alarms and faults, please refer to the separate Sumpro
1
Batteries Not
2
AC Input Voltage
®
Troubleshooting Guide on our web site.
LCD Display Description Remedy
Installed
LOST
The unit will detect that batteries are connected by installing fully charged
batteries or if it draws su󰀩cient
current while charging.
The unit has detected a loss of AC power from the utility and has switched to DC mode.
Install batteries of the same age, make and model. Once the unit detects that batteries are present, the unit will always assume batteries are connected unless the unit is completely
powered o󰀨.
The unit must detect good AC voltage before switching back to AC mode.
3
AC Input Voltage
UNDERVOLTAGE
4
AC Input Voltage
OVERVOLTAGE
5
Invert Lock OFF:
10 S
6
Charge Lock OFF:
10 S
www.ionproducts.net
The unit has detected an undervoltage condition and has switched to DC mode.
The unit has detected an overvoltage condition and has switched to DC mode.
The unit has suspended DC mode because of a fault condition. The display shows time left before DC mode will resume.
The unit has suspended battery charging because of a fault condition. The display shows time left before charging start timer can begin.
The unit must detect good AC voltage before switching back to AC mode.
The unit must detect good AC voltage before switching back to AC mode.
DC mode will resume after the time expires.
Battery charging will resume after the timer expires.
Page 10
Ion Technologies Sumpro
Battery Back-Up
LCD Display Description Remedy
7
Cool Lock OFF:
10 S
8
Fault Lock OFF:
10 S
9
Sumpro Status
INVERT SUSPENDED
®
The unit has suspended battery charging because it needs to cool
o󰀨 for a period of time. The display
shows time left before charging start timer can begin.
The unit has entered into a fault condition and has suspended all operations. The display shows time left before operations can begin again.
The unit has stopped DC mode due to a fault condition. Subsequent screens will state info regarding suspension.
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 10 of 12
Battery charging will resume after the timer expires.
Normal operation will resume after the timer expires.
The underlying fault condition must clear and the related lock timer must elapse.
10
Sumpro Status
FAULTED
The unit has detected a fault condition and has stopped all operations until condition clears and/or necessary time has elapsed since fault.
The underlying fault condition must clear and the related lock timer must elapse.
www.ionproducts.net
Page 11
Ion Technologies Sumpro
Battery Back-Up
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
Page 11 of 12
Warranty Registration Card
Please ll out and send back to: Metropolitan Ind. Warranty Department P.O. Box 7266 Romeoville, IL 60446. Or
to register online, go to www.ionproducts.net
Sumpro® Warranty Registration Card
To register your purchase, please ll in the following information:
Name:
Address:
City
Purchased From:
Serial Number*:
Installed By:
* The serial number is located next to the auxiliary inputs.
Date:
State: Zip:
Phone:
www.ionproducts.net
Page 12
Ion Technologies Sumpro
Battery Back-Up
1. Coverage and Term. Metropolitan Industries, Inc. (“Metropolitan”) warrants to the original purchaser (the “Buyer”) of each Ion® product (the “product”), that any part thereof which proves to be defective in material or workmanship within three (3) years from date of manufacture, will be replaced at no charge with a new or remanufactured part, F.O.B. factory. Buyer shall be responsible for all freight charges
and all costs of fi eld labor or other charges incurred in the removal and/or reinstallation of any product, part
or component thereof.
2. Exclusions. THE WARRANTY IS SUBJECT TO THE FOLLOWING CONDITIONS AND
EXCLUSIONS:
(a) The Warranty excludes products or workmanship which becomes defective as a result
of: (i) earthquake, fi re, storms, the elements or any other acts of God; (ii) normal wear and tear from use; (iii) accident, misuse, abuse or neglect; (iv) modifi cations made by Buyer or any third party, other than Metropolitan; and (v) Buyer’s failure to properly install, maintain, service and/or operate the product under normal conditions and according to manufacturer’s instructions.
(b) Metropolitan shall not be responsible for, and the Warranty shall not cover, extended damage which occurs because of Buyer’s failure to notify Metropolitan promptly in writing of apparent defects. (c) Any part or component designated as manufactured by anyone other than Metropolitan shall be covered only by the express warranty of the manufacturer thereof.
(d) The Warranty shall lapse upon Buyer’s failure to fully comply with the terms and conditions of its contract with Metropolitan, including Buyer’s failure to pay the purchase price for the product or any portion thereof. Buyer’s subsequent compliance with the terms and conditions of any such contract, will not
cause the term of the Warranty to extend beyond the time period set forth above. (e) No actions taken by Metropolitan to correct a defect in a product shall extend the Warranty beyond the period set forth above. Metropolitan shall not be obligated to remedy any defect, where otherwise
required pursuant to the Warranty unless and until Buyer notifi es Metropolitan in writing of the defect and then only if such notifi cation is made prior to the expiration of the period set forth above.
3. Process of Claims and Repairs. Metropolitan agrees that if the product or any part or component thereof shall fail to conform to the terms of this Warranty, Metropolitan shall replace such nonconforming product, part or component at the original point of delivery and furnish instruction for its disposition. Any
transportation charges involved in such disposition and all costs of fi eld labor or other charges incurred in the removal and/or reinstallation of any product, part or component thereof shall be the responsibility of Buyer.
4. Limitation on Liability. Notwithstanding any provision to the contrary, Metropolitan’s entire
liability under this Warranty shall not in the aggregate exceed, and Buyer’s exclusive and sole remedies
are, to the extent permitted by law, shall be to secure replacement of the defective product. UNDER NO CIRCUMSTANCES SHALL METROPOLITAN BE LIABLE UNDER THE WARRANTY FOR ANY INDIRECT, PUNITIVE, SPECIAL, EXEMPLARY, CONSEQUENTIAL OR INCIDENTAL DAMAGES (INCLUDING LOST PROFITS, REVENUE, USE OR ECONOMIC ADVANTAGE).
5. Express Waiver of Any Other Warranties. THE EXPRESS WARRANTY SET FORTH IN THIS WRITTEN W ARRANTY IS THE ONL Y W ARRANTY MADE BY METROPOLIT AN, OR ANY OTHER PARTY, IN CONNECTION WITH ANY PRODUCT PURCHASED FROM METROPOLITAN. NEITHER METROPOLITAN, NOR ANY OTHER PARTY, MAKES ANY OTHER EXPRESS OR IMPLIED WARRANTY WHICH IS NOT SET FORTH HEREIN, AND METROPOLITAN HEREBY DISCLAIMS AND BUYER HEREBY WAIVES ALL IMPLIED WARRANTIES, INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
6. Not Transferable. The Warranty may not be transferred and shall be void on the sale or other transfer of the product.
7. Products and Warranty Subject to Change. Metropolitan reserves the right to make revisions to its
products and their specifi cations, and to revise this Warranty and related information without notice.
®
OPERATION MANUAL
Dated: 08/18/2017 Document Name: SUMPRO_100_OM
3 Year Residential W arranty
Page 12 of 12
www.ionproducts.net