INVENTOR COOL/FCOOL-8BS, YX1F, GPC08AH-K3NNC3D Service Manual

ENGLISH
AIR CONDITIONING SYSTEMS
• SERVICE MANUAL
ENGLISH
AIR CONDITIONING SYSTEMS
PORTABLE
MODELS:
COOL FCOOL-8BS
Service Manual
Table of Contents
Part
: Technical Information
............................................................ 1
1. Summary
.................................................................................................... 1
2. Specications
.......................................................................................... 2
3.
Outline Dimension Diagram
..............................................................4
4.
Refrigerant System Diagram
......................................................... ..5
5.
Electrical Part
......................................................................................... ..6
5.1 Wiring Diagram ......................................................................................... ..6
5.2 PCB Printed Diagram ................................................................................ ..7
6.
Function and Control
......................................................................... ..9
6.1 Introduction of control panel ...................................................................... ..9
6.2 Remote Controller Introduction ................................................................. 10
6.3 Introduction of Basic Mode Function ......................................................... 13
Part : Maintenance
............................................................................ 15
7.
Notes Maintenance
............................................................................. 15
8.
Install
.......................................................................................................... 18
8.1 Install Drainage Pipe ................................................................................. 18
8.2 Install Window Frame ................................................................................ 18
8.3 Installation and Disassembly of Heat Discharge Pipe............................... 19
8.4 Operation test ............................................................................................ 21
8.5 Drainage way ............................................................................................ 21
8.6 Clean and Maintenance ............................................................................ 22
9.
Maintenance
........................................................................................... 23
9.1 Error Code ................................................................................................. 23
9.2 Malfunction Detection Flowchart ............................................................... 25
9.3 Maintenance Method for Common Malfunction ........................................ 31
10.
Exploded View and Parts List
.................................................... 33
11.
Removal Procedure
.......................................................................... 35
Appendix:
......................................................................................................46
Appendix 1: Reference Sheet of Celsius and Fahrenheit ............................... 46
Appendix 2: List of Resistance for Temperature Sensor ................................. 47
Appendix 3: Resistance Value Table of Humidity Sensor ............................... 50
Table of Contents
1
Technical Information
Service Manual
COOL FCOOL-8BS
YX1F
1. Summary
Part
: Technical Information
Remote Controller:
ON/OFF MODE
FAN SWING
SLEEP TIMER
+
-
AUTO COOL DRY FAN HEAT
T-ON T-OFF
SWING SLEEP LOCK SPEED
2
Technical Information
Service Manual
Parameter Unit Value
Model GPC08AH-K3NNC3D
Power Supply
Rated Voltage V
220-240
Rated Frequency Hz 50
Phases 1
Cooling Capacity Btu/h 8000
Heating Capacity Btu/h /
Cooling Power Input W 900
Heating Power Input W /
Cooling Power Current A 4.2
Heating Power Current A /
Rated Input W 1130
Rated Current A 4.6
Air Flow Volume(H/M/L) m
3
/h 330/300/250
Dehumidifying Volume L/h 0.75
EER Btu/w.h 8.89
COP Btu/w.h /
SEER /
HSPF /
Application Area m
2
10-16
Climate Type T1
Isolation I
Moisture Protection IPX0
Permissible Excessive Operating Pressure for the Discharge Side
MPa 3.8
Permissible Excessive Operating Pressure for the Suction Side
MPa 1.7
Throttling Method Capillary
Defrosting Method /
Fuse A 3.15
Operation Temp
o
C 16~30
Ambient Temp (Cooling)
o
C 16~35
Ambient Temp (Heating)
o
C /
Sound Pressure Level (H/M/L) dB (A) 54/52/50
Sound Power Level (H/M/L) dB (A) 65/63/61
Dimension (WXHXD) mm 300X790X345
Dimension of Carton Box (LXWXH) mm 562X352X825
Dimension of Package (LXWXH) mm 565X355X840
Net Weight kg 24
Gross Weight kg 28
Refrigerant R410A
Refrigerant Charge kg 0.46
3
Technical Information
Service Manual
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Compressor
Compressor Manufacturer/ Trademark
ZHUHAI LANDA COMPRESSOR
CO., LTD.
Compressor Model QXA-A083A130
Compressor Oil RB68EP
Compressor Type Rotary
L.R.A. A 15
Compressor RLA A 3.5
Compressor Power Input W 740
Overload Protector UP3-A0
Evaporator
Fan Type Centrifugal
Diameter Length(DXL) mm Φ146X108.5
Fan Motor Speed(H/M/L) r/min 1250/1150/1050
Output of Fan Motor W 45
Fan Motor RLA A 0.41
Fan Motor Capacitor μF 3.5
Form Aluminum Fin-copper Tube
Pipe Diameter mm Φ7
mm 2-1.3
Coil Length (LXDXW) mm 377.5X25.4X266.7
Swing Motor Model /
Output of Swing Motor W /
Condenser
Fan Type Centrifugal
Fan Diameter mm Φ185X77
Form Aluminum Fin-copper Tube
Pipe Diameter mm Φ7
mm 2-1.4
Coil Length (LXDXW) mm 343X25.4X266.7
Fan Motor Speed rpm /
Output of Fan Motor W /
Fan Motor RLA A /
Fan Motor Capacitor μF /
4
Technical Information
Service Manual
COOL/FCOOL-8BS
Unit:mm
3. Outline Dimension Diagram
345
300
790
5
Technical Information
Service Manual
4. Refrigerant System Diagram
HEAT EXCHANG
E
(EVAPORATOR)
HEAT EXCHANGE
(CONDENSER
)
COMPRESSOR
CENTRIFUGAL FAN
CENTRIFUGAL FAN
Accumlator
Suction
Discharge
Capillary
Strainer
6
Technical Information
Service Manual
Symbol Symbol Color Symbol Symbol Color Symbol Name
WH White GN Green COMP Compressor
YE Yellow BN Brown Grounding wire
RD Red BU Blue / /
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /
5. Electrical Part
5.1 Wiring Diagram
●Instruction
●Electric Diagram
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
COOL/FCOOL-8BS
7
Technical Information
Service Manual
5.2 PCB Printed Diagram
(1)Silk screen on main board
COOL/FCOOL-8BS
4
3
2
1 15 1314 12
9
11
10
8
5
6
TOP VIEW
BOTTOM VIEW
NO. NAME
1 Connect neutral wire 2 Piezoresistance 3 Fuse 4 Drive replay of compressor 5 Buzzer 6 Interface of display board
7
Interface of high-level detection switch
8
Terminal of outdoor tube temperature sensor
9
Terminal of ambient temperature sensor
10
Terminal of tube temperature
sensor 11 Interface of swing motor 12 Interface of draw water motor 13 Interface of outdoor fan 14 Interface of 4-way valve 15 Interface of fan
Service Manual
(2)Silk screen on display board
COOL/FCOOL-8BS
TOP VIEW
BOTTOM VIEW
receiving head
connect with main baord
8
Technical Information
9
Technical Information
Service Manual
6. Function and Control
6.1 Introduction of control panel
COOL/FCOOL-8BS
Note:
● After putting through the power, air conditioner will give out a sound. After that, you can operate the air condition by pressing buttons on control panel.
● Under ON status, after each pressing of button on control panel, air conditioner will give out a sound. Meanwhile, corresponding function indicator on control panel will ON.
● Under ON status, dual-8 nixie tube on control panel displays set temperature value during cooling operation, while it won’t display under other modes.
● Under OFF status, dual-8 nixie tube on control panel won’t display.
1. ON/OFF button Press this button to turn on or turn off air conditioner.
2. MODE button Press this button to select your required operation mode. Corresponding mode indicator is ON.
COOL: Under this mode, air conditioner operates under cooling mode. Press “Fan Speed” button to adjust fan speed. Cooling indicator is ON. Corresponding speed indicator is ON and dual-8 nixie tube displays set temperature. Temperature setting range is 16℃~30℃. DRY: Under this mode, air conditioner operates at low speed. Drying indicator and low speed indicator is ON. Fan speed can’t be adjusted. Dual-8 nixie tube won’t display. FAN: Under this mode, air conditioner operates at set fan speed. Fan indicator and corresponding speed indicator is ON. Dual-8 nixie tube won’t display.(Note: You must connect the heat-discharge pipe before operating cooling or drying mode. No need for only fan mode.)
3. “+”, “-” button Under cooling mode, press “-” or “+” button to decrease or increase
set temperature 1℃. Set temperature range is 16℃~30℃.This
button is invalid under auto, dry or fan mode.
4. FAN SPEED button Press this button to select your required fan speed. Corresponding speed indicator is ON. (This button invalid under drying mode)
Button function introduction ==
Cool Dry Fan
low medium high auto
ON/OFF buttonMODE button + / - button
fan mode indicator
dry mode indicatorcool mode indicatorsignal receiving window
dual-8 nixie tubewater full indicator
10
Technical Information
Service Manual
6.2 Remote Controller Introduction
AUTO
COOL
DRY
FAN
HEAT
T-ON T-OFF
SWING
SLEEP LOCK
SPEED
+
_
ON/OFF
FAN SWING
SLEEP
TIMER
MODE
ON/OFF button
MODE button
+/- botton
FAN button
SWING button
SLEEP button
TIMER button
Icon Display on Remote
Controller
Operation introduction of remote controlle
r
For auto operation
Timer on Timer off
Sending signal
For air swing For sleeping For locking For setting fan speed
Set temperature
Set time
For cooling
For drying
For fan only
For heating
AUTO
COOL
DRY
FAN
HEAT
T-ON T-OFF
SWING
SLEEP LOCK
SPEED
Buttons on Remote Controller
Note:
When power is connected(stand by condition), you can operate the air conditioner through the remote controller. When unit is on, each time you press the button on remote controller, the sending signal icon on the display of remote controller
will blink once. If the air conditioner gives out a beep sound, it means the signal has been sent.
When unit is off, set temperature will be displayed on the remote controller(If the light of indoor unit display is turned on, the
corresponding icon will be displayed); When unit is on, it will display the icon of the on-going function.
1. ON/OFF Button
Press this button to turn unit on/of
f.
2. MODE Button
Pressing this button once can select your required mode circularly as below(the corresponding icon
will be lit up after the mode is
selected):
(Only for models with heating function.)
11
Technical Information
Service Manual
When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can't be
adjusted and won't be displayed either
. Press FAN button to adjust fan speed. (This function is not available in this air conditioner.)
When selecting cool mode, air conditioner will operate under cool mode. Then press + or - button to adjust set temperature. Press
FA
N button to adjust fan speed. When selecting dry mode, air conditioner will operate at low fan speed under dry mode. In dry mode, fan speed can't be adjusted. When selecting fan mode, air conditioner will operate in fan mode only. Then press FAN button to adjust fan speed. When selecting heat mode, air conditioner will operate under heat mode. Then press + or - button to adjust set temperature. Pr e
ss
FA
N button to adjust fan speed.
3. +/- button
Pressing + or - button once will increase or decrease set temperature by 1 °F(°C). Hold + or - button for 2s, set temperature on
remote controller will change quickl
y. Release the button after your required set temperature is reached.
When setting Timer On, Timer Off or Clock, press + or -- button to adjust the time (See TIMER Button for setting details).
4. F
AN Button
Pressing this button can select fan speed circularly as:
AUTO, SPEED 1( ), SPEED 2( ), SPEED 3( ), SPEED 4( ) (unavailable
in this air conditioner
. Speed 4 is the same with speed 3).
Note:
Under Auto mode, air conditioner will select proper fan speed automatically according to ex-factory setting. Fan speed can't be adjusted under Dry mode.
5. SWING Button
Press this button to turn on up&down air swing.
6. SLEEP
Button
Under Cool, Heat, Dry mode, press this button to turn on Sleep function. Press this button to cancel Sleep function. Under Fan
and
A
uto mode, this function is unavailable.
7. TIMER Button
When unit is on, press this button to set Timer Off. T-OFF and H icon will be blinking. Within 5s, press + or - button to adjust the
When unit is off, press this button to set Timer On. T-ON and H icon will be blinking. Within 5s, press + or - button to adjust the
time for Timer On. Pressing + or - button once will increase or decrease the time by 0.5h. Hold + or - button for 2s, time will
change
quickly. Release the button after your required set time is reached. Then press TIMER button to confirm it. T-ON and H icon wil
l stop
blinking.
Cancel Timer On/Off: If Timer function is set up, press TIMER button once to review the remaining time. Within 5s, press TIMER
Note:
Range of time setting is: 0.5~24h
button again to cancel this function.
The interval between two motions can't exceed 5s, otherwise the remote controller will exit setting status.
Simple operationfi
rst
1.After putting through power
” button on remote controller to turn on the air conditioner.
2.Press “
” button to select your required operation mode: AUTO, COOL, DRY, FAN.
3.Press “+” or “-” button to set your required temperature.(temperature can’t adjusted under
AUTO mode)
4.Press “
” button to select your required fan speed: auto, fi rst notch, second notch, third notch, fourth notch (fourthnotch is same
as third notch for this air conditioner
.)
SPEED 2 (equals to medium fan speed)SPEED 1 (equals to low fan speed)
SPEED 3 (equals to high fan speed) SPEED 4
AUTO
ON/OFF
MODE
FAN
time for Timer Off. Pressing + or - button once will increase or decrease the time by 0.5h. Hold + or - button for 2s, time wil
l change
quickly. Release the button after your required set time is reached. Then press TIMER button to confirm it. T-OFF and H icon wi
ll
stop blinking.
12
Technical Information
Service Manual
1. Press the back side of remote controller on the spot marked with
, and then
push out the cover of battery box along the arrow direction.
2. Replace two No.7 (AAA
1.5V) dry batteries and make sure the positions of + and --
polar are correct
.
3. Reinstall the cover of battery box.
Note:
During operation, point the signal sender of the remote controller at the receiving
window of the indoor unit;
The distance between signal sender and receiving window should be within 8m.
There should be no obstacle between them.
Signal may be interfered easily in the room where there is fl uorescent lamp
or wireless telephone; Remote controller should be close to indoor unit during operation.
Replace new batteries of the same model when replacement is required. If you don't use remote controller for a long time, please take out the batteries. If the display on remote controller is fuzzy or if there's no display, please replace
batteries.
battery
cover of battery box
remove
reinstall
Replacement of Batteries in Remote Controller
13
Technical Information
Service Manual
6.3 Introduction of Basic Mode Function
1. Temperature Parameter
Indoor setting temperature (T
preset
)
Indoor ambient temperature (T
amb.
)
2. Basic Functions of System
After the unit is energized, the interval of start-up time for compressor is no less than 3min under any conditions; when the compressor is started, the unit is off without the temperature change in 6min.
2.1 Cool Mode
2.1.1 Working conditions and process of cooling a) When T
abm.≥Tpreset
+ 1oC (2oF), the unit will start to run in cooling mode, the compressor and kick motor start to run, and fan motor runs under preset fan speed. b) When T
abm.
T
preset
- 1oC (2oF), the compressor and kick motor stop to run, and fan motor runs under preset fan speed.
c) When T
preset
- 1oC (2oF)<T
amb.<Tpreset
+ 1oC (2oF), the unit will keep the current running status.
Under this mode, the temperature setting range is 61
o
F-86oF (16oC -30oC ).
2.2 DRY Mode
2.2.1 Working conditions and process of dry Under this mode, the unit will not display setting temperature and ambient temperature; the fan motor runs under low fan speed; the compressor, fan motor and kick motor continue to run.
2.3 FAN Mode
Under this mode, the unit will not display setting temperature and ambient temperature; the fan motor runs under setting fan speed; the compressor, fan motor and kick motor stop to run. Under this mode, the centigrade temperature setting range is 16
o
C -30oC , the fahrenheit temperature setting range is 61oF-86oF.
2.4 AUTO Mode
Under AUTO mode, the standard cooling T
preset
=25oC (77oF), standard heating T
preset
=20oC (68oF)
It will goes to auto cooling mode when T
amb.
>26oC (79oF); and goes to auto fan mode when T
amb.
<20oC (68oF); 20oC (68oF)T
amb.
≤23oC
(73
o
F), if the previous running is fan (including general fan and auto fan), it will keep the running status of auto fan mode, if the
previous running is not fan, it will goes to auto dry mode; 26
o
C (79oF)≥T
amb.
≥24oC (74oF), it goes to auto dry mode; when the unit is
first energized, 2
o
C (79oF)≥T
amb.
≥20oC (68oF), it runs under dry mode.
3. Other Functions
3.1 Buzzer
When the controller is energized, receiving a signal from remote controller or button, the buzzer will give out a beep.
3.2 Sleep
a) Under cooling mode, after 1h of setting sleep process, Tpreset increases 2oF(1oC); 2h later, Tpreset increases 4oF(2oC). After 2h, the setting temperature never increases, but the upper limit of increased setting temperature is 86
o
F(30oC)
b) Under heating mode, after 1h of setting sleep process, Tpreset decreases 2
o
F(1oC); 2h later, Tpreset decreases 4oF(2oC). After 2h,
the setting temperature never decreases, but the upper limit of decreased setting temperature is 61
o
F(16oC) c) There is no sleep function under fan and dry mode. d) When set sleep function, shift mode will cancel sleep function. e) The setting temperature display is the same with remote controller; it is not influenced by the setting temperature increases/ decreases.
3.3 Auto Fan
a) Auto fan speed under Cooling mode; Tamb≥Tpreset+4
o
F(2oC) High fan;
Tpreset<Tamb.< Tpreset+4
o
F(2oC) Med fan; Tamb≤Tpreset Low fan b) There is 3.5min delay for auto fan shift.
Tpreset +1 °C
Tpreset –1 °C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Original operating status
° 6 min. ° 3 min. ° 6 min.
Setting fan speed
14
Technical Information
Service Manual
3.4 TIMER Function
● General timer
a) TIMER ON: It can set timer on when the system is off, the setting time range is 0.5h-24h, when the time of setting timer on reaches, and the system runs with the previous setting mode. b) TIMER OFF: It can set timer on when the system is on, the setting time range is 0.5h-24h, when the time of setting timer off reaches, the system stop to work.
● Clock timer
a) TIMER ON: If set timer on when the system is running, it continues to run; if set timer on when the system is off, when the time of setting timer on reaches, and the system runs with the previous setting mode. b) TIMER OFF: If set timer off when the system is off, the system keeps the stand-by status when setting timer off; if set timer off when the system is on, when the time of timer off reaches, the system stops to run.
3.5 Memory Function
The system memories the setting running status of previous power-off, and runs automatically with the setting running status before it power-off when it is energized again. If the unit is on before power-off, the compressor will 3min delay protection when it is energized again.
3.6 Indicator Lamp, dual-8 digital pipe
a) When the unit runs, under cooling mode, cooling indicator lamp lights, dual-8 displays preset temperature. b) When the unit runs, under fan mode, fan indicator lamp lights, dual-8 does not display. c) When the unit runs, under dry mode, dry indicator lamp lights, dual-8 does not display. d) When the unit runs, under heating mode, heating indicator lamp lights, dual-8 displays preset temperature.
3.7 Setting button function
a) ON/OFF button: It controls system’s switch. b) Mode button: Mode setting cycle with below sequence: Cooling only unit: cooling-> dry-> fan. c) Temp. ▼ button: Set temperature when the unit is on, the setting temperature decreases 1
o
C or oF per press
Temp. ▼ button; it will never setting when the setting reaches to 16
o
C or 61oF. The button is not valid under auto, dry and fan mode.
d) Temp. ▲ button: Set temperature when the unit is on, the setting temperature increases 1
o
C or oF per press
Temp. ▲ button; it will never setting when the setting reaches to 30
o
C or 86oF. The button is not valid under auto, dry and fan mode.
3.8 Light Control
If set the light is on with remote control, the indicator lamp and dual-8 display the current setting status; if set the light is off with remote control, turn off the lamp immediately. If there is front panel button or remote control button operation when setting light off with remote control, the indicator lamp and dual-8 display current setting status, and turn off the light 5S later. Remote control light button does not controlled by failure display.
3.9 Protection Function
● Anti-freeze Protection
When the anti-freeze protection is inspected, the compressor stops, fan motor runs with setting fan speed. When the anti-freeze protection is canceled and reaches to the 3min time-delay, it runs with the original status. Temperature sensor failure inspection a) Environment temperature sensor is open, short circuit: dual-8 displays F1, the cooling indicator lamp goes out 3S and blinks 1 time, and it will light up 0.5S and go out 0.5S when it is blinking. b) Indoor pipe temperature sensor is open, short circuit: dual-8 displays F2, the cooling indicator lamp goes out 3S and blinks 2 times, and it will light up 0.5S and go out 0.5S when it is blinking. c) Outdoor pipe temperature sensor is open, short circuit: dual-8 displays F4, the cooling indicator lamp goes out 3S and blinks 4 times, and it will light up 0.5S and go out 0.5S when it is blinking. d) The compressor or electric heating pipe stops when the temperature sensor failure and the unit is on, The fan motor will be deal regarding compressor or electric pipe reach to the temperature point and stops.
● Over current Protection
If the system current is inspected too large for 3min continuously, the fan motor runs with setting conditions, other load stops; 3min later, the unit runs with the previously status; if over current protection occurs for 6 times continuously, display error code “E5”, the load stops this time; if block the button except ON/OFF button, it will remote control the unit to off then on, or turn off with button, or re-energized; the time of over current protection will zero clearing with remote control, press to turn on or re-energized.
● Over-ow Protection
If the over-flow is detected for 3S, it will enter into over-flow protection. Display error code H8, heating indicator lamp or over-flow indicator lamp goes out 3S and blinks 8 times.
15
Maintenance
Service Manual
7. Notes for Installation and Maintenance
Electrical Safety Precautions:
1. Avoid contact between refrigerant and re as it generates
poisonous gas. Recycle the refrigerant inside the unit completely before welding pipes.
2. Apply specied refrigerant only. Never have it mixed
with any other refrigerant. Never have air remain in the refrigerant line as it may lead to rupture or other hazards.
3.If refrigerant is leaking seriously, it may cause suffocation or explosion. When using the combustible refrigerant, please put the unit at ventilated place.
4. Never touch the refrigerant piping or compressor without wearing glove to avoid scald or frostbite.
Warnings
Refrigerant Safety Precautions:
Improper installation may lead to re hazard explosion,
electric shock or injury.
Part
: Installation and Maintenance
Safety Precautions: Important!
Please read the safety precautions carefully before installation and maintenance.
The following contents are very important for installation and maintenance. Please follow the instructions below.
●The installation or maintenance must accord with the
instructions.
●Comply with all national electrical codes and local
electrical codes.
●Pay attention to the warnings and cautions in this
manual.
●All installation and maintenance shall be performed by distributor or qualied person.
●All electric work must be performed by a licensed
technician according to local regulations and the instructions given in this manual.
●Be caution during installation and maintenance. Prohibit
incorrect operation to prevent electric shock, casualty and other accidents.
1. Cut off the power supply of air conditioner before checking and maintenance.
2. The air conditioner should be installed in suitable location and ensure the power plug is touchable.
3. Make sure each wiring terminal is connected rmly
during installation and maintenance.
4. Have the unit adequately grounded. The grounding wire can’t be used for other purposes.
5. Must apply protective accessories such as protective boards, cable-cross loop and wire clip.
6. The live wire, neutral wire and grounding wire of power supply must be corresponding to the live wire, neutral wire and grounding wire of the air conditioner.
7. The power cord and power connection wires can’t be pressed by hard objects.
8. If power cord or connection wire is broken, it must be
replaced by a qualied person.
9. For the air conditioner without plug, an air switch must be installed in the circuit. The air switch should be all-pole parting and the contact parting distance should be more than 3mm.
10. Check if there is electric leakage on the unit body. If yes, please eliminate the electric leakage.
11. Replace the fuse with a new one of the same specication
if it is burnt down; don’t replace it with a cooper wire or conducting wire.
12. If the unit is to be installed in a humid place, the circuit breaker must be installed.
16
Maintenance
Service Manual
Main Tools for Installation and Maintenance
1. Level meter, measuring tape
4.Electroprobe
7. Electronic leakage detector
10. Pipe pliers, pipe cutter
2.Screw driver
5. Universal meter
8. Vacuum pump
11. Pipe expander, pipe bender
3.Scissors, saw
6.Torque wrench, open-end wrench, inner
hexagon spanner
9. Pressure meter
12. Soldering appliance, refrigerant container
17
Maintenance
Service Manual
Installation procedures
Accessory list
Optional accessories
(Note: some models are without the following accessories.)
Install wire hook
Install drainage pipe
Install window frame
Install heat discharge pipe and joint
pack up heat discharge pipe
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Preparation before installation
Start installation
Prepare tools
Read the requirements for electric connection
Check after installation and test operation
Finish installation
window frame (3)
wire hook (2)
screw (8) window fastener clip of rear
connection plate
sponge Asponge B(2) drainage pipe
pipe clip
rubber plugremote controller
unit
battery (2) (AAA 1.5V)
pipe hoop (2)
joint Ajoint Bjoint C heat discharge pipe
screw (2) bolt (4) spring
washer (4)
washer (4)nut (4)protective grille (1)support (2) rain shield (1)
18
Maintenance
Service Manual
8. Install
1. Remove the rubber plug at drainage port.(As shown in following fig
2. Fix the drainage pipe clip on the right of rear side plate near drainage port with a screw.(As shown in following fig
3. Put the drainage pipe into drainage port and screw it up, and then bind it with pipe hoop.(As shown in following fig
4. Put the rubber plug into the other side of drainage pipe, fi it with pipe hoop and then fix it in the drainage pipe clip.(As shown in following fig
Note: install drainage pipe before using, otherwise poor drainage will affect normal operation of the unit.
drainage port
drainage pipe clip
Clamp joint C into the inner side of window frame along the direction of arrow.
Note: If the inner width of window is below 28"(718mm), please remove the adjusting plate from window frame and
then cut the window frame to make its width the same as the width of window.
A. Installation in a double-hung sash window.
(1) Cut the sponge B to a proper length and attach it to the window sash.
(2) Open the window; place the window frame on the window sash; slide the adjustment plate to make the window frame close to the window sashes at the left and right side of window; fix the window frame on the windowsill with screws and clips of rear connection plate. (Required quantity is shown in the sheet below)
sponge B (adhesive)
Window width (W) Screw quantity Clip quantity W≤28 3/11"(718mm) 2 2 28 3/11"(718mm)<W≤36 1/2"(927mm) 3 3 36 1/2"(927mm)<W≤64"(1625mm) 4 4
window frame
windowsill
window sash
window sash
clip of rear connection plate
Window width(W)
joint C
window frame
inner side
window frame
cut
adjusting plate
28 3/11"(718mm
)
drainage port
drainage pipe clip
screw
drainage port
drainage pipe clip
pipe hoop
pipe hoop
rubber plug
drainage pipe
8.1 Install Drainage Pipe
8.2 Install Window Frame
19
Maintenance
Service Manual
(3) Cut the sponge B to a proper length and attach it to the window frame.
(4) Close the window securely against the window frame.
sponge B (adhesive)
(5) Cut the sponge A to a proper length and seal the gap between upper part of inner window sash and outer window sash.
(6) Fix the inner window with window bracket and screw, so that it can not slide vertically.
sponge A
outer window
inner window
plastic window
wooden window
window sash
window bracket
B. Installation in a sliding sash window
(1) Cut the sponge B to a proper length and attach it to the window sash.
sponge B (adhesive)
(2) Open the window; place the window frame on the window sash vertically; slide the adjustment plate to make the window frame close to the window sashes at the upper and lower side of window; fix the window frame on the windowsill with screws and clips of rear connection plate. (required quantity is shown in the sheet below)
Window height (H) Screw quantity Clip quantity H≤28 3/11"(718mm) 2 2 28 3/11"(718mm)<H≤36 1/2"(927mm) 3 3 36 1/2"(927mm)<H≤64"(1625mm) 4 4
clip of rear connection plate
windowsill
window sash
window sash
Window height (H)
(3) Cut the sponge B to a proper length and attach it to the window frame.
(4) Close the window securely against the window frame.
sponge B (adhesive)
(5) Cut the sponge A to a proper length and seal the gap between left side of inner window sash and outer window sash.
(6) Fix the inner window with window bracket and screw, so that it can not slide horizontally.
sponge A
inner window
outer window
window sash
window bracke
t
plastic window
wooden window
A. Install heat discharge pipe
(1) Rotate joint A and joint B clockwise into the two ends of heat discharge pipe.
joint B
clockwise
clockwis
e
joint A
heat discharge pipe
8.3 Installation and Disassembly of Heat Discharge Pipe
20
Maintenance
Service Manual
(2) Insert joint A of heat discharge pipe (the side with "TOP" is upwards) into the groove until you hear a sound.(As shown in following fig
(3) Aim the locating pole of joint B of heat discharge pipe at the opening of joint C; rotate it slightly to make joint B and joint C connect tightly.
clasp
groove
the side with "TOP" is upward
s
B. Disassemble heat discharge pipe
(1) Remove joint B from joint C.(As shown in following fig
In order to improve cooling effici ncy, the heat discharge pipe should be as short as possible and flat without curve to ensure smooth heat discharge.(As shown in following fig
●The length of the exhaust pipe is less than 1m. It is recommended to use it with shortest length.
●When installing, exhaust pipe should be as flat as possible. Don't prolong the pipe or connect it with other exhaust pipe.
●Correct installation is as shown in figure (When installing it on wall, height of hall should be about 40cm-130cm from floor)
●Wrong installation is shown in following figure (If the pipe is bent too much, it would easily cause malfunction.)
joint B
joint C
joint B
joint C
locating pole
opening
tightened status
Note of Install heat discharge pipe
correct correct
correct
wrong
130cm
40cm
21
Maintenance
Service Manual
(2) Press the clasp and lift joint A upwards to remove it.(As shown in following fig
●Put through the power supply and then press ON/OFF button on remote controller to start the unit.
●Press mode button to select auto, cooling, drying, fan or heating function, and then check if the unit operates normally.
●If ambient temperature is below 16°C, the unit can't operate in cooling mode.
clasp
joint A
upwards
disassemble
● In cooling or drying operation, the condensation water will be drained to the chassis and spattered by water-striking motor. As the temperature of condenser is high, most of the condensation water will be evaporated and drained to outdoor. So usually, only a little condensation water will be accumulated inside the chassis and you do not need to discharge the water frequently.
● When the chassis is full with water, the buzzer will give out 8 sounds and "H8" is displayed to remind user to discharge water:
●Move the unit to a suitable place for discharging water; do not tilt the unit and keep it horizontal during moving;
●Take the drainage pipe from the clip and pull out the rubber plug on the drainage pipe to discharge water;
●Put back the rubber plug onto drainage pipe after finishing discharging water and then fix the pipe on the cli
●After full water protection is eliminated and the compressor has been stopped for 3 minutes, the unit will resume operation.
8.4 Operation test
8.5 Drainage way
22
Maintenance
Service Manual
8.6 Clean and Maintenance
2. Clean filte
3. Clean heat-removal pipe
(1) Remove the filte
(2) Clean filte Use cleaner or water to clean the filte . If the filter is very dirty (such as grease), use warm water 4℃ (104℉) melted with neutral abluent to clean it and then put at shady place to dry it.
(3) Install filte After the filer is cleaned and dried, reinstall it well.
Remove the heat-removal pipe from air conditioner, clean and dry it , and then reinstall it. (For the method of installation and removal method, please refer to the instruction for "Install and Remove Heat-removal Pipe).
Note:
● The filter should be cleaned about once every three months. If there's much dust in the operation environment, you can increase clean frequency.
● Do not dry the filter with fire or hair dri . Otherwise, it may be deformed or catch fire
Warning
1. Clean outer case and grille
●Before cleaning the air conditioner, please turn off the unit and disconnect power. Otherwise, it may cause electric shock.
●Do not wash air conditioner with water. Otherwise, it may cause electric shock.
●Do not use volatile liquid (such as thinner or gas) to clean the air conditioner. Otherwise, it may damage the appearance of air conditioner.
Clean outer case: If there's dust on the surface of outer case, please use soft towel to wipe it. If the outer case is very dirty (such as grease), please use neutral abluent to wipe it.
Clean grille: Use cleaner or soft brush to clean it.
①②
23
Maintenance
Service Manual
9. Maintenance
9.1 Error Code
NO. Malfunction
Name
Display Method of Indoor Unit
A/C Status Possible Causes
Error
Code
Indicator lamp
(During blinking, ON for 0.5S and
OFF for 0.5 S)
Operation
Inidicato
COOL
Indicator
HEAT
Indicator
1
Indoor ambient temperature sensor is open/short­circuited
F1
OFF 3S and blinks once
Compressor and draw water motor stop operation. Fan operates at set fan speed.
1. The wiring terminal between indoor ambient temperature sensor and main board is loosened or poorly contacted.
2. There’s short circuit due to trip-over of the parts on main board.
3.Indoor ambient temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor).
4. Main board is damaged.
2
Indoor evaporator temperature sensor is open/short­circuited
F2
OFF 3S and blinks twice
Compressor and draw water motor stop operation. Fan operates at set fan speed.
1. The wiring terminal between indoor evaporator temperature sensor and main board is loosened or poorly contacted.
2. There’s short circuit due to the trip-over of the parts on main board.
3.Indoor evaporator temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor).
4. Main board is damaged.
3
Outdoor condenser temperature sensor is open/short­circuited
F4
OFF 3S and blinks 4 times
Compressor and draw water motor stop operation. Fan operates at set fan speed.
1. The wiring terminal between outdoor condenser temperature sensor and main board is loosened or poorly contacted.
2. There’s short circuit due to the trip-over of the parts on main board.
3. Outdoor condenser temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor).
4. Main board is damaged.
4
Overcurrent protection
E5
OFF 3S and blinks 5 times
During cooling and drying operation, indoor fan operates, while other loads stop operation.
1. Unstable supply voltage. Normal fluctuatio shall be within 10% of the rated voltage on the nameplate.
2. Supply voltage is too low and load is too high.
3. Measure the current of live wire on main board. If the current isn’t higher than the overcurrent protection value, please check the controller.
4. Whether heat exchangers are too dirty, or the air inlet and air outlet are blocked.
5. Whether the fan motor operates normally, fan speed is too low or the fan doesn’t run.
6. Whether compressor operates normally. There is abnormal sound, oil leakage or the temperature of the shell is too high, etc.
7. There’s blockage in the system (filt blockage, ice plug, greasy blockage, Y-valve hasn’t been opened completely).
24
Maintenance
Service Manual
NO.
Malfunction
Name
Display Method of Indoor Unit
A/C Status Possible Causes
Error
Code
Indicator lamp
(During blinking, ON for 0.5S and
OFF for 0.5 S)
Operation
Inidicato
COOL
Indicator
HEAT
Indicator
5
Water over-flow protection
H8
The unit stops operation
During cooling or drying operation,condensate water will flow into chassis. If it’s detected that water inside water chassis is full for 3s successively, it comes into water over-flow protection. Buzzer will give out 8 sounds and dual-8 nixie tube displays error code “H8”.
6
Insufficien fluorin protection
F0
Indoor fan runs according to set fan and other loads will stop.
1. Heat exchangers are too dirty or the air inlet/outlet is blocked.
2. Compressor doesn't work normally. Strange noise or leakage occurs. Temperature of the shell is too high.
3. System is blocked inside(dirt block, ice block, oil block, Y-valve not fully open).
4. The refrigerant is leaking.
7
Overload protection for compressor
H3
Indoor fan runs according to set fan and other loads will stop.
1. Heat exchangers are too dirty or the air inlet/outlet is blocked.
2. Fan motor is not working Abnormal fan speed; fan speed is too low or the fan doesn't run.
3. Compressor doesn't work normally. Strange noise or leakage occurs. Temperature of the shell is too high.
4. System is blocked inside(dirt block, ice block, oil block, Y-valve not fully open).
5. Draw-water motor can't operate normally.
6. Water outlet hasn't been blocked well by rubber cork .
7. The refrigerant is leaking and cause overheating protection to compressor.
8
Overload malfunction
E8
During cooling or drying operation, indoor fan operates, while compressor, outdoor fan and water-striking motor stop. “E8” is displayed.
1. The environment is formidable.
2. Heat exchangers are too dirty or the air inlet/outlet is blocked.
3. Fan motor is not working Abnormal fan speed; fan speed is too low or the fan doesn't run.
4. Compressor doesn't work normally. Strange noise or leakage occurs. Temperature of the shell is too high.
5. System is blocked inside(dirt block, ice block, oil block, Y-valve not fully open).
6.Temperature sensor of main board can't detect correctly.
25
Maintenance
Service Manual
(1) Malfunction of temperature sensor F1, F2, F4
9.2 Malfunction Detection Flowchart
Troubleshooting for F1,F2,F4 malfunction
Is
the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Insert the temperature
sensor tightly
Yes
Is malfunction
eliminated
Is there short circuit due to trip-over of
the parts?
Make the parts upright
Is malfunction
eliminated
Replace the mainboard with the same model.
End
No
Is the
temperature sensor normal according
to the Resist ance
Table?
Replace it with a
temperature sensor
with the same model
Yes
Is malfunction
removed
No
No
No
No
No
Yes
Yes
Yes
Yes
26
Maintenance
Service Manual
(2) Malfunction of Overcurrent Protection E5
End
Yes
Malfunction is eliminated
Is the supply voltage unstable with big fluctuation?
Is the supply voltage too low with overload?
The fan is abnormal? Fan speed is too low or fan doesn’t rotate
Measure the current of live wireon the main board with a clamp ampere meter. Is the current higher than the value of the
overcurrent protection?
Is there blockage inside
the system? (Filth blockage, ice plug,
greasy blockage, the Y-valve hasn’t been opened
completely)
Is the compressor running abnormally? Is there abnormal sound or oil leakage; is the temperature of the shell
too high, etc.?
Is the indoor / outdoor
heat exchanger too dirty,or are the air inlet
and outlet blocked?
Normal fluctuation is within 10 % of the rated voltage on the nameplate
Malfunction is eliminated
No
No
No
No
No
No
No
No
No
No
No
No
No
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Troubleshooting for E5 malfunction
Adjust the supply voltage to maintain it within normal range
Clean the indoor and outdoor heat exchangers and remove the blockage of air inlet and outlet
Check the motor and reinstall the motor to have the fan run normally
Replace the mainboard with the same model
Replace the mainboard with the same model
Flush the heat exchangers with high pressure nitrogen
Replace the mainboard with the same model
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
27
Maintenance
Service Manual
(3) Bucket full protection H8
Whether water tray is full
Start up the unit
H8 is displayed
Check whether wires for water-level switch are connected tightly
Adjust connection
Whether malfunction is eliminated?
Whether malfunction is eliminated?
Replace water-level switch
Replace the main board with the same model
Discharge water by referring to instruction manual
Whether malfunction is eliminated?
Yes
Yes
Yes
Yes
Yes
No
No
No
End
No
No
28
Maintenance
Service Manual
4
㕪≏᭵䳌F0ᧂḕ⍱〻
The refrigerant is leaking
Check the leaking status of refrigerant and charge refrigerant
Clean the heat exchangers
and remove
blockage of air inlet/outlet.
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
End
Remove blockage in the system
System is blocked inside
(dirt block, ice block, oil block, Y-valve no
fully open).
Compressor doesn't work
normally. Strange noise or leakage occurs.
Make compressor run normally.
Casing is too hot.
Replace a main board with the same model.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Troubleshooting
for F0 malfunction
Yes
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(4) Malfunction of Insufcient uorine protection F0
29
Maintenance
Service Manual
5
঻㕙ᵪ䗷䖭᭵䳌H3ᧂḕ⍱〻
Draw-water motor can't operate
normally.
The refrigerant is leaking
and cause overheating protection to
compressor.
Replace the draw-water motor.
Water outlet hasn't been blocked well
by rubber cork.
Block the water outlet well.
Check the leaking status of refrigerant and charge refrigerant.
Clean the heat exchangers
and remove
blockage of air inlet/outlet.
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
Check motor and re-install the moto to make it run normally.
Fan motor is not working
Abnormal fan speed; fan speed is too low
or the fan doesn't run.
End
Remove blockage in the system.
System is blocked inside
(dirt block, ice block, oil block, Y-valve no
fully open).
Compressor doesn't work
normally. Strange noise or leakage occurs.
Make compressor run normally.
Casing is too hot.
Replace a main board with the same model.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Troubleshooting
for H3 malfunction
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(5) Malfunction of Overload protection for compressor H3
30
Maintenance
Service Manual
(6)
Overload malfunction E8
Clean the heat exchangers
and remove
blockage of air inlet/outlet.
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
Check motor and re-install the moto to make it run normally.
Fan motor is not working
Abnormal fan speed; fan speed is too low
or the fan doesn't run.
End
Remove blockage in the system.
System is blocked inside
(dirt block, ice block, oil block, Y-valve no
fully open).
Compressor doesn't work
normally. Strange noise or leakage occurs.
Make compressor run normally.
Casing is too hot.
Replace a main board with the same model.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Troubleshooting
for E8 malfunction
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Malfunction is
eliminated.
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Temperature sensor of main board
can't detect correctly.
Replace the temperature sensor.
Whether the environment
is formidable
Operate the unit after ambient tempeature and humidity is decreased or move the unit to the place with low abient temprature and humidity.
31
Maintenance
Service Manual
9.3 Maintenance Method for Common Malfunction
1. Air Conditioner Can't be Started Up
2. Poor Cooling (Heating) for Air Conditioner
Possible Causes for Malfunction Distinguish Method (A/C status) Maintenance Method No power supply; power plug hasn’t been inserted tightly and poorly connected; wires hasn’t been connected well.
Operation indicator is OFF and buzzer won’t give out sound.
Check whether there’s power supply; Check power plug and wire connection.
Ambient temperature sensor is damaged (no connection, loosen, wires are damaged, resistance value for temperature sensor is abnormal).
After energization, the unit will give out a sound, while it can’t be started up after pressing ON/OFF button.
Check wire connection of temperature sensor or replace temperature sensor.
Electric leakage for air conditioner
After energization, room circuit breaker trips off at once.
Make sure the air conditioner is grounded reliably. Make sure wires of air conditioner is connected correctly. Check the wiring inside air conditioner. Check whether the insulation layer of power cord is
damaged; if yes, place the power cord. Model selection for air switch is improper
After energization, air switch trips off. Select proper air switch.
Malfunction of remote controller
After energization, operation indicator is bright, while no display on remote controller or buttons have no action.
Replace batteries for remote controller.
Repair or replace remote controller.
Water inside water chassis is full
Dual8 nixie tube displays H8 and buzzer gives out 8 sounds (water over-flow protection)
Discharge condensate water.
Malfunction of water-level switch
Check water-level switch and connection (refer
to detection flow chart 3).
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature. Fan speed is set too slow Small fan blow at air outlet Set the fan speed at high or medium.
Filter unit is blocked
Check the filter to see whether it s blocked by sundries
Clean the filte .
Refrigerant is leaking
Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit's pressure is much lower than regulated range
Find out the leakage causes and deal with it. Add refrigerant.
Evaporator is frosted
Has set COOL (DRY) mode, but there’s no cool fan
The system is defrosting. Resume operation after defrosting is finished
Malfunction of capillary
Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit't pressure is much lower than regulated range. If refrigerant isn’t leaking, part of capillary is blocked
Replace the capillary.
Malfunction of fan Fan can’t operate
Refer to point 3 for detailed maintenance method.
Malfunction of compressor Compressor can't operate
Refer to point 4 of maintenance method for details.
32
Maintenance
Service Manual
6. Abnormal Sound and Vibration
Possible causes Discriminating method (air conditioner status) Troubleshooting
When turn on or turn off the unit, the panel and other parts will expand and there's abnormal sound
There's the sound of "PAPA"
Normal phenomenon. Abnormal sound will disappear after a few minutes.
When turn on or turn off the unit, there's abnormal sound due to flow of refrigerant inside air conditioner
Water-running sound can be heard
Normal phenomenon. Abnormal sound will disappear after a few minutes.
There’re foreign objects inside air conditioner or parts are contacting with each other
Abnomal sound
Take out foreign objects. Adjust the position of parts. Stick damping plaster between contacting parts.
Abnormal shake of compressor Outdoor unit gives out abnormal sound
Adjust the support foot mat of compressor, tighten the bolts.
Abnormal sound inside the compressor
Abnormal sound inside the compressor
If add too much refrigerant during maintenance, please reduce refrigerant properly. Replace compressor for other circumstances.
4. Compressor Can't Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Wrong wire connection, or poor connection
Check the wiring status according to circuit diagram
Connect wires according to wiring diagram to make sure all wiring terminals are connected firml
Capacity of compressor is damaged
Measure the capacity of fan capacitor with an universal meter and find that the capacity is out o the deviation range indicated on the nameplate of fan capacitor.
Replace the compressor capacitor
Power voltage is a little low or high
Use universal meter to measure the power supply voltage. The voltage is a little high or low
Suggest to equip with voltage regulator
Coil of compressor is burnt out
Use universal meter to measure the resistance between compressor terminals and it's 0
Repair or replace compressor
Cylinder of compressor is blocked Compressor can't operate Repair or replace compressor
5. Unit hasn't stop operation afer bucket full or bucket full protection occurs frequently
Possible causes Discriminating method (air conditioner status) Troubleshooting
Water-level switch is open­circuited
The unit hasn’t stop operation when water is full and there’s water leakage
Check and repair the water-level switch
Draw water motor is damaged
Water over-flow protection occurs frequently and H8 is displayed
Replace draw water motor
3. Fan Can't Swing
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Wrong wire connection, or poor connection
Check the wiring status according to circuit diagram
Connect wires according to wiring diagram to make sure all wiring terminals are connected firml
Fan capacitor is damaged
Use universal meter to measure voltage at both ends of fan capacitor
Replace fan capacitor
Supply voltage is too low or too high
Use universal meter to measure the voltage
You are suggested to equip with voltage regulator
Motor is damaged
Above circumstances are normal, while the fan can’t operate
Repair or replace motor
33
Maintenance
Service Manual
10. Exploded View and Parts List
COOL/FCOOL-8BS
54
53525150
49
48
1
2
3
4
5
6
7
8
91012
11
1315161718
19
202122
23
24
14
25
26
27 28 29 30
31
32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47
34
Maintenance
Service Manual
Above data is subject to change without notice.
NO.
Description
Part Code
QtyGPC08AH-K3NNC3D 1 Membrane 63066036 1 2 Display Board 30567026 1 3 Guide blade lever 2 10586015 1 4 Guide blade 1 10516059 4 5 Guide blade 2 10516062 1 6 Front Panel 20006078S 1 7 Right side plate 20056112 1 8 Discharge Tube 03001300037 1 9 Inhalation Tube 03001000047 1
10
00106531 1 11 Overload Protector 00180259 1 12
15006032 1 13 Splash Water Flywheel 10336003 1 14 Fan Motor 2 1501606202 1 15 Castor 24236009 4 16 Chassis 22226062 1 17 Water level switch sub-assy 26156045 1 18 water level switch base 26156041 1 19 Water Level Switch 45010211 1 20 Water retaining box 20186259 1 21 Capillary Sub-Assy 03006549 1 22 Condenser Assy 01106132 1 23 Left side plate 20056111 1 24 Filter sub-assy2 11126071 1 25 Filter sub-assy1 11126070 1 26 Remote controlbox 20186094 1 27 Rear Plate 20056113 1 28 Evaporator Assy 01006107 1 29 Electric Box Assy 01406549 1 30 Ambient Temperature Sensor 390000451 1 31 Main Board 30137038 1 32 Capacitor CBB65 3300008108 1 33 Capacitor CBB61 3301074705 1 34 Electric Box Cover 01416013 1 35 Water Tray 12416009 1 36 Cover of Propeller Housing 22246086 1 37 Propeller Housing (upper) 22206044 1 38 Centrifugal fan 1 10316060 1 39 Propeller Housing (lower) 22206045 1 40 Guide blade lever 1 10586015 1 41 Air Louver 2 10516061 1 42 Air Louver 1 10516060 4 43 Fan Motor 1 1501606903 1 44 Motor Holder 26156089 1 45 Rear Grill 01476020 1 46 Centrifugal fan 2 1031606101 1 47 Diversion Circle 10376038 1 48 Power Cord 4002046431 1 49 Remote Controller 30510065 1 50 Rear Clip 2611601001 1 51 Plastic Pipe End 06646017 1 52 P Phose 0523602203 1 53 Joint 26116087 1 54 Drainage hose 05230013 1
Service Manual
11. Removal Procedure
Warning: disconnect power supply before removal; discharge the refrigerant completely before unsoldering the pipes.
1.Remove remote controller box
2.Remove filter sub-assy
Break out the remote controller box, then push the middle of remote controller box to make clasps remove from remote controller box.
Pull the filter sub-assy outward by hand to remove the filter.
remote controller box
remote controller box
filter sub-assy
filter sub-assy2
filter sub-assy1
35
Maintenance
Service Manual
3.Remove panel assy
Remove the five screws fixing panel, lift
and pull outward to remove the panel.
screws
panel assy
Remove the six screws fixing rear plate to
remove the rear plate.
screws
rear
plate
for C4 panel
4.Remove rear plate
36
Maintenance
Service Manual
5.Remove left & right side plate
Remove left side plate: unscrew 7 screws as diagram shown to remove left side plate. Remove right side plate: unscrew 7 screws of right side plate to remove it.
6.Remove electric box cover
Unscrew 2 screw to remove the electric box cover.
Step Procedure
screws
left side plate right side plate
screws
screws
electric box cover
electric box
37
Maintenance
Service Manual
7.Remove electric box assembly
Pull out wiring of electric box, then unscrew 3 screws of electric box to remove electric box assembly.
8.Remove facing bar
Unscrew 2 screws fixing facing bar to remove it.
9.Remove volute cover
Unscrew 3 screws fixing volute cover to remove it.
Step Procedure
electric box assembly
screws
screws
screws volute cover
facing bar
electric box wiring
38
Maintenance
Service Manual
10.Remove evaporator assembly
Unsolder the spot weld, then unscrew 5 screws fixing evaporator to remove it. (note: The refrigerant must be discharg­ed before unsoldering.)
11.Remove facing bar 2
Unscrew 3 screws fixing facing bar to remove the facing bar 2.
Step Procedure
evaporator assembly
screws
spot weld
screws
screws
facing bar 2
39
Maintenance
Service Manual
12.Remove facing bar 1
Unscrew 4 screws fixing facing bar to remove the facing bar 1.
13.Remove duct assembly
Unscrew 2 screws to remove duct assembly.
Step Procedure
screws
screws
duct assembly
facing bar 1
40
Maintenance
Service Manual
14.Remove connecting rod and vertical louver
15.Remove volute (upper) and mesh enclosure
Break out connecting rod and vertical louver by hand to remove them.
Unscrew 4 screws as diagram shown to remove volute (upper) and mesh enclosure.
Step Procedure
vertical louver 2
vertical louver 1
connecting rod
volute (upper)
mesh enclosure
screws
41
Maintenance
Service Manual
16.Remove centrifugal louver (upper)
Unscrew nuts of centrifugal louver (upper) and motor to remove centrifugal louver (upper).
16.Remove volute (lower) and water tray
Unscrew 3 screws as diagram shown to remove volute (lower) and water tray.
Step Procedure
centrifugal louver (upper)
nut
screws
volute (lower)
water tray
42
Maintenance
Service Manual
18.Remove diversion ring
19.Remove centrifugal louver (lower)
20.Remove motor
remove diversion ring.
Unscrew nuts of centrifugal louver anticlockwise, take out gasket to remove the centrifugal louver (lower).
the motor.
Step Procedure
screws
diversion ring
centrifugal louver (lower)
nut
screws
motor
motor tray
43
Maintenance
Service Manual
21.Remove water retaining tray
Unscrew 2 screws fixing water retaining tray to remove water retaining tray.
22.Remove condenser assembly
Unscrew 2 screws, then unsolder the spot weld to remove condenser assembly. (Note: The refrigerant must be discharged before unsoldering.)
Step Procedure
screws
water retaining tray
screws
condenser assembly
spot weld
44
Maintenance
Service Manual
23.Remove compressor assembly
Unscrew 3 bolts of compressor chassis, then take out gasket to remove compressor.
24.Remove motor sub-assy, water level switch sub-assy and caster wheel
(1) Unscrew 2 screws of bottom of sub-assy to remove motor sub-assy. (2) Unscrew 2 screws fixing water level switch to remove water level switch sub-assy. (3) Unscrew 8 screws fixing caster wheel to remove the 4 caster wheels.
Step Procedure
bolts
compressor and spareparts
screws
screws
motor sub-assy
water lvel switch sub-assy
chassis
caster wheels
45
Maintenance
Service Manual
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Set temperature
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Ambient temperature
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
32/33 32 0 55/56 55.4 13 79/80 78.8 26 34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28 37/38 37.4 3 61/62 60.8 16 84/85 84.2 29 39/40 39.2 4 63 62.6 17 86/87 86 30 41/42 41 5 64/65 64.4 18 88/89 87.8 31 43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33 46/47 46.4 8 70/71 69.8 21 93/94 93.2 34 48/49 48.2 9 72 71.6 22 95/96 95 35 50/51 50 10 73/74 73.4 23 97/98 96.8 36 52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6
12 77/78 77 25
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
61 60.8 16 69/70 69.8 21 78/79 78.8 26 62/63 62.6 17 71/72 71.6 22 80/81 80.6 27 64/65 64.4 18 73/74 73.4 23 82/83 82.4 28 66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
46
Maintenance
Service Manual
Appendix 2: List of Resistance for Temperature Sensor
Resistance table of temperature sensor (15K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 138.1 20 18.75 59 3.848 98 1.071
-18 128.6 21 17.93 60 3.711 99 1.039
-17 121.6 22 17.14 61 3.579 100 1.009
-16 115 23 16.39 62 3.454 101 0.98
-15 108.7 24 15.68 63 3.333 102 0.952
-14 102.9 25 15 64 3.217 103 0.925
-13 97.4 26 14.36 65 3.105 104 0.898
-12 92.22 27 13.74 66 2.998 105 0.873
-11 87.35 28 13.16 67 2.896 106 0.848
-10 82.75 29 12.6 68 2.797 107 0.825
-9 78.43 30 12.07 69 2.702 108 0.802
-8 74.35 31 11.57 70 2.611 109 0.779
-7 70.5 32 11.09 71 2.523 110 0.758
-6 66.88 33 10.63 72 2.439 111 0.737
-5 63.46 34 10.2 73 2.358
112 0.717
-4 60.23 35 9.779 74 2.28 113 0.697
-3 57.18 36 9.382 75 2.206 114 0.678
-2 54.31 37 9.003 76 2.133 115 0.66
-1 51.59 38 8.642 77 2.064 116 0.642
0 49.02 39 8.297 78 1.997 117 0.625
1 46.6 40 7.967 79 1.933 118 0.608
2 44.31 41 7.653 80 1.871 119 0.592
3 42.14 42 7.352 81 1.811 120 0.577
4 40.09 43 7.065 82 1.754 121 0.561
5 38.15 44 6.791 83 1.699 122 0.547
6 36.32 45 6.529 84 1.645 123 0.532
7 34.58 46 6.278 85 1.594 124 0.519
8 32.94 47 6.038 86 1.544 125 0.505
9 31.38 48 5.809 87 1.497 126 0.492
10 29.9 49 5.589 88 1.451 127 0.48
11 28.51 50 5.379 89 1.408 128 0.467
12 27.18 51 5.197
90 1.363 129 0.456
13 25.92 52 4.986 91 1.322 130 0.444
14 24.73 53 4.802 92 1.282 131 0.433
15 23.6 54 4.625 93 1.244 132 0.422
16 22.53 55 4.456 94 1.207 133 0.412
17 21.51 56 4.294 95 1.171 134 0.401
18 20.54 57 4.139 96 1.136 135 0.391
19 19.63 58 3.99 97 1.103 136 0.382
47
Maintenance
Service Manual
Resistance table of temperature sensor (20K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 181.4 20 25.01 59 5.13 98 1.427
-18 171.4 21 23.9 60 4.948 99 1.386
-17 162.1 22 22.85 61 4.773 100 1.346
-16 153.3 23 21.85 62 4.605 101 1.307
-15 145 24 20.9 63 4.443 102 1.269
-14 137.2 25 20 64 4.289 103 1.233
-13 129.9 26 19.14 65 4.14 104 1.198
-12 123 27 18.13 66 3.998 105 1.164
-11 116.5 28 17.55 67 3.861 106 1.131
-10 110.3 29 16.8 68 3.729 107 1.099
-9 104.6 30 16.1 69 3.603 108 1.069
-8 99.13 31 15.43 70 3.481 109 1.039
-7 94 32 14.79 71 3.364 110 1.01
-6 89.17 33 14.18 72 3.252 111 0.983
-5 84.61 34 13.59 73 3.144
112 0.956
-4 80.31 35 13.04 74 3.04 113 0.93
-3 76.24 36 12.51 75 2.94 114 0.904
-2 72.41 37 12 76 2.844 115 0.88
-1 68.79 38 11.52 77 2.752 116 0.856
0 65.37 39 11.06 78 2.663 117 0.833
1 62.13 40 10.62 79 2.577 118 0.811
2 59.08 41 10.2 80 2.495 119 0.77
3 56.19 42 9.803 81 2.415 120 0.769
4 53.46 43 9.42 82 2.339 121 0.746
5 50.87 44 9.054 83 2.265 122 0.729
6 48.42 45 8.705 84 2.194 123 0.71
7 46.11 46 8.37 85 2.125 124 0.692
8 43.92 47 8.051 86 2.059 125 0.674
9 41.84 48 7.745 87 1.996 126 0.658
10 39.87 49 7.453 88 1.934 127 0.64
11 38.01 50 7.173 89 1.875 128 0.623
12 36.24 51 6.905
90 1.818 129 0.607
13 34.57 52 6.648 91 1.736 130 0.592
14 32.98 53 6.403 92 1.71 131 0.577
15 31.47 54 6.167 93 1.658 132 0.563
16 30.04 55 5.942 94 1.609 133 0.549
17 28.68 56 5.726 95 1.561 134 0.535
18 27.39 57 5.519 96 1.515 135 0.521
19 26.17 58 5.32 97 1.47 136 0.509
48
Maintenance
Service Manual
Resistance table of temperature sensor (50K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-29 853.5 10 98 49 18.34 88 4.75
-28 799.8 11 93.42 50 17.65 89 4.61
-27 750 12 89.07 51 16.99 90 4.47
-26 703.8 13 84.95 52 16.36 91 4.33
-25 660.8 14 81.05 53 15.75 92 4.20
-24 620.8 15 77.35 54 15.17 93 4.08
-23 580.6 16 73.83 55 14.62 94 3.96
-22 548.9 17 70.5 56 14.09 95 3.84
-21 516.6 18 67.34 57 13.58 96 3.73
-20 486.5 19 64.33 58 13.09 97 3.62
-19 458.3 20 61.48 59 12.62 98 3.51
-18 432 21 58.77 60 12.17 99 3.41
-17 407.4 22 56.19 61 11.74 100 3.32
-16 384.5 23 53.74 62 11.32 101 3.22
-15 362.9 24 51.41 63 10.93
102 3.13
-14 342.8 25 49.19 64 10.54 103 3.04
-13 323.9 26 47.08 65 10.18 104 2.96
-12 306.2 27 45.07 66 9.83 105 2.87
-11 289.6 28 43.16 67 9.49 106 2.79
-10 274 29 41.34 68 9.17 107 2.72
-9 259.3 30 39.61 69 8.85 108 2.64
-8 245.6 31 37.96 70 8.56 109 2.57
-7 232.6 32 36.38 71 8.27 110 2.50
-6 220.5 33 34.88 72 7.99 111 2.43
-5 209 34 33.45 73 7.73 112 2.37
-4 198.3 35 32.09 74 7.47 113 2.30
-3 199.1 36 30.79 75 7.22 114 2.24
-2 178.5 37 29.54 76 7.00 115 2.18
-1 169.5 38 28.36 77 6.76 116 2.12
0 161 39 27.23 78 6.54 117 2.07
1 153 40 26.15 79 6.33 118 2.02
2 145.4 41 25.11
80 6.13 119 1.96
3 138.3 42 24.13 81 5.93 120 1.91
4 131.5 43 23.19 82 5.75 121 1.86
5 125.1 44 22.29 83 5.57 122 1.82
6 119.1 45 21.43 84 5.39 123 1.77
7 113.4 46 20.6 85 5.22 124 1.73
8 108 47 19.81 86 5.06 125 1.68
9 102.8 48 19.06 87 4.90 126 1.64
49
Maintenance
Service Manual
Appendix 3: Resistance Value Table of Humidity Sensor
Relative
humidity
Temperature
(℃)
%RH 5
6
7
8
9
10
11
12
13
14
90 5.35 4.92 4.55 4.23 3.95 3.70 3.47 3.25 3.05 2.87 89 5.80 5.33 4.93 4.58 4.27 4.00 3.74 3.51 3.29 3.09 88 6.29 5.77 5.33 4.95 4.62 4.32 4.03 3.78 3.54 3.32 87 6.82 6.25 5.77 5.36 4.99 4.66 4.35 4.08 3.82 3.58 86 7.40 6.78 6.25 5.80 5.40 5.04 4.70 4.40 4.11 3.85 85 8.03 7.35 6.78 6.28 5.84 5.45 5.09 4.75 4.45 4.16 84 8.71 7.97 7.35 6.81 6.33 5.91 5.50 5.14 4.80 4.49 83 9.44 8.65 7.97 7.39 6.87 6.41 5.96 5.56 5.19 4.84 82 10.25 9.39 8.65 8.02 7.46 6.96 6.47 6.03 5.62 5.24 81 11.13 10.19 9.40 8.71 8.10 7.56 7.03 6.54 6.09
5.68 80 12.09 11.07 10.21 9.46 8.80 8.21 7.62 7.08 6.59 6.13 79 13.14 12.03 11.09 10.28 9.57 8.93 8.28 7.70 7.16 6.66 78 14.27 13.07 12.05 11.17 10.40 9.70 8.99 8.35 7.75 7.20 77 15.50 14.20 13.10 12.14 11.30 10.55 9.78 9.07 8.43 7.83 76 16.84 15.43 14.24 13.21 12.30 11.48 10.64 9.87 9.16 8.51 75 18.31 16.78 15.49 14.37 13.38 12.50 11.58 10.75 9.98 9.26 74 19.91 18.25 16.85 15.64 14.57 13.62 12.62 11.72 10.89 10.12 73 21.67 19.87 18.35 17.04 15.88 14.84 13.71 12.67 11.72 10.84 72 23.61 21.66 20.00 18.57 17.31 16.18 14.98 13.90 12.89 11.96 71 25.78 23.64 21.84 20.27 18.89 17.66 16.35 15.16 14.06 13.05 70 28.15 25.82 23.85 22.15 20.65 19.30 17.91 16.63 15.46 14.37 69 30.78 28.24 26.10 24.24 22.60 21.13 19.60 18.19 16.91 15.71 68
33.69 30.92 28.58 26.55 24.76 23.16 21.48 19.94 18.53 17.22 67 36.90 33.88 31.33 29.11 27.16 25.42 23.56 21.86 20.29 18.85 66 40.45 37.16 34.37 31.96 29.84 27.93 25.83 23.92 22.15 20.52 65 44.38 40.78 37.74 35.11 32.78 30.70 28.42 26.34 24.42 22.65 64 48.75 44.81 41.48 38.59 36.05 33.77 31.24 28.93 26.80 24.83 63 53.64 49.31 45.65 42.48 39.68 37.17 34.34 31.74 29.36 27.15 62 59.14 54.36 50.32 46.82 43.73 40.97 37.83 34.96 32.32 29.87 61 65.31 60.02 55.55 51.68 48.26 45.20 41.70 38.51 35.58 32.86 60 72.27 66.40 61.43 57.13 53.33 49.94 46.07 42.53 39.28 36.27 59 80.13 73.58 68.04 63.25 59.01 55.23 50.94 47.03 43.43 40.10 58 88.92 81.61 75.43 70.08 65.36 61.14 56.40 52.08 48.
11 44.43 57 98.86 90.68 83.77 77.78 72.50 67.78 62.49 57.67 53.23 49.12 56 112.59 102.79 94.50 87.33 81.00 75.33 69.42 64.03 59.07 54.48 55 122.69 112.51 103.91 96.45 89.88 84.00 77.42 71.41 65.88 60.76 54 137.09 125.76 116.19 107.89 100.57 94.03 86.69 79.99 73.82 68.11 53 153.46 140.88 130.25 121.03 112.91 105.64 97.26 89.61 82.58 76.06 52 172.19 158.19 146.35 136.10 127.05 118.96 109.52 100.90 92.97 85.63 51 193.69 178.04 164.81 153.36 143.25 134.21 123.35 113.43 104.31 95.86 50 218.48 200.85 185.94 173.02 161.63 151.44 139.14 127.90 117.57 108.01 49 247.23 227.16 210.19 195.49 182.52 170.92 156.84 143.98 132.15 121.20 48 278.74 256.20 237.15 220.64 206.08 193.06 177.34 163.00 149.80 137.58 47 315.50 289.95 268.35 249.64 233.14 218.37 200.56 184.30 169.34 155.49
46 357.93 328.94 304.43 283.20 264.47 247.72 227.57 209.18 192.25 176.59 45 406.44 373.72 346.05 322.08 300.94 282.03 259.22 238.40 219.24 201.51 44 463.66 426.44 394.96 367.70
343.66 322.14 296.25 272.62 250.87 230.74 43 531.25 488.59 452.53 421.28 393.73 369.08 339.44 312.38 287.50 264.45 42 611.22 562.01 520.40 484.35 452.55 424.11 390.24 359.31 330.86 304.52 41 707.78 650.29 601.68 559.58 522.44 489.21 450.38 414.92 382.31 352.11 40 823.98 756.22 698.93 649.30 605.53 566.37 521.46 480.46 442.74 407.81 39 962.72 882.62 814.90 756.23 704.48 658.19 604.79 556.03 511.18 469.66
HIS-06 temperature and humidity characteristic5℃~14
Unit:KΩ
50
Maintenance
Service Manual
HIS-06 temperature and humidity characteristic 15℃~24℃
Relative
humidity
Temperature
(℃)
%RH 15
16
17
18
19
20
21
22
23
24
90 2.70 2.56 2.43 2.31 2.19 2.08 1.99 1.91 1.83 1.75 89 2.91 2.76 2.61 2.48 2.35 2.23 2.13 2.04 1.95 1.86 88 3.12 2.96 2.80 2.66 2.52 2.39 2.28 2.18 2.08 1.98 87 3.36 3.18 3.01 2.85 2.70 2.56 2.44 2.33 2.22 2.12 86 3.61 3.42 3.23 3.06 2.90 2.75 2.62 2.50 2.38 2.27 85 3.90 3.69 3.49 3.30 3.12 2.95 2.81 2.67 2.54 2.42 84 4.20 3.97 3.76 3.55 3.36 3.18 3.03 2.88 2.74 2.61 83 4.52 4.28 4.05 3.83 3.63 3.43 3.26 3.10 2.94 2.79 82 4.89 4.63 4.38 4.14 3.92 3.71 3.52 3.33 3.16 2.99 81 5.29 5.00 4.73 4.48 4.24 4.01 3.80 3.60 3.42
3.23 80 5.70 5.39 5.10 4.83 4.57 4.33 4.10 3.88 3.68 3.48 79 6.19 5.85 5.53 5.22 4.94 4.67 4.41 4.17 3.94 3.72 78 6.69 6.32 5.96 5.63 5.32 5.02 4.75 4.49 4.24 4.01 77 7.27 6.85 6.46 6.09 5.74 5.41 5.11 4.83 4.56 4.31 76 7.90 7.44 7.00 6.59 6.20 5.83 5.51 5.21 4.92 4.65 75 8.60 8.08 7.60 7.14 6.71 6.30 5.95 5.62 5.30 4.99 74 9.40 8.82 8.28 7.77 7.29 6.83 6.45 6.09 5.74 5.41 73 10.02 9.44 8.89 8.38 7.89 7.43 7.01 6.60 6.21 5.84 72 11.10 10.43 9.79 9.19 8.63 8.09 7.62 7.17 6.74 6.33 71 12.10 11.36 10.67 10.02 9.40 8.82 8.31 7.82 7.36 6.92 70 13.36 12.52 11.72 10.98 10.27 9.60 9.03 8.49 7.97 7.48 69 14.60 13.67 12.79 11.97 11.19 10.45 9.82 9.23 8.66 8.11 68 16.00 14.96 13.99 13.07 12.20 11.37 10.68 10.02 9.39 8.78 67 17.50 16.35 15.27 14.26 13.30 12.39 11.61 10.86 10.15 9.47 66 19.00 17.76 16.60 15.51 14.47 13.49 12.64 11.83 11.05 10.31 65 21.00 19.59 18.26 17.01 15.82 14.70 13.76 12.86 12.01 11.19 64 23.00 21.43 19.96 18.57 17.25 16.00 14.98 14.00 13.06 12.16 63 25.10 23.38 21.77 20.24 18.80 17.44 16.31 15.24 14.22 13.24 62 27.60 25.66 23.84 22.13 20.51 18.97 17.73 16.55 15.42 14.34 61 30.33 28.17 26.14 24.23 22.42 20.71 19.37 18.10 16.88 15.72 60 33.47 31.05 28.78 26.64 24.62 22.70 21.24 19.84 18.50 17.23 59 37.00 34.31 31.77 29.39 27.13 24.99 23.37 21.83 20.36 18.95 58 41.00 38.00 35.18 32.52 30.00 27.61 25.82
24.11 22.47 20.90
57 45.30 41.99 38.88 35.95 33.18 30.54 28.59 26.72 24.94 23.24
38 1128.50 1033.61 953.39 883.90 822.61 767.78 704.83 647.37 594.51 545.56 37 1325.87 1213.40 1118.31 1035.94 963.29 898.30 823.48 755.17 692.34 634.16 36 1563.51 1430.14 1317.38 1219.71 1133.55 1056.48 967.04 885.39 810.28 740.74 35 1855.67 1695.83 1560.69 1443.63 1340.37 1248.00 1140.34 1042.06 951.64 867.93 34 2213.60 2020.33 1856.92 1715.37 1590.51 1478.82 1349.81 1232.04 1123.70 1023.39 33 2665.63 2426.92 2225.10 2050.27 1896.06 1758.12 1605.77 1466.69 1338.74 1220.28 32 3230.73 2933.36 2681.95 2464.17 2272.06 2100.23 1916.82 1749.39 1595.37 1452.76 31 3962.78 3585.59 3266.69 2990.44 2746.77 2528.80 2308.12 2106.66 1921.33 1749.74 30 4915.40 4431.65 4022.65 3668.35 3355.84 3076.30 2801.20 2550.06 2319.03 2105.13 29 6180.16 5548.66 5014.73 4552.22 4144.26 3779.32 3431.59 3114.13 2822.10 2551.72 28 7874.08 7035.10 6325.74 5711.27 5169.27 4684.43 4243.82 3841.57 3471.54 3128.95 27 10162.49 9029.08 8070.80 7240.70 6508.50 5853.53 5293.25 4781.75 4311.22 3875.57 26 13243.42
11702.63 10399.92 9271.46 8276.08 7385.69 6658.01 5993.68 5382.56 4816.75 25 17366.01 15270.67 13499.09 11964.48 10610.86 9400.00 8447.52 7577.98 6778.07 6037.48 24 22845.46 20023.30 17637.20 15570.26 13747.10 12116.22 10866.57 9725.72 8676.25 7704.59 23 30130.06 26367.98 23187.18 20431.85 18001.48 15827.43 14156.73 12631.50 11228.43 9929.38 22 39673.45 34712.87 30518.76 26885.65 23681.03 20814.39 18624.92 16626.08 14787.33 13084.91 21 51880.00 45447.42 40008.75 35297.56 31142.00 27424.72 24504.12 21837.82 19385.06 17114.16 20 68057.37 59623.21 52492.24 46315.10 40866.49 35992.53 32084.71 28517.14 25235.30 22196.79
Unit:KΩ
51
Maintenance
Service Manual
56 50.20 46.55 43.12 39.89 36.83 33.93 31.76 29.69 27.71 25.82 55 56.00 51.92 48.08 44.47 41.05 37.80 35.35 33.02 30.79 28.65 54 62.80 58.20 53.88 49.80 45.95 42.29 39.51 36.87 34.34 31.92 53 70.00 64.95 60.21 55.74 51.51 47.50 44.33 41.31 38.42 35.65 52 78.80 73.12 67.79 62.76 58.00 53.49 49.86 46.40 43.10 39.94 51 88.00 81.79 75.97 70.47 65.27 60.34 56.11 52.08 48.23 44.54 50 99.10 92.12 85.57 79.39 73.55 68.00 63.15 58.52 54.10 49.86 49 111.00 103.28 96.04 89.20 82.74 76.61 70.94 65.54 60.38 55.44 48 126.20 117.27 108.88 100.97 93.48 86.38 79.89 73.71 67.79 62.13 47 142.60 132.48 122.97 114.00 105.52 97.48 90.16 83.18 76.51 70.12 46 162.00 150.38 139.46 129.16 119.43 110.19 101.62 93.45 85.64 78.17 45 185.00 171.49 158.81 146.85 135.53 124.80 115.00 105.66 96.74 88.20 44 212.00 196.23 181.41 167.45 154.23 141.70 130.18 119.19 108.69 98.64 43 243.00 224.65 207.41 191.15 175.78 161.19 148.03 135.48 123.49 112.01 42 280.00 258.38 238.08 218.93 200.82 183.64 168.64 154.32 140.65 127.56 41 324.00 298.37 274.29 251.59 230.12 209.75 192.53 176.11 160.43 145.41 40 375.30 344.95 316.43 289.55 264.12 240.00 220.30 201.52 183.57 166.39 39 431.00 395.97 363.07 332.05 302.71 274.87 251.94 230.08 209.19 189.19 38 500.00 458.51 419.54 382.80 348.04 315.07 289.04 264.21 240.49 217.78 37 580.00 531.11 485.18 441.88 400.92 362.06 332.09 303.52 276.21 250.07 36 676.00 618.14 563.79 512.55 464.08 418.09 383.52 350.57 319.07 288.92 35 790.00 721.80 657.74 597.34 540.20 486.00 445.77 407.41 370.75 335.66 34 930.00 848.96 772.84 701.08 633.19 568.78 521.38 476.19 433.01 391.66 33 1110.00 1011.10 918.19 830.60 747.75 669.14 613.58 560.59 509.97 461.49 32 1320.00 1201.45 1090.09 985.09 885.78 791.56 725.62 662.75 602.68 545.17 31 1590.00 1444.80 1308.40 1179.80 1058.15 942.75 863.43 787.81 715.55 646.36 30 1906.00 1731.91 1568.38 1414.20 1268.36 1130.00 1034.60 943.64 856.73 773.51 29 2300.00 2089.81 1892.37 1706.22 1530.13 1363.08 1244.55 1131.54 1023.56 920.17 28 2810.00 2550.31 2306.37 2076.38 1858.82 1652.43 1505.84 1366.07 1232.52 1104.65 27 3470.00 3144.23 2838.22 2549.70 2276.79 2017.87 1836.86 1664.27 1499.35 1341.45 26 4290.00 3885.50 3505.53 3147.28 2808.41 2486.92 2253.64 2031.21 1818.67 1615.18 25 5348.00 4843.01 4368.65 3921.40 3498.35 3097.00 2802.48 2521.66 2253.33 1996.42 24 6800.00 6152.28 5543.84 4970.19 4427.56 3912.77 3538.27 3181.20 2840.01 2513.33 23 8720.00 7888.61 7107.64 6371.32 5674.82 5014.05 4529.95 4068.38 3627.32 3205.04 22 11500.00 10371.38 93
11.21 83
11.65 7366.14 6469.15 5839.63 5239.39 4665.85 4116.71 21 15000.00 13512.80 12115.79 10798.65 9552.74 8370.76 7546.29 6760.17 6009.01 5289.82 20 19368.00 17441.37 15631.58 13925.26 12311.23 10780.00 9716.41 8702.31 7733.29 6805.52
HIS-06 temperature and humidity characteristic 25
℃~34℃
Relative humidity
Temperature
(℃)
%RH 25
26
27
28
29
30
31
32
33
34
90 1.68 1.62 1.57 1.52 1.47 1.42 1.37 1.33 1.28 1.24 89 1.78 1.72 1.66 1.61 1.55 1.50 1.45 1.40 1.36 1.31 88 1.89 1.83 1.76 1.70 1.65 1.59 1.54 1.49 1.44 1.39 87 2.02 1.95 1.88 1.81 1.74 1.68 1.63 1.57 1.52 1.47 86 2.16 2.08 2.00 1.93 1.85 1.78 1.72 1.66 1.61 1.55 85 2.30 2.21 2.13 2.05 1.97 1.89 1.82 1.76 1.70 1.64 84 2.48 2.38 2.28 2.19 2.10 2.01 1.94 1.87 1.80 1.73 83 2.65 2.54 2.43 2.33 2.24 2.14 2.06 1.98 1.91 1.83 82 2.83 2.71 2.60 2.49 2.38 2.28 2.19 2.11 2.02 1.94 81 3.06 2.93 2.80 2.67 2.55 2.44 2.34 2.24 2.15
2.06 80 3.28 3.14 3.00 2.86 2.73 2.60 2.49 2.38 2.28 2.18 79 3.51 3.35 3.20 3.05 2.91 2.78 2.65 2.54 2.42 2.31 78 3.78 3.61 3.44 3.28 3.12 2.97 2.83 2.70 2.57 2.45 77 4.06 3.87 3.69 3.51 3.34 3.17 3.03 2.88 2.74 2.61 76 4.38 4.17 3.97 3.77 3.58 3.40 3.23 3.07 2.92 2.77 75 4.70 4.47 4.25 4.04 3.84 3.64 3.46 3.28 3.11 2.94 74 5.09 4.83 4.59 4.35 4.12 3.90 3.70 3.51 3.32 3.14
Unit:KΩ
52
Maintenance
Service Manual
73 5.49 5.21 4.94 4.68 4.43 4.19 3.97 3.75 3.54 3.34 72 5.93 5.62 5.33 5.04 4.77 4.50 4.26 4.02 3.80 3.57 71 6.49 6.13 5.79 5.46 5.14 4.84 4.57 4.32 4.07 3.83 70 7.00 6.61 6.24 5.88 5.53 5.20 4.91 4.63 4.35 4.09 69 7.59 7.16 6.75 6.35 5.96 5.59 5.27 4.97 4.67 4.38 68 8.20 7.73 7.28 6.84 6.42 6.01 5.67 5.34 5.01 4.70 67 8.82 8.32 7.83 7.36 6.91 6.47 6.10 5.74 5.38 5.04 66 9.60 9.03 8.49 7.96 7.46 6.97 6.57 6.18 5.80 5.43 65 10.40 9.78 9.18 8.61 8.06 7.52 7.08 6.65 6.24 5.84 64 11.30 10.62 9.96 9.33 8.72 8.13 7.65 7.19 6.74 6.30 63 12.30 11.55 10.82 10.12 9.45 8.80 8.27 7.75 7.26 6.78 62 13.30 12.49 11.71 10.96 10.23 9.53 8.96 8.41 7.87 7.35 61 14.60 13.69 12.81 11.97 11.15 10.36 9.73 9.12 8.53 7.96 60 16.00 14.99 14.02 13.08 12.17 11.30 10.61 9.94 9.29 8.66 59 17.60 16.48 15.40 14.35 13.35 12.38 11.61 10.87 10.15 9.46 58 19.40 18.15 16.95 15.79 14.68 13.60 12.75 11.93 11.13 10.36 57 21.60 20.18 18.81 17.49 16.22 14.99 14.05 13.14 12.26 11.41 56 24.00 22.40 20.86 19.37 17.94 16.55 15.50 14.48 13.50 12.54 55 26.60 24.81 23.10 21.44 19.84 18.30 17.13 16.00 14.90 13.83 54 29.60 27.59 25.66 23.81 22.01 20.28 18.96 17.69 16.46 15.26 53 33.00 30.74 28.57 26.48 24.46 22.52 21.04 19.62 18.24 16.90 52 36.90 34.35 31.90 29.53 27.25 25.05 23.38 21.77 20.21 18.69 51 41.00 38.18 35.47 32.86 30.34 27.90 26.03 24.22 22.46 20.76 50 45.80 42.62 39.55 36.60 33.75 31.00 28.91 26.89 24.93 23.03 49 50.70 47.20 43.83 40.59 37.45 34.43 32.08 29.81 27.61 25.47 48 56.70 52.72 48.90 45.21 41.66 38.22 35.62 33.10 30.67 28.30 47 64.00 59.37 54.91 50.61 46.46 42.46 39.57 36.78 34.07 31.45 46 71.00 65.89 60.97 56.22 51.65 47.23 43.99 40.85 37.81 34.86 45 80.00 74.13 68.48 63.03 57.78 52.70 49.02 45.46 42.00 38.65 44 89.00 82.54 76.32 70.33 64.54 58.96 54.75 50.69 46.74 42.92 43 101.00 93.48 86.25 79.28 72.55 66.06 61.28 56.65 52.17 47.82 42 115.00 106.23 97.79 89.66 81.81 74.23 68.69 63.33 58.14 53.10 41 131.00 120.81 111.01 101.56 92.44 83.64 77.33 71.23 65.31 59.57 40 149.90 138.01 126.56 115.53 104.88 94.60 87.37 80.37 73.58 66.99 39 170.00 156.52 143.54 131.04 118.97 107.32 99.08 91.11 83.38
75.88 38 196.00 180.09 164.79 150.04 135.81 122.06 112.71 103.65 94.88 86.37 37 225.00 206.61 188.92 171.87 155.41 139.52 128.86 118.54 108.53 98.82 36 260.00 238.50 217.80 197.86 178.62 160.04 147.90 136.16 124.77 113.73 35 302.00 276.83 252.61 229.27 206.76 185.00 170.96 157.37 144.19 131.41 34 352.00 322.66 294.42 267.21 240.96 215.59 199.30 183.53 168.24 153.40 33 415.00 380.13 346.58 314.24 283.04 252.90 233.57 214.84 196.70 179.09 32 490.00 448.82 409.19 371.01 334.16 298.57 275.69 253.53 232.06 2
11.23 31 580.00 531.32 484.48 439.35 395.79 353.72 326.76 300.66 275.37 250.83 30 693.69 634.81 578.16 523.57 470.89 420.00 387.67 356.36 326.02 296.58 29 821.00 751.60 684.82 620.48 558.38 498.40 459.39 421.61 385.00 349.49 28 982.00 898.01 817.20 739.32 664.18 591.58 544.87 499.65 455.82 413.29 27 1190.00 1085.85 985.63 889.06 795.87 705.85 649.51 594.96 542.09 490.80 26 1420.00 1297.43 1179.49 1065.83 956.17 850.22 781.68 715.32 651.00 588.59 25 1750.00 1597.27 1450.30 1308.67 1172.02 1040.00 954.91
872.53 792.68 715.22
24 2200.00 2005.83 1818.99 1638.94 1465.21 1297.38 1189.66 1085.37 984.29 886.22 23 2800.00 2551.47 2312.32 2081.87 1859.50 1644.68 1506.06 1371.84 1241.75 1115.55 22 3590.00 3270.74 2963.54 2667.51 2381.86 2105.90 1925.97 1751.75 1582.89 1419.07 21 4600.00 4191.56 3798.54 3419.81 3054.38 2701.33 2467.06 2240.24 2020.39 1807.10 20 5915.63 5385.23 4874.84 4383.03 3908.47 3450.00 3152.84 2865.12 2586.25 2315.70
53
Maintenance
Service Manual
HIS-06 Characteristic of temperature and humidity 35℃~ 45
Relative
humidity
Temperature
(℃)
%RH 35
36
37
38
39
40
41
42
43
44
45
90 1.20 1.17 1.14 1.11 1.08 1.05 1.02 1.00 0.98 0.95 0.93 89 1.27 1.23 1.20 1.16 1.13 1.10 1.07 1.05 1.02 1.00 0.97 88 1.34 1.30 1.26 1.22 1.19 1.15 1.12 1.09 1.07 1.04 1.02 87 1.42 1.37 1.33 1.29 1.25 1.21 1.18 1.15 1.12 1.09 1.06 86 1.50 1.45 1.40 1.36 1.31 1.27 1.24 1.20 1.17 1.14 1.11 85 1.58 1.53 1.48 1.43 1.38 1.33 1.29 1.26 1.23 1.19 1.16 84 1.67 1.61 1.56 1.50 1.45 1.40 1.36 1.32 1.29 1.25 1.21 83 1.76 1.70 1.64 1.58 1.52 1.47 1.43 1.39 1.35 1.31 1.27 82 1.86 1.79 1.73 1.66 1.60 1.54 1.50 1.45 1.41 1.37
1.33 81 1.97 1.90 1.82 1.75 1.69 1.62 1.57 1.53 1.48 1.44 1.40 80 2.08 2.00 1.93 1.85 1.78 1.71 1.66 1.61 1.56 1.51 1.46 79 2.20 2.12 2.03 1.95 1.88 1.80 1.74 1.69 1.64 1.59 1.54 78 2.33 2.24 2.15 2.07 1.98 1.90 1.84 1.78 1.72 1.67 1.61 77 2.48 2.38 2.28 2.18 2.09 2.00 1.94 1.87 1.81 1.75 1.69 76 2.62 2.51 2.41 2.31 2.21 2.12 2.05 1.98 1.91 1.84 1.78 75 2.78 2.67 2.56 2.45 2.34 2.24 2.16 2.09 2.01 1.94 1.87 74 2.96 2.84 2.71 2.60 2.48 2.37 2.29 2.20 2.12 2.04 1.97 73 3.14 3.01 2.88 2.75 2.63 2.51 2.42 2.33 2.24 2.15 2.07 72 3.36 3.21 3.06 2.92 2.78 2.65 2.55 2.46 2.36 2.27 2.18 71 3.60 3.44 3.28 3.12 2.97 2.82 2.71 2.61 2.50 2.40 2.30 70 3.83 3.65 3.48 3.32 3.16 3.00 2.88 2.77 2.65 2.54 2.43 69 4.10 3.91 3.73 3.55 3.37 3.20 3.07 2.94 2.82 2.70 2.58 68 4.40 4.19 3.99 3.79 3.60 3.41 3.27 3.13 2.99 2.86 2.73 67 4.71 4.49 4.27 4.06 3.85 3.65 3.49 3.34 3.19 3.05 2.90 66 5.08 4.83 4.59 4.36 4.13 3.91 3.74 3.57 3.41 3.25 3.09 65 5.45 5.19 4.93 4.68 4.44 4.20 4.01 3.83 3.65 3.47 3.30 64 5.88 5.59 5.31 5.04 4.78 4.52 4.31 4.11 3.91 3.72 3.53 63 6.31 6.00 5.70 5.41 5.13 4.85 4.63 4.41 4.20 4.00 3.80 62 6.84 6.50 6.17 5.84 5.53 5.22 4.98 4.75 4.52 4.30 4.09 61 7.40 7.03 6.66 6.31 5.97 5.63 5.37 5.12 4.88 4.64 4.41 60 8.05 7.64 7.24 6.86 6.48
6.11 5.83 5.55 5.28 5.01 4.76 59 8.78 8.33 7.89 7.46 7.05 6.64 6.33 6.02 5.72 5.43 5.14 58 9.61 9.10 8.61 8.13 7.66 7.20 6.86 6.52 6.19 5.87 5.56 57 10.58 10.00 9.43 8.88 8.34 7.82 7.44 7.08 6.72 6.36 6.02 56 11.61 10.96 10.33 9.71 9.
11 8.53 8.11 7.70 7.30 6.91 6.53 55 12.80 12.07 11.36 10.68 10.00 9.35 8.88 8.42 7.97 7.53 7.10 54 14.10 13.29 12.50 11.73 10.98 10.25 9.72 9.21 8.70 8.21 7.73 53 15.60 14.68 13.78 12.90 12.05 11.22 10.63 10.06 9.50 8.96 8.42 52 17.22 16.18 15.18 14.20 13.24 12.31 11.66 11.02 10.40 9.79 9.19 51 19.10 17.93 16.79 15.68 14.59 13.54 12.81 12.10 11.40 10.72 10.05 50 21.18 19.87 18.60 17.36 16.15 14.97 14.14 13.33 12.54 11.77 11.01 49 23.40 21.97 20.57 19.21 17.89 16.60 15.65 14.73 13.82 12.94 12.08 48 26.00 24.35 22.75 21.20 19.68 18.20 17.17 16.16 15.18 14.21 13.27 47 28.90 27.06 25.28 23.54 21.85 20.20 19.03 17.88 16.77 15.68 14.61 46 32.00 29.95 27.96 26.03 24.14 22.30 21.00 19.74 18.50 17.29 16.11 45 35.40 33.16 30.99 28.87 26.81 24.80 23.33 21.90 20.50 19.14 17.80 44 39.20 36.71 34.29 31.93 29.64 27.40 25.79 24.21 22.67 21.17 19.70 43 43.60 40.77 38.02 35.35 32.74 30.20 28.45 26.73 25.06 23.43 21.83 42 48.20 45.06 42.00 39.02 36.13 33.30 31.40 29.55 27.74 25.97 24.25 41 54.00 50.43 46.97 43.59 40.30 37.10 34.98 32.92 30.90 28.93 27.00 40 60.60 56.63 52.78 49.02 45.36 41.80 39.36 36.98 34.66 32.39 30.17 39 68.60 64.04 59.61 55.30 51.10 47.00 44.23 41.53 38.89 36.31 33.78 38 78.10 72.70 67.45 62.33 57.35 52.50 49.44 46.45 43.54 40.69 37.90
Unit:KΩ
54
Maintenance
Service Manual
37 89.40 82.99 76.75 70.68 64.76 59.00 55.58 52.24 48.98 45.80 42.68 36 103.00 95.43 88.06 80.89 73.91 67.10 63.17 59.33 55.59 51.93 48.35 35 119.00 110.35 101.94 93.75 85.77 78.00 73.18 68.47 63.88 59.39 55.00 34 139.00 129.32 119.90 110.73 101.80 93.10 86.80 80.66 74.66 68.80 63.07
33 162.00 149.97 138.28 126.90 115.81 105.00 98.24 91.63 85.19 78.89 72.73 32 191.00 176.44 162.29 148.50 135.08 122.00 114.10 106.40 98.87 91.52 84.34 31 227.00 209.28 192.04 175.27 158.93 143.00 133.62 124.46 115.52 106.79 98.25 30 268.00 247.75 228.05 208.88 190.20 172.00 160.04 148.37 136.97 125.83 114.95 29 315.00 291.16 267.97 245.41 223.43 202.00 187.96 174.26 160.88 147.81 135.03 28 372.00 342.25 313.32 285.16 257.73 231.00 215.94 201.25 186.90 172.88 159.17 27 441.00 404.50 369.01 334.45 300.80 268.00 251.39 235.18 219.35 203.88 188.76
26 528.00 484.54 442.27 401.13 361.06 322.00 301.66 281.81 262.43 243.49 224.98 25 640.00 590.21 541.79 494.65 448.75 404.00 375.91 348.49 321.72 295.57 270.00 24 791.00 735.73 681.97 629.64 578.68 529.00 486.67 445.36 405.02 365.60 327.08 23 993.00 926.97 862.74 800.23 739.35 680.00 621.22 563.85 507.84 453.11 399.61
22 1260.00 1171.18 1084.80 1000.72 918.82 839.00 766.05 694.86 625.34 557.42 491.03
21 1600.00 1476.79 1356.97 1240.33 1126.73 1016.00 929.53 845.14 762.74 682.23 603.53
20 2053.00 1880.43 1712.58 1549.22 1390.09 1235.00 1131.26 1030.03 931.17 834.59 740.18
55
Maintenance
AIR CONDITIONING SYSTEMS
Scan here to download the latest version of this manual.
AIR CONDITIONING SYSTEMS
PORTABLE
Loading...