INVENTOR P8MVI32-09WiFi, P8MVO32-09, P8MVI32-18WiFi, P8MVO32-18, P8MVI32-24WiFi Installation Manual

...
• INSTALLATION MANUAL
• ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
• MANUAL DE INSTALARE
ENGLISH | ΕΛΛΗΝΙΚΑ | ROMANA
MODELS:
P8MVI32-09WiFi / P8MVO32-09 P8MVI32-12WiFi / P8MVO32-12 P8MVI32-18WiFi / P8MVO32-18 P8MVI32-24WiFi / P8MVO32-24
WALL MOUNTED UNIT
Table of Contents
Installation Manual
Indoor Unit Installation........ 11
1. Select installation location.......................... 11
2. Attach mounting plate to wall....................
12
3. Drill wall hole for connective piping............
12
4. Prepare refrigerant piping...........................
14
5. Connect drain hose....................................
15
6. Connect signal cable..................................
17
7. Wrap piping and cables..............................
18
8. Mount indoor unit.....................................
18
Outdoor Unit Installation...
20
8
1. Select installation location.................. 20
2. Install drain joint................................
21
3. Anchor outdoor unit..........................
22
4. Connect signal and power cables.......23
Safety Precautions........................... 4
0
1
5
Accessories........................................ 6
2
4
Unit Parts.......................................... 10
3
Installation Summary - Indoor Unit........
Refrigerant Piping Connection........ 25
A. Note on Pipe Length................................................ 25
B. Connection Instructions –Refrigerant Piping............. 25
1. Cut pipe..............................................................
25
2. Remove burrs......................................................
26
3. Flare pipe ends....................................................
26
4. Connect pipes.....................................................
27
Air Evacuation................... 29
1. Evacuation Instructions......................29
2. Note on Adding Refrigerant...............30
Electrical and Gas Leak Checks........ 31
Test Run............................................ 32
European Disposal Guidelines........ 34
6
7
8
9
10
Information servicing .................... 34
11
MC MC
Cau t i o n: Risk of fire
(for R32/R290 refrigerant ony )
Page 4 
This symbol indicates that ignoring instructions may cause death or serious injury.
This symbol indicates that ignoring instructions may cause moderate injury to your person, or damage to your unit or other property.
Safety Precautions
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury.
The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.
WARNING
CAUTION
WARNING
Do notmodify the length of the power supply cord or use an extension cord to power the unit. Do not
Do not
share the electrical outlet with other appliances. Improper or insufficient power supply
can cause fire or electrical shock.
When connecting refrigerant piping, do not
let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
allow children to play with the air conditioner. Children must be supervised around the
unit at all times.
1.
Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire.
2.
Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire. (In North America,installation must be performed in
accordance with the requirement of NEC and CEC by authorized personnel only.)
3.
Contact an authorized service technician for repair or maintenance of this unit.
4.
Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
5.
Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
This symbol indicates that you must never perform the action indicated.
6.
7.
8.
9.
10.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames,an operating gas appliance or an operating electric heater) Do not pierce or burn. Appliance shall be stored in a well -ventilated area where the room size corresponds to the room area as specifiec for operation. Be aware that refrigerants may not contain an odour. NOTE: Clause 7 to 10 are required for the units adopt R32/R290 Refrigerant.
Page 5 
WARNING
11.
For all electrical work, follow all local and national wiring standards, regulations, and the Installation Manual. You must use an independent circuit and single outlet to supply power. Do not connect other appliances to the same outlet. Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire.
12.
For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock.
13.
14.
15.
16.
All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.
This appliance can be used by children aged from 8 years and above and persons with reduced Physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
CAUTION
For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
Do not
install the unit in a location that may be exposed to combustible gas leaks. If combustible
gas accumulates around the unit, it may cause fire. Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit.
1.
The product must be properly grounded at the time of installation, or electrical shock may occur.
In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Note about Fluorinated Gasses
1. This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
Compliance with national gas
regulations shall be observed.
2. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3. Product uninstallation and recycling must be performed by a certified technician.
4. If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
2. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
3.
The appliance shall be stored so as to prevent mechanical damage from occurring.
4. Any person who is involve with working on or breaking into a refrigerant circuit should hold a
current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification.
Name
Shape Quantity
1
1
1
(for cooling & heating
models only)
Clip anchor
Mounting plate fixing screw ST3.9 X 25
Remote controller
Fixing screw for remote controller holder ST2.9 x 10
Remote controller holder
Dry battery AAA.LR03
Seal
Drain joint
Mounting plate
1
Accessories
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.
5
5
2
1
Optional Parts
2
Page 6 
WARNING
2
2
2
2
1
1
1
Owner’s manual
Installation manual
Remote controller illustration
Page 7 
Name
Shape Quantity
Parts you must purc hase. Consult the dealer about the pipe size.
Conn ecting pipe assembly
Liqu id side
Gas sid e
Φ
6. 3 5( 1 /4 i n)
Φ
9. 5 2( 3 /8in)
Φ
9. 5 2( 3 /8in)
Φ
12 . 7( 1 /2in)
Φ
16( 5/8in )
Appliance shall be stored in a well -ventilated area where the room size corresponds to the room area as specifiec for operation. For R32 frigerant models: Appliance shall be installed, operated and stored in a room with a floor area larger than 4m
2
.
Appliance shall not be installed in an unvertilated space, if that space is smaller than 4m
2
.
For R290 refrigerant models, the minimum room size needed: <=9000Btu/h units: 13m >9000Btu/h and <=12000Btu/h units: 17m >12000Btu/h and <=18000Btu/h units: 26m >18000Btu/h and <=24000Btu/h units: 35m
Φ
19( 3/ 4in )
• INSTALLATION MANUAL
• ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
• MANUAL DE INSTALARE
ENGLISH | ΕΛΛΗΝΙΚΑ | ROMANA
MODELS:
P8MVI32-09WiFi / P8MVO32-09 P8MVI32-12WiFi / P8MVO32-12 P8MVI32-18WiFi / P8MVO32-18 P8MVI32-24WiFi / P8MVO32-24
OUTDOOR UNIT
AIR CONDITIONING SYSTEMS
• USER’S MANUAL
• ΕΓΧΕΙΡΙΔΙΟ ΧΡΗΣΗΣ
• MANUAL UTILIZATORULUI
ENGLISH | ΕΛΛΗΝΙΚΑ | ROMANA
WALL MOUNTED UNIT
MODELS:
P8MVI32-09WiFi / P8MVO32-09 P8MVI32-12WiFi / P8MVO32-12 P8MVI32-18WiFi / P8MVO32-18 P8MVI32-24WiFi / P8MVO32-24
AIR CONDITIONING SYSTEMS
ENGLISH | ΕΛΛΗΝΙΚΑ | ROMANA
MODELS:
P8MVI32-09WiFi / P8MVO32-09 P8MVI32-12WiFi / P8MVO32-12 P8MVI32-18WiFi / P8MVO32-18 P8MVI32-24WiFi / P8MVO32-24
• USER’S MANUAL
• ΕΓΧΕΙΡΙΔΙΟ ΧΡΗΣΗΣ
• MANUAL UTILIZATORULUI
REMOTE CONTROLLER
AIR CONDITIONING SYSTEMS
Page 8 
Installation Summary - Indoor Unit
2
Select Installation Location
(Page 11)
Attach Mounting Plate
(Page 12)
Drill Wall Hole
(Page 12)
Determine Wall Hole Position
(Page 12)
1 2
3
4
12cm (4.75in)
2.3m (90.55in)
12cm (4.75in)
15cm (5.9in)
Page 9 
Mount Indoor Unit
(Page 19)
STEP
8
Wrap Piping and Cable (not applicable for some locations in the US )
(Page 19)
Connect Piping
(Page 25)
Connect Wiring
(Page 17)
Prepare Drain Hose
(Page 16)
5 6 7
8
9
Page 10 
Unit Parts
3
NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.
Fig. 2.1
NOTE: The installation must be performed in accordance with the requirement of local and
national standards. The installation may be slightly different in different areas.
Wall Mounting Plate
Power Cable (Some Units)
Refrigerant Piping
Signal Cable
Remote Controller
Drainage Pipe
Louver
Remote Controller Holder (Some Units)
Air filter(pull it out)
Front Panel
Outdoor Unit Power Cable (Some Units)
1 2 3 4
5
6
7
8
9
10
11
1 2
1
2
3
4
6
7 8
9
10
11
Air-break switch
3
1
2
4
5
6
7
8
11
5
Page 11 
Indoor Unit Installation
4
Installation Instructions – IndoorUnit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.
Step 1: Select installation location
Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
o
Good air circulation
o
Convenient drainage
o
Noise from the unit will not disturb other people
o
Firm and solid—the location will not vibrate
o
Strong enough to support the weight of the unit
o
A location at least one meter from all other electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following
locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or
clothing Near any obstacle that might block air
circulation Near the doorway In a location subject to direct sunlight
NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping: While choosing a location, be aware that you
should leave ample room for a wall hole (see Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to both the left and right.
Fig. 3.1-a
Page 12
Refer to the following diagram to ensure proper distance from walls and ceiling:
Step 2: Attach mounting plate to wall
The mounting plate is the device on which you will mount the indoor unit.
1.
Remove the screw that attaches the mounting plate to the back of the indoor unit.
2.
Place the mounting plate against the wall in a location that meets the standards in the Select Installation Location step. (See Mounting Plate Dimensions for detailed information on mounting plate sizes.)
3.
Drill holes for mounting screws in places that:
• have studs and can support the weight of the unit
• correspond to screw holes in the mounting plate
4. Secure the mounting plate to the wall with the screws provided.
5.
Make sure that mounting plate is flat against the wall.
NOTE FOR CONCRETE OR BRICK WALLS:
If the wall is made of brick, concrete, or similar material, drill 5mm-diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors provided. Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors.
Step 3: Drill wall hole for connective piping
You must drill a hole in the wall for refrigerant piping, the drainage pipe, and the signal cable that will connect the indoor and outdoor units.
Fig. 3.1-b
12cm (4.75in)
or more
2.3m (90.55in) or more
12cm (4.75in)
or more
15cm (5.9in) or more
1. Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions on the next page to help you determine the optimal position. The wall hole should have a 65mm
(2.5in) diameter at least, and at a slightly lower angle to facilitate drainage.
CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.
2. Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill, drill a hole in the wall. Make sure that the hole is drilled at
a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 5mm to 7mm (0.2-0.275in). This will ensure proper water drainage. (See Fig. 3.2)
3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.
Page 13 
Wall
Indoor Outdoor
mm7-5
(0.2-0.275in)
MOUNTING PLATE DIMENSIONS
Different models have different mounting plates. In order to ensure that you have ample room to mount the indoor unit, the diagrams to the right show different types of mounting plates along with the following dimensions:
Width of mounting plate
Height of mounting plate
Width of indoor unit relative to plate
Height of indoor unit relative to plate
Recommended position of wall hole (both to the left and right of mounting plate)
Relative distances between screw holes
Fig. 3.2
Model B
Model D
302mm(11.9in)
805mm(31.7in)
1106mm(43.5in)
599mm(23.6in)
342mm(13.5in)
Model C
964mm(37.9in)
482mm(19in)
325mm(12.8in)
406.4mm(16in)
452.7mm(17.8in)
249mm(9.8in)
153mm(6in)102mm(4in)
39mm(1.5in)
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
Indoor unit outline
54mm(2.1in)
Model A
717mm(28.2in)
302mm(11.9in)
318mm(12.5in)
409mm(16.1in)
249mm(9.8in)
153mm(6in)102mm(4in)
39mm(1.5in)
pipe hole
φ
65mm
2.56 in
pipe hole
φ
65mm
2.56 in
Indoor unit outline
54mm(2.1in)
71mm(2.80in)
132mm (5.20in)
219mm(8.62in)
262mm(10.31in)439mm(17.28in)
Indoor unit outline
Indoor unit outline
174mm (6.85in)
320mm(12.60in)
130mm (5.12in)
55mm(2.17in)
558mm(21.97in)
Correct orientation of Mounting Plate
Φ
NOTE: When the gas side connective pipe is 16mm(5/8in) or more, the wall hole should be 90mm(3.54in).
Page 14 
If refrigerant piping is already embedded in the wall, do the following:
Step 1:Hook the indoor unit on the mounting plate:
Step 2: Prepare refrigerant piping:
1. Disassemble the louver:
Fig. 3.5
Move to left or right
30-50mm
(1.2-1.95in)
30-50mm
(1.2-1.95in)
1. Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit. If you find that you don’t have ample room to connect embedded pipes to the indoor unit, the unit can be adjusted left or right by about 30-50mm (1.25-1.95in), depending on the model. (See Fig.3.4)
CAUTION
Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit’s performance.
Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque requirements, technique, etc.
NOTE ON PIPING ANGLE
Refrigerant piping can exit the indoor unit from four different angles:
Left-hand side
Left rear
Right-hand side
Right rear
Refer to Fig. 3.3 for details.
Fig. 3.3
Fig. 3.4
2. Open and fix the position of the panel Firstly, unscrew the two screws showed in the picture below, then open the panel, and fix the position of the panel by the latch(see Fig.3.6).
Page 15 
If there is no refrigerant piping embedded in the wall, do the following:
Fig. 3.6
Fig. 3.7
Step 3. Connect drain hose and refrigerant
piping (refer to Refrigerant Piping Connection section of this manual for instructions).
Step 4. Keep pipe connection point exposed to perform the leak test (refer to Electrical Checks
and Leak Checks section of this manual).
Step 5. After the leak test, wrap the connection
point with insulation tape. Step 6. Remove the bracket or wedge that is
propping with insulation tape.
Step 7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
1. Based on the position of the wall hole relative
to the mounting plate, choose the side from which the piping will exit the unit.
2. If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit. (See Fig. 3.8). This will create a slot through which your piping can exit the unit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.
3.
Use scissors to cut down the length of the insulating sleeve to reveal about 40mm (1.57in) of the refrigerant piping. This serves two purposes:
• To facilitate the Refrigerant Piping Connection process.
• To facilitage Gas Leak Checks and enable you to check for dents
Knock-out Panel
Fig. 3.8
3. Use the holder in the mounting plate to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable, and drain hose.
Page 16
4.
Connect the indoor unit’s refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions.
5. Based on the position of the wall hole relative to the mounting plate, determine the necessary angle of your piping.
6. Grip the refrigerant piping at the base of the bend.
7. Slowly, with even pressure, bend the piping towards the hole. Do not dent or damage the piping during the process.
Step 5: Connect drain hose
By default, the drain hose is attached to the left­hand side of unit (when you’re facing the back of the unit). However, it can also be attached to the right-hand side.
1. To ensure proper drainage, attach the drain hose on the same side that your refrigerant piping exits the unit.
2. Attach drain hose extension (purchased separately) to the end of drain hose.
3. Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks.
4. For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation.
5. Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to Fig. 3.9
DO NOT kink the drain hose.
DO NOT
create a water trap.
DO NOT put the end of drain hose in water or a container that will collect water.
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.
CORRECT
Make sure there are no
kinks or dent in drain
hose to ensure proper
drainage.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT
Do not place the end
of the drain hose in
water or in containers
that collect water. This
will prevent proper
drainage.
NOT CORRECT
Kinks in the drain hose
will create water traps.
Fig. 3.9
Fig. 3.10
Fig. 3.11
Fig. 3.12
Page 17 
BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire. If connecting power to fixed wiring, install a surge protector and main power switch with a capacity of 1.5 times the maximum current of the unit.
5.
6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
11.
If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials.
Step 6: Connect signal cable
The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection.
Cable Types
Indoor Power Cable(if applicable): H05VV-F or H05V2V2-F
Outdoor Power Cable:H07RN-F
Signal Cable:H07RN-F
Minimum Cross-Sectional Area of
Power and Signal Cables
Other Regions
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area (mm²)
> 3 and 6 0.75
> 6 and 10 1 > 10 and 16 1.5 > 16 and 25 2.5 > 25 and 32 4 > 32 and 40 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
North America
Appliance Amps (A)
AWG
10 18 13 16 18 14 25 12 30 10
Page 18 
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board, such as:
Indoor unit: T5A/250VAC Outdoor unit(applicalbe to units adpot
R32 or R290 refrigerant only): T20A/250VAC(<=18000Btu/h units) T30A/250VAC(>18000Btu/h units)
NOTE: The fuse is made of ceramic.
1. Prepare the cable for connection: a.
Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about 40mm (1.57in) of the wires inside.
b.
Strip the insulation from the ends of the wires.
c.
Using wire crimper, crimp u-type lugs on the ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.
2. Open front panel of the indoor unit by loosen
the screws according to picture Fig.4.7, which provide big space for wiring connection.
3.
Open the wire box cover to connect the cable.
WARNING
4. Unscrew the cable clamp below the terminal block and place it to the side.
5. Facing the back of the unit, remove the plastic panel on the bottom left-hand side.
ALL WIRING MUST PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED ON THE INSIDE OF THEINDOOR UNIT’S WIRE COVER.
Terminal block
Wire
cover Cable clamp
Fig. 3.13
The Wiring Diagram is located
on the inside of the indoor unit’s
wire cover.
6. Feed the signal wire through this slot, from the back of the unit to the front.
7. Facing the front of the unit, match the wire colors with the labels on the terminal block, connect the u-lug and and firmly screw each wire to its corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES
This is dangerous, and can cause the air conditioning unit to malfunction.
8. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
9. Replace the wire cover on the front of the unit, and the plastic panel on the back.
NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS.
Page 19 
Step 7: Wrap piping and cables
Before passing the piping, drain hose, and the signal cable through the wall hole, you must bundle them together to save space, protect them, and insulate them.
1. Bundle the drain hose, refrigerant pipes, and signal cable according to Fig. 3.14.
Indoor Unit
Space behind unit
Refrigerant piping
Drain hose
Signal wire
Insulation tape
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the drain hose at the top of the bundle can cause the drain pan to overflow, which can lead to fire or water damage.
DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES
While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
2. Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain hose tightly together. Double-check that all items are bundled in accordance with Fig. 3.14.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to
Electrical Checks
and Leak Checks
section of this manual).
Step 8: Mount indoor unit If you installed new connective piping to the
outdoor unit, do the following:
1. If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and signal wire through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure to the left and right-hand sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure to the left and the right-hand sides of the unit.
Fig. 3.14
Page 20 
Outdoor Unit Installation
5
evoba )ni42( mc06
60cm (24in)
on righ t
30cm (12in)
on left
200cm (79in)
in fron t
30cm (12in)
from back wall
Installation Instructions – Outdoor Unit
Step 1: Select installation location
Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
o
Meets all spatial requirements shown in Installation Space Requirements (Fig. 4.1)
o
Good air circulation and ventilation
o
Firm and solid—the location can support the unit and will not vibrate
o
Noise from the unit will not disturb others
o
Protected from prolonged periods of direct sunlight or rain
DO NOT
install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit will disturb others
Near animals or plants that will be harmed by hot air discharge
Near any source of combustible gas In a location that is exposed to large
amounts of dust In a location exposed to a excessive amounts
of salty air
Fig. 4.1
Page 21 
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds.
See Fig. 4.2 and Fig. 4.3 below.
Strong wind
Strong wind
Strong wind
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit.
If the unit is frequently exposed to salty air (seaside):
Use outdoor unit that is specially designed to resist corrosion.
Step 2: Install drain joint
Heat pump units require a drain joint. Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal
(see Fig. 4.4 - A ), do the following:
1.
Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2.
Insert the drain joint into the hole in the base pan of the unit.
3.
Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4.
Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. 4.4 - B ), do the following:
1.
Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2.
Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
Seal
Drain joint
(A) (B)
Base pan hole of outdoor unit
Seal
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.
Fig. 4.2
Fig. 4.3
Fig. 4.4
Wind Baffle
Page 22 
If you will install the unit on the ground or on a concrete mounting platform, do the
following:
1. Mark the positions for four expansion bolts based on dimensions in the Unit Mounting Dimensions chart.
2. Pre-drill holes for expansion bolts.
3. Clean concrete dust away from holes.
4. Place a nut on the end of each expansion bolt.
5. Hammer expansion bolts into the pre-drilled holes.
6. Remove the nuts from expansion bolts, and place outdoor unit on bolts.
7. Put washer on each expansion bolt, then replace the nuts.
8. Using a wrench, tighten each nut until snug.
WARNING
Step 3: Anchor outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted
bracket.
UNIT MOUNTING DIMENSIONS
The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.
W
A
W
B
D
Air inlet
Air outlet
Air inlet
Fig. 4.5
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.
Outdoor Unit Dimensions (mm)
W x H x D
Mounting Dimensions
Distance A (mm) Distance B (mm)
681x434x285 (26.8”x17”x11.2”) 460 (18.10”) 292 (11.49”)
700x550x270 (27.5”x21.6”x10.62”) 450 (17.7”) 260 (10.24”)
780x540x250 (30.7”x21.25”x9.85”) 549 (21.6”) 276 (10.85”)
845x700x320 (33.25”x27.5”x12.6”) 560 (22”) 335 (13.2”)
810x558x310 (31.9”x22”x12.2”) 549 (21.6”) 325 (12.8”)
900x860x315 (35.4”x33.85”x12.4”) 590 (23.2”)
333 (13.1”)
945x810x395 (37.2”x31.9”x15.55”) 640 (25.2”)
405 (15.95”)
946x810x420 (37.21”x31.9”x16.53”)
673 (26.5”) 403 (15.87”)
946x810x410 (37.21”x31.9”x16.14”)
673 (26.5”) 403 (15.87”)
845x702x363 (33.25”x27.63”x14.29”)
540 (21.26”)
350 (13.8”)
700x550x275 (27.5”x21.6”x10.82”) 450 (17.7”) 260 (10.24”)
770x555x300 (30.3”x21.85”x11.81”) 487 (19.2”) 298 (11.73”)
800x554x333 (31.5”x21.8”x13.1”) 514 (20.24”) 340 (13.39”)
Page 23 
If you will install the unit on a wall-mounted bracket , do the following:
CAUTION
Before installing a wall-mounted unit, make sure that the wall is made of solid brick, concrete, or of similarly strong material. The
wall must be able to support at least four times the weight of the unit.
1.
Mark the position of bracket holes based on dimensions in the Unit Mounting Dimensions chart.
2.
Pre-drill the holes for the expansion bolts.
3.
Clean dust and debris away from holes.
4.
Place a washer and nut on the end of each expansion bolt.
5.
Thread expansion bolts through holes in mounting brackets, put mounting brackets in position, and hammer expansion bolts into the wall.
6.
Check that the mounting brackets are level.
7.
Carefully lift unit and place its mounting feet on brackets.
8.
Bolt the unit firmly to the brackets.
TO REDUCE VIBRATIONS OF WALL­MOUNTED UNIT
If allowed, you can install the wall-mounted unit with rubber gaskets to reduce vibrations and noise.
Step 4: Connect signal and power cables
The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.
BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1.
All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.
2.
All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units.
3.
If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4.
Power voltage should be within 90-110% of
rated voltage. Insufficient power supply can cause electrical shock or fire.
5.
If connecting power to fixed wiring, install a surge protector and main power switch with a capacity of 1.5 times the maximum current of the unit.
6.
If connecting power to fixed wiring, a switch
or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in
(3mm) must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
7.
Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
8.
Make sure to properly ground the air conditioner.
9.
Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
10. Do not
let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
11.
If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials.
Page 24 
WARNING
1.
Prepare the cable for connection:
USE THE RIGHT CABLE
Indoor Power Cable (if applicable): H05VV-F or H05V2V2-F
Outdoor Power Cable: H07RN-F
Signal Cable: H07RN-F
Minimum Cross-Sectional Area of
Power and Signal Cables
Other Regions
Rated Current of
Appliance (A)
Nominal Cross-
Sectional Area (mm²)
> 3 and 6 0.75
> 6 and 10 1
> 10 and 16 1.5 > 16 and 25 2.5
> 25 and 32 4
> 32 and 40 6
a. Using wire strippers, strip the rubber
jacket from both ends of cable to reveal about 40mm (1.57in) of the wires inside.
b. Strip the insulation from the ends of the
wires.
c. Using a wire crimper, crimp u-lugs on the
ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.
2.
Unscrew the electrical wiring cover and remove it.
3.
Unscrew the cable clamp below the terminal block and place it to the side.
4.
Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal.
5.
After checking to make sure every connection is secure, loop the wires around to prevent rain water from flowing into the terminal.
6.
Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
7.
Insulate unused wires with PVC electrical tape. Arrange them so that they do not touch any electrical or metal parts.
8.
Replace the wire cover on the side of the unit, and screw it in place.
Cover
Outdoor Unit Wiring Diagram
is located on the inside of the
wire cover on the outdoor unit.
Fig. 4.6
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
WARNING
ALL WIRING MUST PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIRGRAM LOCATED INSIDE THE OUTDOOR UNIT’S WIRE COVER.
North America
Appliance Amps (A)
AWG
10 18 13 16 18 14 25 12 30 10
Page 25 
Refrigerant Piping Connection
6
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care
to cut and flare them properly. This will ensure efficient operation and minimize the need for
future maintenance. For R32/R290 refrigerant models, the pipe connection points must be placed outside of room.
1. Measure the distance between the indoor and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 5.1 for bad cut examples.
Oblique Rough Warped
90°
Fig. 5.1
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model Capacity (BTU/h) Max. Length (m) Max. Drop Height (m)
R410A Inverter Split Air
Conditioner
< 15,000 25 (82ft) 10 (33ft)
15,000 and < 24,000 30 (98.5ft) 20 (66ft) 24,000 and < 36,000 50 (164ft) 25 (82ft) 36,000 and 60,000 65 (213ft) 30 (98.5ft)
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft). A minimum pipe run of 3 metres is
required to minimise vibration & excessive noise. For special tropical area, the maximum length of refrigerant pipe should not exceed 10 meters(32.8ft) and no refrigerant can be added(For R290 refrigerant models).
Refer to the table below for specifications on the maximum length and drop height of piping.
Page 26 
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.
1.
Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2.
Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1.
After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
2.
Sheath the pipe with insulating material.
3.
Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring. See
Fig. 5.3.
Flare nut
Copper pipe
4.
Remove PVC tape from ends of pipe when ready to perform flaring work.
5.
Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the table below.
PIPING EXTENSION BEYOND FLARE FORM
Fig. 5.2
Fig. 5.3
Fig. 5.4
Outer Diameter of
Pipe (mm)
A (mm)
Min. Max.
Ø 6.35 (Ø 0.25”) 0.7 (0.0275”) 1.3 (0.05”)
Ø 9.52 (Ø 0.375”)
1.0 (0.04”) 1.6 (0.063”)
Ø 12.7 (Ø 0.5”) 1.0 (0.04”) 1.8 (0.07”)
Ø 16 (Ø 0.63”) Ø 19 (Ø 0.75”)
2.0 (0.078”) 2.2 (0.086”)
2.0 (0.078”) 2.4 (0.094”)
Flare form
Pipe
A
Fig. 5.5
Page 27 
6.
Place flaring tool onto the form.
7.
Turn the handle of the flaring tool clockwise until the pipe is fully flared.
8.
Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or to deform the piping in any way. You should first connect the low-pressure pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is 10cm. See
Fig.5.6.
≥10cm (4in)Radius
TORQUE REQUIREMENTS
Instructions for Connecting Piping to Indoor Unit
1.
Align the center of the two pipes that you will connect. See Fig. 5.7
.
Indoor unit tubing Flare nut Pipe
2.
Tighten the flare nut as tightly as possible by hand.
3.
Using a spanner, grip the nut on the unit tubing.
4.
While firmly gripping the nut on the unit tubing, use a torque wrench to tighten the flare nut according to the torque values in the Torque Requirements table below. Loosen the flaring nut slightly, then tighten again.
Fig. 5.6
Fig. 5.7
Fig. 5.8
Outer Diameter of Pipe (mm) Tightening Torque (N•cm) Add. Tightening Torque (N•cm)
Ø 6.35 (Ø 0.25”) 1,500 (11lb•ft) 1,600 (11.8lb•ft)
Ø 9.52 (Ø 0.375”) 2,500 (18.4lb•ft) 2,600 (19.18lb• ft)
Ø 12.7 (Ø 0.5”) 3,500 (25.8lb•ft) 3,600 (26.55lb•ft)
Ø 16 (Ø 0.63”)
Ø 19 (Ø 0.75”)
4,500 (33.19lb•ft)
6,500 (47.94lb•ft)
4,700 (34.67lb•ft)
6,700 (49.42lb•ft)
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements shown in the table above.
Page 28 
Instructions for Connecting Piping to Outdoor Unit
1.
Unscrew the cover from the packed valve on the side of the outdoor unit. (See Fig. 5.9)
2.
Remove protective caps from ends of valves.
3.
Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand.
4.
Using a spanner, grip the body of the valve. Do not grip the nut that seals the service valve. (See Fig. 5.10)
USE SPANNER TO GRIP MAIN BODY OF VALVE
Torque from tightening the flare nut can snap off other parts of valve.
5.
While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.
6.
Loosen the flaring nut slightly, then tighten again.
7.
Repeat Steps 3 to 6 for the remaining pipe.
Fig. 5.9
Fig. 5.10
Valve cove
Page 29 
Air Evacuation
7
Preparations and Precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
o
Check to make sure that both high­pressure and low-pressure pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual.
o
Check to make sure all wiring is connected properly.
Evacuation Instructions
Before using the manifold gauge and vacuum pump, read their operation manuals to familiarize yourself with how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Pressure hose / Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
1.
Connect the charge hose of the manifold gauge to service port on the outdoor unit’s low pressure valve.
2.
Connect another charge hose from the manifold gauge to the vacuum pump.
MC MC
Fig. 6.1
3.
Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.
4.
Turn on the vacuum pump to evacuate the system.
5.
Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-10 Pa).
5
Page 30 
CAUTION
DO NOT mix refrigerant types.
6.
Close the Low Pressure side of the manifold gauge, and turn off the vacuum pump.
7.
Wait for 5 minutes, then check that there has been no change in system pressure.
8.
If there is a change in system pressure, refer to Gas Leak Check section for information on how to check for leaks. If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve).
9.
Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then close the valve after 5 seconds.
10.
Watch the Pressure Gauge for one minute to make sure that there is no change in
pressure. The Pressure Gauge should read slightly higher than atmospheric pressure.
Flare nut
Cap
V
alve body
Valve stem
11.
Remove the charge hose from the service port.
12.
Using hexagonal wrench, fully open both the high pressure and low pressure valves.
13.
Tighten valve caps on all three valves (service port, high pressure, low pressure) by hand. You may tighten it further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. Do not try to force the valve to open further.
Note on Adding Refrigerant
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Fig. 6.2
Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is 7.5m (25’). In other areas, the standard pipe length is 5m (16‘). The refrigerant should be charged from the service port
on the outdoor unit’s low pressure valve.
The additional refrigerant to be charged can be
calculated using the following formula:
For R290 refrigerant unit, the total amount of refrigerant to be charged is no more than: 387g(<=9000Btu/h), 447g(>9000Btu/h and <=12000Btu/h), 547g(>12000Btu/h and <=18000Btu/h), 632g(>18000Btu/h and <=24000Btu/h).
Connective Pipe
Length (m)
Air Purging
Method
Additional Refrigerant
< Standard pipe length Vacuum Pump N/A
> Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25”)
R32:
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 0.13oZ/ft
R290:
R290:
(Pipe length – standard length) x 10g/m
(Pipe length – standard length) x 0.10oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
R32:
(Pipe length – standard length) x 24g/m
(Pipe length – standard length) x 0.26oZ/ft
(Pipe length – standard length) x 18g/m
(Pipe length – standard length) x 0.19oZ/ft
R410A:
R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Loading...
+ 90 hidden pages