This option module is specifically designed to be used with the Optidrive P2 and Optidrive
Eco range of variable speed drive products and is intended for professional incorporation into
complete equipment or systems. If installed incorrectly it may present a safety hazard. Before
commencing installation and commissioning, the user should ensure they are fully familiar with the
Optidrive P2, and in particular have read the important safety information and warnings contained
in the Optidrive P2 / Optidrive Eco User Guide.
Note
This User Guide is intended to be used with Optidrive P2 & Eco firmware version 2.00 or later. The firmware version of
the drive can be displayed in parameter P0-28. Previous versions of firmware can be upgraded using Optitools Studio
PC software. Contact your local Invertek Sales Partner for further Information.
Available Functions
The PROFINET Interface is intended to be installed in the Optidrive option slot, and allows the Optidrive to be connected to a
PROFINET network. The interface offers the following functionality:
Cyclic Process Data Exchange
4 Input Words from the network master to the Optidrive
4 Output Words from the Optidrive to the network master
GSD File
A GSDXML fi le for the interface can be obtained from invertekdrives.com
IP Address Confi guration
If it is desired to change the IP Address, an IP address confi guration tool is available for download from invertekdrives.com
Compatibility
This Option is suitable for use on the following product ranges:
Optidrive P2 (ODP-2-.... Drives)
Optidrive Eco (ODV-... Drives)
Optidrive Setup
Set the drive to Fieldbus control mode by setting parameter P1-12 = 4
Ensure Advanced Parameter Access is enabled on the drive by setting P1-14 = 101
By default, DHCP is enabled, and the module IP address will be automatically assigned. If a fi xed IP address is desired, download
the IP address confi guration software from invertekdrives.com
Layout
56
12
77
3
4
1 Network Status LED
2 Module Status LED
3 Ethernet Port 1
4 Ethernet Port 2
5 Port 1 Activity LED
6 Port 2 Activity LED
7 Clamping screws, Torx 8, 0.25Nm
Network Status LED
StateIndication
OffOffl ine / No Power / Not inserted
Green
Flashing Green
Online, Connection with IO Controller
established, IO Controller in RUN state
Online, Connection with IO Controller
established, IO Controller in STOP state
Module Status LED
StateIndication
OffNo Power / Initialising
GreenNormal Operation
Green 1 FlashDiagnostic Event Present
Green 2 Flashes Network Node Identifi cation
RedException Error, Module in Exception State
Red 1 FlashConfi guration Error
Red 2 FlashesIP Address Not Set
Red 3 FlashesStation Name Not Set
Red 4 FlashesInternal Module Error
Installation
Ensure the drive power is removed prior to installing the
option module
Remove the blanking cover from the option module slot
Carefully slide the option module into the slot, ensuring that the
locating tabs are correctly aligned. Do not use excessive force
Tighten the 2 clamping screws to secure the module in place.
Link / Port Activity LEDs
StateIndication
OffNo Link
GreenLink Established, No Communication
Green Flickering Lint Established & Communicating
2 | PROFINET IO Interface 82-PFNET-IN | Version 2.03www.invertekdrives.com
PLC Confi guration
Confi guration of the PLC varies between
different systems.
Refer to information on the specifi c PLC system in
use for further guidance. Scan QR code opposite.
Data Mapping
The Optidrive P2 and Optidrive Eco support a 4 word cyclic process data exchange. The format and data contained in these words
are shown below.
Input Data (PDI) Telegram
This part of the memory contains the real-time drive commands sent from the network master to the Optidrive, allowing the Optidrive
to be controlled. The functions of the first two data words (PDI 1 and PDI 2) are fixed, to allow basic control over the drive operation
and output frequency to be achieved. The configuration of the remaining two words can be adjusted by the user.
PDI Word 1: Fixed Function : Drive Control Word
A 16 Bit control word is used to control the behaviour of the drive when P1-12 = 4. The bits function as follows:
BitNameDescription
0Drive Run0 : Drive Stop
1 : Drive Run
1Fast Stop Select0 : No Function
1 : Drive Stop with Deceleration Ramp 2
2Fault Reset0 : No Function
1 : Rising Edge fault reset request
3Coast Stop0 : No Function
1 : Drive Coasts to stop. Overrides bit 0
4–15Not Used
PDI Word 2: Fixed Function : Frequency Setpoint
This word is used to transfer the frequency setpoint to the Optidrive. The input data is a 16bit signed integer including one decimal
place. For example, a value of 500 represents a frequency setpoint to the Optidrive of 50.0Hz, value 123 gives 12.3Hz. For a
negative (reverse) speed reference, a negative value can be transferred to the drive, where the MSB of the high byte must be 1.
For example, -1(0xFFFF) gives -0.1Hz. -234(0xFF16) gives -23.4Hz.
The allowed input value range is from -5000 to +5000; however the drive output speed will be limited by the maximum speed set
by P1-01.
PDI Word 3 : User Defined Function
The function of this data word can be selected by the user using drive parameter P5-14. The possible setting options are shown below:
0: Torque limit/reference (Optidrive P2 Only) – This option must be selected if the drive output torque limit / setpoint is to be
controlled from the fieldbus. This also requires setting P4-06 = 3. The input data is a 16bit unsigned integer including one decimal
place. For example, a value of 500 represents a torque setpoint to the Optidrive of 50.0%, value 123 gives 12.3%.
The allowed input value range is from 0 to +2000; however the drive output torque will be limited by the maximum limit set by P4-07.
1: User PID reference register – This option allows the setpoint to the PID controller to be received from the Fieldbus. In order for this
option to be used, P9-38 must be set to 1, and the PID User setpoint must not be utilised within the drive PLC function.
2: User register 3 - The value received by the drive in PDI 3 is transferred to User Register 3. This option allows the function of the
process data word to be defined in Parameter Group 9. In this case, User Register 3 should not be written to within any PLC function
code, although the value can be read.
For normal operation, Bit 3 has the highest priority, bit 0
has the lowest priority (bit 3>bit 1>bit 0). For normal run/
stop control, Bit 0 only should be used.
Note that the start/stop (bit 0), fast stop (bit 1) and coast
stop (bit 3) can only be used to control the drive when
P2-37= 0 to 3. If P2-37 > 3, the start/stop function is
controlled directly by the drive control terminals. The Reset
function (bit 2) will operate providing that the drive is set
for Fieldbus control P1-12 = 4.
PDI Word 4: User Defined Function
The function of this data word can be selected by the user using drive parameter P5-13. The possible setting options are shown below:
0: Fieldbus Ramp Control – This option must be selected if the drive acceleration and deceleration ramps are to be controlled from
the fieldbus. P5-07 must also be set to 1 to enable this function.
1: User register 4 – The value received by the drive in PDI 4 is transferred to User Register 4. This option allows the function of the
process data word to be defined in Parameter Group 9. In this case, User Register 3 should not be written to within any PLC function
code, although the value can be read.
Version 2.03 | PROFINET IO Interface 82-PFNET-IN | 3www.invertekdrives.com
Output Data
This part of the memory contains the real-time drive data returned from the Optidrive to the network master. The function of the first two
data words (PDO 1 and PDO 2) is fixed. The configuration of the remaining two words can be adjusted by the user.
PDO Word 1: Fixed Function : Drive Status & Error Code:
This word contains 2 bytes with information as follows:
High byte : Gives the drive error (fault) code. (Valid when the drive is tripped)
Low byte : Gives the drive status information, 8 bits which function as follows:
BitLogic 0Logic 1Notes
0Drive StoppedDrive RunningIndicates when the output to the motor is enabled
1Drive HealthyDrive Fault (Tripped)Indicates when the drive has tripped. The fault code is indicated in the high
byte as shown below
2Auto Control
Mode
3OKInhibitIndicates the status of the STO / Hardware Inhibit circuit
4OKMaintenance Time Reached Indicates that the programmable System Maintenance Time Interval has
5Not in StandbyStandbyNo Function Assigned
6 Not ReadyDrive ReadyMains Power applied, No Inhibit, No Trip, Enable Input present
7Normal LoadLow/High Mode Detected Optidrive Eco Only. Indicates when low or high load condition is detected
8 – 15 Last / Current Fault CodeIndicates the last or current fault code. For further fault code information,
Hand Control ModeOptidrive Eco Only. Indicates when Hand control is selected
expired
refer to the Optidrive User Guide
PDO Word 2 : Fixed Function : Output Frequency
This word gives the real time drive output frequency information. The data is a 16bit signed integer with one decimal place.
e.g. value 123 means 12.3Hz. Value -234 (0xFF16) means -23.4Hz.
PDO Word 3 : Output Current
Data to be transferred in this word can be selected by the User in drive parameter P5-12. The possible settings are as follows:
0: Motor current – Output current to 1 decimal place, e.g. 100 = 10.0 Amps
1: Power (x.xx kW) Output power in kW to two decimal places, e.g. 400 = 4.00kW
2: Digital input status – Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3: Analog Input 2 Signal Level – 0 to 1000 = 0 to 100.0%
4: Drive Heatsink Temperature – 0 to 100 = 0 to 100°C
5: User register 1 – User Defined Register 1 Value
6: User register 2 – User Defined Register 1 Value
7: P0-80 value – User Selected data value
PDO Word 4 : User Defined
Data to be transferred in this word can be selected by the User in drive parameter P5-08. The possible settings are as follows:
0 : Output Torque (Optidrive P2 Only) – 0 to 2000 = 0 to 200.0%
1 : Output Power – Output power in kW to two decimal places, e.g. 400 = 4.00kW
2 : Digital Input Status – Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3 : Analog Input 2 Signal Level – 0 to 1000 = 0 to 100.0%
4 : Drive Heatsink Temperature – 0 to 100 = 0 to 100°C
Ñ82-PFNET-IN_V2.035Ó
82-PFNET-IN_V2.03