INVENTOR V6MCRI32-18WiFiR, U6MRS32-18 Installation Manuals

• INSTALLATION MANUAL
• ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
• MANUAL DE INSTALARE
ENGLISH | ΕΛΛΗΝΙΚΑ | ROMANA
AIR CONDITIONING SYSTEMS
CASSETTE TYPE
MODELS:
Indoor Unit Parts ........................................ 10
Indoor Unit Installation Instructions .......11
Outdoor Unit Installation ......................... 14
Outdoor Unit Installation Instructions ......14
Drain Joint Installation .................................16
Notes on Drilling Hole in Wall ...................16
Drainpipe Installation ...............................17
Table of Contents
Installation Manual
Indoor Unit Installation
........................... 10
4
3
5
Accessories
....................................................
04
Safety Precautions
.....................................
09
1
2
Refrigerant Piping Connection .......................19
Notes on Pipe Length and Elevation ..............19
Refrigerant Piping Connection Instructions ...20
Wiring ................................................. 23
Outdoor Unit Wiring .................. 24
Indoor Unit Wiring ..................... 25
Air Evacuation ..................................................26
Evacuation Instructions ................................ 26
Note on Adding Refrigerant ..........................27
Test Run ............................................................... 30
6
7
8
10
Panel Installation ......................................... 28
9
L N
MC MC
European Disposal Guidelines ....................31
11
................................... 32
12
(for R32/R290 refrigerant only )
Caution : Risk of fire
WARNING:
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants. For more details ,
please refer to the section of “ Information on servicing” . (This is only required for the unit adopts R32/R290 Refrigerant).
Information Servicing
Refrigerant Piping Connection .......................19
Notes on Pipe Length and Elevation ..............19
Refrigerant Piping Connection Instructions ...20
Wiring ................................................. 23
Outdoor Unit Wiring .................. 24
Indoor Unit Wiring ..................... 25
Air Evacuation ..................................................26
Evacuation Instructions ................................ 26
Note on Adding Refrigerant ..........................27
Test Run ............................................................... 30
6
7
8
10
Panel Installation ......................................... 28
9
L N
MC MC
European Disposal Guidelines ....................31
11
................................... 32
12
(for R32/R290 refrigerant only )
Caution : Risk of fire
WARNING:
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants. For more details ,
please refer to the section of “ Information on servicing” . (This is only required for the unit adopts R32/R290 Refrigerant).
Information Servicing
Page 4
Safety Precautions
1
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
WARNING
Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.
Failure to observe a caution may result in injury or equipment damage.
CAUTION
WARNING
1. Carefully read the Safety Precautions before installation.
2. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
3. Only trained and certied technicians should install, repair and service this air conditioning unit.
4. Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment and personal property.
(In North America,installation must be performed in accordance with the requirement
of NEC and CEC by authorized personnel only.)
5. Strictly follow the installation instructions set forth in this manual.
6. Before you install the unit, consider strong winds, typhoons and earthquakes that might affect your unit and locate it accordingly. Failure to do so could cause the equipment to fail.
7. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
(EN Standard requirements)
8. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
9. This appliance is not intended for use by persons(including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.(IEC Standard requirement )
10. Children should be supervised to ensure that they do not play with the appliance. (IEC Standard requirement )
This symbol indicates that you must never perform the action indicated.
WARNING
For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
Do not install the unit in a location that may be exposed to combustible gas leaks. If
combustible gas accumulates around the unit, it may cause re. Do not
operate your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit.
1.
The product must be properly grounded at the time of installation, or electrical shock may occur.
2.
Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
CAUTION
11. If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or similarly qualied persons in order to avoid a hazard.
12. The appliance shall be installed in accordance with national wiring regulations.
13. An all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA,the residual current device (RCD) having a rated residual operating current not exceeding 30mA,and disconnection must be incorporated in the xed wiring in accordance with the wiring rules.
14. The appliance disconnection must be incorporated with an all-pole disconnection device in the xed wiring in accordance with the wiring rules.
15. Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certicate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specication.
16. Servicing shall only be performed as recommended by the equipment manufacturer.
17. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants.
18. The appliance shall be stored so as to prevent mechanical damage from occurring.
19. Keep ventilation openings clear of obstruction.
20. Do not turn on the power until all work has been completed.
21. When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit
22. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
23. Removal of the plug has to be such that an operator can check from any of the points to which he has access that the plug remains removed.
24. If this is not possible, due to the construction of the appliance or its installation, a disconnection with a locking system in the isolated position shall be provided.
25. How to install the appliance to its support, please read the information for details in "indoor unit installation" and "outdoor unit installation".
Page 5
WARNING
For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
Do not install the unit in a location that may be exposed to combustible gas leaks. If
combustible gas accumulates around the unit, it may cause re. Do not
operate your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit.
1.
The product must be properly grounded at the time of installation, or electrical shock may occur.
2.
Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
CAUTION
11. If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or similarly qualied persons in order to avoid a hazard.
12. The appliance shall be installed in accordance with national wiring regulations.
13. An all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA,the residual current device (RCD) having a rated residual operating current not exceeding 30mA,and disconnection must be incorporated in the xed wiring in accordance with the wiring rules.
14. The appliance disconnection must be incorporated with an all-pole disconnection device in the xed wiring in accordance with the wiring rules.
15. Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certicate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specication.
16. Servicing shall only be performed as recommended by the equipment manufacturer.
17. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants.
18. The appliance shall be stored so as to prevent mechanical damage from occurring.
19. Keep ventilation openings clear of obstruction.
20. Do not turn on the power until all work has been completed.
21. When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit
22. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
23. Removal of the plug has to be such that an operator can check from any of the points to which he has access that the plug remains removed.
24. If this is not possible, due to the construction of the appliance or its installation, a disconnection with a locking system in the isolated position shall be provided.
25. How to install the appliance to its support, please read the information for details in "indoor unit installation" and "outdoor unit installation".
Page 6
1.
Cautions for using R32/R290 refrigerant
Installation (Space)
- That the installation of pipe-work shall be kept to a minimum.
- That pipe-work shall be protected from physical damage.
- That compliance with national gas regulations shall be observed.
- That mechanical connections shall be accessible for maintenance purposes.
- In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
- When disposing of the product is used, be based on national regulations, properly processed.
-The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specied for operation.
-Spaces where refrigerant pipes shall be compliance with national gas regulations.
2. Servicing
- Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certicate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specication.
- Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open ames,an operating gas appliance or an operating electric heater) Do not pierce or burn. Be aware that refrigerants may not contain an odour. Be more careful that foreign matter(oil, water,etc) does not enter the piping. Also, when storing the piping, securely seal the opening by pinching, taping, etc. For indoor units, use R32 areless joint assy only when connecting the indoor unit and connecting piping(when connecting indoors). Use of pipes, areless nut or are nuts other than specied, may cause product malfunction, burst piping, or injury due to high internal pressure of the refrigerant cycle caused by any inow air. Appliance shall be installed, operated and stored in a room with a oor area larger than X m² (Please see the following form ). The appliance shall not be installed in an unventilated space, if that space is smaller than X m² (Please see the following form ).
3.
4.
5.
6.
7.
8.
Table.1-1
Table.1-2
Note about Fluorinated Gasses
1.
This air-conditioning unit contains fluorinated greenhouse gasses. For specic information on the type of gas and the amount, please refer to the relevant label on the unit itself or the “Owner's Manual - Product Fiche ” in the packaging of the outdoor unit. (European Union products only).
2.
Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3.
Product uninstallation and recycling must be performed by a certified technician.
4.
For equipment that contains uorinated greenhouse gases in quantities of 5 tonnes of CO equivalent or more, but of less than 50 tonnes of CO equivalent, If the system has a leak- detection system installed, it must be checked for leaks at least every 24 months.
2
2
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
R32
Refrigerant Type
Installation Height H0(m)
LFL(kg/m )
3
Floor Area (m )
2
0.306
0.6
1.0
1.8
2.2
4
0.68
1.14
2.05
2.50
7
0.90
1.51
2.71
3.31
10
1.08
1.80
3.24
3.96
15
1.32
2.20
3.97
4.85
20
1.53
2.54
4.58
5.60
30
1.87
3.12
5.61
6.86
50
2.41
4.02
7.24
8.85
Max Refrigerant Charge (kg)
R32
LFL(kg/m )
3
Charge Amount in kg
0.306
0.6
1.0
1.8
2.2
1.224 1.836
29
10
3
2
2.448
51
19
6
4
3.672
116
42
13
9
4.896
206
74
23
15
6.12
321
116
36
24
7.956
543
196
60
40
Min. Room Area (m )
2
Minimum Room Area ( m )
2
Refrigerant Type
Installation Height H0(m)
Page 7
Table.1-1
Table.1-2
Note about Fluorinated Gasses
1.
This air-conditioning unit contains fluorinated greenhouse gasses. For specic information on the type of gas and the amount, please refer to the relevant label on the unit itself or the “Owner's Manual - Product Fiche ” in the packaging of the outdoor unit. (European Union products only).
2.
Installation, service, maintenance and repair of this unit must be performed by a certified
technician.
3.
Product uninstallation and recycling must be performed by a certified technician.
4.
For equipment that contains uorinated greenhouse gases in quantities of 5 tonnes of CO equivalent or more, but of less than 50 tonnes of CO equivalent, If the system has a leak­detection system installed, it must be checked for leaks at least every 24 months.
2
2
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
R32
Refrigerant Type
Installation Height H0(m)
LFL(kg/m )
3
Floor Area (m )
2
0.306
0.6
1.0
1.8
2.2
4
0.68
1.14
2.05
2.50
7
0.90
1.51
2.71
3.31
10
1.08
1.80
3.24
3.96
15
1.32
2.20
3.97
4.85
20
1.53
2.54
4.58
5.60
30
1.87
3.12
5.61
6.86
50
2.41
4.02
7.24
8.85
Max Refrigerant Charge (kg)
R32
LFL(kg/m )
3
Charge Amount in kg
0.306
0.6
1.0
1.8
2.2
1.224 1.836
29
10
3
2
2.448
51
19
6
4
3.672
116
42
13
9
4.896
206
74
23
15
6.12
321
116
36
24
7.956
543
196
60
40
Min. Room Area (m )
2
Minimum Room Area ( m )
2
Refrigerant Type
Installation Height H0(m)
Page 8
CAUTION
CAUTION
CAUTION
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
This symbol shows that information is available such as the operating manual or installation manual.
This symbol shows that this appliance uses a ammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of re.
This symbol shows that the operation manual should be read carefully.
WARNING
CAUTION
Explanation of symbols displayed on the indoor unit or outdoor unia (applicable to the unit adopts R32/R290 Refrigerant only):
Accessories
2
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.
Name Shape Quantity
Indoor unit installation
Installation paper template (some models)
1
Refrigeration Fittings
Insulation for gas pipe tting (some models)
Insulation for liquid pipe tting (some models)
1
Drainpipe Fittings
Outlet pipe sheath (some models)
1
Outlet pipe clasp (some models)
1
Drain joint (some models)
1
Seal ring (some models)
1
Installation Accessory (some models)
Ceiling hook
Copper nut (some units)
4
2
Suspension bolt
4
Throttle (some units)
1
Anti-shock rubber
1
1
1
1
1
Owner’s manual Installation manual
1
Optional accessories
There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller. This indoor unit requires installation of an optional decoration panel.
EMC Magnetic Ring (some models)
Magnetic ring (wrap the electric wires S1 & S2 ( P & Q & E ) around the magnetic ring twice)
Magnetic ring (Hitch it on the connective cable between indoor unit and outdoor unit after installation.)
S1&S2(P&Q&E)
Used to make the connective pipes between indoor and outdoor units.
Others
Page 9
Accessories
2
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.
Name Shape Quantity
Indoor unit installation
Installation paper template (some models)
1
Refrigeration Fittings
Insulation for gas pipe tting (some models)
Insulation for liquid pipe tting (some models)
1
Drainpipe Fittings
Outlet pipe sheath (some models)
1
Outlet pipe clasp (some models)
1
Drain joint (some models)
1
Seal ring (some models)
1
Installation Accessory (some models)
Ceiling hook
Copper nut (some units)
4
2
Suspension bolt
4
Throttle (some units)
1
Anti-shock rubber
1
1
1
1
1
Owner’s manual Installation manual
1
Optional accessories
There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller. This indoor unit requires installation of an optional decoration panel.
EMC Magnetic Ring (some models)
Magnetic ring (wrap the electric wires S1 & S2 ( P & Q & E ) around the magnetic ring twice)
Magnetic ring (Hitch it on the connective cable between indoor unit and outdoor unit after installation.)
S1&S2(P&Q&E)
Used to make the connective pipes between indoor and outdoor units.
Others
Page 10
Indoor Unit Installation
3
Indoor Unit Parts
(within indoor unit)
Drain pipe
Drain pump
Air outlet
Air inlet
Display panel
Front grille
Louver
Refrigerant pipe
Fig. 3.1
Safety Precautions
WARNING
Securely install the indoor unit on a
structure that can sustain its weight. If the structure is too weak, the unit may fall causing personal injury, unit and property damage, or even death.
• Install the indoor unit at a height of more than 2.5m (8’) above the floor.
DO NOT install the indoor unit in a bathroom or laundry room as excessive moisture can short the unit and corrode the wiring.
CAUTION
• Install the indoor and outdoor units, cables and wires at least 1m (3.2’) from televisions or radios to prevent static or image distortion. Depending on the appliances, a 1m (3.2’) distance may not be sufficient.
•If the indoor unit is installed on a metal part of the building, it must be grounded.
Indoor Unit Installation Instructions
NOTE: Panel installation should be done
after piping and wiring.
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following requirements:
o The unit is at least 1m (39”) from the nearest
wall.
o There is enough room for installation and
maintenance.
o There is enough room for the connecting
pipe and drainpipe.
o The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
o The air inlet and outlet are not impeded. o The airflow can fill the entire room. o There is no direct radiation from heaters.
CAUTION
DO NOT install the unit in the following
locations:
In areas with oil drilling or fracking In coastal areas with high salt content in
the air
In areas with caustic gases in the air, such
as near hot springs
In areas with power fluctuations, such as
factories
In enclosed spaces, such as cabinets In kitchens that use natural gas
In areas with strong electromagnetic waves In areas that store flammable materials or gas
In rooms with high humidity, such as
bathrooms or laundry rooms
RECOMMENDED DISTANCES BETWEEN THE INDOOR UNIT AND THE CEILING
The distance between the mounted indoor unit and the internal ceiling should meet the following specifications. (See Fig. 3.2)
Connecting point
of drain pipe
Connecting point of refrigerant pipe (liquid side)
Connecting point of refrigerant pipe (gas side)
Front panel
Ground
Ceiling board
>2.5m / 8.2’
60cm / 23.6” (Ceiling hole)
Ceiling
Fig. 3.2
>29cm / 11.4”
26cm / 10.2”
Page 11
Indoor Unit Installation Instructions
NOTE: Panel installation should be done
after piping and wiring.
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following requirements:
o The unit is at least 1m (39”) from the nearest
wall.
o There is enough room for installation and
maintenance.
o There is enough room for the connecting
pipe and drainpipe.
o The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
o The air inlet and outlet are not impeded. o The airflow can fill the entire room. o There is no direct radiation from heaters.
CAUTION
DO NOT install the unit in the following
locations:
In areas with oil drilling or fracking In coastal areas with high salt content in
the air
In areas with caustic gases in the air, such
as near hot springs
In areas with power fluctuations, such as
factories
In enclosed spaces, such as cabinets In kitchens that use natural gas
In areas with strong electromagnetic waves In areas that store flammable materials or gas
In rooms with high humidity, such as
bathrooms or laundry rooms
RECOMMENDED DISTANCES BETWEEN THE INDOOR UNIT AND THE CEILING
The distance between the mounted indoor unit and the internal ceiling should meet the following specifications. (See Fig. 3.2)
Connecting point
of drain pipe
Connecting point of refrigerant pipe (liquid side)
Connecting point of refrigerant pipe (gas side)
Front panel
Ground
Ceiling board
>2.5m / 8.2’
60cm / 23.6” (Ceiling hole)
Ceiling
Fig. 3.2
>29cm / 11.4”
26cm / 10.2”
Page 12
CAUTION
The unit body should align perfectly with the hole. Ensure that the unit and the hole are the same size before moving on.
2. Drill 4 holes 5cm (2”) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
3. Using a hammer, insert the ceiling hooks into the pre-drilled holes. Secure the bolt using the included washers and nuts.
4. Install the four suspension bolts (See Fig. 3.4).
Step 2: Hang indoor unit.
1. Use the included paper template to cut a rectangular hole in the ceiling, leaving at least 1m (39”) on all sides. The hole will be 60x60cm (23.6x23.6”) big. Be sure to mark the areas where ceiling hook holes will be drilled.
Fig. 3.4
Fig. 3.3
545mm / 21.5” (Suspension bolt)
570mm / 22.4”(Body)
647mm / 25.5”(Ceiling opening)
523mm / 20.6”
(Suspension bolt)
570mm / 22.4” (Body)
647mm / 25.5” (Ceiling opening)
Refrigerant piping side
Drain hose side
>1m / 39”
>1m / 39”
>1m / 39”
>1m / 39”
5. Mount the indoor unit. You will need two people to lift and secure it. Insert suspension bolts into the unit’s hanging holes. Fasten them using the included washers and nuts (See Fig. 3.5).
Fig. 3.5
NOTE: The bottom of the unit should be
24mm (0.9”) higher than the ceiling board. Generally, L (indicated in Fig. 3.6) should be half the length of the suspension bolt or long enough to prevent the nuts from coming off.
Fig. 3.6
CAUTION
Ensure that the unit is completely level. Improper installation can cause the drain pipe to back up into the unit or water leakage.
Wall
Ceiling board
Main body
24mm (0.9”)
L
NOTE: Ensure that the indoor unit is level. The unit is equipped with a built-in drain pump and oat switch. If the unit is tilted against the direction of condensate ows (the drainpipe side is raised), the oat switch may malfunction and cause water to leak.
Water level
Fig. 3.7
NOTE FOR NEW HOME INSTALLATION
When installing the unit in a new home, the ceiling hooks can be embedded in advance. Make sure that the hooks do not come loose due to concrete shrinkage. After installing the indoor unit, fasten the installation paper template onto the unit with bolts (M6X12) to determine in advance the dimension and position of the opening on the ceiling. Follow the instructions above for the remainder of the installation.
Installation template
M6 x 12 Bolts
Main body
Fig. 3.8
Page 13
5. Mount the indoor unit. You will need two people to lift and secure it. Insert suspension bolts into the unit’s hanging holes. Fasten them using the included washers and nuts (See Fig. 3.5).
Fig. 3.5
NOTE: The bottom of the unit should be
24mm (0.9”) higher than the ceiling board. Generally, L (indicated in Fig. 3.6) should be half the length of the suspension bolt or long enough to prevent the nuts from coming off.
Fig. 3.6
CAUTION
Ensure that the unit is completely level. Improper installation can cause the drain pipe to back up into the unit or water leakage.
Wall
Ceiling board
Main body
24mm (0.9”)
L
NOTE: Ensure that the indoor unit is level. The unit is equipped with a built-in drain pump and oat switch. If the unit is tilted against the direction of condensate ows (the drainpipe side is raised), the oat switch may malfunction and cause water to leak.
Water level
Fig. 3.7
NOTE FOR NEW HOME INSTALLATION
When installing the unit in a new home, the ceiling hooks can be embedded in advance. Make sure that the hooks do not come loose due to concrete shrinkage. After installing the indoor unit, fasten the installation paper template onto the unit with bolts (M6X12) to determine in advance the dimension and position of the opening on the ceiling. Follow the instructions above for the remainder of the installation.
Installation template
M6 x 12 Bolts
Main body
Fig. 3.8
Page 14
Outdoor Unit Installation
Outdoor Unit Installation Instructions
Step 1: Select installation location.
The outdoor unit should be installed in the location that meets the following requirements:
o Place the outdoor unit as close to the indoor
unit as possible.
o Ensure that there is enough room for
installation and maintenance.
o The air inlet and outlet must not be
obstructed or exposed to strong wind.
o Ensure the location of the unit will not be
subject to snowdrifts, accumulation of leaves or other seasonal debris. If possible, provide an awning for the unit. Ensure the awning does not obstruct airflow.
o The installation area must be dry and well
ventilated.
o There must be enough room to install the
connecting pipes and cables and to access them for maintenance.
o The area must be free of combustible gases
and chemicals.
o
The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length.
o If possible, DO NOT install the unit where it
is exposed to direct sunlight.
o If possible, make sure the unit is located far
away from your neighbors’ property so that the noise from the unit will not disturb them.
o If the location is exposed to strong winds (for
example: near a seaside), the unit must be placed against the wall to shelter it from the wind. If necessary, use an awning. (See Fig. 4.1 & 4.2)
o Install the indoor and outdoor units, cables
and wires at least 1 meter from televisions or radios to prevent static or image distortion. Depending on the radio waves, a 1 meter distance may not be enough to eliminate all interference.
Strong wind
Strong wind
Strong wind
Fig. 4.1
Fig. 4.2
Step 2: Install outdoor unit.
Fix the outdoor unit with anchor bolts (M10)
>60cm / 23.6”
Fix with bolts
CAUTION
Be sure to remove any obstacles that
may block air circulation.
Make sure you refer to Length
Specifications to ensure there is enough room for installation and maintenance.
Fig. 4.3
4
Page 15
Air Outlet
(Wall or obstacle)
H
D
W
Air inlet
Air inlet
Air inlet
Air inlet
(Wall or obstacle)
Table 4.1: Length Specications of Split
Type Outdoor Unit (unit: mm/inch)
Table 4.2: Length Specications of Vertical
Discharge Outdoor Unit (unit: mm/inch)
MODEL
DIMENSIONS
W H D
18 633/25 554/21.8554/21.8
24 633/25 554/21.8554/21.8
36 759/29.8 554/21.8554/21.8
36 633/25 600/23.6600/23.6
48 759/29.8 710/28710/28
60 843/33 710/28710/28
Split Type Outdoor Unit
(Refer to Fig 4.4, 4.5, 4.6, 4.10 and Table 4.1)
Vertical Discharge Type Outdoor Unit
(Refer to Fig 4.7, 4.8, 4.9 and Table 4.2)
Fig. 4.7
Fig. 4.8
Fig. 4.9
Fig. 4.6
Fig. 4.5
A
B
D
Fig. 4.4
Outdoor Unit Dimensions
W x H x D
Mounting Dimensions
Distance A Distance B
760x590x285 (29.9x23.2x11.2) 530 (20.85) 290 (11.4)
810x558x310 (31.9x22x12.2) 549 (21.6) 325 (12.8)
845x700x320 (33.27x27.5x12.6) 560 (22) 335 (13.2)
900x860x315 (35.4x33.85x12.4) 590 (23.2) 333 (13.1)
945x810x395 (37.2x31.9x15.55) 640 (25.2) 405 (15.95)
990x965x345 (38.98x38x13.58) 624 (24.58) 366 (14.4)
946x810x420 (37.24x31.9x16.53) 673 (26.5)
403 (15.87)
946x810x410 (37.24x31.9x16.14) 673 (26.5)
403 (15.87)
952x1333x410 (37.5x52.5x16.14) 634 (24.96)
404 (15.9)
952x1333x415 (37.5x52.5x16.34) 634 (24.96)
404 (15.9)
845x702x363 (33.27x27.6x14.3)
540 (21.26)
350 (13.8)
938x1369x392 (36.93x53.9x15.43) 634 (24.96) 404 (15.9)
900x1170x350 (35.4x46x13.8) 590 (23.2) 378 (14.88)
800x554x333 (31.5x21.8x13.1) 514 (20.24) 340 (13.39)
>152.4cm / 60”
>45.7cm / 18” >45.7cm / 18”
>45.7cm / 18”
>45.7cm / 18”
W
H
W
H
Outdoor Unit Types and Specifications
Page 16
M
N
P
30 cm / 11.8” from back wall
60 cm / 23.6” on right
60 cm / 23.6” above
30 cm / 11.8” on left
200 cm / 78” in front
NOTE: The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 4.10)
Fig. 4.10
Fig. 4.11
NOTE: Make sure the water drains to a safe
location where it will not cause water damage or a slipping hazard.
Seal
Drain joint
(A) (B)
Base pan hole of outdoor unit
Seal
Fig. 4.12
Notes On Drilling Hole In Wall
You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.
1. Determine the location of the wall hole based on the location of the outdoor unit.
2. Using a 65-mm (2.5”) core drill, drill a hole in the wall.
NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.
3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you nish the installation process.
Fig. 5.11
L
H
300 cm / 118” or more
A
60 cm / 23.6”
or more
150 cm / 59”
or more
25 cm / 9.8”
or more
25 cm / 9.8”
or more
Rows of series installation
L H
L 1/2H
L A
25 cm / 9.8” or more
1/2H < L H
30 cm / 11.8” or more
L > H
Can not be installed
Table 4.3 The relations between H, A and L are as follows.
Drain Joint Installation
If the drain joint comes with a rubber seal (see Fig. 4.12 - A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. 4.12 - B ), do the following:
Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
NOTE ON DRAINPIPE INSTALLATION
When using an extended drainpipe, tighten the indoor connection with an additional protection tube to prevent it from pulling loose.
The drainpipe should slope downward at a gradient of at least 1/100 to prevent water from flowing back into the air conditioner.
To prevent the pipe from sagging, space hanging wires every 1-1.5m (40-59”).
If the outlet of the drainpipe is higher than the body’s pump joint, provide a lift pipe for the exhaust outlet of the indoor unit. The lift pipe must be installed no higher than 75cm (29.5”) from the ceiling board and the distance between the unit and the lift pipe must be less than 30cm (11.8”). Incorrect installation could cause water to flow back into the unit and flood.
To prevent air bubbles, keep the drain hose level or slightly tiled up (<75mm / 3”).
The drainpipe is used to drain water from the unit. Improper installation may cause unit and property damage.
CAUTION
Insulate all piping to prevent condensation, which could lead to water damage.
If the drainpipe is bent or installed
incorrectly, water may leak and cause a malfunction of the water- level switch.
In HEAT mode, the outdoor unit will
discharge water. Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage due to frozen drain water.
DO NOT pull the drainpipe forcefully as
this could cause it to disconnect.
NOTE ON PURCHASING PIPES
This installation requires a polyethylene tube (outside diameter = 3.7-3.9cm, inside diameter = 3.2cm), which can be obtained at your local hardware store or from your dealer.
Indoor Drainpipe Installation
Install the drainpipe as shown in Fig 5.2.
1. Cover the drainpipe with heat insulation to prevent condensation and leakage.
2. Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the mouth of the hose and clip it rmly with a pipe clasp. (Fig 5.1)
Drainpipe connecting port
Drain hose
Metal clamp
Insulation
Fig. 5.1
Drainpipe Installation
5
Downward slope
1/100
1-1.5m
(39-59”)
Fig. 5.2
Fig. 5.3
≤75cm (29.5”)
Ceiling
1 - 1.5m
(39-59”)
0 - 75mm
(3”)
≤30cm (11.8”)
≤53cm (20.8”)
22cm (8.6”)
Page 17
NOTE ON DRAINPIPE INSTALLATION
When using an extended drainpipe, tighten the indoor connection with an additional protection tube to prevent it from pulling loose.
The drainpipe should slope downward at a gradient of at least 1/100 to prevent water from flowing back into the air conditioner.
To prevent the pipe from sagging, space hanging wires every 1-1.5m (40-59”).
If the outlet of the drainpipe is higher than the body’s pump joint, provide a lift pipe for the exhaust outlet of the indoor unit. The lift pipe must be installed no higher than 75cm (29.5”) from the ceiling board and the distance between the unit and the lift pipe must be less than 30cm (11.8”). Incorrect installation could cause water to flow back into the unit and flood.
To prevent air bubbles, keep the drain hose level or slightly tiled up (<75mm / 3”).
The drainpipe is used to drain water from the unit. Improper installation may cause unit and property damage.
CAUTION
Insulate all piping to prevent condensation, which could lead to water damage.
If the drainpipe is bent or installed
incorrectly, water may leak and cause a malfunction of the water- level switch.
In HEAT mode, the outdoor unit will
discharge water. Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage due to frozen drain water.
DO NOT pull the drainpipe forcefully as
this could cause it to disconnect.
NOTE ON PURCHASING PIPES
This installation requires a polyethylene tube (outside diameter = 3.7-3.9cm, inside diameter = 3.2cm), which can be obtained at your local hardware store or from your dealer.
Indoor Drainpipe Installation
Install the drainpipe as shown in Fig 5.2.
1. Cover the drainpipe with heat insulation to prevent condensation and leakage.
2. Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the mouth of the hose and clip it rmly with a pipe clasp. (Fig 5.1)
Drainpipe connecting port
Drain hose
Metal clamp
Insulation
Fig. 5.1
Drainpipe Installation
5
Downward slope
1/100
1-1.5m
(39-59”)
Fig. 5.2
Fig. 5.3
≤75cm (29.5”)
Ceiling
1 - 1.5m
(39-59”)
0 - 75mm
(3”)
≤30cm (11.8”)
≤53cm (20.8”)
22cm (8.6”)
Page 18
3.
Using a 65-mm (2.5”) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig. 5.5). Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you nish the installation process.
Wall
Indoor
Outdoor
≈ 12mm / 0.5 inch
Fig. 5.5
NOTE: When drilling the wall hole, make sure
to avoid wires, plumbing, and other sensitive components.
4. Pass the drain hose through the wall hole. Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.
NOTE: The drainpipe outlet should be at least 5cm (1.9”) above the ground. If it touches the ground, the unit may become blocked and malfunction. If you discharge the water directly into a sewer, make sure that the drain has a U or S pipe to catch odors that might otherwise come back into the house.
NOTE: When connecting multiple drainpipes, install the pipes as shown in Fig 5.4.
0-53cm (20.8”)
≥10cm
(4”)
Fig. 5.4
Refrigerant Piping Connection
Safety Precautions
WARNING
All eld piping must be completed by a licensed technician and must comply with the local and national regulations.
When the air conditioner is installed in a
small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. If the refrigerant leaks and its concentration exceeds its proper limit, hazards due to lack of oxygen may result.
When installing the refrigeration system,
ensure that air, dust, moisture or foreign substances do not enter the refrigerant circuit. Contamination in the system may cause poor operating capacity, high pressure in the refrigeration cycle, explosion or injury.
Ventilate the area immediately if there is refrigerant leakage during the installation. Leaked refrigerant gas is both toxic and flammable. Ensure there is no refrigerant leakage after completing the installation work.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in Table 6.1:
Table 6.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of model Capacity
(Btu/h)
Length of
piping
Maximum drop
height
North America, Australia and the eu frequency conversion Split Type
<15K 25/82 10/32.8
15K - <24K 30/98.4 20/65.6
24K - <36K 50/164 25/82
36K - 60K 65/213 30/98.4
Other Split Type
12K 15/49 8/26
18K-24K 25/82 15/49
30K-36K 30/98.4 20/65.6
42K-60K 50/164 30/98.4
6
Fig. 6.1
Oil traps
CAUTION
If the indoor unit is installed higher than the outdoor unit:
An oil trap should be installed every 10m (32.8ft) of vertical suction line riser. (See Fig. 6.1)
-If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas piping can prevent this.
The indoor unit is installed higher than the outdoor unit
Page 19
Refrigerant Piping Connection
Safety Precautions
WARNING
All eld piping must be completed by a licensed technician and must comply with the local and national regulations.
When the air conditioner is installed in a
small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. If the refrigerant leaks and its concentration exceeds its proper limit, hazards due to lack of oxygen may result.
When installing the refrigeration system,
ensure that air, dust, moisture or foreign substances do not enter the refrigerant circuit. Contamination in the system may cause poor operating capacity, high pressure in the refrigeration cycle, explosion or injury.
Ventilate the area immediately if there is refrigerant leakage during the installation. Leaked refrigerant gas is both toxic and flammable. Ensure there is no refrigerant leakage after completing the installation work.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in Table 6.1:
Table 6.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of model Capacity
(Btu/h)
Length of
piping
Maximum drop
height
North America, Australia and the eu frequency conversion Split Type
<15K 25/82 10/32.8
15K - <24K 30/98.4 20/65.6
24K - <36K 50/164 25/82
36K - 60K 65/213 30/98.4
Other Split Type
12K 15/49 8/26
18K-24K 25/82 15/49
30K-36K 30/98.4 20/65.6
42K-60K 50/164 30/98.4
6
Fig. 6.1
Oil traps
CAUTION
If the indoor unit is installed higher than the outdoor unit:
An oil trap should be installed every 10m (32.8ft) of vertical suction line riser. (See Fig. 6.1)
-If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas piping can prevent this.
The indoor unit is installed higher than the outdoor unit
Page 20
Refrigerant Piping Connection Instructions
CAUTION
The branching pipe must be installed
horizontally. An angle of more than 10° may cause malfunction.
DO NOT install the connecting pipe until
both indoor and outdoor units have been installed.
Insulate both the gas and liquid piping to
prevent water leakage.
Step1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.
For R32/R290 refrigerantmodels, the pipe connection points must be placed outside of room. The connection pipes can not be reused.
1. Measure the distance between the indoor
and outdoor units.
2. Using a pipe cutter, cut the pipe a little
longer than the measured distance.
CAUTION
DO NOT deform pipe while cutting. Be extra
careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
1. Make sure that the pipe is cut at a perfect
90° angle. Refer to Fig. 6.3 for examples of bad cuts.
Oblique
Rough
Warped
90°
Fig. 6.3
Fig. 6.2
CAUTION
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be upsized. Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below7.62m/s (1500fpm (feet per minute)), oil return will be decreased. An oil trap should be installed every 6m(20ft) of vertical suction line riser. (See Fig. 6.2)
The outdoor unit is installed higher than the indoor unit
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 6.3.
Table 6.3: PIPING EXTENSION BEYOND FLARE FORM
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high-pressure pipe.
1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you will connect.
Indoor unit tubing
Flare nut
Pipe
Fig. 6.8
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 6.3.
NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.
Fig. 6.9
Step 2: Remove burrs.
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Fig. 6.4
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring. See Fig. 6.5
Flare nut
Copper pipe
Fig. 6.5
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form
Pipe
Fig. 6.6
Pipe gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min. Max.
Ø 6.4
R0.4~0.8
45
°
±
2
90
°
±
4
A
Fig. 6.7
Ø 9.5
Ø 12.7
Ø 15.9
18-20N.m
(183-204kgf.cm)
8.4/0.33 8.7/0.34
25-26 N.m
(255-265 kgf.cm)
13.2/0.52 13.5/0.53
35-36 N.m
(357-367 kgf.cm)
16.2/0.64 16.5/0.65
45-47 N.m
(459-480 kgf.cm)
19.2/0.76 19.7/0.78
Page 21
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 6.3.
Table 6.3: PIPING EXTENSION BEYOND FLARE FORM
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high-pressure pipe.
1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you will connect.
Indoor unit tubing
Flare nut
Pipe
Fig. 6.8
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 6.3.
NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.
Fig. 6.9
Step 2: Remove burrs.
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Fig. 6.4
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring. See Fig. 6.5
Flare nut
Copper pipe
Fig. 6.5
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form
Pipe
Fig. 6.6
Pipe gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min. Max.
Ø 6.4
R0.4~0.8
45
°
±
2
90
°
±
4
A
Fig. 6.7
Ø 9.5
Ø 12.7
Ø 15.9
18-20N.m
(183-204kgf.cm)
8.4/0.33 8.7/0.34
25-26 N.m
(255-265 kgf.cm)
13.2/0.52 13.5/0.53
35-36 N.m
(357-367 kgf.cm)
16.2/0.64 16.5/0.65
45-47 N.m
(459-480 kgf.cm)
19.2/0.76 19.7/0.78
Page 22
Installation Of The Throttle. (Some Models)
Indoor
Indoor
Indoor
Outdoor
Outdoor
Outdoor
1 Throttle 2 Liquid pipe 3 Gas pipe
Precautions
- For ensuring throttled efciency, please mount the throttle as horizontally as possible.
- Wrap the supplied anti-shock rubber at external of the throttle for denoise.
1 Anti-shock rubber 2 Throttle
CAUTION
Ensure to wrap insulation around the
piping. Direct contact with the bare piping may result in burns or frostbite.
Make sure the pipe is properly connected.
Over tightening may damage the bell mouth and under tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
min-radius 10cm (3.9”)
Fig. 6.10
6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.
NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
7. Thread this pipeline through the wall and connect it to the outdoor unit.
8. Insulate all the piping, including the valves of the outdoor unit.
9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).
Wiring
7
Safety Precautions
WARNING
Be sure to disconnect the power supply before working on the unit.
All electrical wiring must be done
according to local and national regulations.
Electrical wiring must be done by a
qualied technician. Improper connections may cause electrical malfunction, injury and fire.
An independent circuit and single outlet must be used for this unit. DO NOT plug
another appliance or charger into the same outlet. If the electrical circuit capacity is not enough or there is a defect in the electrical work, it can lead to shock, fire, unit and property damage.
Connect the power cable to the terminals and fasten it with a clamp. An insecure
connection may cause fire.
Make sure that all wiring is done correctly and the control board cover is properly
installed. Failure to do so can cause overheating at the connection points, fire, and electrical shock.
Ensure that main supply connection is
made through a switch that disconnects all poles, with contact gap of a least 3mm (0.118”).
DO NOT modify the length of the power cord or use an extension cord.
CAUTION
Connect the outdoor wires before connecting the indoor wires.
Make sure you ground the unit. The
grounding wire should be away from gas pipes, water pipes, lightning rods, telephone or other grounding wires. Improper grounding may cause electrical shock.
DO NOT connect the unit with the power
source until all wiring and piping is completed.
Make sure that you do not cross your
electrical wiring with your signal wiring, as this can cause distortion and interference.
Follow these instructions to prevent distortion when the compressor starts:
No other equipment should be connected to the same power circuit.
The unit’s power information can be found on the rating sticker on the product.
The unit must be connected to the main
outlet. Normally, the power supply must have a low output impedance of 32 ohms.
NOTE: The fuse is made of ceramic.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner s circuit board(PCB) is designed with a fuse to provide overcurrent protection. The specications of the fuse are printed on the circuit board, such as: Indoor unit: T3.15A/250VAC, T5A/250VAC. (applicable for unit adopts R32 refrigerant) Outdoor unit: T20A/250VAC.
,
Page 23
Wiring
7
Safety Precautions
WARNING
Be sure to disconnect the power supply before working on the unit.
All electrical wiring must be done
according to local and national regulations.
Electrical wiring must be done by a
qualied technician. Improper connections may cause electrical malfunction, injury and fire.
An independent circuit and single outlet must be used for this unit. DO NOT plug
another appliance or charger into the same outlet. If the electrical circuit capacity is not enough or there is a defect in the electrical work, it can lead to shock, fire, unit and property damage.
Connect the power cable to the terminals and fasten it with a clamp. An insecure
connection may cause fire.
Make sure that all wiring is done correctly and the control board cover is properly
installed. Failure to do so can cause overheating at the connection points, fire, and electrical shock.
Ensure that main supply connection is
made through a switch that disconnects all poles, with contact gap of a least 3mm (0.118”).
DO NOT modify the length of the power cord or use an extension cord.
CAUTION
Connect the outdoor wires before connecting the indoor wires.
Make sure you ground the unit. The
grounding wire should be away from gas pipes, water pipes, lightning rods, telephone or other grounding wires. Improper grounding may cause electrical shock.
DO NOT connect the unit with the power
source until all wiring and piping is completed.
Make sure that you do not cross your
electrical wiring with your signal wiring, as this can cause distortion and interference.
Follow these instructions to prevent distortion when the compressor starts:
• No other equipment should be connected to the same power circuit.
• The unit’s power information can be found on the rating sticker on the product.
• The unit must be connected to the main outlet. Normally, the power supply must
have a low output impedance of 32 ohms.
NOTE: The fuse is made of ceramic.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner s circuit board(PCB) is designed with a fuse to provide overcurrent protection. The specications of the fuse are printed on the circuit board, such as: Indoor unit: T3.15A/250VAC, T5A/250VAC. (applicable for unit adopts R32 refrigerant) Outdoor unit: T20A/250VAC.
,
Page 24
b. Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal about 15cm (5.9”) of the wires inside.
c. Strip the insulation from the ends of the
wires.
d.
Using a wire crimper, crimp u-lugs on the
ends of the wires.
NOTE: While connecting the wires, please strictly follow the wiring diagram (found inside the electrical box cover).
2. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, disassemble the bolts from the maintenance board and remove the protection board. (See Fig. 7.1)
3.
Connect the u-lugs to the terminals
Match the wire colors/labels with the labels on the terminal block, and rmly screw the u-lug of each wire to its corresponding terminal.
4.
Clamp down the cable with designated cable
clamp.
5. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.
6.
Reinstall the cover of the electric control box.
Outdoor Unit Wiring
Power Specications
WARNING
Before performing any electrical or wiring work, turn off the main power to the system.
1. Prepare the cable for connection a. You must first choose the right cable size
before preparing it for connection. Be sure to use H07RN-F cables.
Table 7.1: Minimum Cross-Sectional Area of
Power and Signal Cables North America
Rated Current of
Appliance (A)
AWG
7 18
7 - 13 16 13 - 18 14 18 - 25 12 25 - 30 10
Table 7.2: Other Regions
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area (mm²)
6 0.75
6 - 10 1 10 - 16 1.5 16 - 25 2.5
25- 32 4 32 - 45 6
Cover
Screw
Fig. 7.1
Fig. 7.2
1 Control box lid 2 Wiring diagram label 3 Power supply terminal block 4 Clamp for wiring 5 Wiring between units 6 Plastic cover 7 Clamp (eld supply)
Indoor Unit Wiring
1.
Prepare the cable for connection
a.
Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal about 15cm (5.9”) of the wires inside.
b.
Strip the insulation from the ends of the
wires.
c. Using wire crimper, crimp the u-lugs to
the ends of the wires.
2.
Open the front panel of the indoor unit. Using a screwdriver, remove the cover of the electric control box on your indoor unit.
3.
Thread the power cable and the signal cable through the wire outlet.
4.
Connect the u-lugs to the terminals. Match the wire colors/labels with the labels on
the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.
CAUTION
While connecting the wires, please strictly
follow the wiring diagram.
The refrigerant circuit can become very hot.
Keep the interconnection cable away from the copper tube.
5. Clamp down cable with the designated cable clamp to secure it in place. The cable should not be loose, and should not pull on the u-lugs.
6. Reinstall the electric box cover and the front panel of the indoor unit.
Page 25
Indoor Unit Wiring
1.
Prepare the cable for connection
a.
Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal about 15cm (5.9”) of the wires inside.
b.
Strip the insulation from the ends of the
wires.
c. Using wire crimper, crimp the u-lugs to
the ends of the wires.
2.
Open the front panel of the indoor unit. Using a screwdriver, remove the cover of the electric control box on your indoor unit.
3.
Thread the power cable and the signal cable through the wire outlet.
4.
Connect the u-lugs to the terminals. Match the wire colors/labels with the labels on
the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.
CAUTION
While connecting the wires, please strictly
follow the wiring diagram.
The refrigerant circuit can become very hot.
Keep the interconnection cable away from the copper tube.
5. Clamp down cable with the designated cable clamp to secure it in place. The cable should not be loose, and should not pull on the u-lugs.
6. Reinstall the electric box cover and the front panel of the indoor unit.
Page 26
Air Evacuation
Safety Precautions
CAUTION
• Use a vacuum pump with a gauge reading lower than -0.1MPa and an air discharge capacity above 40L/min.
• The outdoor unit does not need vacuuming. DO NOT open the outdoor unit’s gas and
liquid stop valves.
• Ensure that the Compound Meter reads
-0.1MPa or below after 2 hours. If after three hours of operation and the gauge reading is still above -0.1MPa, check if there is a gas leak or water inside the pipe. If there is no leakage, perform another evacuation for 1 or 2 hours.
DO NOT use refrigerant gas to evacuate
the system.
Evacuation Instructions
Before using manifold gauge and vacuum pump, read their operation manuals to familiarize yourself with how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
Fig. 8.1
1. Connect the charge hose of the manifold gauge to service port on the outdoor unit’s low pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge.Keep the High Pressure side closed.
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa).
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has been no change in system pressure.
NOTE: If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.
8. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then close the valve after 5 seconds.
Flare nut
Cap
Valve body
Valve stem
Fig. 8.2
9. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. The Pressure Gauge should read slightly higher than atmospheric pressure.
10.Remove the charge hose from the service port.
11.Using hexagonal wrench, fully open both the high pressure and low pressure valves.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.
12.Tighten valve caps by hand, then tighten it using the proper tool.
8
Note On Adding Refrigerant
CAUTION
Refrigerant charging must be performed after wiring, vacuuming and the leak test.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage or impact the unit’s function.
Charging with unsuitable substances may cause explosions or accidents. Ensure that the
appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use protective gear when charging
the system.
For the R290 or R32 refrigerant model, make sure the condtions within the area have been
made safe by control of ammable material when the refrigerant added into air conditioner.
DO NOT mix refrigerants types.
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is
7.5m (25’) In other areas, the standard pipe length is 5m (16‘). The additional refrigerant to be charged can be calculated using the following formula:
Liquid Side Diameter
R32 :
(Total pipe length - standard pipe length)x 12g(0.13oZ)/m(ft)
(Total pipe length - standard pipe length)x 24g(0.26oZ)/m(ft)
(Total pipe length - standard pipe length)x 40g(0.42oZ)/m(ft)
φ6.35(1/4”) φ9.52(3/8”) φ12.7(1/2”)
R22 (orice tube in the indoor unit):
(Total pipe length - standard pipe length)x 30g (0.32oZ)/m(ft)
(Total pipe length - standard pipe length)x 65g(0.69oZ)/m(ft)
(Total pipe length - standard pipe length)x 115g(1.23oZ)/m(ft)
R22 (orice tube in the outdoor unit):
(Total pipe length - standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length - standard pipe length) x30(0.32oZ)/m(ft)
(Total pipe length - standard pipe length) x60g(0.64oZ)/m(ft)
(Total pipe length - standard pipe length) x65g(0.69oZ)/m(ft)
R410A: (orice tube in the indoor unit):
(Total pipe length - standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length - standard pipe length) x65g(0.69oZ)/m(ft)
(Total pipe length - standard pipe length) x115g(1.23oZ)/m(ft)
R410A: (orice tube in the outdoor unit):
(Total pipe length - standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length - standard pipe length) x30g(0.32oZ)/m(ft)
Page 27
Note On Adding Refrigerant
CAUTION
• Refrigerant charging must be performed after wiring, vacuuming and the leak test.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage or impact the unit’s function.
• Charging with unsuitable substances may cause explosions or accidents. Ensure that the
appropriate refrigerant is used.
• Refrigerant containers must be opened slowly. Always use protective gear when charging the system.
• For the R290 or R32 refrigerant model, make sure the condtions within the area have been
made safe by control of ammable material when the refrigerant added into air conditioner.
DO NOT mix refrigerants types.
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is
7.5m (25’) In other areas, the standard pipe length is 5m (16‘). The additional refrigerant to be charged can be calculated using the following formula:
Liquid Side Diameter
R32 :
(Total pipe length ­standard pipe length)x 12g(0.13oZ)/m(ft)
(Total pipe length ­standard pipe length)x 24g(0.26oZ)/m(ft)
(Total pipe length ­standard pipe length)x 40g(0.42oZ)/m(ft)
φ6.35(1/4”) φ9.52(3/8”) φ12.7(1/2”)
R22 (orice tube in the indoor unit):
(Total pipe length ­standard pipe length)x 30g (0.32oZ)/m(ft)
(Total pipe length ­standard pipe length)x 65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length)x 115g(1.23oZ)/m(ft)
R22 (orice tube in the outdoor unit):
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length) x30(0.32oZ)/m(ft)
(Total pipe length - standard pipe length) x60g(0.64oZ)/m(ft)
(Total pipe length - standard pipe length) x65g(0.69oZ)/m(ft)
R410A: (orice tube in the indoor unit):
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length ­standard pipe length) x65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length) x115g(1.23oZ)/m(ft)
R410A: (orice tube in the outdoor unit):
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
Page 28
Panel Installation
9
CAUTION
DO NOT place the panel facedown on the
floor, against a wall, or on uneven surfaces.
Step 1: Remove the front grille.
1. Push both of the tabs towards the middle simultaneously to unlock the hook on the grille.
2. Hold the grille at a 45° angle, lift it up slightly and detach it from the main body.
Fig. 9.1
Fig. 9.2
Fig. 9.3
Fig. 9.4
Step 2: Install the panel
Align the indicate "" on the decoration panel to the indicate "" on the unit . Attach the decoration panel to the unit with the supplied screws as shown in gure below.
1 Intake grille 2 Grille hook
1 Decoration panel 2 Screws (M5)(supplied with the panel)
After installing the decoration panel, ensure that there is no space between the unit body and decoration panel. Otherwise air may leak through the gap and cause dewdrop. (See gure below)
Fig. 9.5
Fig. 9.7
Fig. 9.8
Fig. 9.6
Step 3: Mount the intake grille. Step 5: Fasten the control box lid with 2
screws .
Step 6: Close the intake grille, and close the 2 grille hooks.
Ensure that the buckles at the back of the grille be properly seated in the groove of the panel.
Step 4: Connect the 2 wires of the decoration panel to the mainboard of the unit.
Page 29
Fig. 9.5
Fig. 9.7
Fig. 9.8
Fig. 9.6
Step 3: Mount the intake grille. Step 5: Fasten the control box lid with 2
screws .
Step 6: Close the intake grille, and close the 2 grille hooks.
Ensure that the buckles at the back of the grille be properly seated in the groove of the panel.
Step 4: Connect the 2 wires of the decoration panel to the mainboard of the unit.
Page 30
Before Test Run
A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:
a) The indoor and outdoor units are properly
installed.
b) Piping and wiring are properly connected. c) Ensure that there are no obstacles near the
inlet and outlet of the unit that might cause poor performance or product malfunction.
d) The refrigeration system does not leak. e) The drainage system is unimpeded and
draining to a safe location.
f) The heating insulation is properly installed.
The grounding wires are properly connected.
g) h) The length of the piping and the added
refrigerant stow capacity have been recorded.
i) The power voltage is the correct voltage
for the air conditioner.
CAUTION
Failure to perform the test run may result in unit damage, property damage or personal injury.
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit a. Ensure the remote control and its buttons
work properly.
b. Ensure the louvers move properly and can
be changed using the remote control.
c. Double check to see if the room
temperature is being registered correctly.
d. Ensure the indicators on the remote
control and the display panel on the indoor unit work properly.
e. Ensure the manual buttons on the indoor
unit works properly.
f. Check to see that the drainage system is
unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal
noise during operation.
5. For the Outdoor Unit a. Check to see if the refrigeration system is
leaking.
b. Make sure there is no vibration or
abnormal noise during operation.
c. Ensure the wind, noise, and water
generated by the unit do not disturb your neighbors or pose a safety hazard.
6. Drainage Test a. Ensure the drainpipe flows smoothly. New
buildings should perform this test before finishing the ceiling.
b. Remove the test cover. Add 2,000ml of
water to the tank through the attached tube.
c. Turn on the main power switch and run
the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to
see if it makes any unusual noises.
e. Check to see that the water is discharged.
It may take up to one minute before the unit begins to drain depending on the drainpipe.
f. Make sure that there are no leaks in any of
the piping.
g. Stop the air conditioner. Turn off the main
power switch and reinstall the test cover.
NOTE: If the unit malfunctions or does not
operate according to your expectations, please refer to the Troubleshooting section of the Owner’s Manual before calling customer service.
Test Run
10
11
Users in European Countries may be required to properly dispose of this unit. This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment.
DO NOT
dispose of this product as household waste or
unsorted municipal waste.
When disposing of this appliance, you have the following options:
Dispose of the appliance at designated municipal electronic waste collection facility.
When buying a new appliance, the retailer will take back the old appliance free of charge.
The manufacturer will also take back the old appliance free of charge.
Sell the appliance to certified scrap metal dealers.
NOTE: Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water
and enter the food chain.
European Disposal Guidelines
Loading...
+ 82 hidden pages