INVENTOR O3MVI32-09WiFiR, O3MVO32-09O3MVI32-12WiFiR, O3MVO32-24, O3MVO32-12O3MVI32-18WiFiR, O3MVO32-18O3MVI32-24WiFiR Service Manual

• SERVICE MANUAL
ENGLISH
WALL MOUNTED UNIT
AIR CONDITIONING SYSTEMS
MODELS:
O3MVI32-09WiFiR/O3MVO32-09 O3MVI32-12WiFiR/O3MVO32-12 O3MVI32-18WiFiR/O3MVO32-18 O3MVI32-24WiFiR/O3MVO32-24
Table of Contents
Page
1. Safety Precautions ........................................................................................ 1
1. Precautions
2. Information servicing
2. Specifications ................................................................................................ 7
1. Model Reference
2. Electrical Wiring Diagrams
3. Product Features ........................................................................................... 13
1. Operation Modes and Functions
4. Maintenance and Disassembly .................................................................... 20
1. Maintenance
2. Disassembly
5. Troubleshooting ............................................................................................ 59
1. Safety Caution
2. General Troubleshooting
3. Error Diagnosis and Troubleshooting Without Error Code
4. Quick Maintenance by Error Code
5. Troubleshooting by Error Code
Appendix ............................................................................................................. 86
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K)
ii) Temperature Sensor Resistance Value Table for TP (°C – K)
iii) Pressure On Service Port
Caution: Risk of fire/flammable material
Contents
1. Precautions .............................................................................................................2
2. Information servicing ............................................................................................3
Safety Precautions
Safety
Precautions
Page 2
1. Precautions
To prevent personal injury, or property or unit damage, adhere to all precautionary measures and instructions outlined in this manual. Before servicing a unit, refer to this service manual and its relevant sections.
Failure to adhere to all precautionary measures listed in this section may result in personal injury, damage to the unit or to property, or in extreme cases, death.
WARNING indicates a potentially hazardous situation which if not avoided could result in serious personal injury, or death.
CAUTION indicates a potentially hazardous situation which if not avoided could result in minor or moderate personal injury, or unit damage.
1.1 In case of Accidents or Emergency
WARNING
If a gas leak is suspected, immediately turn off the gas and ventilate the area if a gas leak is suspected before turning the unit on.
If strange sounds or smoke is detected from the unit, turn the breaker off and disconnect the power supply cable.
If the unit comes into contact with liquid, contact an authorized service center.
If liquid from the batteries makes contact with skin or clothing, immediately rinse or wash the area well with clean water.
Do not insert hands or other objects into the air inlet or outlet while the unit is plugged in.
Do not operate the unit with wet hands.
Do not use a remote controller that has previously
been exposed to battery damage or battery leakage.
CAUTION
Clean and ventilate the unit at regular intervals when operating it near a stove or near similar devices.
Do not use the unit during severe weather conditions. If possible, remove the product from the window before such occurrences.
1.2 Pre-Installation and Installation
WARNING
Use this unit only on a dedicated circuit.
Damage to the installation area could cause the unit
to fall, potentially resulting in personal injury, prop­erty damage, or product failure.
Only qualified personnel should disassemble, install, remove, or repair the unit.
Only a qualified electrician should perform electri- cal work. For more information, contact your dealer, seller, or an authorized service center.
CAUTION
While unpacking be careful of sharp edges around the unit as well as the edges of the fins on the con­denser and evaporator.
1.3 Operation and Maintenance
WARNING
Do not use defective or under-rated circuit breakers.
Ensure the unit is properly grounded and that a
dedicated circuit and breaker are installed.
Do not modify or extend the power cable. Ensure the power cable is secure and not damaged during operation.
Do not unplug the power supply plug during operation.
Do not store or use flammable materials near the unit.
Do not open the inlet grill of the unit during operation.
Do not touch the electrostatic filter if the unit is equipped with one.
Do not block the inlet or outlet of air flow to the unit.
Do not use harsh detergents, solvents, or similar items
to clean the unit. Use a soft cloth for cleaning.
Do not touch the metal parts of the unit when removing the air filter as they are very sharp.
Do not step on or place anything on the unit or outdoor units.
Do not drink water drained from the unit
Avoid direct skin contact with water drained from the
unit.
Use a firm stool or step ladder according to manufacturer procedures when cleaning or maintaining the unit.
CAUTION
Do not install or operate the unit for an extended period of time in areas of high humidity or in an environment directly exposing it to sea wind or salt spray.
Do not install the unit on a defective or damaged installation stand, or in an unsecure location.
Ensure the unit is installed at a level position
Do not install the unit where noise or air discharge
created by the outdoor unit will negatively impact the environment or nearby residences.
Do not expose skin directly to the air discharged by the unit for prolonged periods of time.
Ensure the unit operates in areas water or other liquids.
Ensure the drain hose is installed correctly to ensure proper water drainage.
When lifting or transporting the unit, it is recommended that two or more people are used for this task.
When the unit is not to be used for an extended time, disconnect the power supply or turn off the breaker.
Safety
Precautions
Page 3
2. Information servicing
2.1 Checks to the area
• Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized.
• For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work
on the system.
2.2 Work procedure
• Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being
present while the work is being performed.
2.3 Work procedure
• All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out.
• Work in confined spaces shall be avoided.
• The area around the work space shall be sectioned off. Ensure that the conditions within the area have been made
safe by control of flammable material.
2.4 Checking for presence of refrigerant
• The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres.
• Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. no sparking,
adequately sealed or intrinsically safe.
2.5 Presence of fire extinguisher
• If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand.
• Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
2.6 No ignition sources
• No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion.
• All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the
surrounding space.
• Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks.
• NO SMOKING signs shall be displayed.
2.7 Ventilated area
• Ensure that the area is in the open or that it is adequately ventilated before breaking into the
• system or conducting any hot work. A degree of ventilation shall continue during the period
• that the work is carried out. The ventilation should safely disperse any released refrigerant
• and preferably expel it externally into the atmosphere.
2.8 Checks to the refrigeration equipment
• Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
• the charge size is in accordance with the room size within which the refrigerant containing parts are installed;
• the ventilation machinery and outlets are operating adequately and are not obstructed;
• if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; marking to the equipment continues to be visible and legible.
• markings and signs that are illegible shall be corrected;
• refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
2.9 Checks to electrical devices
• Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include:
Safety
Precautions
Page 4
• that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• that there no live electrical components and wiring are exposed while charging, recovering or purging the system;
• that there is continuity of earth bonding.
2.10 Repairs to sealed components
• During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
• Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
2.11 Repair to intrinsically safe components
• Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
• Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
2.12 Cabling
• Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check
shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
2.13 Detection of flammable refrigerants
• Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
2.14 Leak detection methods
• The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
• If a leak is suspected, all naked flames shall be removed or extinguished.
• If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the systemremote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
2.15 Removal and evacuation
• When breaking into the refrigerant circuit to make repairs or for any other purpose, conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration.
• The following procedure shall be adhered to:
• remove refrigerant;
• purge the circuit with inert gas;
• evacuate;
• purge again with inert gas;
• open the circuit by cutting or brazing.
Safety
Precautions
Page 5
• The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.
• Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
2.16 Charging procedures
• In addition to conventional charging procedures, the following requirements shall be followed:
• Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigeration system.
• Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
2.17 Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken.
In case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
• Become familiar with the equipment and its operation.
• Isolate system electrically.
• Before attempting the procedure ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
• Pump down refrigerant system, if possible.
• If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
• Make sure that cylinder is situated on the scales before recovery takes place.
• Start the recovery machine and operate in accordance with manufacturer’s instructions.
• Do not overfill cylinders. (No more than 80 % volume liquid charge).
• Do not exceed the maximum working pressure of the cylinder, even temporarily.
• When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
• Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
2.18 Labelling
• Equipment shall be labelled stating that it has been de­commissioned and emptied of
• refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
2.19 Recovery
• When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct numbers of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
Safety
Precautions
Page 6
• Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order.
• Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
• If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
Contents
1. Model Reference ....................................................................................................8
2. Electrical Wiring Diagrams ....................................................................................9
2.1 Indoor Unit ....................................................................................................9
2.2 Outdoor Unit ...............................................................................................11
Specifications
Specifications
Page 8
1. Model Reference
Refer to the following table to determine the specific indoor and outdoor unit model number of your purchased equipment.
Indoor Unit Model Outdoor Unit Model Capacity (Btu) Power Supply
O3MVI32-09WiFiR O3MVO32-09
9k
220-240V~, 50Hz,
1Phase
O3MVI32-12WiFiR O3MVO32-12
12k
O3MVI32-24WiFiR O3MVO32-18
18k
O3MVI32-24WiFiR O3MVO32-24
24k
Specifications
Page 9
2. Electrical Wiring Diagrams
2.1 Indoor unit
Abbreviation Paraphrase
Y/G Yellow-Green Conductor
ION Positive and Negative Ion Generator
CAP Capacitor
PLASMA Electronic Dust Collector
L LIVE
N NEUTRAL
Heater The Electric Heating Belt of Indoor Unit
T1 Indoor Room Temperature
T2 Coil Temperature of Indoor Heat Exchanger Middle
Specifications
Page 10
O3MVI32-09WiFiR, O3MVI32-12WiFiR, O3MVI32-18WiFiR, O3MVI32-24WiFiR
INDOOR WIRING DIAGRAM
P1
P2
S
16022000020169
HEATER
OPTIONAL
Applicalbe for MONO unit with 1W standby control feature
Applicable for MULTI and MONO unit without 1W standby control feature
X Y E 12V/5V
HA HB
To CCM Comm.Bus or 485 Wire-controller
To Randomly Connected Wire-controller
To Remote Switch
To Remote Alarm
4
3
- - - - This symbol indicates the element is optional,the actual shape shall prevail.
M
M
M
5(3or2)
ION
OPTIONAL
Y/G
3
Applicable to AC motor only
OPTIONAL
CAP
2
OPTIONAL
OPTIONAL
CN701
SWITCH BOARD
2
Specifications
Page 11
2.2 Outdoor Unit
Abbreviation Paraphrase
4-WAY Gas Valve Assembly/4-WAY VALVE
AC-FAN Alternating Current FAN
DC-FAN Direct Current FAN
CT1 AC Current Detector
COMP Compressor
L-PRO Low Pressure Switch
H-PRO High Pressure Switch
EEV Electronic Expansion Valve
O3MVO32-09, O3MVO32-12, O3MVO32-18
4-WAY
OPTIONAL: DC-FAN
CN 7
AC-FAN
CAPACITOR
PAN HEATER
CRANKCASE HEAT ER
BROWN
I NDOOR UNI T
S
W
2(N)
L
N
BLUE OR BLACK
1(L)
Y/G
AMBIENT TEMP. SENSOR
Y/G
Y/G
Y/G
Y/G
Y/G
U
V
W
BLUE
RED
BLACK
Y/G
Specifications
Page 12
O3MVO32-24
BLAC
K(BLUE
)
OPTIONAL:
HEATER 2
H
E
A
TE
R
1
O
P
T
IO
N
A
L
CN4
BR
OWN
BLUE
16022000019069
()YELLOW
3
Applicable to the units adopting DC motor only
Applicable to the units adopting AC motor only
CN3
CN30
TO I NDOOR UNI T
POWER SUPPL Y
Y/G
O
PTI
O
NA
L
O
PTI
O
NAL
Contents
1. Operation Modes and Functions ........................................................................14
1.1 Abbreviation ................................................................................................14
1.2 Safety Features ............................................................................................14
1.3 Display Function ..........................................................................................14
1.4 Fan Mode ....................................................................................................15
1.5 Cooling Mode .............................................................................................15
1.6 Heating Mode .............................................................................................15
1.7 Auto-mode ..................................................................................................16
1.8 Drying Mode ...............................................................................................16
1.9 Forced Operation Function ..........................................................................16
1.10 Sleep Function .............................................................................................16
1.11 Auto-Restart Function ..................................................................................16
1.12 Refrigerant Leakage Detection .....................................................................17
1.13 8°C Heating(Optional) ................................................................................17
1.14 Self Clean(Optional) ....................................................................................17
1.15 Follow Me(Optional) ...................................................................................17
1.16 Silence(Optional) .......................................................................................17
1.17 Information Inquiry ......................................................................................17
Product Features
Product Features
Page 14
1. Operation Modes and Functions
1.1 Abbreviation
Unit element abbreviations
Abbreviation Element
T1 Indoor room temperature
T2 Coil temperature of evaporator
T3 Coil temperature of condenser
T4 Outdoor ambient temperature
TS Set temperature
TP Compressor discharge temperature
1.2 Safety Features
Compressor three-minute delay at restart
Compressor functions are delayed for up to one minute upon the first startup of the unit, and are delayed for up to three minutes upon subsequent unit restarts.
Zero crossing detection error protection
If AC can not detect zero crossing signal for 4 minutes or the zero crossing signal time interval is not correct, the unit will stop and the LED will display the failure. The correct zero crossing signal time interval should be between 6-13ms.
Automatic shutoff based on discharge temperature
If the compressor discharge temperature exceeds 108°C for a period of time, the compressor ceases operation.
Automatic shutoff based on fan speed
If the indoor fan speed registers below 300RPM for an extended period of time, the unit ceases operation and the corresponding error code is displayed on the indoor unit.
Inverter module protection
The inverter module has an automatic shutoff mechanism based on the unit’s current, voltage, and temperature. If automatic shutoff is initiated, the corresponding error code is displayed on the indoor unit and the unit ceases operation.
Indoor fan delayed operation
• When the unit starts, the louver is automatically activated and the indoor fan will operate after a period of 7 seconds.
• If the unit is in heating mode, the indoor fan is regulated by the anti-cold wind function.
Compressor preheating
Preheating is automatically activated when T4 sensor is lower than 3°C.
Sensor redundancy and automatic shutoff
• If one temperature sensor malfunctions, the air conditioner continues operation and displays the corresponding error code, allowing for emergency use.
• When more than one temperature sensor is malfunctioning, the air conditioner ceases operation.
Refrigerant leakage detection
This function is active only when cooling mode is selected. It will detect if the compressor is being damaged by refrigerant leakage or by compressor overload. This is measured using the coil temperature of evaporator T2 when the compressor is in operation.
1.3 Display Function
Unit display functions
Function Display
Temperature Set temperature value
Temperature (fan and Drying mode)
Room temperature
Activation of Timer ON, Fresh, Swing, Turbo, or Silent
(3s)
Cancellation of Timer OFF, Fresh, Swing, Turbo, or Silent
(3s)
Defrost
Warming in heating mode
Self-clean (available on select units only)
Heating in room temperature under 8°C
Product Features
Page 15
1.4 Fan Mode
When fan mode is activated:
• The outdoor fan and compressor are stopped.
• Temperature control is disabled and no temperature setting is displayed.
• The indoor fan speed can be set to high, medium, low, or auto.
• The louver operations are identical to those in cooling mode.
• Auto fan: In fan-only mode, AC operates the same as auto fan in cooling mode with the temperature set at
24°C.
1.5 Cooling Mode
1.5.1 Compressor Control
T means the temperature compensation.
• When T1-Ts < T- 2 , the compressor ceases operation.
• When T1-Ts > T+3, the compressor continues operation.
• When the AC is operating in mute mode, the compressor operates at a low frequency.
• When the current exceeds the preset value, the current protection function activates and the compressor ceases operation.
1.5.2 Indoor Fan Control
• In cooling mode, the indoor fan operates continuously. The fan speed can be set to high, medium, low, or auto.
• If the compressor ceases operations when the configured temperature is reached, the indoor fan motor operates at the minimum or configured speed.
1.5.3 Outdoor Fan Control
• The outdoor unit will be run at different fan speed according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are different.
1.5.4 Condenser Temperature Protection
When condenser temperature is more than setting value, the compressor ceases operations..
1.5.5 Evaporator Temperature Protection
When evaporator temperature drops below a configured value, the compressor and outdoor fan cease operations.
1.6 Heating Mode
1.6.1 Compressor Control
T means the temperature compensation.
• When T1-Ts>-T, the compressor ceases operation.
• When T1-Ts<-T-1.5°C, the compressor continues operation.
• When the AC is operating in mute mode, the compressor operates at a low frequency.
• When the current exceeds the preset value, the current protection function activates and the compressor ceases operation.
1.6.2 Indoor Fan Control:
• When the compressor is on, the indoor fan can be set to high/medium/low/auto. And the anti-cold wind function has the priority.
• When indoor unit coil temp. is low, the anti-cold air function will start and indoor fan motor will run at low speed, the speed can’t be changed ,when the temp. is lower than setting value, the indoor fan motor will stop.
• When the indoor temp reaches the setting temp., the compressor will stop, the indoor fan motor will run at the minimum speed or setting speed.(The anti-cold air function is valid).
1.6.3 Outdoor Fan Control:
• The outdoor unit will be run at different fan speed according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are different.
1.6.4 Defrosting mode
• The unit enters defrosting mode according to the temperature value of T3 and T4 as well as the compressor running time.
• In defrosting mode, the compressor continues to run, the indoor and outdoor motor will cease operation, the defrost light of the indoor unit will turn on, and
the “ ” symbol is displayed.
• If any one of the following conditions is satisfied, defrosting ends and the machine switches to normal heating mode:
• T3 rises above TCDE1°C.
• T3 maintained above TCDE2°C for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting mode.
1.6.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset protection value, the compressor ceases operations.
Product Features
Page 16
1.7 Auto-mode
• This mode can be selected with the remote controller and the setting temperature can be changed between 17°C~30°C.
• In auto mode, the machine selects cooling, heating, or fan-only mode on the basis of T (T =T1-Ts).
T Running mode
T>2 Cooling
-2℃≤∆T2 Fan-onlyT<-2 Heating*
Heating*: In auto mode, cooling only models run the fan
• The louver operates same as in relevant mode.
• If the machine switches mode between heating and cooling, the compressor will keep stopping for certain time and then choose mode according to T1-Ts.
• If the setting temperature is modified, the machine will choose running function again.
1.8 Drying mode
• Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
• All protections are active and the same as that in cooling mode.
1.9 Forced operation function
• Forced cooling mode:
The compressor and outdoor fan continue to run and the indoor fan runs at low speed. After running for 30 minutes, the AC will switch to auto mode with a preset temperature of 24°C.
• Forced auto mode:
Forced auto mode operates the same as normal auto mode with a preset temperature of 24°C.
• The unit exits forced operation when it receives the following signals:
• Switch on
• Switch off
• Timer on
• Timer off
• Changes in:
• mode
• fan speed
• sleeping mode
• Follow me
1.10 Sleep function
• The sleep function is available in cooling, heating, or auto mode.
• The operational process for sleep mode is as follows:
• When cooling, the temperature rises 1°C (to not higher than 30°C) every hour. After 2 hours, the temperature stops rising and the indoor fan is fixed at low speed.
• When heating, the temperature decreases 1°C(to not lower than 17°C) every hour. After 2 hours, the temperature stops decreasing and the indoor fan is fixed at low speed. Anti-cold wind function takes priority.
• The operating time for sleep mode is 7 hours, after which, the unit exits this mode and switches off.
• The timer setting is available in this mode.
1.11 Auto-Restart function
• The indoor unit has an auto-restart module that allows the unit to restart automatically. The module automatically stores the current settings (not including the swing setting) and, in the case of a sudden power failure, will restore those setting automatically within 3 minutes after power returns.
• If the unit was in forced cooling mode, it will run in this mode for 30 minutes and turn to auto mode with temperature set to 24°C.
• If there is a power failure while the unit is running, the compressor starts 3 minutes after the unit restarts. If the unit was already off before the power failure, the compressor starts 1 minute after the unit restarts.
1.12 Refrigerant Leakage Detection
With this new technology, the display area will show “EC” when the outdoor unit detects refrigerant leakage.
1.13 8°C Heating(Optional)
In heating mode, the temperature can be set to as low as 8°C, preventing the indoor area from freezing if unoccupied during severe cold weather.
1.14 Self clean(Optional)
• If you press “Self Clean” when the unit is in cooling or drying mode:
• For cooling models, the indoor unit will run in low fan mode for a certain time, then ceases operation.
Product Features
Page 17
• For heat pump models, the indoor unit will run in fan-only mode, then low heat, and finally in fan­only mode.
• Self Clean keeps the indoor unit dry and prevents mold growth.
1.15 Follow me(Optional)
• If you press “Follow Me” on the remote, the indoor unit will beep. This indicates the follow me function is active.
• Once active, the remote control will send a signal every 3 minutes, with no beeps. The unit automatically sets the temperature according to the measurements from the remote control.
• The unit will only change modes if the information from the remote control makes it necessary, not from the unit’s temperature setting.
• If the unit does not receive a signal for 7 minutes or you press “Follow Me,” the function turns off. The unit regulates temperature based on its own sensor and settings.
1.16 Silence (Optional)
Press “Silence” on the remote control to enable the SILENCE function. While this function is active, the compressor frequency is maintained at a lower level than F2. The indoor unit will run at faint breeze, which reduces noise to the lowest possible level.
1.17 Information Inquiry
• To enter information inquiry status, complete the following procedure within ten seconds:
• Press LED 3 times.
• Press SWING 3 times.
• If you are successful, you will hear beeps for two seconds.
• Use the LED and SWING buttons to cycle through information displayed.
• Pressing LED will display the next code in the sequence. Pressing SWING will show the previous.
• The following table shows information codes. The screen will display this code for two seconds, then the information for 25 seconds.
Product Features
Page 18
Displayed code Explanation
Displayed
value
Meaning Additional Notes
T1
T2
T3
T4
Tb
TP
TH
FT
Fr
Room temperature
-1F,-1E,-1d,-1c,­1b,-1A
-19—99
A0,A1,…A9
b0,b1,…b9
c0,c1,…c9
d0,d1,…d9
E0,E1,…E9
F0,F1,…F9
-25,-24,-23,-22,
-21,-20
-19—99
100,101,…109
110,111,…119
120,121,…129
130,131,…139
140,141,…149
150,151,…159
1. All displayed temperatures use actual values.
2. All temperatures are displayed in °C regardless of remote used.
3. T1, T2, T3, T4, and T2B display ranges from -25 to 70 °C. TP display ranges from -20 to 130 °C.
4. The frequency display ranges from 0 to 159HZ.
5. If the actual values exceed or fall short of the defined range, the values closest to the maximum and minimum values will be displayed.
Indoor coil temperature
Outdoor coil temperature
Ambient temperature
Outlet temperature of indoor coil
Discharge temperature
Suction temperature
Targeted frequency
Actual frequency
IF
Indoor fan speed
0
1,2,3,4
14-FF
OFF
Low speed, Medium speed, High speed, Turbo.
Actual fan speed is equal to the display value converted to decimal value and multiplied by 10. This is measured in RPM.
N/A
Used for some large capacity motors.
Used for some small capacity motors.
The display value is 14-FF (hexadecimal). The corresponding fan speed ranges from 200 to 2550RPM.
OF
Outdoor fan speed
LA
EXV opening angle 0-FF
Actual EXV opening value is equal to the display value converted to decimal value and then multiplied by 2.
-
CT
Compressor continuous running time
0-FF 0-255 minutes
If the actual value exceeds or falls short of the defined range, the value closest to the maximum and minimum will be displayed.
ST
Causes of compressor stop
0-99
For a detailed explanation, contact technical support.
-
Product Features
Page 19
Displayed code Explanation
Displayed
value
Meaning Additional Notes
A0
Reserved
0-FF
2-28
5-20
5-25
- -
A1
0
1
2
3
4
5
6
L
A
U
T
A
5
T
Contents
1. Maintenance ........................................................................................................21
1.1 First Time Installation Check ........................................................................21
1.2 Refrigerant Recharge ...................................................................................23
1.3 Re-Installation .............................................................................................24
1.3.1 Indoor Unit ..................................................................................24
1.3.2 Outdoor Unit ...............................................................................26
2. Disassembly .........................................................................................................28
2.1 Indoor Unit ..................................................................................................28
2.2 Outdoor Unit ...............................................................................................40
Maintenance and Disassembly
Maintenance and
Disassembly
Page 21
1. Maintenance
1.1 First Time Installation Check
Air and moisture trapped in the refrigerant system affects the performance of the air conditioner by:
• Increasing pressure in the system.
• Increasing the operating current.
• Decreasing the cooling or heating efficiency.
• Congesting the capillary tubing due to ice build-up in the refrigerant circuit.
• Corroding the refrigerant system.
To prevent air and moisture from affecting the air conditioner’s performance, the indoor unit, as well as the pipes between the indoor and outdoor unit, must be be leak tested and evacuated.
Leak test (soap water method)
Use a soft brush to apply soapy water or a neutral liquid detergent onto the indoor unit connections and outdoor unit connections. If there is gas leakage, bubbles will form on the connection.
Air purging with vacuum pump
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
)RUYK
)RUYK
3GTOLURJ\GR\K
36G
6XKYY[XK
MG[MK
.GTJRK2U
.GTJRK.O
)NGXMKNUYK
)NGXMKNUYK
<GI[[S V[SV
<GI[[S V[SV
)USVU[TJSKZKX
2U
.O
Maintenance and
Disassembly
Page 22
Procedure:
1. Tighten the flare nuts of the indoor and outdoor
units, and confirm that both the 2- and 3-way valves are closed.
2. Connect the charge hose with the push pin of Handle Lo to the gas service port of the 3-way valve.
3. Connect another charge hose to the vacuum pump.
4. Fully open the Handle Lo manifold valve.
5. Using the vacuum pump, evacuate the system for
30 minutes.
a. Check whether the compound meter indicates
-0.1 MPa (14.5 Psi).
• If the meter does not indicate -0.1 MPa (14.5 Psi) after 30 minutes, continue evacuating for an additional 20 minutes.
• If the pressure does not achieve -0.1 MPa
(14.5 Psi) after 50 minutes, check for leakage.
• If the pressure successfully reaches -0.1 MPa (14.5 Psi), fully close the Handle Lo valve, then cease vacuum pump operations.
b. Wait for 5 minutes then check whether the gauge
needle moves after turning off the vacuum pump. If the gauge needle moves backward, check wether there is gas leakage.
6. Loosen the flare nut of the 3-way valve for 6 or 7 seconds and then tighten the flare nut again.
a. Confirm the pressure display in the pressure
indicator is slightly higher than the atmospheric pressure.
b. Remove the charge hose from the 3-way valve.
7. Fully open the 2- and 3-way valves and tighten the
cap of the 2- and 3-way valves.
Maintenance and
Disassembly
Page 23
1.2 Refrigerant Recharge
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
)NKIQ\GR\K
56+4
)259+
)NGXMOTM
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
5VKT
5VKT
2U
.O
+RKIZXUTOIYIGRK
I_ROTJKX
Prior to recharging the refrigerant, confirm the additional amount of refrigerant required using the following table:
Models Standard length Max. elevation Max. length Additional refrigerant
9k&12k 5m (16.4ft) 10m (32.8ft) 25m (82.0ft) 12g/m (0.13oz/ft)
18k 5m (16.4ft) 20m (65.6ft) 30m (98.4ft) 12g/m (0.13oz/ft)
24k 5m (16.4ft) 25m (82ft) 50m (164ft) 24g/m (0.26oz/ft)
Procedure:
1. Close both 2- and 3-way valves.
2. Slightly connect the Handle Lo charge hose to the
3-way service port.
3. Connect the charge hose to the valve at the bottom of the cylinder.
4. If the refrigerant is R410A, invert the cylinder to ensure a complete liquid charge.
5. Open the valve at the bottom of the cylinder for 5 seconds to purge the air in the charge hose, then fully tighten the charge hose with push pin Handle Lo to the service port of 3-way valve..
6. Place the charging cylinder onto an electronic scale and record the starting weight.
7. Fully open the Handle Lo manifold valve, 2- and
3-way valves.
8. Operate the air conditioner in cooling mode to charge the system with liquid refrigerant.
9. When the electronic scale displays the correct weight (refer to the gauge and the pressure of the low side to confirm), turn off the air conditioner, then disconnect the charge hose from the 3-way service port immediately..
10. Mount the caps of service port and 2- and 3-way valves.
11. Use a torque wrench to tighten the caps to a torque of 18 N.m.
12. Check for gas leakage.
Maintenance and
Disassembly
Page 24
1.3 Re-Installation
1.3.1 Indoor Unit
Collecting the refrigerant into the outdoor unit
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
)RUYK
)RUYK
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
5VKT
)RUYK
2U
.O
Procedure:
1. Confirm that the 2- and 3-way valves are opened.
2. Connect the charge hose with the push pin of Handle
Lo to the 3-way valve’s gas service port.
3. Open the Handle Lo manifold valve to purge air from the charge hose for 5 seconds and then close it quickly.
4. Close the 2-way valve.
5. Operate the air conditioner in cooling mode. Cease
operations when the gauge reaches 0.1 MPa (14.5 Psi).
6. Close the 3-way valve so that the gauge rests between 0.3 MPa (43.5 Psi) and 0.5 MPa (72.5 Psi).
7. Disconnect the charge set and mount the caps of service port and 2- and 3-way valves.
8. Use a torque wrench to tighten the caps to a torque of 18 N.m.
9. Check for gas leakage.
Maintenance and
Disassembly
Page 25
Air purging with vacuum pump
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
)RUYK
)RUYK
3GTOLURJ\GR\K
36G
6XKYY[XK
MG[MK
.GTJRK2U
.GTJRK.O
)NGXMKNUYK
)NGXMKNUYK
<GI[[S V[SV
<GI[[S V[SV
)USVU[TJSKZKX
2U
.O
Procedure:
1. Tighten the flare nuts of the indoor and outdoor
units, and confirm that both the 2- and 3-way valves are closed.
2. Connect the charge hose with the push pin of Handle Lo to the gas service port of the 3-way valve.
3. Connect another charge hose to the vacuum pump.
4. Fully open the Handle Lo manifold valve.
5. Using the vacuum pump, evacuate the system for 30
minutes.
a. Check whether the compound meter indicates
-0.1 MPa (14.5 Psi).
• If the meter does not indicate -0.1 MPa (14.5 Psi) after 30 minutes, continue evacuating for an additional 20 minutes.
• If the pressure does not achieve -0.1 MPa (14.5
Psi) after 50 minutes, check for leakage.
• If the pressure successfully reaches -0.1 MPa (14.5 Psi), fully close the Handle Lo valve, then cease vacuum pump operations.
b. Wait for 5 minutes then check whether the gauge
needle moves after turning off the vacuum pump. If the gauge needle moves backward, check wether there is gas leakage.
6. Loosen the flare nut of the 3-way valve for 6 or 7 seconds and then tighten the flare nut again.
a. Confirm the pressure display in the pressure
indicator is slightly higher than the atmospheric pressure.
b. Remove the charge hose from the 3-way valve.
7. Fully open the 2- and 3-way valves and tighten the
cap of the 2- and 3-way valves.
Maintenance and
Disassembly
Page 26
1.3.2 Outdoor Unit
Evacuation for the whole system
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
56+4
)259+
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
5VKT
5VKT
2U
.O
<GI[[SV[SV
Procedure:
1. Confirm that the 2- and 3-way valves are opened.
2. Connect the vacuum pump to the 3-way valve’s
service port.
3. Evacuate the system for approximately one hour. Confirm that the compound meter indicates
-0.1 MPa (14.5Psi).
4. Close the valve (Low side) on the charge set and turn off the vacuum pump.
5. Wait for 5 minutes then check whether the gauge
needle moves after turning off the vacuum pump. If the gauge needle moves backward, check whether there is gas leakage.
6. Disconnect the charge hose from the vacuum pump.
7. Mount the caps of service port and 2- and 3-way
valves.
8. Use a torque wrench to tighten the caps to a torque of 18 N.m.
Maintenance and
Disassembly
Page 27
Refrigerant charging
/TJUUX[TOZ
2OW[OJYOJK
-GYYOJK
)NKIQ\GR\K
56+4
)259+
)NGXMOTM
:]U]G_\GR\K
:NXKK]G_\GR\K
5[ZJUUX[TOZ
5VKT
5VKT
2U
.O
+RKIZXUTOIYIGRK
I_ROTJKX
Note: 1. Mechanical connectors used indoors shall comply with local regulations.
2. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated.
Procedure:
1. Close both 2- and 3-way valves.
2. Slightly connect the Handle Lo charge hose to the
3-way service port.
3. Connect the charge hose to the valve at the bottom of the cylinder.
4. If the refrigerant is R410A, invert the cylinder to ensure a complete liquid charge.
5. Open the valve at the bottom of the cylinder for 5 seconds to purge the air in the charge hose, then fully tighten the charge hose with push pin Handle Lo to the service port of 3-way valve..
6. Place the charging cylinder onto an electronic scale and record the starting weight.
7. Fully open the Handle Lo manifold valve, 2- and
3-way valves.
8. Operate the air conditioner in cooling mode to charge the system with liquid refrigerant.
9. When the electronic scale displays the correct weight (refer to the gauge and the pressure of the low side to confirm), turn off the air conditioner, then disconnect the charge hose from the 3-way service port immediately..
10. Mount the caps of service port and 2- and 3-way valves.
11. Use a torque wrench to tighten the caps to a torque of 18 N.m.
12. Check for gas leakage.
Maintenance and
Disassembly
Page 28
2. Disassembly
2.1 Indoor unit
1. Front Panel
Procedure Illustration
1) Hold the front panel by the tabs on the both sides and lift it (see CJ_AF_ INV_001).
2) Push up the bottom of an air filter, and then pull it out downwards (see CJ_AF_INV_002).
CJ_AF_INV_001
CJ_AF_INV_002
Note: This section is for reference only. Actual unit appearance may vary.
Front Panel
Tab
Filter
Maintenance and
Disassembly
Page 29
Procedure Illustration
3) Open the horizontal louver and push the hook towards left to open it (see CJ_AF_INV_003).
4) Bend the horizontal louver lightly by both hands to loosen the hooks, then remove the horizontal louver (see CJ_AF_INV_004).
CJ_AF_INV_003
CJ_AF_INV_004
Note: This section is for reference only. Actual unit appearance may vary.
Hook
Horizontal Louver
Hook
Maintenance and
Disassembly
Page 30
Procedure Illustration
5) Remove 1 screw and then remove the electrical cover(see CJ_AF_INV_005-1 and CJ_AF_INV_005-2).
6) Disconnect the connector for display board(see CJ_AF_INV_005-3) .
7) Remove the display board(see CJ_AF_ INV_005-4).
CJ_AF_INV_005
Note: This section is for reference only. Actual unit appearance may vary.
CJ_AF_INV_005-1
CJ_AF_INV_005-2
CJ_AF_INV_005-3
CJ_AF_INV_005-4
Maintenance and
Disassembly
Page 31
Procedure Illustration
8) Open the screw caps(2) and the remove the screws(see CJ_AF_ INV_006).
9) Release the 4 hooks.
10) Release the seven hooks in the back (see CJ_AF_INV_007).
CJ_AF_INV_006
CJ_AF_INV_007
Note: This section is for reference only. Actual unit appearance may vary.
Hooks
Maintenance and
Disassembly
Page 32
Procedure Illustration
11) Pull out the panel frame while pushing the hook through a clearance between the panel frame and the heat exchanger (see CJ_AF_INV_008).
CJ_AF_INV_008
Note: This section is for reference only. Actual unit appearance may vary.
Panel Frame
Maintenance and
Disassembly
Page 33
2. Electrical parts
Note: Remove the front panel (refer to 1. Front panel) before disassembling electrical parts.
Procedure Illustration
1) Remove the fixing screw and then remove the cover of electronic box and the terminal cover (see CJ_AF_ INV_009).
2) Pull out the room temperature sensor (T1) and the coil temperature sensor (T2) (see CJ_AF_INV_010).
3) Remove the two screws used for the ground connection (see CJ_AF_ INV_010).
CJ_AF_INV_009
CJ_AF_INV_010
Note: This section is for reference only. Actual unit appearance may vary.
T1 Sensor
Ground Screws
T2 Sensor
Fixing Screw
Electronic Cover
Maintenance and
Disassembly
Page 34
Procedure Illustration
4) Remove the fixing screw (see CJ_AF_ INV_011-1).
5) Pull out the Electrical control box along the direction indicated in right image. to remove it (CJ_AF_INV_011-2).
6) Disconnect the wires. Then remove the electronic main board (CJ_AF_ INV_012).
CJ_AF_INV_011-2
CJ_AF_INV_012
Note: This section is for reference only. Actual unit appearance may vary.
Fixing Screw
Electronic Box
Indoor Fan Motor
Applicable to AC Motor Only
Swing Motor
Display Board
Pipe Temperature Sensor
Room Temperature Sensor
CJ_AF_INV_011-1
Maintenance and
Disassembly
Page 35
Procedure Illustration
7) Remove the fixing screw, then remove the capacitor of fan motor (see CJ_AF_ INV_013).
CJ_AF_INV_013
Note: This section is for reference only. Actual unit appearance may vary.
Capacitor of Fan Motor
Maintenance and
Disassembly
Page 36
3. Evaporator
Note: Remove the front panel and electrical parts (refer to 1. Front panel and 2. Electrical parts) before disassembling evaporator.
Procedure Illustration
1) Disassemble the pipe holder located at the rear of the unit (see CJ_AF_INV_014).
2) Remove the screws on the evaporator located at the fixed plate (see CJ_AF_ INV_015).
3) Remove the two screws on the evaporator located at the base of the bearing side (see CJ_AF_INV_016).
CJ_AF_INV_014
CJ_AF_INV_015
CJ_AF_INV_016
Note: This section is for reference only. Actual unit appearance may vary.
Pipe Holder
Screws
Screws
Maintenance and
Disassembly
Page 37
Procedure Illustration
4) Pull out the evaporator (see CJ_AF_ INV_017).
CJ_AF_INV_017
Note: This section is for reference only. Actual unit appearance may vary.
Evaporator
Maintenance and
Disassembly
Page 38
4. Fan motor and fan
Note: Remove the front panel, electrical parts and evaporator (refer to 1. Front panel, 2. Electrical parts, and
3. Evaporator). before disassembling fan motor and fan.
Procedure Illustration
1) Remove the two screws and remove the fixing board of the fan motor (see CJ_AF_ INV_018).
2) Remove the Bearing sleeve(see CJ_AF_ INV_019).
3) Remove the fixing screw (see CJ_AF_ INV_020).
4) Pull out the fan motor and fan assembly from the side.
CJ_AF_INV_018
CJ_AF_INV_019
CJ_AF_INV_020
Note: This section is for reference only. Actual unit appearance may vary.
Fixing Screw
Screws
Maintenance and
Disassembly
Page 39
5. Step motor
Note: Remove the front panel and electrical parts (refer to 1. Front panel, 2. Electrical parts) before disassembling step motor.
Procedure Illustration
1) Remove the two screws, then remove the stepping motor (see CJ_AF_INV_021).
CJ_AF_INV_021
Note: This section is for reference only. Actual unit appearance may vary.
Stepping Motor
Maintenance and
Disassembly
Page 40
2.2 Outdoor unit
1. Panel Plate
O3MVO32-09, O3MVO32-12
Procedure Illustration
1) Turn off the air conditioner and the power breaker.
2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_AB30_INV_001).
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see CJ_ AB30_INV_002).
CJ_AB30_INV_001
CJ_AB30_INV_002
Note: This section is for reference only. Actual unit appearance may vary.
Big Handle
Top Cover
Maintenance and
Disassembly
Page 41
Procedure Illustration
4) Remove the screws of the front panel and then remove the front panel (6 screws) (see CJ_AB30_INV_003).
5) Remove the screws of water collecting cover (1 screw) (see CJ_AB30_ INV_004).
CJ_AB30_INV_003
CJ_AB30_INV_004
Note: This section is for reference only. Actual unit appearance may vary.
Front Panel
Water Collecting Cover
Maintenance and
Disassembly
Page 42
Procedure Illustration
1) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_AB30_INV_005).
CJ_AB30_INV_005
Note: This section is for reference only. Actual unit appearance may vary.
Right Panel
Maintenance and
Disassembly
Page 43
O3MVO32-18,
Procedure Illustration
1) Turn off the air conditioner and the power breaker.
2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_B30_INV_001).
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see CJ_ B30_INV_002).
CJ_B30_INV_001
CJ_B30_INV_002
Note: This section is for reference only. Actual unit appearance may vary.
Top Cover
Big Handle
Maintenance and
Disassembly
Page 44
Procedure Illustration
1) Remove the screws of the front panel and then remove the front panel (8 screws) (see CJ_B30_INV_003).
2) Remove the screws of water collecting cover and then remove the water collecting cover (1 screw) (see CJ_B30_ INV_004).
CJ_B30_INV_003
CJ_B30_INV_004
Note: This section is for reference only. Actual unit appearance may vary.
Front Panel
Water Collecting Cover
Maintenance and
Disassembly
Page 45
Procedure Illustration
3) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_B30_INV_005).
CJ_B30_INV_005
Note: This section is for reference only. Actual unit appearance may vary.
Right Panel
Maintenance and
Disassembly
Page 46
O3MVO32-24
Procedure Illustration
1) Turn off the air conditioner and the power breaker.
2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_CA30_INV_001).
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see CJ_ CA30_INV_002).
CJ_CA30_INV_001
CJ_CA30_INV_002
Note: This section is for reference only. Actual unit appearance may vary.
Top Cover
Big Handle
Maintenance and
Disassembly
Page 47
Procedure Illustration
4) Remove the screws of the front panel and then remove the front panel (7 screws) (see CJ_CA30_INV_003).
5) Remove the screws of water collecting cover and then remove the water collecting cover (1 screw) (see CJ_ CA30_INV_004).
CJ_CA30_INV_003
CJ_CA30_INV_004
Note: This section is for reference only. Actual unit appearance may vary.
Front Panel
Water Collecting Cover
Maintenance and
Disassembly
Page 48
Procedure Illustration
1) Remove the screws of the right panel and then remove the right panel (6 screws) (see CJ_CA30_INV_005).
CJ_CA30_INV_005
Note: This section is for reference only. Actual unit appearance may vary.
Right Panel
Maintenance and
Disassembly
Page 49
2. Fan disassembly
Note: Remove the panel plate and (refer to 1. Panel plate) before disassembling fan.
O3MVO32-09,
O3MVO32-12, O3MVO32-18
Procedure Illustration
1) Remove the nut securing the fan with a spanner (see CJ_ODU_
INV_001).
2) Remove the fan.
3) Remove the screws of the top cover. (2 screws) (see CJ_ODU_INV_002).
4) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_INV_003).
CJ_ODU_INV_001
CJ_ODU_INV_002
CJ_ODU_INV_003
Note: This section is for reference only. Actual unit appearance may vary.
D-cut
Hook
Maintenance and
Disassembly
Page 50
Procedure Illustration
5) Disconnect the connector for fan motor from the electronic control board (see
CJ_ODU_INV_004).
6) Remove the fixing screws of the fan motor (4 screws) (see CJ_ODU_INV_005).
7) Remove the fan motor.
CJ_ODU_INV_004
CJ_ODU_INV_005
Note: This section is for reference only. Actual unit appearance may vary.
Fan Motor
Maintenance and
Disassembly
Page 51
O3MVO32-24
Procedure Illustration
1) Remove the nut securing the fan with a spanner (see CJ_ODU_
INV_006).
2) Remove the fan.
3) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_INV_007).
CJ_ODU_INV_006
CJ_ODU_INV_007
Note: This section is for reference only. Actual unit appearance may vary.
Hook
D-cut
Maintenance and
Disassembly
Page 52
Procedure Illustration
4) Disconnect the connector for fan motor from the electronic control board (see
CJ_ODU_INV_008).
5) Remove the fixing screws of the fan motor (4 screws) (see CJ_ODU_INV_009).
6) Remove the fan motor.
CJ_ODU_INV_008
CJ_ODU_INV_009
Note: This section is for reference only. Actual unit appearance may vary.
Maintenance and
Disassembly
Page 53
3. Electrical parts
Note: Remove the panel plate and fan assembly (refer to 1. Panel plate and 2. Fan assembly) before
disassembling electrical parts.
O3MVO32-09,
O3MVO32-12, O3MVO32-18
Procedure Illustration
1) Remove the connector for the compressor (see CJ_ODU_INV_010).
2) Pull out the two blue wires connected with the four way valve (CJ_ODU_
INV_010).
3) Pull out connectors of the condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(TP) (CJ_ODU_INV_010).
4) Disconnect the electronic expansion valve wire (CJ_ODU_INV_010).
5) Then remove the electronic control box (see CJ_ODU_INV_010).
CJ_ODU_INV_010
Compressor
T3, T4, TP
Electronic Expansion Valve
4-Way Valve
Maintenance and
Disassembly
Page 54
O3MVO32-24
Procedure Illustration
1) Remove the connector for the compressor (see CJ_ODU_INV_011).
2) Pull out the two blue wires connected with the four way valve (see CJ_ODU_
INV_011).
3) Pull out connectors of the condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(T5) (see CJ_ODU_INV_011).
4) Disconnect the electronic expansion valve wire (see Fig CJ_ODU_INV_011).
5) Remove the connector for the DR and reactor (see Fig CJ_ODU_INV_011).
6) Then remove the electronic control box (see Fig CJ_ODU_INV_011).
CJ_ODU_INV_011
Note: This section is for reference only. Actual unit appearance may vary.
Reactor
DR
T3, T4, TP
Compressor
4-Way Valve
Electronic Expansion Valve
Maintenance and
Disassembly
Page 55
4. Sound blanket
WARNING: Recover refrigerant from the refrigerant circuit before remove the compressor.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts, and 3. Fan assembly) before disassembling sound blanket.
Procedure Illustration
1) Remove the sound blanket (side and top) (see CJ_ODU_INV_012).
CJ_ODU_INV_012
Note: This section is for reference only. Actual unit appearance may vary.
Sound Blanket(side)
Sound Blanket(top)
Maintenance and
Disassembly
Page 56
5. Four-way valve (for heat pump models)
WARNING: Recover refrigerant from the refrigerant circuit before remove the four-way valve.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts, and 3. Fan assembly) before disassembling four-way valve.
Procedure Illustration
1) Heat up the brazed parts and then detach the the four-way valve and the pipe (see CJ_ODU_INV_013).
2) Remove the four-way valve assembly with pliers.
CJ_ODU_INV_013
Note: This section is for reference only. Actual unit appearance may vary.
Maintenance and
Disassembly
Page 57
6. Compressor
WARNING: Recover refrigerant from the refrigerant circuit before remove the compressor.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts, and 3. Fan assembly) before disassembling compressor.
Procedure Illustration
1) Remove the flange nut of terminal cover and remove the terminal cover (see CJ_
ODU_INV_014).
2) Disconnect the connectors (see CJ_ODU_
INV_015).
CJ_ODU_INV_014
CJ_ODU_INV_015
Note: This section is for reference only. Actual unit appearance may vary.
Terminal Cover
Maintenance and
Disassembly
Page 58
Procedure Illustration
3) Remove the hex nuts and washers securing the compressor, located on the bottom plate (see CJ_ODU_INV_016).
4) Heat up the brazed parts and then remove the the discharge pipe and the suction pipe (see CJ_ODU_INV_017).
5) Lift the compressor from the base pan assembly with pliers.
CJ_ODU_INV_016
CJ_ODU_INV_017
Note: This section is for reference only. Actual unit appearance may vary.
Discharge Pipe
Suction Pipe
Contents
1. Safety Caution .....................................................................................................61
2. General Troubleshooting ....................................................................................62
3. Error Diagnosis and Troubleshooting Without Error Code ...............................63
3.1 Remote maintenance ...................................................................................63
3.2 Field maintenance .......................................................................................64
4. Quick Maintenance by Error Code ......................................................................65
5. Troubleshooting by Error Code ...........................................................................70
5.1 Common Check Procedures.........................................................................70
5.2 E0/F4 (EEPROM parameter error) .................................................................72
5.3 E1 (Indoor and outdoor unit communication error) ......................................73
5.4 E2 (Zero crossing detection error diagnosis and solution) ............................75
5.4 E3/F5 (Fan speed is operating outside of the normal range diagnosis and
solution) ......................................................................................................76
5.5 E4/E5/F1/F2/F3 (Open circuit or short circuit of temperature sensor diagnosis
and solution) ................................................................................................78
5.6 E7 (Indoor PCB /Display board communication error) ...................................79
5.7 EC (Refrigerant Leakage Detection diagnosis and solution) ..........................80
5.8 F0(Overload current protection diagnosis and solution) ................................81
5.9 P0(IPM malfunction or IGBT over-strong current protection diagnosis and
Troubleshooting
Contents
solution) .....................................................................................................82
5.10 P1(Over voltage or too low voltage protection diagnosis and solution) .........83
5.11 P2(High temperature protection of IPM module diagnosis and solution) .......84
5.12 P4(Inverter compressor drive error diagnosis and solution) ...........................85
Troubleshooting
Page 61
1. Safety Caution
WARNING
Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting.
For other models, connect discharge resistance (approx.100Ω 40W) or a soldering iron plug between the positive and negative terminals of the electrolytic capacitor. The terminals are located on the bottom surface of the outdoor PCB.
Note: This picture is for reference only. Actual appearances may vary.
Electrolytic Capacitors
Troubleshooting
Page 62
2. General Troubleshooting
2.1 Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the operation lamp will flash in a corresponding series, the timer lamp may turn on or begin flashing, and an error code will be displayed. These error codes are described in the following table:
Operation
lamp
flashes
Timer lamp
LED
Display
Error Information Solution
1 time
OFF E0
Indoor unit EEPROM parameter error Page 72
2 times
OFF E1
Indoor / outdoor units communication error Page 73
3 times
OFF E2
Zero-crossing signal detection error Page 75
4 times
OFF E3
The indoor fan speed is operating outside of the normal range Page 76
5 times
OFF E4
Indoor room temperature sensor T1 is in open circuit or has short circuited
Page 78
6 times
OFF E5
Evaporator coil temperature sensor T2 is in open circuit or has short circuited
Page 78
9 times
OFF E7
Indoor PCB /Display board communication error Page 79
7 times
OFF EC
Refrigerant leak detected Page 80
1 time
ON F0
Overload current protection Page 81
2 times
ON F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
Page 78
3 times
ON F2
Condenser coil temperature sensor T3 is in open circuit or has short circuited
Page 78
4 times
ON F3
Compressor discharge temperature sensor TP open circuit or short circuit
Page 78
5 times
ON F4
Outdoor unit EEPROM parameter error Page 72
6 times
ON F5
The outdoor fan speed is operating outside of the normal range Page 76
1 time
FLASH p0
IPM malfunction or IGBT over-strong current protection Page 82
2 times
FLASH p1
Over voltage or over low voltage protection Page 83
3 times
FLASH p2
High temperature protection of IPM module Page 84
5 times
FLASH p4
Inverter compressor drive error Page 85
For other errors:
The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a temperature reading.
Troubleshooting:
Test the unit using the remote control. If the unit does not respond to the remote, the indoor PCB requires replacement. If the unit responds, the display board requires replacement.
Troubleshooting
Page 63
3. Error Diagnosis and Troubleshooting Without Error Code
WARNING
Be sure to turn off unit before any maintenance to prevent damage or injury.
3.1 Remote maintenance
SUGGESTION: When troubles occur, please check the following points with customers before field maintenance.
Problem Solution
1 Unit will not start Page 66-67
2 The power switch is on but fans will not start Page 66-67
3 The temperature on the display board cannot be set Page 66-67
4 Unit is on but the wind is not cold(hot) Page 66-67
5 Unit runs, but shortly stops Page 66-67
6 The unit startup and stop frequently Page 66-67
7 Unit runs continuously but insufficient cooling(heating) Page 66-67
8 Cool can not change to heat Page 66-67
9 Unit is noisy Page 66-67
Troubleshooting
Page 64
3.2 Field maintenance
Problem Solution
1 Unit will not start Page 68-69
2 Compressor will not start but fans run Page 68-69
3 Compressor and condenser (outdoor) fan will not start Page 68-69
4 Evaporator (indoor) fan will not start Page 68-69
5 Condenser (Outdoor) fan will not start Page 68-69
6 Unit runs, but shortly stops Page 68-69
7 Compressor short-cycles due to overload Page 68-69
8 High discharge pressure Page 68-69
9 Low discharge pressure Page 68-69
10 High suction pressure Page 68-69
11 Low suction pressure Page 68-69
12 Unit runs continuously but insufficient cooling Page 68-69
13 Too cool Page 68-69
14 Compressor is noisy Page 68-69
15 Horizontal louver can not revolve Page 68-69
Troubleshooting
Page 65
4. Quick Maintenance by Error Code
If you do not have the time to test whether specific parts are faulty, you can directly change the required parts according the error code.
You can find the parts to replace by error code in the following table.
Part requiring replacement
Error Code
E0 E1 E3 E4 E5 E7 EC F0 F1
Indoor PCB
x x
Outdoor PCB x x x x x x
Reactor x x x x x x x x
Indoor fan motor x x x x x x x x
Outdoor fan motor x x X x x x x x x
Temperature sensor x x x x x
T2 Sensor x x x x x x x x
Additional refrigerant x x x x x x x x x
Compressor x x x x x x x x
IPM board x x x x x x x x x
Outdoor unit x x x x x x x x
Display board x x x x x x x x
Part requiring replacement
Error Code
F2 F3 F4 F5 P0 P1 P2 P4
Indoor PCB
x x x x x x x x
Outdoor PCB
Reactor x x x x x x x
Indoor fan motor x x x x x x x x
Outdoor fan motor x x x x x x x
Temperature sensor x x x X x x
T2 Sensor x x x x x x x x
Additional refrigerant x x x x x x x x
Compressor x x x x x x
IPM board x x x x x
Outdoor unit x x x x x x x x
Troubleshooting
Page 66
1.Remote Maintenance
Possible causes of trouble
Power failure
The main power tripped
Loose connections
Faulty transformer
The voltage is too high or too low
The r emote c ontrol is power ed off
Broken remote control
Dirty air filter
Dirty condenser fins
The setting temperature is higher/lower than the
room's(cooling/heating)
The ambient temperature is too high/low when the
mode is cooling/heating
Fan mode
SILENCE function is activated(optional function)
Frosting and defrosting frequently
Unit will not start ☆ ☆
The power switch is on but fans will not start
☆ ☆ ☆
The temperature on the di spl ay board cannot be set
Unit is on but the wind is not cold(hot)
Unit runs, but shortly stops
The unit starts up and stops frequently
Unit runs continuous ly but ins uffici ent cooling(heating) ☆ ☆
Cool can not change to heat
Unit is noisy
Test method / remedy
Test voltage
Close the power switch
Inspect connections - tighten
Change the transformer
Test voltage
Replace the battery of the remote control
Replace the remote contr ol
Clean or replac e
Clean
Adjust the setting temperatur e
Turn the AC later
Adjust to cool mode
Turn off SILENCE function.
Turn the AC later
Refrigerant Circuit
Electrical Circuit
Troubleshooting
Page 67
Heavy load condition
Loosen hold down bolts and / or screws
Bad air proof
The air inlet or outlet of either unit is blocked
Inter fer enc e from cell phone tower s and remote
boosters
Shipping plates remain attached
☆ ☆
Check heat load
Tighten bolts or screws
Close all the windows and doors
Remove the obstacles
Reconn ect the power or press ON/OFF
button on remote c ontr ol to restar t
Remove them
Others
Troubleshooting
Page 68
2.Field Maintenance
Possible causes of trouble
Power failure
Blown fuse or varistor
Loose connections
Shorted or broken wires
Safety device opens
Faulty thermostat / r oom temperatur e sensor
Wr ong settin g place of temper ature sensor
Faulty transfor mer
Shorted or open capacitor
Faulty magnetic contactor for compressor
Faulty magnetic contactor for fan
Low voltage
Faulty stepping motor
Shorted or grounded compressor
Shorted or grounded fan motor
Unit will not start
☆ ☆
☆ ☆
Compressor will not start but fans run
Compressor and condenser (outdoor) fan wil l not start
Evaporator (indoor) fan will not start
Condenser (Outdoor) fan will not start
Unit runs, but shortly stops
Compressor s hort-cycles due to overload
High discharge pressure
Low dis charge pressure
High suction pressure
Low suction pressure
Unit runs continuous ly but ins uffici ent cooli ng
Too cool
Compressor is noisy
Horizontal louver ca n not revolve ☆ ☆
Test method / remedy
Test voltage
Inspect fuse type & size
Inspect connections - tighten
Test circuits with tester
Test co ntinuity of safety d evice
Test co ntinuity of thermostat / sensor & wiring
Place the temperatur e sensor at the central of
the air inlet grille
Chec k control circ uit with tester
Chec k capacitor with tester
Test co ntinuity of coil & c ontac ts
Test co ntinuity of coil & c ontac ts
Test voltage
Replace the stepping motor
Check r esistanc e with multimeter
Check r esistanc e with multimeter
Electrical Circuit
Troubleshooting
Page 69
Compressor stuck
Shortage of refrigerant
Restricted liquid line
Dirty air filter
Dirty evaporator coil
Insufficient air through evaporator coil
Overcharge of refrigerant
Dirty or partially blocked condenser
Air or incompressible gas in refrigerant cycle
Short cycling of condensing air
High temperature condensing medium
Insufficient condensing medium
Broken compressor internal parts
Ineffic ient c omp ressor
Expansion valve obstructed
Expansion valve or capillary tube closed completely
Leaking power element on exp ansion valve
Poor installation of feeler bulb
Heavy load condition
Loosen hold down bolts and / or screws
Shipping plates remain attached
Poor choices of capacity
Contact of piping with other piping or external plate
☆ ☆
☆☆☆ ☆ ☆
☆ ☆
☆ ☆ ☆
☆ ☆ ☆
☆ ☆
☆ ☆ ☆
☆ ☆
☆ ☆
Replace the co mpressor
Leak test
Replace r estr icted part
Clean or rep lace
Clean coil
Check fan
Change charged refrigerant volume
Clean condenser or remove obstacle
Purge, evacuate and recharge
Remove obstruction to air flow
Remove obstruction in air or water flow
Remove obstruction in air or water flow
Replace c omp ressor
Test c ompressor effic ienc y
Replace v alve
Replace v alve
Replace v alve
Fix feeler bu lb
Check h eat load
Tighten bolts or screws
Remove them
Choose AC of lager capacity or add the number
of AC
Rectify piping so as not to contact each other or
with ex ternal plate
Refrigerant Circuit
Others
Troubleshooting
Page 70
5. Troubleshooting by Error Code
5.1 Common Check Procedures
5.1.1 Temperature Sensor Check
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Temperature Sensors.
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor discharge temp.(Tp) sensor.
Measure the resistance value of each winding by using the multi-meter.
5.1.2 Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
KSK89D53UEZ KSM135D23UFZ KTF235D22UMT
Blue - Red
2.35Ω(20°C/68°F) 1.28Ω(20°C/68°F) 0.75Ω(20°C/68°F)Blue - Black
Red - Blue
Troubleshooting
Page 71
5.1.3 IPM Continuity Check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance
value
Digital tester
Normal resistance
value
(+)Red (-)Black
(Several MΩ)
(+)Red (-)Black
(Several MΩ)
P
N U
N
U V
V W
W (+)Red
Troubleshooting
Page 72
5.2 E0/F4 (EEPROM parameter error)
Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Faulty indoor PCB
• Faulty outdoor PCB
Troubleshooting and repair:
Shut off the power supply and turn it
on 2 minutes later.
Is it still displaying the error
code?
The unit is operating normally.
NO
If the EEPROM chip is welded on main
PCB, replace the main PCB directly.
Otherwise, check if the EEPROM chip
plugged in main PCB well.
YES
Is it plugged well?
Correct the connection.
NO
Replace the indoor/outdoor
main PCB.
Remarks:
The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two images:
Note: These images are for reference only.
Troubleshooting
Page 73
5.3 E1 (Indoor and outdoor unit communication error)
Description: The indoor unit has not received feedback from the outdoor unit for 110 seconds, four consecutive times.
Recommended parts to prepare:
• Faulty indoor PCB
• Faulty outdoor PCB
• Faulty reactor
Troubleshooting and repair:
Power off, then restart the unit after 2 minutes.
Does a problem remain?
The unit is operating normally
NO
Measure Vs. (Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
YES
Is the voltage moving
alternately between Positive and
negative?
Check the outdoor wiring connection.
Is it normal?
Check the reactor.
YES
Is it normal?
Replace the outdoor PCB.
Power on.
YES
Is the error
resolved?
Replace the indoor PCB.
NO
Replace the
reactor
NO
Check the indoor wiring
connections
Is it normal?
Replace the indoor PCB.
Power on.
YES
Is the error resolved?
Replace the outdoor PCB.
NO
The voltage moves alternately with
positive value.
NO
The voltage is a
certain value
NO
Troubleshooting
Page 74
Remarks:
• Use a multimeter to test the resistance of the reactor which does not connect with capacitor.
• The normal value should be around zero ohm. Otherwise, the reactor must have malfunction.
Troubleshooting
Page 75
5.4 E2 (Zero crossing detection error diagnosis and solution)
Description: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time
interval is abnormal.
Recommended parts to prepare:
• Connection mistake
• Faulty PCB
Troubleshooting and repair:
Check the connections and
power supply.
Correct the connections. Turn on the unit when the power supply is good.
NO
Indoor main PCB is defective. Replace
indoor main PCB.
YES
Is it normal?
Troubleshooting
Page 76
5.5 E3/F5 (Fan speed is operating outside of the normal range)
Description: When the indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will
display the failure(E3). When the outdoor fan speed registers below 200RPM or over 1500RPM for an extended period of time, the unit will stop and the LED will display the failure(F5).
Recommended parts to prepare:
• Wiring mistake
• Faulty fan assembly
• Faulty fan motor
• Faulty PCB
Troubleshooting and repair:
YES
Power off, then restart the unit after 2 minutes.
Is it within normal parameters?
Replace the fan motor
Does a problem remain?
The unit is operating normallyNO
Shut off the power supply,
Rotate
the fan by hand.
YES
Does it turn easily?
Find the cause
of the problem and
resolve it
NO
Check the wiring of fan motor.
YES
Is it improperly wired?
Ensure proper connections
Measure the voltage for
the fan motor from the PCB.
YES
Replace the indoor/outdoor
PCB
NO
Troubleshooting
Page 77
Index:
1. Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
• DC motor voltage input and output (voltage: 220-240V~):
No. Color Signal Voltage
1 Red Vs/Vm 280V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 14-17.5V
5 Yellow Vsp 0~5.6V
6 Blue FG 14-17.5V
2. Indoor AC Fan Motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply) or 50V(115V power supply), the PCB must has problems and need to be replaced.
Troubleshooting
Page 78
5.6 E4/E5/F1/F2/F3 (Open circuit or short circuit of temperature sensor diagnosis and solution)
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Recommended parts to prepare:
• Wiring mistake
• Faulty sensor
• Faulty PCB
Troubleshooting and repair:
Check the connection between
temperature sensor and PCB.
Replace indoor or outdoor PCB
Is it within acceptable
parameters?
Is it properly wired?
Ensure proper connections.
NO
Measure the resistance value
of the sensor.
YES
Replace the Sensor.
NO
YES
Troubleshooting
Page 79
5.7 E7 (Indoor PCB /Display board communication error)
Description: Indoor PCB does not receive feedback from Display board for 120 seconds.
Recommended parts to prepare:
• Wiring mistake
• Faulty PCB
• Display board malfunction
Troubleshooting and repair:
Power off,
then restart the unit
2 minutes later.
Is it still displaying
the error code?
Check the wirings and
connection.
YES
The unit is operating normally.
NO
Are all the
connections
good?
Correct the connection or replace the Wirings.
NO
Replace the indoor main
PCB.
YES
Is the error
extinguished?
Replace the Display board.
NO
Troubleshooting
Page 80
5.8 EC (Refrigerant Leakage Detection diagnosis and solution)
Description: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
In the beginning 8 minutes after the compressor starts up, if T2<Tcool-1°C does not keep continuous 4 seconds and compressor running frequency higher than 50Hz does not keep continuous 3 minutes, and this situation happens 3 times, the display area will show “EC” and AC will turn off.
Recommended parts to prepare:
• Faulty T2 sensor
• Faulty indoor PCB
• System problems, such as leakage or blockages
Troubleshooting and repair:
Power off, then restart the unit 2 minutes later.
Are any leakages
present?
Check System for blockages
and
clear
blockages if present.
Does a problem remain?
Put your hands in front of the
indoor air outlet.
YES
Is there cool
air blowing out from
indoor air outlet?
Is
it
securely
attached?
Replace the
indoor PCB
YES
Check the T2 sensor.
YES
Check system for leakages.
NO
NO
Repair the leakage and
recharge the refrigerant.
YES
NO
Troubleshooting
Page 81
5.9 F0(Overload current protection diagnosis and solution)
Description: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
• Power supply problems.
• System blockage
• Faulty PCB
• Wiring mistake
• Compressor malfunction
Troubleshooting and repair:
Check the power supply.
Do any exist?
Are they within acceptable
parameters?
Are they properly connected?
Is it in working order?
Replace the outdoor unit.
Is it in working order?
Check system for blockages.
YES
Stop the unit.
NO
Clear the blockage.
NO
Check the compressor resistance values.
YES
Replace the compressor.
NO
Check the connections and wires.
YES
Ensure proper connections or
replace the wires.
NO
Check the reactor.
YES
YES
Replace outdoor PCB.
NO
Troubleshooting
Page 82
5.10 P0(IPM malfunction or IGBT over-strong current protection diagnosis and solution)
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED shows
“P0” and the AC turn off.
Recommended parts to prepare:
• Wiring mistake
• IPM malfunction
• Faulty outdoor fan assembly
• Compressor malfunction
• Faulty outdoor PCB
Troubleshooting and repair:
Check the wiring between
PCB and compressor.
Does an error exist?
Ensure proper connections
or
replace the wires and connectors.
YES
Check the IPM.
NO
Is it in working order?
Replace the IPM board or replace the outdoor PCB.
NO
Check the outdoor fan and the
outdoor unit ventilation.
YES
Is it in working order?
Please refer to the solution of
the
Fan
Speed is Out of Controlmalfunction.
NO
Check the compressor
resistance values.
YES
Are they within
acceptable parameters?
Replace the compressor.
Replace the outdoor PCB.
YES
NO
Troubleshooting
Page 83
5.11 P1(Over voltage or too low voltage protection diagnosis and solution)
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
• Power supply issues
• System leakage or blockage
• Faulty PCB
Troubleshooting and repair:
Check the power supply
.
Is it in working order?
Turn off the unit.
NO
Check the connections and wires.
YES
Are they in working order?
Ensure proper connections or
replace the wires.
NO
Power on and measure the
voltage between P and N.
YES
While the unit is in standby, is the voltage between P and N is around DC 310V, 340V or 380V? When start up
the unit, is it in 220V~400V?
Replace the IPM board.
NO
Check the reactor.
YES
Is it in working order?
Replace outdoor PCB.NO
Replace the reactor.
YES
Troubleshooting
Page 84
5.12 P2(High temperature protection of IPM module diagnosis and solution)
Description: If the temperature of IPM module is higher than setting value, the LED displays this failure code.
Recommended parts to prepare:
• Faulty PCB
• Connection problems
Troubleshooting and repair:
Check the fastening screws on the
PCB and IPM radiator.
Are they
fixed tightly?
Replace the outdoor
control PCB.
Tighten the screws and apply
silicon grease.
NO
YES
Troubleshooting
Page 85
5.13 P4(Inverter compressor drive error diagnosis and solution)
Description: An abnormal inverter compressor drive is detected by a special detection circuit, including communication
signal detection, voltage detection, compressor rotation speed signal detection and so on.
Recommended parts to prepare:
• Wiring mistake
• IPM malfunction
• Faulty outdoor fan assembly
• Compressor malfunction
• Faulty outdoor PCB
Troubleshooting and repair:
Check the wiring between the
PCB and compressor.
Is it improperly wired?
Ensure proper connections or replace
the wires and connectors.
YES
Check the IPM.
NO
Is it functioning
properly?
Replace the IPM board or
replace the outdoor PCB.
NO
Check the outdoor fan and
the outdoor unit ventilation.
YES
Is it functioning
properly?
Please refer to “Fan
Speed Malfunction”
NO
Check the compressor
resistance values.
YES
Are they within
acceptable parameters?
Replace the compressor.NO
Replace the outdoor PCB.
YES
Contents
i) Temperature Sensor Resistance Value Table for T1, T2, T3, and T4 (°C – K) ....87
ii) Temperature Sensor Resistance Value Table for TP (°C – K)..............................88
iii) Pressure On Service Port .....................................................................................89
Appendix
Page 87
Appendix
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
Page 88
Appendix
ii) Temperature Sensor Resistance Value Table for TP (°C – K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.717
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849      
12 54 99.69 52 126 18.26 92 198 4.703      
13 55 95.05 53 127 17.58 93 199 4.562      
14 57 90.66 54 129 16.94 94 201 4.426      
15 59 86.49 55 131 16.32 95 203 4.294      
16 61 82.54 56 133 15.73 96 205 4.167      
17 63 78.79 57 135 15.16 97 207 4.045      
18 64 75.24 58 136 14.62 98 208 3.927      
19 66 71.86 59 138 14.09 99 210 3.812      
Page 89
Appendix
iii) Pressure On Service Port(R32)
Cooling chart:
°F(°C)
ODT
IDT
0(-17) 5(-15)
15
(9.44)
45
(7.22)
75
(23.89)
85
(29.44)
95 (35)
105
(40.56)
115
(46.11)
120
(48.89)
BAR 70/59 6.5 6.6 7.4 8.2 8.4 8.0 8.3 8.8 10.3 10.8
BAR 75/63 6.8 6.9 8.1 8.8 8.8 8.5 8.9 9.3 10.9 11.4
BAR 80/67 7.2 7.3 8.7 9.7 9.5 9.1 9.3 9.8 11.4 12.1
BAR 90/73 7.9 8.0 9.8 10.7 10.5 9.7 10.2 10.8 12.6 13.3
°F(°C)
ODT
IDT
0(-17) 5(-15)
15
(9.44)
45
(7.22)
75
(23.89)
85
(29.44)
95 (35)
105
(40.56)
115
(46.11)
120
(48.89)
PSI 70/59 95 96 108 118 121 115 119 128 150 157
PSI 75/63 99 101 117 128 126 122 129 135 158 165
PSI 80/67 105 106 125 141 138 132 135 143 165 176
PSI 90/73 114 115 142 155 152 141 148 157 184 193
°F(°C)
ODT
IDT
0(-17) 5(-15)
15
(9.44)
45
(7.22)
75
(23.89)
85
(29.44)
95 (35)
105
(40.56)
115
(46.11)
120
(48.89)
MPA 70/59 0.65 0.66 0.74 0.82 0.84 0.80 0.83 0.88 1.03 1.08
MPA 75/63 0.68 0.69 0.81 0.88 0.88 0.85 0.89 0.93 1.09 1.14
MPA 80/67 0.72 0.73 0.87 0.97 0.95 0.91 0.93 0.98 1.14 1.21
MPA 90/73 0.79 0.80 0.98 1.07 1.05 0.97 1.02 1.08 1.26 1.33
0
0.2
0.4
0.6
0.8
1
1.2
1.4
70/59
75/63
80/67
90/73
Page 90
Appendix
Heating chart:
°F(°C)
ODT
IDT
57/53
(13.89/11.67)
47/43
(8.33/6.11)
37/33
(2.78/0.56)
27/23
(-2.78/-5)
17/13 (-8.33/
-10.56)
0/-2(-17/-19)
-17/-18
(-27/-28)
BAR 55 30.9 29.1 25.8 23.3 21.2 18.9 16.8
BAR 65 33.2 30.6 27.1 25.9 23.8 20.9 19.4
BAR 75 34.5 32.1 28.4 26.8 25.4 21.9 20.4
°F(°C)
ODT
IDT
57/53
(13.89/11.67)
47/43
(8.33/6.11)
37/33
(2.78/0.56)
27/23
(-2.78/-5)
17/13 (-8.33/
-10.56)
0/-2(-17/-19)
-17/-18
(-27/-28)
PSI 55 448 421 374 337 308 273 244
PSI 65 480 444 394 375 346 303 282
PSI 75 499 466 411 389 369 318 296
°F(°C)
ODT
IDT
57/53
(13.89/11.67)
47/43
(8.33/6.11)
37/33
(2.78/0.56)
27/23
(-2.78/-5)
17/13 (-8.33/
-10.56)
0/-2(-17/-19)
-17/-18
(-27/-28)
MPA 55 3.09 2.91 2.58 2.33 2.12 1.89 1.68
MPA 65 3.32 3.06 2.71 2.59 2.38 2.09 1.94
MPA 75 3.45 3.21 2.84 2.68 2.54 2.19 2.04
0
0.5
1
1.5
2
2.5
3
3.5
4
55
65
75
Scan here to download the latest version of this manual.
Σαρώστε εδώ για να κατεβάσετε την τελευταία έκδοση του εγχειριδίου.
wall mounted unit
AIR CONDITIONING SYSTEMS
Loading...