INVT HT1106S, HT1115L, HT1106L, HT1120L, HT1110S User Manual

...
Important Safety Instructions
True Online 6-20k UPS User Manual
1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating
instructions before operating the uninterruptible power systems (UPS). Adhere to all
equipment can be operated by individuals without previous training.
This product is designed for commercial/industrial use only. It is intended for use with lift
support and other designated “critical” devices. Maximum load must not exceed that shown
on the UPS rating label. The UPS is designed for data processing equipment. If uncertain,
consult your dealer or local representative.
This UPS is designed for use on a properly grounded (earthed), 220/230/240VAC, 50 or
60Hz supply. The factory default setting is 220VAC/50Hz. Installation instructions and
warning notices are in this manual.
The UPS 06-20@220/230/240VAC is designed for use with a three-wire input (L,N,G).
WARNING
THE BA TTE RY CAN PRESENT A RISK OF ELECTRICAL SHOCK AND HIGH SHORT CIRCUIT CURRENT. FOLLOWING PRECAUTIONS SHOULD BE OBSERVED BEFORE REPLACING THE BATTERY.
z Wear rubber gloves and boots.
z Remove rings, watches and other metal objects.
z Use tools with insulated handles.
z Do not lay tools or other metal objects on the batteries.
z If the battery is damaged in any way or shows signs of leakage, contact your local
representative immediately.
z Do not dispose of batteries in a fire. The batteries may explode.
z Handle, transport and recycle batteries in accordance with local representative.
WARNING
ALTHOUGH THE UPS HAS BEEN DESIGNED AND MANU FACTURED TO ENSURE PERSONAL SAFETY, IMPROPER USE CAN RESULT IN
Important Safety Instructions
True Online 6-20k UPS User Manual
2
ELECTRICAL SHOCK OR FIRE. TO ENSURE SAFETY, OBSERVE THE FOLLOWING PRECAUTIONS:
z Turn off and unplug the UPS before cleaning it.
z Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
z Never block or insert any objects into the ventilation holes or other openings of the
UPS.
z Do not place the UPS power cord where it might be damaged.
Contents
True Online 6-20k UPS User Manual
1
CONTENTS
IMPORTANT SAFETY INSTRUCTIONS ............................................................................................. 1
1. ELECTROMAGNETIC COMPATIBILITY ..................................................................................... 3
2. INTRODUCTION .................................................................................................................................. 4
3. SYSTEM DESCRIPTION .................................................................................................................... 7
3.1
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/FRI FILTERS .................................. 7
3.2
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT ............................................................... 7
3.3
INVERTER .......................................................................................................................................... 7
3.4
BATTERY CHARGER .......................................................................................................................... 8
3.5
DC-TO-DC CONVERTER ................................................................................................................... 8
3.6
BATTERY ........................................................................................................................................... 8
3.7
DYNAMIC BYPASS ............................................................................................................................ 8
4. PRODUCT SPECIFICATION AND PERFORMANCE ................................................................... 9
4.1
MODEL DESCRIPTION ....................................................................................................................... 9
4.2
PRODUCT SPECIFICA TION AND PERFORMANCE ................................................................................ 9
5. INSTALLA TION .................................................................................................................................. 11
5.1
UNPACKING AND INSPECTION ......................................................................................................... 11
5.2
CONNECT INPUT/OUTPUT POWER .................................................................................................. 11
5.3
OPERATING PROCEDURE FOR CONNECTING THE LONG BACKUP TIME MODEL UPS WITH THE
EXTERNAL BATTERY
............................................................................................................................. 15
5.4
PARALLEL OPERATION .................................................................................................................... 15
6. CONTROLS AND INDICATORS ..................................................................................................... 20
7. OPERATION ........................................................................................................................................ 23
7.1
OPERATION MODE .......................................................................................................................... 23
Contents
True Online 6-20k UPS User Manual
2
7.2 PARALLEL OPERATION .................................................................................................................... 23
7.3
MAINTENANCE BYPASS OPERATION MODE ....................................................................... 24
8. BATTERY MAINTENANCE ............................................................................................................. 27
9. NOTES FOR BATTERY DISPASAL AND REPLACEMENT PROCEDURES .......................... 28
9.1
BATTERY DISPOSAL ........................................................................................................................ 28
9.2
BATTERY REPLACEMENT PROCEDURES ......................................................................................... 28
10. TROUBIE SHOOTING .................................................................................................................... 29
10.1
CHECKING UPS STATUS ................................................................................................................ 29
10.2
ADJUST THE FACTORS CAUSED THE PROBLEM .............................................................................. 29
ANNEX A. RATED PARAMETERS SET ON LCD ............................................................................ 34
ANNEX B. INTELIGENT SLOT ........................................................................................................... 36
ANNEX C. EPO
......................................................................................................... 37
Introduction
True Online 6-20k UPS User Manual
3
1. ELECTROMAGNETIC COMPATIBILITY
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission.........IEC/EN 62040-2 Category C3
Radiated Emission............IEC/EN 62040-2 Category C3
*EMS
ESD..................................IEC/EN 61000-4-2 Level 4
RS....................................IEC/EN 61000-4-3 Level 3
EFT..................................IEC/EN 61000-4-4 Level 4
SURGE............................IEC/EN 61000-4-5 Level 4
Low Frequency Signals..............:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restrictions or additional measures may be needed to
prevent disturbances.
NOTICE
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent radio interference.
Operated the UPS in an indoor enviroment only in an ambient temperature range of
0-40°C(32-104°F). Install it in a clean environment, free from moisture, flammable liquids,
gases and corrosive substance.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS
on/off push buttons do not electrically isolate internal parts. Under no circumstance attempt
to gain access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the panel indications are not in accordance with these
operating instructions or the UPS performance alters in use. Refer all fault to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the precautions. Keep unauthorized personnel away from the batteries. Proper
disposal of batteries is required. Refer to your local laws and regulations for disposal
requirement.
DO NOT CONNECT equipment that could overload the UPS or demand DC current
from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryer or any
appliance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol
cleaners.
Introduction
True Online 6-20k UPS User Manual
4
2. INTRODUCTION
Congratulations on your choice of the UPS uninterruptible power system(UPS), the
UPS comes in nominal power ratings of 6000VA,10000VA,15000VA and 20,000VA. It is
designed to provide conditioned power to microcomputers and other sensitive electronic
equipment.
When it is generated, alternating current is clean and stable. However, during
transmission and distribution it may be subject to voltage sags, spikes and complete power
failure that may interrupt computer operations, cause data loss and even damage
equipment. The UPS protects equipment from these disturbances.
The UPS is a compact, on-line UPS. An on-line UPS continuously conditions and
regulates its output voltage, whether utility power is present or not. It supplies connected
equipment with clean sine wave power. Sensitive electronic equipment operates best from
sine wave power.
For ease of use, the UPS features a LCD display to indicate all information for UPS,
and provide kinds of function buttons.
6K,10K long backup model 6K,10K standard model 15K,20K long backup model
Fig 1. Front View of UPS Series
Introduction
True Online 6-20k UPS User Manual
5
1 1
1
2
2
2
3
4 5
6
7
8
9
10
11
12
3
4 5
6
7
8
9
10
11
12
3
4 5
6
8
7
11
10
9
12
13
13
13
6K long backup model 10K long backup model 6K standard model
1
1
2
2
3
3
4
4
5
5
6
6
7 7
8
8
9
10
10
11
11
12
13
13
10K standard model 15K,20K long backup model
Fig 2. Rear View
Introduction
True Online 6-20k UPS User Manual
6
Function instructions:
1. SNMP card slot
2. Dry contactor slot
3. USB port
4. RS232
5. EPO
6. Parallel ports
7. Fans
8. Reserved customer function
9. External battery connector. Optional for standard model.
10. Internal maintenance bypass
11. Input breaker
12. Cable entry protector
13. Terminal cover
System Description
True Online 6-20k UPS User Manual
7
3. SYSTEM DESCRIPTION
3.1 Transient Voltage Surge Suppression (TVSS) and EMI/FRI Filters
These UPS components provide surge protection and filter both electromagnetic
interference (EMI) and radio frequency interference (RFI). They minimize any surge or
interference present in the utility line and keep the sensitive equipment protected.
3.2 Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC
power to regulated DC power for use by the inverter while ensuring that the waveform of the
input current used by the UPS is near ideal. Extracting this sine wave input current achieves
two objects:
z The utility power is used as efficiency as possible by the UPS.
z The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being
protected by the UPS.
3.3 Inverter
In normal operation, the inverter utilize the DC output of the power factor correction
circuit and inverters it into precise, regulated sine wave AC power. Upon a utility power
failure, the inverter receives its required energy from the battery through the DC-to-DC
converter. In both modes of operation, the UPS inverter is on-line and continuously
generating clean, precise, regulated AC output power.
System Description
True Online 6-20k UPS User Manual
8
3.4 Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to
continuously float charge the batteries. The batteries are being charged whenever the UPS
is connected to utility power.
3.5 DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises the DC
voltage to the optimum operating voltage for the inverter. The converter includes boost
circuit which is also used as PFC.
3.6 Battery
The 6K/10K Standard include value-regulated, non-spoilable, lead acid batteries inside.
To maintain battery design life, operate the UPS in an ambient temperature of 15-25°C.
3.7 Dynamic Bypass
The UPS provides an alternate path for utility power to the connected load in the
unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature or
any other failure condition, the UPS automatically transfers the connected load to bypass.
Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED. To
manually transfer the connected load from the inverter to bypass, press the ON/OFF button
or Manual Bypass button once.
NOTICEThe bypass power path does NOT protect the connected equipment from disturbances in the utility supply.
Production Specification and Performance
True Online 6-20k UPS User Manual
9
4. PRODUCT SPECIFICATION And PERFORMANCE
4.1 Model Description
This manual is applicable to the following models:
“L” Model: Long backup time
4.2 Product Specification and Performance
1. General Specification Model 6KS 6KL 10KS
0KL 15KL 20KL Power Rating 6KVA/5.4KW 10KVA/9KW 15KVA/13.5KW 20KVA/18KW Frequency (Hz) 50/60
Input
Voltage (176-275)VAC Current 34A max. 57A max 87A max 115A max
Battery
Voltage 192VDC 192VDC 192VDC 192VDC Current 37A max 60A max 90A max 120A max
Output
Voltage 220V/230V/240V Current 27/26/25A 45/43/42A 68/65/63A 91/87/83A
Dimension (W*D*H) mm
250*562*480/L
250*562*650/S
250*562*480/L
250*562*650/S
250*562*770 250*562*770
Weight (kg) 57 18 65 20 33 33
2. Electrical Performance Input
Model Voltage Frequency Power Factor
UPS Single-phase 40-70Hz >0.99(Full load)
Model No. Type
6KS
Standard
10KS
6KL
Long backup time
10KL
15KL
20KL
Product Specification and Performance
True Online 6-20k UPS User Manual
10
3. Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C <95% <1000m 0°C-70°C
NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity Crest ratio
±1% 0.9 lag
±0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 10
minutes
130% load: transfers to
Bypass mode after 1
minute
150% load :transfers to
Bypass mode after 0.5
minute and shutdown the
output after 1 minute
3:1
maximum
Installation
True Online 6-20k UPS User Manual
11
5. INSTALLATION
The system should be installed and wired only by qualified electricians in accordance
with applicable safety regulations.
NOTICEUPS operation in sustained temperature outside the range of 15-25
°
C (59°-77°F)
reduces battery life.
5.1 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
1 UPS
1 user manual
2 connectorsred and whitefor battery with 4 contacts (6KL and 10KL)
2 cable entry protector (6K and 10K)
2) Inspect the appearance of the UPS to see if there is any damage during transportation.
Do not turn on the unit and notify the carrier and dealer immediately if there is any
damage or lacking of some parts.
5.2 Connect Input/Output Power
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least
0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until the UPS is fully
dried inside out before proceeding installation and use. Otherwise there are hazards
of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and
the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. Open the battery
breaker for long backup time model (“L” model).
1) Open the terminal block cover located on the rear panel of the UPS, please refer to
the appearance diagram.
2) For 6k(L) UPS, it is recommended to select the UL1015 10AWG(6mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output
wirings.
3) For 10k(L) UPS, it is recommended to select the UL1015 8AWG(10mm
2
) wire or
Installation
True Online 6-20k UPS User Manual
12
other insulated wire which complies with AWG Standard for the UPS input and output
wirings.
4) For 15kL/20kL UPS, it is recommended to select the UL1015 6AWG(25mm
2
) wire or
other insulated wire which complies with AWG Standard for the UPS input wires and
output wirings. It is better to use 3 wires (UL1015 10AWG) connecting input A/B/C
separately from same source as fig.4.
NOTICEDo not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed. For the long backup time modes, make sure that the capacity of batteries is larger than 24AH to avoid over charging.
5) For 6-10K, connect the input and output wires to the corresponding input and output
terminals according to the fig.3. Make sure that wires be connected to terminals
through cable entry protector shown as fig.3:
(a) Cables entry
(b) Wiring connection
Fig 3. Input and Output Terminal Block Wiring Diagram of 6K(L)/10K(L)
Installation
True Online 6-20k UPS User Manual
13
6) For 15KL/20KL,connect the input 3 line wires to input A/B/C separately as fig.4. Or
connect 1 input wire to input C.
(aCables entry
(b) Wiring connection
Fig 4. Input and Output Terminal Block Wiring Diagram of 15KL/20KL
NOTICEYou must make sure that the input and output wires and the input and output terminals are connected tightly. NOTICE: Please make sure that if there is a copper bar shorting input A/B/C terminal for UPS 15KL/20KL, or else you must contact with supplier.
7 The protective earth ground wire refers to the wire connection between the
equipment which consumes electric equipment and the ground wire. The wire
diameter of protective earth ground wire should be at least as above mentioned for
each model and green wire or green wire with yellow ribbon wire is used.
8 For 6K and 10K UPS,
Installation
True Online 6-20k UPS User Manual
14
9 After having completed the installation, make sure the wiring connection is correct.
10 Please install the output breaker between the output terminal and the load, and the
breaker should with leakage current protective function if necessary.
11) To connect the load with the UPS, please turn off all the loads first, then perform the
connection and finally turn on the loads one by one.
12) No matter the UPS is connected to the utility power or not, the output of the UPS may
have electricity. The parts inside the unit may still have hazardous voltage after
turning off the UPS. To make the UPS have no output, power off the UPS, and then
disconnect the utility power supply.
13) Suggest charging the batteries for 8 hours before use. After connection, turn the input
breaker in the “ON” position, the UPS will charge the batteries automatically. You can
also use the UPS immediately without charging the batteries first, but the backup
time may be less than the standard value.
14) If it is necessary to connect the inductive load such as a monitor or a laser printer to
the UPS, the start-up power should be used for calculating the capacity of the UPS,
as its start-up power consumption is too big when it is started.
5.3 Operating procedure for connecting the long backup time model UPS
with the external battery
Take out Anderson connector and make battery cables according to site’s application
shown as below:
NOTICE: make sure that the red Anderson connector be connected to battery + and the black Anderson connector be connected to battery -, or else it may destroy UPS. For the long backup time modes, make sure that the capacity of batteries is larger than 24AH to avoid over
Installation
True Online 6-20k UPS User Manual
15
charging.
1. The nominal DC voltage of external battery pack is 192VDC. Each battery pack
consists of 16 pieces of 12V maintenance free batteries in series. To achieve longer
backup time, it is possible to connect multi-battery packs, but the principle of “same
voltage, same type” should be strictly followed.
2. For UPS 15KL/20KL, select the UL1015 6AWG(25mm
2
) wire or other insulated wire
which complies with UL Standard for the UPS battery wirings. The procedure of
installing battery bank should be complied with strictly. Otherwise you may encounter
the hazardous of electric shock.
1) A DC breaker must be connected between the battery pack and the UPS. The
capacity of breaker must be not less than the data specified in the general
specification.
2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of
batteries in series.
3) You must connect the external battery cable to the battery first, if you connect
the cable to the UPS first, you may encounter the hazardous of electric shock.
The positive pole of the battery is connected to the UPS with red wire; the
negative pole of the battery is connected to the UPS with black wire; the green
and yellow ribbon wire is connected to the ground of the battery cabinet.
3. To complete the connection of the external battery cable into the UPS. Do not
attempt to connect any loads to the UPS now. You should connect the input power
wire to the right position first. And then set the breaker of the battery pack in the “ON”
position. After that set the input breaker in the “ON” position. The UPS begins to
charge the battery packs at the time.
5.4 Parallel operation
1. Brief introduction
As long as the UPS is equipped with parallel cables, up to 3 UPSs can be connected
in parallel to realize output power sharing and power redundancy.
2. Parallel installation
1) Users need to opt two standard 15-pin communication cables which length is
appropriate to be less than 3m. shown as fig.5:
Installation
True Online 6-20k UPS User Manual
16
Fig.5 communication cables connection
2) Strictly follow the stand-alone wiring requirement to perform the input wiring of
each UPS.
3) Connect the output wires of each UPS to an output breaker panel.
4) Each UPS need an independent battery pack.
5) Please refer to the wiring diagram in the next page, and opt suitable breaker.
The requirement of the output wiring is as follows:
When the distance between the UPSs in parallel and the breaker panel is
less than 20 meters, the difference between the wires of input & output of the
UPSs is required to be less than 20%.
When the distance between the UPSs in parallel and the breaker panel is
greater than 20 meters, the difference between the wires of input & output of
the UPSs is required to be less than 10%.
The wiring diagram are shown as follows:
Installation
True Online 6-20k UPS User Manual
17
(a)Wiring Diagram of 6K(L/S)/10K(L/S)
Installation
True Online 6-20k UPS User Manual
18
UPS2 input
breaker
UPS1 input breaker
utility
UPS2 battery breaker
UPS1 battery breaker
UPS2 output breaker
UPS1 output breaker
PE
Input
A
N
+-
L
Battery input Output
N
BC
PE
Input
A
N
+-
L
Battery input Output
N
BC
(b)Wiring Diagram of 15KL/20KL
Fig.6 wiring diagram
Installation
True Online 6-20k UPS User Manual
19
3. Operation
1) To perform the general operation, follow the stand-alone operating requirement.
2) Startup: The units transfer to INV mode simultaneously as they start up sequentially
in Line mode.
3) Shutdown: the units shut down sequentially in INV mode. When the last one
completes the shutdown action, each unit will shut down the inverter simultaneously
and transfer to Bypass mode.
It is easy to operate the equipment, with no previous training. You just need to read
through this manual and operate according to the instructions in it.
Rectifier/
PFC
Inverter
Bypass
Charger
UPS 1#
Rectifier/
PFC
Inverter
Bypass
Charger
UPS 2#
Utility Power Input
Load
Output 1# Output 2#
Parallel Communication
Cables
Fig 7. Parallel Installation Diagram
Controls and Indicators
True Online 6-20k UPS User Manual
20
6. CONTROLS And INDICATORS
Fig.8 Display Panel
Description of Panel
Controls Description
ON/OFF
1.Press on/off to start inverter when rectifier is OK
NOTE
Not available when UPS is set in automatically start mode
2.Press on/off directly when there is no main input, press again
to start UPS
3. Press on/off to shutdown inverter when UPS is in normal
mode.
4.Press on/off to shutdown UPS completely when UPS is in
battery mode
HOME Back to main menu
Left and right
ENTER Press to choose
Indicators Description
STATUS UPS status: green--normal mode, red--UPS is abnormal
REC Rectifier indicator: green--rectifier is normal, green
Controls and Indicators
True Online 6-20k UPS User Manual
21
flicker--rectifier is starting, red--rectifier fault, red
flicker--rectifier alarm, dark—rectifier is not working
INV
Inverter indicator: green--inverter is normal, green
flicker--inverter is starting or tracking with bypass(ECO),
red—inverter fault and load is not on inverter, red
flicker—inverter fault and load is on inverter, dark—inverter is
not working
BYP
Bypass indicator: green—bypass is normal, dark—UPS is in
normal mode and bypass is normal, red—bypass fault, red
flicker—bypass alarm
BAT
Battery indicator: green—battery charge, green flicker—battery
discharge, dark—battery is connected, red—battery fault, red
flicker—battery alarm
OUTPUT Output indicator: green—output is normal, red—output alarm
Fig 9. LCD Main Menu
Description of Main Menu
Display Function Submenu
Input information
Main input: voltage, current, frequency, PF
Bypass input:
Voltage, current, frequency, PF
Battery
information
Battery: voltage, discharge current, battery
status, battery temperature, capacity
DCbus voltage
Controls and Indicators
True Online 6-20k UPS User Manual
22
Display Function Submenu
Output
information
Output information:
Voltage, current, frequency, PF
Load information:
Active power, apparent power, percent
Status of UPS
Alarms, S-code, firmware version, system
information
Set and function
Set: language, contrast, communication
set(SNT, Modbus), Modbus set
Function: function 1(transfer to bypass/escape,
fault clear, mute on/off), function 2(battery test,
maintenance test, stop test)
History log /
Rated capacity:
10KVA
1phase in/out: 1/1
/
Input voltage /
Battery voltage
and capacity
remained
/
Output voltage
and load percent
/
System working
mode
S--single mode, E--ECO mode, P-parallel
mode, 2-the unit ID is 2 in system, the units ID
in parallel system should be different
Mute on, mute off
Operation
True Online 6-20k UPS User Manual
23
7. OPERATION
7.1 Operation Mode
1. Turn on the UPS in normal mode
1) After you make sure that the power supply connection is correct, and then close the
battery breaker (this step only for long backup time model), after that close the input
breaker. At this time the fans rotate and the UPS operates in Bypass mode.
2) After REC led is ready green, pressing the ON/OFF button continuously for more
than 1 second, then choose ON to enter, the INV green led flickers.
NOTE
In some application, UPS is set to start automatically, this step is not need.
3) About 1 minute later, the UPS turn into normal Line mode. If the utility power is
abnormal, the UPS will operate in Battery mode without output interruption of the
UPS.
2. Turn on the UPS from battery without utility power
1) After you make sure that the breaker of the battery pack is in the “ON” position (this
step only for long backup time model).
2) Press the ON/OFF button once to power on the LCD, then press ON/OFF button
again, choose ON to enter.
3) A few seconds later, the UPS turns into Battery mode.
3. Turn off the UPS in normal mode
1) Press ON/OFF button in condition of normal mode, then choose OFF to transfer to
bypass.
2) Open the input breaker to turn off utility power supply, then open the battery breaker
to turn off UPS completely.
4. Turn off the UPS in Battery mode
1) To power off the UPS by pressing the ON/OFF button continuously for more than 1
second, then choose OFF.
2) When being powered off, the UPS will turn into No Output mode. Finally not any
display is shown on the display panel and no voltage is available from the UPS
output.
NOTICEPlease turn off the connected loads before turning on the UPS and turn on the loads one by one after the UPS is working in INV mode. Turn off all of the connected loads before turning off the UPS.
7.2 Parallel Operation
1. Parallel Machine Maintenance
Operation
True Online 6-20k UPS User Manual
24
This UPS system has parallel machine function, if you want to add single machine to
parallel system, please follow operational process of joining new machine; if you must
remove UPS, please follow operational processes of removing parallel machine.
2. How to install a new parallel UPS system:
1) Before installing a new parallel UPS system, user need to prepare the input and
output wires, the output breaker, and the parallel cables.
2) Open the input and output breakers of each UPS. Connect the input wires, output
wires and battery wires.
3) Connect each UPS one by one with the parallel cables.
4) Close the battery breakers and the input breakers of all of the UPSs in the parallel
system in turn.
5) Turn on each UPS in turn and observe their display. Make sure that each UPS
displays normal and all the UPSs transfer to the INV mode normally.
Notice: close output 1# breaker and 2# breaker as fig.7 to make sure that output of every
UPS are shorted before starting UPS, or else the parallel system will fail to start.
3. How to remove a single UPS from the parallel system:
1) If you need to remove one UPS of the UPSs parallel system which is on normal
running, press the ON/OFF button of the UPS that is confirmed to be removed
continuously and the UPS will cut off its output immediately.
2) Turn off the input breaker; the external mains input breaker, the output breaker and
the battery breaker.
3) Press the others UPSs’s ON/OFF button. All of them transfer to the Bypass mode.
4) Remove the parallel cables of the UPS that need to be removed.
5) Press ON/OFF button of remained UPSs, then press YES to make the UPSs transfer
to INV output.
7.3 Maintenance Bypass Mode
Maintenance Bypass Mode operates on the condition that the inner power supply of
the UPS is cut off and the load is supplied by the maintenance bypass.
Operation
True Online 6-20k UPS User Manual
25
To transfer the UPS to Maintenance Mode, the following procedures should be followed.
1. Check the status before the Maintenance Mode.
Before transferring to the Maintenance Mode, the circuit breakers (CB) are in the
following status: Input and Output are closed (in the on position); the Maintenance
Bypass is open, as it is shown in the figure above;
2. Transfer to the Maintenance Mode for maintenance
(a) Enter the menu -->function 1-->transfer to bypass and the system transfers to
bypass.
Remove the cover that protects the Maintenance Bypass CB from misoperation and
Operation
True Online 6-20k UPS User Manual
26
the UPS transfers to Bypass Mode with warning and wait until the LED indicator for
bypass goes green
(b) Close the Maintenance Bypass CB;
(c) Open the CB for output and input and disconnect the battery( For the standard UPS
type , pull out Battery terminal of positive and negative ; for the long run type UPS,
open the battery CB).
3. Transfer back to Normal Mode
After the maintenance is finished, follow the procedures below to transfer the UPS to
Normal Mode from Maintenance Bypass Mode.
(a) Connect the battery (For the standard UPS type, connect the Battery terminal of
positive and negative; for the long run type UPS, close the battery CB)
(b) Close the CB for Input and Output.
(c) Open the CB for Maintenance Bypass and install the cover.
True Online 6-20k UPS User Manual Battery Maintenance
True Online 6-20k UPS User Manual
27
8. BATTERY MAINTENANCE
The UPS only requires minimal maintenance. The batteries used for standard models are
value regulated, sealed lead-acid, maintenance free battery. When being connected to the
utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and
also offers the protective function of overcharging and over-discharging.
zThe UPS should be charged once every 4 to 6 months if it has not been used for a long
time.
zIn the regions of hot climates, the battery should be charged and discharged every 2
months. The standard charging time should be at least 12 hours.
zUnder normal conditions, the battery life lasts 3 to 5 years. In case if the battery is found
in bad condition, earlier replacement should be made.
zBattery replacement should be performed by qualified personnel.
zReplace batteries with the same number and same type of batteries.
zDo not replace the battery individually. All the batteries should be replaced at the same
time following the instructions of the battery supplier.
Battery Maintenance
True Online 6-20k UPS User Manual
28
9. NOTES for BATTERY DISPASAL and REPLACEMENT
PROCEDURES
9.1 Battery Disposal
1) Before disposing of batteries, remove jewelry, watches and other metal objects.
2) Use rubber gloves and boots, use tools with insulated handles.
3) If it is necessary to replace any connection cables, please purchase the original
materials from the authorized distributors or service centers, so as to avoid overheat
or spark resulting in fire due to insufficient capacity.
4) Do not dispose of batteries or battery packs in a fire. The batteries may explode.
5) Do not open or mutilate batteries, released electrolyte is highly poisonous and
harmful to the skin and eyes.
6) Do not short the positive and negative of the battery electrode, otherwise, it may
result in electric shock or fire.
7) Make sure that there is no voltage before touching the batteries. The battery circuit is
not isolated from the input potential circuit. There may be hazardous voltage
between the battery terminals and the ground.
8) Even though the input breaker is disconnected, the components inside the UPS are
still connected with the batteries, and there are potential hazardous voltages.
Therefore, before any maintenance and repairs work is carried out, switch off the
breaker of the battery pack or disconnect the jumper wire of connecting between the
batteries.
9) Batteries contain hazardous voltage and current. Battery maintenance such as the
battery replacement must be carried out by qualified personnel who are
knowledgeable about batteries. No other persons should handle the batteries
9.2 Battery Replacement Procedures
1) Press ON/OFF button to transfer to bypass mode
2) Switch the maintenance switch from UPS to Manual BYP
3) Remove both side covers from the UPS.
4) Disconnect the battery wires one by one.
5) Remove metal bars which are used to fasten batteries.
6) Replace batteries one by one.
7) Screw metal bars back to UPS.
8) Connect the battery wires one by one. Take care of electrical shock while
connecting the last wire.
Trouble Shooting
True Online 6-20k UPS User Manual
29
10. TROUBIE SHOOTING
This section describes checking the UPS’s status. This section also indicates various UPS
symptoms a user may encounter and provides a troubleshooting guide in the event the UPS
develops a problem. Use the following information to determine whether external factors
caused the problem and how to remedy the situation.
10.1 Checking UPS status
It recommended that checking the UPS operation status every six months.
z Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an
alarm?
z Check whether the UPS is operating in Bypass mode. Normally, the UPS operates
in Normal Mode. If it is operating in Bypass Mode, stop and contact your local
representative, or Channel Support.
z Check whether the battery is discharging. When the utility input is normal, the
battery should not discharge. If the UPS is operating in Battery Mode, stop and
contact your local representative, or Channel Support.
10.2 Adjust the factors caused the problem
When the fault indicator is on, press button to get S-code. So,S1 indicates status
and A0-A5 indicates the exact fault of UPS, S-code list is shown as follow:
Description of S-Code
Seq. Items 0 1 Solution
1
A0
1
Synchronous
Fault
Sync
Not
sync.
Check whether bypass
voltage/frequency is normal
2 2 Main Input Fault OK Fault Check whether input is normal
3 3 REC Fault OK Fault
REC over temperature, bus
over voltage, input current
unbalance, soft start fail
4 4 INV Fault OK Fault
INV over temperature, INV
IGBT broken, INV relay fault
5 5 Reserved
6 6 Reserved
7 7 Reserved
8 8 Reserved
9 9 Reserved
Trouble Shooting
True Online 6-20k UPS User Manual
30
Seq. Items 0 1 Solution
10 10 Reserved
11 11 Reserved
12 12 Reserved
13 13
Input phase A
over current
OK Fault
Check if rectifier IGBT is
broken, DC bus is shorted, or
IGBT drivers are lost, input
voltage display is wrong
14 14
Input phase B
over current
OK Fault
15 15
Input phase C
over current
OK Fault
16 16
Output voltage
Fault
OK Fault
Check if inverter IGBT is
broken, IGBT drivers are lost
17
A1
1 Reserved
18 2 Reserved
19 3 Reserved
20 4 Reserved
21 5 Reserved
22 6 Reserved
23 7 Reserved
24 8 Reserved
25 9
Input voltage
Fault
OK Fault Input voltage out of range
26 10
Input Frequency
Fault
OK Fault Input frequency out of range
27 11
Input Sequence
Fault
OK Fault
Input sequence is wrong, check
whether input wires connection
is ok.
28 12
REC soft-start
Fault
OK Fault
Check whether rectifier SCR is
broken, or SCR drivers are lost.
29 13 Reserved
30 14 Reserved
31 15
REC over
temperature
OK Fault
Check if the environmental
temperature is over 40, if
rectifier IGBTs is properly
Trouble Shooting
True Online 6-20k UPS User Manual
31
Seq. Items 0 1 Solution
installed.
32 16
Positive bus over
voltage
OK Fault UPS requires service
33
A2
1
Negative bus over
voltage
OK Fault UPS requires service
34 2 Fan Fault OK Fault At least one of fans fail.
35 3 Reserved
36 4 Reserved
37 5
Positive bus
under voltage
OK Fault UPS requires service
38 6
Negative bus
under voltage
OK Fault UPS requires service
39 7 Battery reversed OK Fault
Check if the battery wires
connection is OK
40 8 Reserved
41 9 Reserved
42 10 Reserved
43 11 Reserved
44 12 Reserved
45 13
Battery over
temperature
OK Fault
Check if environmental temp is
too high or batteries life is over
46 14 Reserved
47 15 Reserved
48 16 Reserved
49
A3
1
Battery voltage
low
OK Fault
50 2 Reserved
51 3 Battery EOD OK Fault
52 4 Reserved
53 5 Reserved
54 6 Reserved
55 7 BYP voltage Fault OK Fault
Check if bypass input voltage is
normal
Trouble Shooting
True Online 6-20k UPS User Manual
32
Seq. Items 0 1 Solution
56 8
Bypass SCR or
relay fault
OK Fault UPS requires service.
57 9 Reserved
58 10 Reserved
59 11
BYP frequency
over track range
OK Fault
Check if bypass input
frequency is abnormal
60 12 Reserved
61 13 Reserved
62 14
Over load time
out
OK Fault
63 15 Reserved
64 16 Reserved
65
A4
1 Manual shutdown normal
shutdo
wn
66 2 INV protect OK Fault
67 3
Transfer times
limit in one hour
OK Fault
Transfer times between
inverter and bypass is over 5
times in one hour
68 4 Reserved
69 5 Reserved
70 6 Reserved
71 7 Reserved
72 8
INV over
temperature Fault
OK Fault
Check if environmental temp is
over 40°C, or fans are
abnormal
73 9 Reserved
74 10 Reserved
75 11 Over load OK
Over
load
Check load level indicator and
remove non-essential load.
Recalculate the load and
remove number of loads
connected to UPS.
76 12 INV relay or fuse OK Fault Check if inverter relay is
Trouble Shooting
True Online 6-20k UPS User Manual
33
Seq. Items 0 1 Solution
Fault shorted or opened.
77 13 Reserved
78 14
Parallel
connection fault
OK Fault
Check whether parallel
connection cable disconnect.
79 15 Reserved
80 16 Reserved
81
A5
1 Reserved
82 2 Output shorted OK Fault
Shutdown UPS and open
output breaker, check if load is
effective or short internally,
check if output connector is
shorted.
83 3 Battery test None OK 2--Fault
84 4
Battery
maintenance
None OK 2--Fault
85 5 Reserved
86 6 Reserved
87 7 Reserved
88 8 Reserved
89 9 Reserved
90 10 Reserved
91 11 Reserved
92 12 Reserved
93 13 Reserved
94 14 Reserved
95 15 Reserved
96 16 Reserved
Rated Parameters Set on LCD
True Online 6-20k UPS User Manual
34
Annex A. Rated Parameters Set on LCD
1. Power on LCD
2. Press button
together for 3 seconds, enters in rated setting menu as
below
3. Press button “ENTER” to activate setting function as below. Shadow means the current
parameter can be set now.
4. Input voltage setting is activated. Press to select the rated input voltage.
The voltages are available for customer such as: 110V, 120V, 127V, 200V, 208V, 220V, 230V,
240V.
5. Press “ENTER” button to confirm input voltage selection and activate output voltage
setting menu as below. Press
to select the rated output voltage. Output
voltages are available for customer such as: 110V, 120V, 127V, 200V, 208V, 220V, 230V,
240V.
RATE SET
OP
IP
FREQ HZ 50
V(LN) 230 V(LN) 220
50
230
230
Rated Parameters Set on LCD
True Online 6-20k UPS User Manual
35
6. Press “ENTER” button to confirm output voltage selection and activate frequency setting.
Press
to select the rated frequency. 50Hz and 60Hz are available for
selection.
7. Press “ENTER” button to confirm frequency selection, and the current parameters are
shown on LCD as below
8. Shutdown UPS completely and restart UPS to activate the setting. Enter in and
enter in system information to check if the rated setting has been activated as below
Rated Parameters Set on LCD
True Online 6-20k UPS User Manual
36
Annex B. Intelligent Slot
(a) DB9 connector
2
6
1
7 8 4 9 3 5
(b)Phoenix Term inal
Intelligent Slot Description
Pins Function Denotation
1 UPS Faults Low Voltage: UPS Fault
2 Normal warning Low Voltage: UPS unusual
3 GND /
4 Far-away cut off Utility usualUPS cut off Rectifier and Inverter;
Battery Mode: cut off the whole system
High Voltage: Far-away cut off the machine
5 Power Supply 12VDC~24VDC
6 Bypass Mode High Voltage: UPS work under Bypass Mode
7 Battery Low Voltage Low Voltage: Battery Low Voltage
8 Normal Mode High Voltage: UPS work under Normal Mode
9 Utility Fault Low Voltage: Utility Fault
Rated Parameters Set on LCD
True Online 6-20k UPS User Manual
37
Annex C. EPO
EPO is used to quickly cut off machine under emergency, the function is triggered by
customer’s connector. By shorting common-open point NO with +24V, EPO function is
effective.
Far-away EPO connector denotation:
Pins Name Denotation
P1
24V +24V,the same connect points for NC and NO
P2 EPO_NO
EPO function is effective by Shorting common-open point
NO and +24V
Loading...