INVENTOR V4MKI-24UR, V4MKI-36UR, U4MRS-24, U4MRS-36 Installation Manual

• INSTALLATION MANUAL
ENGLISH
FLOOR/CEILING TYPE
MODELS:
V4MKI-24UR/U4MRS-24 V4MKI-36UR/U4MRS-36
Accessories .................................................... 04
b. Indoor Unit Installation Instructions ....... 10
Safety Precautions ..................................... 05
Outdoor Unit Installation ......................... 11
a. Outdoor Unit Installation Instructions ..... 14
b. Outdoor Unit Types and Specifications ... 15
c. Notes on Drilling Hole in Wall .................... 16
Drainpipe Installation ............................... 17
Table of Contents
Installation Manual
Indoor Unit Installation
........................... 09
Installation Overview ............................... 08
1
2
5
3
4
6
Page 3
Refrigerant Piping Connection ...................... 19
A. Notes on Pipe Length and Elevation ............... 19
B. Refrigerant Piping Connection Instructions ... 20
Wiring ................................................. 22
a. Outdoor Unit Wiring ................... 22
b. Indoor Unit Wiring ...................... 23
c. Power Specifications .................... 24
Air Evacuation
................................................ 26
a. Evacuation Instructions ............................... 26
b. Note on Adding Refrigerant ...................... 27
Test Run .......................................................................................... 2829
MC MC
7
8
9
10
L N
(R32/R290 refrigerant )
C au t i o n : R isk of fire
European Disposal Guidelines .......................................................
11
Information servicing...................................................................... 30
12
Page 4
Accessories
1
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and re, or equipment failure.
Name Shape Quantity
Refrigeration Fittings
Soundproof/insulation sheath (some models)
1
Drainpipe Fittings
Outlet pipe sheath (some models)
1
Outlet pipe clasp (some models)
1
Drain joint (some models)
1
Seal ring (some models)
1
EMC Magnetic Ring (some models)
Remote controller & Its Frame (some models)
Magnetic ring (wrap the electric wires S1 & S2 ( P & Q & E ) around the magnetic ring twice)
Magnetic ring (Hitch it on the connective cable between indoor unit and outdoor unit after installation.)
1
1
1
2
1
1
1
1
2
Remote controller
Fixing screw for remote controller holder ST2.9 x 10
Remote controller holder
Dry battery AAA
Owner’s manual
Installation manual
Remote controller illustration
S1&S2(P&Q&E)
Page 5
Safety Precautions
2
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury.
The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.
Failure to observe a caution may result in injury or equipment damage.
WARNING
CAUTION
WARNING
• Carefully read the Safety Precautions before installation.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially
designed air-conditioning units is highly recommended.
This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
• Only trained and certified technicians should install, repair and service this air conditioning unit.
Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment and personal property.
• Strictly follow the installation instructions set forth in this manual.
Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment.
Before you install the unit, consider strong winds, typhoons and earthquakes that might aect your unit and locate it accordingly. Failure to do so could cause the equipment to fail.
After installation, ensure there are no refrigerant leaks and that the unit is operating properly. Refrigerant is both toxic and flammable and poses a serious health and safety risk.
An all-pole disconnection device which has at least 3mm clearances in all poles , and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the xed wiring in accordance with the wiring rules.
Page 6 Page 6
Amount of refrigerant to be charged (kg)
maximum installation height (m)
Minimum room area (m²)
2.048 1.8m 4
2.048 0.6m 35
2.048-3.0 1.8m 8
2.048-3.0 0.6m 80
>3.0 1.8m 9 >3.0
Model (Btu/h)
30000
30000
30000-48000
30000-48000
>48000 >48000 0.6m 80
WARNING
Appliance shall be installed, operated and stored in a room with a oor area larger than X m²,
installation of pipe-work shall be kept to a minimum X m²(Please see the following form ). The appliance shall not be installed in an unventilated space, if that space is smaller than X m² (Please see the following form ).Spaces where refrigerant pipes shall be compliance with national gas regulations.
Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certicate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specication.
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of ammable refrigerants.
Appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specied for operation.
Appliance shall be stored in a room without continuously operating open ames (for example an operating gas appliance) and ignition sources (for example an operating electric heater).
The appliance shall be stored in a room without continuously operating ignition sources
(for example: open ames, an operating gas appliance or an operating electric heater).
Do not pierce or burn.
The appliance shall be stored so as to prevent mechanical damage from occurring.
Be aware that the refrigerants may not contain an odour.
Keep ventilation openings clear of obstruction.
Compliance with national gas regulations shall be observed.
A warning that the appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specied for operation.
Note about Fluorinated Gasses
1. This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
2.
Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3. Product uninstallation and recycling must be performed by a certified technician.
4. If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
CAUTION CAUTION
CAUTION
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
This symbol shows that information is available such as the operating manual or installation manual.
This symbol shows that this appliance uses a ammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of re.
This symbol shows that the operation manual should be read carefully.
WARNING
CAUTION
Explanation of symbols displayed on the indoor unit or outdoor unia (applicable to the unit adopts R32/R290 Refrigerant only):
Page 7
Page 8
Unit Installation
Overview
Installation Overview
3
L N
1
2
3
4
5
MC MC
6
7
Install the indoor unit
(Page 9)
INSTALLATION ORDER
Install the outdoor unit
(Page 14)
Install the drainpipe
(Page 17)
Evacuate the refrigeration system
(Page 26)
Connect the wires
(Page 22)
Connect the refrigerant pipes
(Page 19)
Perform a test run
(Page 28)
Page 9
Indoor Unit
Installation
Air inlet
Display panel
Air outlet
grille
Louver
Installation part
Indoor Unit Installation
4
Indoor Unit Parts
Fig. 4.1
Safety Precautions
WARNING
Securely install the indoor unit on a structure that can sustain its weight. If the structure is too weak, the unit may fall and cause personal injury, unit and property damage, or death.
DO NOT install the indoor unit in a
bathroom or laundry room as excessive moisture can short the unit and corrode the wiring.
CAUTION
Install the indoor and outdoor units, cables, and wires at least 1m (3.2’) from televisions and radios to prevent static or image distortion. Depending on the appliances, a 1m (3.2’) distance may not be sucient.
If the indoor unit is installed on metal, it must be electrically grounded.
Page 10 
Indoor Unit
Installation
Indoor Unit Installation Instructions
NOTE: Panel installation should be performed
after piping and wiring have been completed.
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following requirements:
Enough room exists for installation and
maintenance.
Enough room exists for the connecting the
pipe and drainpipe.
The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
The air inlet and outlet are not blocked.The airflow can fill the entire room.There is no direct radiation from heaters.
CAUTION
DO NOT install the unit in the following
Areas with oil drilling or fracking Coastal areas with high salt content in the
air
Areas with caustic gases in the air, such as
hot springs
Areas that experience power uctuations,
such as factories
Enclosed spaces, such as cabinets Kitchens that use natural gas Areas with strong electromagnetic waves Areas that store flammable materials or gas Rooms with high humidity, such as
bathrooms or laundry rooms
RECOMMENDED DISTANCES BETWEEN THE INDOOR UNIT
The distance between the mounted indoor unit should meet the specications illlustrated in the following diagram. (See Fig. 4.2)
Fig. 4.2
≥35mm
≥1000mm
≥ 35mm
≥ 35mm
locations:
Page 11
Indoor Unit
Installation
Fig. 4.3
Refrigerant pipe
connection
(D. gas side)
Refrigerant pipe
connection
(E. Liquid side)
Drain point
Hook
A
C
D
E
B
Table 4.1: Indoor parts installation size
MODEL(Btu/h) Length of A (mm/inch) Length of B (mm/inch)
18K~24K 1068/42 675/26.6 30K~48K 1285/50.6 675/26.6 36K~48K 1650/65 675/26.6
60K 1650/65 675/26.6
Length of C (mm/inch) Length of D (mm/inch) Length of E (mm/inch)
235/9.3 983/38.7 220/8.7 235/9.3 1200/47.2 220/8.7 235/9.3 1565/61.6 220/8.7 235/9.3 1565/61.6 220/8.7
Page 12
Indoor Unit
Installation
Cut o the roof beam. Strengthen the area at which the cut was
made and consolidate the roof beam.
Fig. 4.6
Fig. 4.7
Fig. 4.8
Original concrete bricks
Steel roof beam structure
Install and use the supporting angle steel directly. (See Fig.4.8)
Fig. 4.4
Wood
Place the square timber traversely over the roof beam, then install the hanging screw bolts. (See Fig.4.4)
Timber over the beam
Roof beam
Hanging screw bolts
Ceiling
Fig. 4.5
New concrete bricks
Inlaying or embedding the screw bolts.
(Blade shape insertion)
(Slide insertion)
Steel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Hanging screw bolt
Hanging bolts
Supporting angle steel
CAUTION
The unit body should align perfectly with the hole. Ensure that the unit and the hole are the same size before moving on.
2.
Install the pipes and lines in the ceiling after
installing the main body. When choosing where to start the, determine the direction of the pipes to be drawn out. In cases where there is a ceiling, position the refrigerant pipes, drain pipes, and indoor and outdoor lines to the connection points before mounting the machine.
3.
The installation of hanging screw bolts.
4. After the selection of installation location, position the refrigerant pipes, drain pipes, and indoor and outdoor wires to the connection points before mounting the machine.
5.
Drill 4 holes 10cm (4”) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
6.
Secure the bolt using the included washers
and nuts.
7.
Install the four suspension bolts.
8.
Mount the indoor unit. You will need two
people to lift and secure it. Insert suspension bolts into the unit’s hanging holes. Fasten them using the included washers and nuts. (See Fig. 4.9).
Fig. 4.9
Step 2: Hang indoor unit
Install the hanging hook with expansible bolt into the concrete to a depth of 45~50mm to prevent loosening.
Page 13
Indoor Unit
Installation
Fig. 4.10
Fig. 4.12
Fig. 4.13
Fig. 4.14
9. Remove the side board and the grille. (See Fig. 4.10).
Fig. 4.11
Screw nut
Washer
Hanging screw bolt
Overhang part
Shockproof cushion
NOTE: Conrm the minimum drain tilt is 1/100 or
more.
10. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit on a at level by using a level to prevent leaks. (See Fig. 4.11).
Wall Mounting Installtion
Ceiling Installation
20mm
D. Refrigerant pipe
connection (D.gas side)
Drain point
Downward slope between(1-2)/100
E. Refrigerant pipe
connection
(E. Liquid side)
Side board
Grille
Hanging arm
Hanging
screw bolt
Page 14
Outdoor Unit
Installation
Outdoor Unit Installation
Outdoor Unit Installation Instructions
Step 1: Select installation location.
The outdoor unit should be installed in the location that meets the following requirements:
Place the outdoor unit as close to the indoor
unit as possible.
Ensure that there is enough room for
installation and maintenance.
The air inlet and outlet must not be
obstructed or exposed to strong wind.
Ensure the location of the unit will not be
subject to snowdrifts, accumulation of leaves or other seasonal debris. If possible, provide an awning for the unit. Ensure the awning does not obstruct airflow.
The installation area must be dry and well
ventilated.
There must be enough room to install the
connecting pipes and cables and to access them for maintenance.
The area must be free of combustible gases
and chemicals.
The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length.
If possible, DO NOT install the unit where it
is exposed to direct sunlight.
If possible, make sure the unit is located far
away from your neighbors’ property so that the noise from the unit will not disturb them.
If the location is exposed to strong winds (for
example: near a seaside), the unit must be placed against the wall to shelter it from the wind. If necessary, use an awning. (See Fig. 5.1 & 5.2)
Install the indoor and outdoor units, cables
and wires at least 1 meter from televisions or radios to prevent static or image distortion. Depending on the radio waves, a 1 meter distance may not be enough to eliminate all interference.
Strong wind
Strong wind
Fig. 5.1
Fig. 5.2
Step 2: Install outdoor unit.
Fix the outdoor unit with anchor bolts (M10)
>60cm / 23.6”
Fix with bolts
CAUTION
Be sure to remove any obstacles that
may block air circulation.
Make sure you refer to Length
Specifications to ensure there is enough room for installation and maintenance.
Fig. 5.3
5
Page 15
Outdoor Unit
Installation
>120cm / 47”
Air Outlet
(Wall or obstacle)
H
D
W
>30cm / 11.8”
Air inlet
Air inlet
Air inlet
Air inlet
(Wall or obstacle)
>30cm / 11.8”
>30cm / 11.8”
>30cm / 11.8”
Table 5.1: Length Specifications of Split Type
Outdoor Unit (unit: mm/inch)
Table 5.2: Length Specifications of Vertical
Discharge Outdoor Unit (unit: mm/inch)
MODEL
DIMENSIONS
W H D
18 633/25 554/21.8554/21.8
24 633/25 554/21.8554/21.8
36 759/29.8 554/21.8554/21.8
36 633/25 600/23.6600/23.6
48 759/29.8 710/28710/28
60 843/33 710/28710/28
Split Type Outdoor Unit
(Refer to Fig 5.4, 5.5, 5.6, 5.10 and Table 5.1)
Vertical Discharge Type Outdoor Unit
(Refer to Fig 5.7, 5.8, 5.9 and Table 5.2)
Fig. 5.7
Fig. 5.8
Fig. 5.9
Fig. 5.6
Fig. 5.5
A
B
D
W
H
W
H
Fig. 5.4
Outdoor Unit Dimensions
W x H x D
Mounting Dimensions
Distance A Distance B
760x590x285 (29.9x23.2x11.2) 530 (20.85) 290 (11.4)
810x558x310 (31.9x22x12.2) 549 (21.6) 325 (12.8)
845x700x320 (33.27x27.5x12.6) 560 (22) 335 (13.2)
900x860x315 (35.4x33.85x12.4) 590 (23.2) 333 (13.1)
945x810x395 (37.2x31.9x15.55) 640 (25.2) 405 (15.95)
990x965x345 (38.98x38x13.58) 624 (24.58) 366 (14.4)
946x810x420 (37.24x31.9x16.53) 673 (26.5)
403 (15.87)
946x810x410 (37.24x31.9x16.14) 673 (26.5)
403 (15.87)
952x1333x410 (37.5x52.5x16.14) 634 (24.96)
404 (15.9)
952x1333x415 (37.5x52.5x16.34) 634 (24.96)
404 (15.9)
845x702x363 (33.27x27.6x14.3)
540 (21.26)
350 (13.8)
938x1369x392 (36.93x53.9x15.43) 634 (24.96) 404 (15.9) 900x1170x350 (35.4x46x13.8) 590 (23.2) 378 (14.88)
800x554x333 (31.5x21.8x13.1) 514 (20.24) 340 (13.39)
Page 16
Outdoor Unit
Installation
NOTE:
The minimum distance between the
outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 5.10)
M
N
P
30 cm / 11.8” from back wall
60 cm / 23.6” on right
60 cm / 23.6” above
30 cm / 11.8” on left
200 cm / 78” in front
Fig. 5.10
Drain Joint Installation
NOTE: Make sure the water drains to a safe
location where it will not cause water damage or a slipping hazard.
Seal
Drain joint
(A) (B)
Base pan hole of outdoor unit
Seal
Fig. 5.12
Notes On Drilling Hole In Wall
You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.
1.
Determine the location of the wall hole
based on the location of the outdoor unit.
2.
Using a 65-mm (2.5”) core drill, drill a hole
in the wall.
NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
3.
Place the protective wall cu in the hole. This protects the edges of the hole and will help seal it when you nish the installation process.
Fig. 5.11
L
H
300 cm / 118” or more
A
60 cm / 23.6”
or more
150 cm / 59”
or more
25 cm / 9.8”
or more
25 cm / 9.8”
or more
Rows of series installation
L H
L 1/2H
L A
25 cm / 9.8” or more
1/2H < L H
30 cm / 11.8” or more
L > H
Can not be installed
Table 5.3 The relations between H, A and L are as follows.
If the drain joint comes with a rubber seal (see Fig. 5.12 - A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. 5.12 - B ), do the following:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
Page 17
Drainpipe
Installation
NOTE ON DRAINPIPE INSTALLATION
When using an extended drainpipe, tighten the indoor connection with an additional protection tube to prevent it from pulling loose.
The drainpipe should slope downward at a
gradient of at least 1/100 to prevent water from flowing back into the air conditioner.
To prevent the pipe from sagging, space
hanging wires every 1-1.5m (39-59”).
Incorrect installation could cause water to
flow back into the unit and flood it.
The drainpipe is used to drain water from the unit. Improper installation may cause unit and property damage.
CAUTION
Insulate all piping to prevent condensation and water damage.
If the drainpipe is bent or installed
incorrectly, water may leak and cause a malfunction of the water-level switch.
In HEAT mode, the outdoor unit will
discharge water. Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage due to frozen drain water.
DO NOT pull the drainpipe forcefully as this
could cause it to disconnect.
NOTE ON PURCHASING PIPES
This installation requires a polyethylene tube (outside diameter = 3.7-3.9cm, inside diameter = 3.2cm), which can be obtained at your local hardware store or dealer.
Indoor Drainpipe Installation
Install the drainpipe as shown in Figure 6.2.
1.
2.
Drainpipe connecting port
Drain hose
Pipe clasp
Insulation
Fig. 6.1
Drainpipe Installation
Fig. 6.2
6
Cover the drainpipe with heat insulation to prevent condensation and leakage.
Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the mouth of the hose and clip it rmly with a pipe clasp. (Fig 6.1)
Downward slope
1/100
1-1.5m
(39-59”)
NOTE: When connecting multiple drainpipes, install the pipes as shown in Fig 6.3.
≥10cm
(4”)
Fig. 6.3
Page 18
Drainpipe
Installation
3. Using a 65-mm (2.5”) core drill, drill a hole in
the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig. 6.4). Place the protective wall cu in the hole. This protects the edges of the hole and will help seal it when you nish the installation process.
Wall
IndoorOutdoor
≈ 12mm / 0.5 inch
Fig. 6.4
NOTE: When drilling the hole in the wall, make
sure to avoid wires, plumbing, and other sensitive components.
4. Pass the drain hose through the hole. Make sure the water drains to a safe location where it will not cause water damage or a slippage.
NOTE: The drainpipe outlet should be at least 5cm (1.9”) above the ground. If it touches the ground, the unit may become blocked and malfunction. If you discharge the water directly into a sewer, make sure that the drain has a U or S pipe to prevent unwanted odors from entering the house.
Page 19
Refrigerant Piping
Connection
Refrigerant Piping Connection
Safety Precautions
WARNING
All eld piping must be completed by a licensed technician and must comply with
the local and national regulations.
When the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. If the refrigerant leaks and its concentration exceeds its proper limit, hazards due to lack of oxygen may result.
When installing the refrigeration system, ensure that air, dust, moisture or foreign
substances do not enter the refrigerant circuit. Contamination in the system may cause poor operating capacity, high pressure in the refrigeration cycle, explosion or injury.
Ventilate the area immediately if there is refrigerant leakage during the installation.
Leaked refrigerant gas is both toxic and flammable. Ensure there is no refrigerant leakage after completing the installation work.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in Table 7.1:
Table 7.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of model Capacity
(Btu/h)
Length of
piping
Maximum drop
height
North America, Australia and the eu frequency conversion Split Type
<15K 25/82 10/32.8
15K - <24K 30/98.4 20/65.6
24K - <36K 50/164 25/82
36K - 60K 65/213 30/98.4
Other Split Type
12K 15/49 8/26
18K-24K 25/82 15/49
30K-36K 30/98.4 20/65.6
42K-60K 50/164 30/98.4
Refrigerant Piping with Twin Indoor Units
When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:
L
L1
L2
H2
The line branch pipe
Indoor unit
Outdoor unit
H1
Indoor unit
The drop height
between two
indoor units
must be less
than or equal to
50cm (19.6”)
The drop height between indoor
unit and outdoor unit must be less than or equal to 20m
(65.6’)
Fig. 7.1
7
Page 20
Refrigerant Piping
Connection
Table 7.2
Permitted length
Piping length
Total piping length 18K+18K 30m/98’ L+Max
(L1, L2)
24K+24K
30K+30K
50m/164’
(farthest distance from the line pipe branch)
15m/49’ L1, L2
(farthest distance from the line pipe branch)
10m/32.8’ L1-L2
Drop height
Drop height between indoor and outdoor unit
20m/65.6’ H1
Drop height between two indoor units
0.5m/1.6’ H2
Refrigerant Piping Connection Instructions
CAUTION
The branching pipe must be installed
horizontally. An angle of more than 10° may cause malfunction.
DO NOT install the connecting pipe until
both indoor and outdoor units have been installed.
Insulate both the gas and liquid piping to
prevent water leakage.
Step1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.
1.
Measure the distance between the indoor
and outdoor units.
2.
Using a pipe cutter, cut the pipe a little
longer than the measured distance.
CAUTION
DO NOT deform pipe while cutting. Be extra
careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
1.
Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 7.2 for examples of bad cuts
Oblique
Rough
Warped
90°
Fig. 7.2
Step 2: Remove burrs.
Burrs can aect the air-tight seal of refrigerant piping connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Fig. 7.3
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring. See Fig. 7.4
Flare nut
Copper pipe
Fig. 7.4
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form
Pipe
Fig. 7.5
Page 21
Refrigerant Piping
Connection
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.3.
Table 7.3: PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min. Max.
Ø 6.4
R0.4~0.8
45
°
±
2
90
°
±
4
A
Fig. 7.6
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high­pressure pipe.
1.
When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
2.
Align the center of the two pipes that you
will connect.
Indoor unit tubing
Flare nut
Pipe
Fig. 7.7
3.
Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 7.5.
NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.
Fig. 7.8
CAUTION
Ensure to wrap insulation around the piping.
Direct contact with the bare piping may result in burns or frostbite.
Make sure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
min-radius 10cm (3.9”)
Fig. 7.9
6.
After connecting the copper pipes to the
indoor unit, wrap the power cable, signal cable and the piping together with binding tape.
NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
7. Thread this pipeline through the wall and connect it to the outdoor unit.
8. Insulate all the piping, including the valves of the outdoor unit.
9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).
Ø 22
65-67 N.m
(663-683 kgf.cm)
23.2/0.91 23.7/0.93
75-85N.m
(765-867 kgf.cm)
26.4/1.04 26.9/1.06
18-20 N.m
(183-204 kgf.cm)
8.4/0.33 8.7/0.34
25-26 N.m
(255-265 kgf.cm)
13.2/0.52 13.5/0.53
35-36 N.m
(357-367 kgf.cm)
16.2/0.64 16.5/0.65
45-47 N.m
(459-480 kgf.cm)
19.2/0.76 19.7/0.78
Page 22
Wiring
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board(PCB) is designed with a fuse to provide overcurrent protection. The specications of the fuse are printed on the circuit board, such as: Indoor unit: T5A/250VAC, T10A/250VAC. (applicable for unit adopts R32 refrigerant) Outdoor unit: T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for >24000Btu/h unit)
Wiring
Safety Precautions
WARNING
Be sure to disconnect the power supply before working on the unit.
All electrical wiring must be done according to local and national regulations.
Electrical wiring must be done by a qualied technician. Improper connections may cause electrical malfunction, injury and fire.
An independent circuit and single outlet must be used for this unit. DO NOT plug another appliance or charger into the same outlet.If the electrical circuit capacity is not enough or there is a defect in the electrical work, it can lead to shock, fire, unit and property damage.
Connect the power cable to the terminals and fasten it with a clamp. An insecure
connection may cause fire.
Make sure that all wiring is done correctly and the control board cover is properly installed. Failure to do so can cause overheating at the connection points, fire, and electrical shock.
Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least 3mm (0.118”).
DO NOT modify the length of the power
cord or use an extension cord.
CAUTION
Connect the outdoor wires before connecting the indoor wires.
Make sure you ground the unit. The grounding wire should be away from gas
pipes, water pipes, lightning rods, telephone or other grounding wires. Improper grounding may cause electrical shock.
DO NOT connect the unit with the power
source until all wiring and piping is completed.
Make sure that you do not cross your electrical wiring with your signal wiring, as
this can cause distortion and interference.
Follow these instructions to prevent distortion when the compressor starts:
The unit must be connected to the main outlet. Normally, the power supply must
have a low output impedance of 32 ohms.
No other equipment should be connected to the same power circuit.
The unit’s power information can be found on the rating sticker on the product.
Outdoor Unit Wiring
WARNING
Before performing any electrical or wiring work, turn o the main power to the system.
1. Prepare the cable for connection
a. You must first choose the right cable size
before preparing it for connection. Be sure to use H07RN-F cables.
Table 8.1: Minimum Cross-Sectional Area
of Power and Signal Cables North America
Rated Current of
Appliance (A)
AWG
7 18
7 - 13 16 13 - 18 14 18 - 25 12 25 - 30 10
8
NOTE: The fuse is made of ceramic.
Page 23
Wiring
b. Using wire strippers, strip the rubber jacket
from both ends of a signal cable to reveal about 15cm (5.9”) of the wires inside.
c.
Strip the insulation from the ends of the wires.
d. Using a wire crimper, crimp u-lugs on the
ends of the wires.
NOTE: While connecting the wires, strictly follow the wiring diagram (found inside the electrical box cover).
2. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, disassemble the bolts from the maintenance board and remove the protection board. (See Fig. 8.1, 8.2)
Cover
Screw
Fig. 8.1
Protection Board
Fig. 8.2
3. Connect the u-lugs to the terminals Match the wire colors/labels with the labels on the terminal block and rmly screw the u-lug of each wire to its corresponding terminal.
4. Clamp down the cable with the designated cable clamp.
5. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.
6. Reinstall the cover of the electric control box.
Indoor Unit Wiring
1. Prepare the cable for connection a. Using wire strippers, strip the rubber jacket
from both ends of a signal cable to reveal about 15cm (5.9”) of the wires inside.
b. Strip the insulation from the ends of the
wires.
c. Using a wire crimper, crimp the u-lugs to
the ends of the wires.
2. Open the front panel of the indoor unit. Using a screwdriver,remove the cover of the electric control box on your indoor unit.
3. Thread the power cable and the signal cable through the wire outlet.
4. Connect the u-lugs to the terminals. Match the wire colors/labels with the labels on
the terminal block and firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.
Connective wiring diagram
Wiring diagram
Fig. 8.3
control box
wire outlet
Table 8.2: Other Regions
Rated Current of
Appliance (A)
Area (mm²)
Nominal Cross-Sectional
6 0.75
6 - 10 1 10 - 16 1.5 16 - 25 2.5
25- 32 4
32 - 45 6
Fig. 8.4
Magnetic ring
(if supplied and packed with the accessories)
1 2 3
Pass the belt through the hole of the Magnetic ring to fix it on the cable
Page 24
Wiring
Power Specifications
NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A.
Indoor Power Supply Specifications
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
POWER
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20 32/25 50/40 70/55 70/60
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
POWER
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
POWER
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20 32/25 50/40 70/55 70/60
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
POWER
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
Outdoor Power Supply Specifications
CAUTION
While connecting the wires, please strictly follow the wiring diagram.
The refrigerant circuit can become very hot. Keep the interconnection cable away from the
copper tube.
5. Clamp down the cable with the designated cable clamp to secure it in place. The cable should not be loose and should not pull on the u-lugs.
6. Reattach the electric box cover.
Page 25
Wiring
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
POWER
(indoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
220-240V 220-240V 220-240V220-240V 220-240V
CIRCUIT BREAKER/
FUSE(A)
15/10 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V
208-240V
208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20 25/20 40/30 50/40 50/40
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
POWER
(indoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 45/35
MODEL
(Btu/h)
36K 37K~60K 36K 37K~60K
POWER (indoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
220-240V 220-240V 220-240V 220-240V
CIRCUIT BREAKER/FUSE(A) 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 3 Phase 3 Phase 3 Phase 3 Phase
FREQUENCY
AND VOLT
380-420V 380-420V 208-240V 208-240V
CIRCUIT BREAKER/FUSE(A) 25/20 32/25 32/25 40/30
Inverter Type A/C Power Specifications
Independent Power Supply Specifications
MODEL
(Btu/h)
18K 19K~24K 25K~36K 37K~48K 49K~60K
POWER (indoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V208-240V 208-240V
CIRCUIT BREAKER/
FUSE(A)
15/10 15/10 15/10 15/10 15/10
POWER
(outdoor)
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
FREQUENCY
AND VOLT
208-240V 208-240V 208-240V
208-240V
208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20 32/25 50/40 70/55 70/60
Page 26
Air Evacuation
Air Evacuation
Safety Precautions
CAUTION
Use a vacuum pump with a gauge reading lower than -0.1MPa and an air discharge capacity above 40L/min.
The outdoor unit does not need vacuuming.
DO NOT open the outdoor unit’s gas and liquid stop valves.
Ensure that the Compound Meter reads
-0.1MPa or below after 2 hours. If after three hours of operation and the gauge reading is still above -0.1MPa, check if there is a gas leak or water inside the pipe. If there is no leakage, perform another evacuation for 1 or 2 hours.
DO NOT use refrigerant gas to evacuate the
system.
Evacuation Instructions
Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
Fig. 9.1
1. Connect the manifold gauge’s charge hose to the service port on the outdoor unit’s low pressure valve.
2. Connect the manifold gauge’s charge hose from the to the vacuum pump.
3. Open the Low Pressure side of the manifold gauge.Keep the High Pressure side closed.
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa).
6. Close the manifold gauge’s Low Pressure valve and turn o the vacuum pump.
7. Wait for 5 minutes, then check that there has been no change in system pressure.
NOTE: If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.
8. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.
Flare nut
Cap
Valve body
Valve stem
Fig. 9.2
9. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.
10.Remove the charge hose from the service port.
11.Using hexagonal wrench, fully open both the
high pressure and low pressure valves.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.
12. Tighten valve caps by hand, then tighten it
using the proper tool.
9
Page 27
Air Evacuation
Note On Adding Refrigerant
CAUTION
Refrigerant charging must be performed after wiring, vacuuming, and the leak testing.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage the unit or impact it’s functioning.
Charging with unsuitable substances may cause explosions or accidents. Ensure that the appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use protective gear when charging the
system.
For the R290 or R32 refrigerant model, make sure the condtions within the area have been made safe by control of ammable material when the refrigerant added into air conditioner.
The maximum refrigerant charge amount of R32 is 305 grams.
DO NOT mix refrigerants types.
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is
7.5m (25’) In other areas, the standard pipe length is 5m (16‘). The additional refrigerant to be charged can be calculated using the following formula:
Liquid Side Diameter
R32 :
(Total pipe length ­standard pipe length)x 12g(0.13oZ)/m(ft)
(Total pipe length ­standard pipe length)x 24g(0.26oZ)/m(ft)
(Total pipe length ­standard pipe length)x 40g(0.42oZ)/m(ft)
φ6.35(1/4”) φ9.52(3/8”) φ12.7(1/2”)
R22 (orifice tube in the indoor unit):
(Total pipe length ­standard pipe length)x 30g (0.32oZ)/m(ft)
(Total pipe length ­standard pipe length)x 65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length)x 115g(1.23oZ)/m(ft)
R22 (orifice tube in the outdoor unit):
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length) x30(0.32oZ)/m(ft)
(Total pipe length - standard pipe length) x60g(0.64oZ)/m(ft)
(Total pipe length - standard pipe length) x65g(0.69oZ)/m(ft)
R410A: (orifice tube in the indoor unit):
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length ­standard pipe length) x65g(0.69oZ)/m(ft)
(Total pipe length ­standard pipe length) x115g(1.23oZ)/m(ft)
R410A: (orifice tube in the outdoor unit):
(Total pipe length ­standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length ­standard pipe length) x30g(0.32oZ)/m(ft)
Page 28
Test Run
Before Test Run
A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:
a) Indoor and outdoor units are properly
installed.
b) Piping and wiring are properly connected. c)
No obstacles near the inlet and outlet of
the unit that might cause poor performance or product malfunction.
d) Refrigeration system does not leak. e) Drainage system is unimpeded and
draining to a safe location.
f) Heating insulation is properly installed. g) Grounding wires are properly connected. h) Length of the piping and additional
refrigerant stow capacity have been recorded.
i) Power voltage is the correct voltage
for the air conditioner.
CAUTION
Failure to perform the test run may result in unit damage, property damage, or personal injury.
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit a. Ensure the remote control and its buttons
work properly.
b. Ensure the louvers move properly and can
be changed using the remote control.
c. Double check to see if the room
temperature is being registered correctly.
d. Ensure the indicators on the remote
control and the display panel on the indoor unit work properly.
e. Ensure the manual buttons on the indoor
unit works properly.
f. Check to see that the drainage system is
unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal
noise during operation.
5. For the Outdoor Unit a. Check to see if the refrigeration system is
leaking.
b. Make sure there is no vibration or
abnormal noise during operation.
c. Ensure the wind, noise, and water
generated by the unit do not disturb your neighbors or pose a safety hazard.
6. Drainage Test a. Ensure the drainpipe flows smoothly. New
buildings should perform this test before finishing the ceiling.
b. Remove the test cover. Add 2,000ml of
water to the tank through the attached tube.
c. Turn on the main power switch and run
the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to
see if it makes any unusual noises.
e. Check to see that the water is discharged.
It may take up to one minute before the unit begins to drain depending on the drainpipe.
f. Make sure that there are no leaks in any of
the piping.
g. Stop the air conditioner. Turn o the main
power switch and reinstall the test cover.
NOTE: If the unit malfunctions or does not operate according to your expectations, please refer to the Troubleshooting section of the Owner’s Manual before calling customer service.
Test Run
10
Page 29
European Disposal
Guidelines
11
Users in European Countries may be required to properly dispose of this unit. This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment.
DO NOT
dispose of this product as household waste or
unsorted municipal waste.
When disposing of this appliance, you have the following options:
Dispose of the appliance at designated municipal electronic waste collection facility.
When buying a new appliance, the retailer will take back the old appliance free of charge.
The manufacturer will also take back the old appliance free of charge.
Sell the appliance to certified scrap metal dealers.
NOTE: Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.
European Disposal Guidelines
Page 30
12
1. Checks to the area
3. General work area
4. Checking for presence of refrigerant
5. Presence of re extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry power or CO2 fire extinguisher adjacent to the charging area.
7. Ventilated area
Ensure that the area is in the open or that it it adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
6. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. NO SMOKING signs shall be displayed.
2. Work procedure
All mintenance staff and others working in the local area shall be instructed on the nature of work being carried out. work in confined sapces shall be avoided. The area around the work space shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
Works shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. no sparking, adequately sealed or intrinsically safe.
,,
,,
,
,
Information
Servicing
Information Servicing
(Required for the units adopt R32/R290 Refrigerant only)
Page 31
Information
Servicing
,
 
9. Checks to electrical devices
10. Repairs to sealed components
the charge size is in accordance with the room size within which the refrigerant containing parts are installed; the ventilation machinery and outlets are operating adequately and are not obstructed; if an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of refrigerant; marking to the equipment continues to be visible and legible. marking and signs that are illegible shall be corrected; refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, and adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking that there no live electrical components and wiring are exposed while charging, recovering or purging the system; that there is continuity of earth bonding.
10.1 During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
10.2 Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer s specifications. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Instrinsically safe components do not have to be isolated prior to working on them.
Page 32
 
  
Information
Servicing
11. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinscially safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
12. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
15. Removal and evacuation
When breaking into the refrigerant circuit to make repairs of for any other purpose conventional procedures shall be used, However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system.
13. Detection of ammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch(or any other detector using a naked flame) shall not be used.
14. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected ,all naked flames shall be removed or extinguished. If a leakage of refrigernat is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated(by means of shut off valves) in a part of the system remote from the leak . Oxygen free nitrogen(OFN) shall then be purged through the system both before and during the brazing process.
Page 33
Information
Servicing
 
  
 
 
17. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken.
In case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. a) Become familiar with the equipment and its operation. b) Isolate system electrically c) Before attempting the procedure ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders; all personal protetive equipment is available and being used correctly; the recovery process is supervised at all times by a competent person; recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer s instructions.
16. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed: Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete(if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
,
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not closed to any ignition sources and there is ventilation available.
Page 34
Information
Servicing
18. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
19. Recovery
When removing refrigerant from a system, either for service or decommissioning, it is recommended good practice that all refrigerants are removed safely. When tranferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct numbers of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant(i.e special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to retruning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
h) Do not overfill cylinders. (No more than 80% volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
Page 35
Information
Servicing
1. Transport of equipment containing ammable refrigerants Compliance with the transport regulations
2. Marking of equipment using signs Compliance with local regulations
3. Disposal of equipment using ammable refrigerants Compliance with national regulations
4. Storage of equipment/appliances The storage of equipment should be in accordance with the manufacturer’s instructions.
5. Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
20. Transportation, marking and storage for units
FLOOR/CEILING TYPE
Loading...