iO HVAC Controls ZP2-HC-ESP Installation And Operation Instructions Manual

ZP2-HC-ESP Installation and Operation Instructions
1 Heat / 1 Cool - Auto Changeover
First Call Priority - Time Share
with Integrated ESP Static Pressure Module
3AMP
SPEED UP
3= 1SEC MIN
ON
. . .
OFF
ON
. . .
OFF
1 2
3AMP
OVERVIEW:
The ZP2-HC-ESP is a residential/light commercial zone control panel that includes integrated ESP static pressure control logic designed to eliminate the need for a conventional bypass damper when used with 3-wire zone dampers.
SEQUENCE OF OPERATION:
The panel allows a single HVAC unit to have up to two separate zones. Each zone is controlled by its own thermostat. When a zone thermostat calls for heating or cooling, the zone not calling will have its dampers powered closed, and the zone calling will have its dampers powered opened. The heating or cooling equipment will also be brought on. As zone dampers open and close, the ZPA-SPS Static Pressure Sensor continuously monitors the system static pressure. If the static pressure goes above the static pressure setpoint, the panel will send a signal to the non-calling zone damper to start to open to a point where the static pressure setpoint is maintained. The SPS LED will come on with the non-calling zone LED until the static pressure reaches setpoint. The small amount of air allowed to bleed into non­calling zone eliminates air noise and assures proper airflow through the HVAC system. This also prevents coil freeze up and high temperature issues. When all calls are
satisfied, all zone dampers will go to the full open position provided none of the thermostats are calling for ventilation mode. If opposite calls take place, the first zone to call receives priority. When the first call is satisfied, the system will changeover and take care of the opposite call. If zones being served (heating or cooling) have not been satisfied within 20 minutes while an opposite call is taking place, the system will changeover. When the zone is satisfied or 20 minutes has elapsed, the system will again changeover if an opposite call exists. This is referred to as Auto­Changeover - First Call Priority - Time Share. In the event of a tie, cooling will receive priority.
HIGH AND LOW LIMIT PROTECTION:
A ZPA-DTS Discharge Temperature Sensor should be mounted on the discharge air plenum of the HVAC unit and wired to the DA terminals on the panel. The sensor is used for both high (adjustable) and low (fixed) limit protection. The high limit setting can be adjusted using the two slide switches located on the panel. (See switch location and settings on page 2) Low limit is fixed at 45° F. When the discharge air temperature rises above the high limit setting or falls below the low limit setting, the panel will cycle the equipment off while the fan continues to run. The LIMIT LED blinks when high or low limit is reached. In cooling mode, a 3 minute time delay is activated to prevent short cycling of the equipment.
VENTILATION MODE:
Zone ventilation is established by the individual zone thermostat fan setting. When no calls are taking place, any thermostat set in the fan AUTO mode will not receive ventilation air and its zone damper will be closed. Any zone thermostat set in the fan ON mode will receive ventilation air and its zone damper will be opened. Heating or cooling calls take priority over ventilation mode. The ESP function will continue to maintain the system static pressure by modulating open the non-calling ventilation zone as required.
POWER REQUIREMENTS:
The panel is powered by a single 24VAC, 40VA transformer. Never use the equipment transformer.
1
ZP2-HC-ESP Panel Layout
SPEED UP
BUTTON
3 AMP FUSE PROTECTS
PRINTED CIRCUIT BOARD
24 VOLTS
ZONE 1
THERMOSTAT
ZONE 1 DAMPER
3 AMP
ON
.
.
.
OFF
ON
.
.
.
OFF
SPEED UP
3= 1SEC MIN
1 2
24 VOLT POWER LED
1ST STAGE HEATING LED
1ST STAGE COMPRESSOR LED
FAN LED
LIMIT LED (ON WHEN DAS IS DETECTED. BLINKS WHEN TEMP EXCEEDS HIGH OR LOW LIMIT)
STATIC PRESSURE SENSOR LED (ON WHEN STATIC PRESSURE IS ABOVE SETPOINT)
ZONE 1 DAMPER LED
ZONE 2 DAMPER LED
HIGH LIMIT
ADJUSTMENT
SWITCHES
ZONE 2
THERMOSTAT
ZONE 2 DAMPER
ESP ZONE BYPASS
SELECTOR
PINS
3 AMP
HVAC UNIT
TERMINALS
STATIC PRESSURE
SENSOR TERMINALS
DISCHARGE
AIR SENSOR
3 AMP FUSE PROTECTS
THE RELAY CONTACTS
2
TRANSFORMER
24VAC POWER
C (24V COMMON)
R (24V HOT)
ZONE 1
W (1ST STAGE HEAT)
THERMOSTAT
Y1 (1ST STAGE COMPRESSOR)
G (FAN)
POWER CLOSE
COMMON
ZONE 1
POWER OPEN
DAMPER
ZP2-HC-ESP TERMINAL DESIGNATIONS
C (24V COMMON)
R (24V HOT)
ZONE 2
W (1ST STAGE HEAT)
THERMOSTAT
Y1 (1ST STAGE COMPRESSOR)
G (FAN)
POWER CLOSE
COMMON
ZONE 2
POWER OPEN
DAMPER
R (24V HOT)
W (1ST STAGE HEAT)
Y1 (1ST STAGE COMPRESSOR)
G (FAN)
WIRE TO ZPA-SPS
PRESSURE SENSOR
WIRE TO ZPA-DTS
DISCHARGE TEMPERATURE
SENSOR
HVAC UNIT
3