INVENTOR C1VI-09, C1VO-09, C1VO-12, C1VI-12 Service Manual

C1VI - 09 / C1VO - 09 C1VI - 12 / C1VO - 12
a
b
e
2
3
3 7 7 8 8
9
11
Simply
...............................................43
.46
..........................................................................44
. 59
C1VI-09 C1VI-12
ON OFF
MODE
FAN
CLOCK TIMER ON
X-FAN TEMP
TIMER OFF
TURBO SLEEP LIGH T
C1VO-09 C1VO-12
2
C1VI - 09 / C1VO - 09
C1VI - 09 / C1VO - 09
C1VI - 09
3
C1VO - 09
4
C1VI - 12 / C1VO - 12
C1VI - 12 / C1VO - 12
C1VI - 12
5
C1VO - 12
6
a
12K
09K
Current(A)
757060504030
1
2
3
4
5
6
7
Compressor Speed (rps)
20
12K
09K
Current(A)
757060
50
4030
1
2
3
4
5
6
7
Compressor Speed (rps)
20
Condition Cooling Indoor:DB26.7
WB19.4 Indoor air flow: Super High Pipe length:5m
Condition Heating Indoor:DB21.1 Indoor air flow: Super High Pipe length:5m
09K
12K
Capacity ratio(%)
110
60
1070-8
40
50
70
80
90
100
120
Outdoor temp(
-15
09K
12K
Capacity ratio(%)
110
60
48423835
40
50
70
80
90
100
120
Outdoor temp(
32
Condition Heating Indoor:DB21.1 Indoor air flow: Super High Pipe length:5m
Condition Cooling Indoor:DB26.7
WB19.4 Indoor air flow: Super High Pipe length:5m
7
Indoor side noise when blowing
Outdoor side noise when Compressor speed changed
Compressor Speed(rps)
706050403020
45
50
55
Noise/dB(A)
75
09K 12K
Indoor fan motor rotating speed
LowMiddleHighSupper High
25
30
35
40
45
Noise/dB(A)
b
8
9
10
TINU ROODTUOTINU ROODNI
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
COOLING
Accumlator
Discharge
Suction
Muffler
Strainer
Capillary
TINU ROODTUOTINU ROODNI
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
COOLING HEATING
Accumlator
Discharge
Suction
Muffler
4-Way valve
reniartSreniartS
Capillary
11
0 0
RT1 RT2
JUMP
CAP
TEM.SENSOR
ROOM
TUBE
TEM.SENSOR
FAN MOTOR
SWING MOTOR(U.D)
AP2
SWING-UD
K4
TUBEROOM
AC-L
PG
PGF
TR_OUT
TR_IN
TC
TRANSFORMER
13
DISPLAY
AP1
CN1
CN2
DISP2
DISP1
M2
M1
PE PE
L1
L1
I
II
L-OUT
ELECTRIC BOX
EVAPORATOR
XT1
W4BU
W3BN
N(1)
OUTDOOR UNIT
2 3
COM-OUT
W1YEGN
W2YEGN
N
W5BK
L
N
BU
YEGN
BN
BN
BU
YEGN
BK
POWER
12
. P
XT
3 2
PE
0
RT1
0
RT2
RT3
0
L
COMP.
PE PE
AP1
AP2
L1
L1
PE
M
TEM.SENSOR
TUBE
OUTROOM TEM.SENSOR
EXHUAST
TEM.SENSOR
YEGN
W9
YEGN
YEGN
YEGN
YEGN
FAN MOTOR
COMP
BU
YE
RD
YEGN
CT1,2
RD
BN
BU
BU
BN
BN
BN BU
BU YE
RD
BN
BK
BU
BU
BN BK
BU
W3
W2 W1
W24
W20
W19
W16
W17
W18
W13
W14
W15
W22
PE
W10 W11
W8
W23
W5 W6
W12
W21
L2
ELECTRIC BOX
MID.ISOLATION SHEET
AC-L5
AC-L4
AC-L
AC-N
COMU AC-N3
U V W
OFAN
OVC-COMP
AC-N2
AC-N1
AC-L3
AC-L2
LX1-2
LX1-1
CN2
E
AC-L
N
AC-L1
N1
PE
R(W)
S(U)
C(V)
E
N(1)
I N D O
O R
U N
I
T
4V
4V
Outdoor Unit
13
1 2 3
4 5 6
7
8 9
10
11
12
14
11 10 9 8
7 6
13
12
14
5
4
32
1
15
1
7
8
4
3
5
6
11
13
12
16
17
18
10
14
9
15
2
2
8
9
10
3
4
11
12
7
6
13
14
5
1
ON/OFF
Press it to start or stop operation.
MODE
Press it to select operation mode (AUTO/COOL/DRY/FAN/HEAT).
+
Press it to increase temperature setting.
-
Press it to decrease temperature setting.
FAN
Press it to set fan speed.
Press it to set swing angle.
TIMER ON
Press it to set auto-on timer.
TIMER OFF
Press it to set auto-off timer.
CLOCK
Press it to set clock.
X-FAN X-FAN is the alternative expression of BLOW for the purpose
of understanding.)
TEMP TURBO SLEEP LIGHT
Press it to turn on/off the light.
171518 19
16
20
21
23
24
22
25
MODE icon:
If MODE button is pressed, current operation mode icon (AUTO), ( COOL), (DRY), (FAN) or (HEAT is only for heat pump models) will show.
SLEEP icon :
is displayed by pressing the SLEEP button. Press this button again to clear the display.
TEMP icon:
Pressing TEMP button, (set temperature), (indoor ambient temperature), (outdoor ambient temperature) and blank is displayed circularly.
Up & down swing icon:
is displayed when pressing the up & down swing button. Press this button again to clear the display.
16
20
21
22
23
24
25
1
2
3
4
5
6
19
LIGHT icon:
is displayed by pressing the LIGHT button.Press LIGHT button again to clear the display.
LOCK icon:
is displayed by pressing "+" and “-” buttons simultaneously.Press them again to clear the display.
SET TIME display:
After pressing TIMER button, ON or OFF will blink.This area will show the set time.
TURBO icon:
is displayed when pressing theTURBO button.Press this button again to clear the display.
DIGITAL display:
This area will show the set temperature. In SAVE mode,"SE" will be displayed. During defrosting operation, “H1” will be displayed.
X-FAN icon:
is displayed when pressing the X-FAN button. Press this button again to clear the display.
FAN SPEED display:
Press FAN button to select the desired fan speed setting(AUTO Low-Med-High).Your selection will be displayed in the LCD windows, except the AUTO fan speed.
ON/OFF:
Press this button to turn on the unit. Press this button again to turn off the unit.
MODE:
Each time you press this button,a mode is selected in a sequence that goes from AUTO, COOL,DRY, FAN, and HEAT *, as the following:
*Note: Only for models with heating function. After energization, AUTO mode is defaulted. In AUTO mode, the set temperature will not be displayed on the LCD, and the unit will automatically select the suitable operation mode in accordance with the room temperature to make indoor room comfortable.
+ :
Press this button to increase set temperature. Hold it down for above 2 seconds to rapidly increase set temperature. In AUTO mode, set temperature is not adjustable.
-:
Press this button to decrease set temperature. Hold it down for above . 2 seconds to rapidly decrease set temperature. In AUTO mode, set temperature is not adjustable.
FAN :
This button is used for setting fan speed in the sequence that goes from AUTO, , , to then back to Auto.
Press this button to set up & down swing angle, which circularly changes as below:
This remote controller is universal. If any command , or is sent out, the unit will carry out the command as indicates the guide louver swings as:
AUTO
COOL DRY FAN HEAT*AUTO
Low speed Medium speed High speed
OFF
17
8
9
10
11
12
13
14
15
16
7
TIMER ON:
Press this button to initiate the auto-ON timer. To cancel the auto-timer program, simply press this button again. After pressing this button, disappears and "ON" blinks . 0 0:00 is displayed for ON time setting. Within 5 seconds, press + or - button to adjust the time value. Every press of either button changes the time setting by 1 minute. Holding down either button rapidly changes the time setting by 1 minute and then 10 minutes. Within 5 seconds after setting, press TIMER ON button to confirm.
TIMER OFF:
Press this button to initiate the auto-off timer. To cancel the auto-timer program, simply press the button again.TIMER OFF setting is the same as TIMER ON.
CLOCK :
Pressing CLOCK button, blinks. Within 5 seconds, pressing + or - button adjusts the present time. Holding down either button above 2 seconds increases or decreases the time by 1 minute every 0.5 second and then by 10 minutes every 0.5 second. During blinking after setting, press CLOCK button again to confirm the setting, and then will be constantly displayed.
X-FAN:
Pressing X -FAN button in COOL or DRY mode,the icon is displayed and the indoor fan will continue operation for 10 minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.
TEMP:
Press this button, could select displaying the indoor setting temperature or indoor ambient temperature.When the indoor unit firstly power on it will display the setting temperature, if the temperature's displaying status is changed from other status to" ",displays the ambient temperature, 5s later or within 5s, it receives other remote control signal that will return to display the setting tempera­ture. if the users haven't set up the temperature displaying status,that will display the setting temperature.
TURBO:
Press this button to activate / deactivate the Turbo function which enables the unit to reach the preset temperature in the shortest time. In COOL mode, the unit will blow strong cooling air at super high fan speed. In HEAT mode, the unit will blow strong heating air at super high fan speed.
SLEEP:
Press this button to go into the SLEEP operation mode. Press it again to cancel this function. This function is available in COOL, HEAT (Only for models with heating function) or DRY mode to maintain the most comfortable temperature for you.
LIGHT:
Press LIGHT button to turn on the display's light and press this button again to turn off the display's light. If the light is turned on , is displayed. If the light is tunrned off, disappears. Combination of "+" and "-" buttons: About lock Press "+ " and "-" buttons simultaneously to lock or unlock the keypad. If the remote controller is locked, is displayed. In this case, pressing any button, blinks three times. Combination of "MODE" and "-" buttons:About switch between Fahrenheit and Centigrade At unit OFF, press "MODE" and "- " buttons simultaneously to switch between
and .
Replacement of Batteries
1.Remove the battery cover plate from the rear of the remote controller. (As shown in the figure)
2.Take out the old batteries.
3.Insert two new AAA1.5V dry batteries, and pay attention to the polarity.
4. Reinstall the battery cover plate.
Notes:
●When replacing the batteries, do not use old or different types of batteries. Otherwise, it may cause malfunction.
●If the remote controller will not be used for a long time,
please remove batteries to prevent batteries from leaking.
●The operation should be performed in its receiving range.
●It should be kept 1m away from the TV set or stereo sound sets.
●If the remote controller does not operate normally, please take the
batteries out and reinsert them after 30 seconds. If it still can't operate properly, replace the batteries.
Sketch map for replacing batteries
18
Start cooling
Stop cooling
Compresso
r
Original working state
Run
Stop
Outdoor fan
Indoor fan
T
preset
T
amb.
6 minutes 6 minutes3 minutes
T
preset
-3
Preset wind speed
When T indoor amb. =Tpreset-2 , after compressor operates at the frequency which is lower than 15Hz for continuous 15 minutes, if Tindoor amb.=Tpreset -2
still, compressor stops operation.
When Tindoor amb.
Tpreset-3 , compressor stops operation and outdoor fan stops operation in 30s later. Indoor fan operates at set speed. When Tpreset-2
Tindoor amb. Tpreset, the previous operation status will be maintained.
19
(4)-10 . Toutdoor amb. -5 , Toutdoor pipe-Tcompensation Toutdoor amb.-3 (5)Toutdoor amb. -10 , Toutdoorpipe-Tcompensation Toutdoor amb.-3 (After energization, for the first defrosting, Tcompensation=0 ; if it is not first defrosting, Tcompensation is determined by Toutdoor pipe of last time of quitting defrosting; a. when Toutdoor pipe
2 , Tcompensation=0 ; b. when Toutdoor pipe 2 , Tcompensation=3
20
21
A
L
B C
D
O(0
)
O(0 )
L1 A1 B1 C1
D1
heating angle
cooling angle
22
23
24
25
Space to the wall
Space to the ceiling
Space to the wall
Space to the wall
Air outlet side
Space to the floor
Above
Above
15cm Above
15cm Above
30cm Above
50cm Above
50cm Above
30cm Above
200cm Above
Above
Space to the obstruction
Air outlet side
Space to the wall
Air inlet side
The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures
15cm
250 cm
300cm
26
Indoor
Outdoor
Wall pipe
Seal pad
bulge
distortion
outlet pipe of indoor unit
insulating tube
connected
insulating tube
drain hose
outlet pipe of indoor unit
drain hose
outlet pipe of indoor unit
outlet pipe of indoor unit
rubber belt
rubber belt
rubber belt
Flooded
Fig.2
Wiring Cover
outdoor unit connection
yellowgreen
brown
N(1)
black
2 3
blue
09K UNIT:
12K UNIT:
Wall
Wall
Wall
Above
150 from
the wall
Above 150 from the wall
Wall
Wall
Wall
Above
150 from
the wall
Above 150 from the wall
Φ55
Φ55
RightLeft
RightLeft
Φ55
Φ55
Above 150 from the ceiling
Above 150 from the ceiling
27
Fig.5
Mounting plate
Fixing hook
Mounting plate
Right
Right rear
Fig.4
Left rear
Left
Fig.3
Tailing 1
Tailing 2
Finally wrap it with tape
Gas side piping insulation
Water drainage pipe
Liquid side
Piping insulation
Gas side pipe
External connection
electric wire Liquid side piping
Spanner
Torque wrench
Piping
Taper nut
Indoor unit piping
Black
Blue
Yellow-green
signal control wire
N(1) 2 3
Brown
Handle
28
Fig.6
Manifold Valve
Multimeter
-76cmHg
Lo Handle
Charging hose
Manometer
Hi handle
Vacuum pump
Low pressure valve
Drain-water hole
Bottom frame
Hose (available commercially, inner dia. 16mm)
Drain connecter
29
Fig. a
filter
Air filter
Fig. b
Fig. c
Healthy
30
40
43
42
41
39
15 14
13
12
16
17
18
19
20
21
22
23
24
38
37
36
35
34
33
32
31
30
29
28
27
11
10
9
8
7
6
5
4
3
2
26
1
25
C1VI - 09
31
C1VI - 09
32
36
33
34
37
21
15
14
13
12
16
41
17
18
19
20
23
24
25
26
27
28
29
30
31
32
38
39
40
11
10
9
8
7
6
4
5
3
1
35
22
2
C1VI - 12
33
C1VI - 12
34
1
2
3
4
5
7
8
9
10 11
13
14
15 16
17
18
192021
22
6
12
C1VO - 09
35
8.2 Outdoor Unit
C1VO - 09
36
1
2
3
4
5
7
8
9
10
11
12
13
14
15 16
17
18
192021
22
23
24
6
C1VO - 12
37
C1V0 - 12
38
The remote controller does not receive signals (after it is powered, the buzzer will sound, unless it has malfunction)
Trip of breaker or blow of fuse
Air conditioner can not
start up
Measure insulation resistance to ground to see if there is any leakage.
The circuit or the part of the air conditioner has malfunction. They heat and break the insula­tion and lead to short circuit or creepage. Measure the insula­tion resistance or eliminate the malfunction one by one. If the breaker itself has malfunction, then replace the breaker.
The transformer connection is loose or has bad contact or the transformer has malfunction.
Fasten the wiring; measure the output voltage of the trans­former , if it is incorrect, change the transformer.
No power
Check power supply circuit.
Power plug is not well plugged in and poor connection.
Check if the plug is properly plugged in and make the loose contact firm.
Fuse of controller burnt out
The air condi­tioner does not react after it is powered ( after the plug is inserted, the buzzer does not sound and the remote startup has no response)
Remote controller malfunction
Receiver loose or poor connection
Receiver is broken
Change controller fuse
Controller is broken
Check remote controller
Remote controller is short of power
Change batteries
First, press the manual switch button AUTO,if there is no response,check based on the above methods. If it runs nor­mally after pressing the button, check again whether the instal­lation position and the connec­tion wire of the reception head is correct. If it is correct,then re­place the receiver or the remote controller.
Power voltage is too low
Check the voltage. If it is lower than 10% of the rated voltage, check the cause, improve the power supply condition and add the sta­bilized voltage power supply.
The breaker trips at once when it is set to “ON”.
The breaker trips in few minutes when it is set to “ON”.
39
Improper set of temperature
Adjust set temperature
If cooling (heating) load is proper
Check the forecasted load of cooling (heating)
The refrigerant has leakage or is insufficient
Check and fill the leakage, then vacuumize it and supplement the re­frigerant as required
Leakage between the high pres­sure and the low pressure in­side the compressor
Replace the compressor
Malfunction of four-way valve Replace the four-way valve
Local block of capillary Replace the capillary
Blockage of cooling system
Judge whether the system is blocked by observing the condensation of evapora­tor and the pressure value of
the high pressure manometer and take measures to deal with the system.
Malfunction of refrige r an t flow
Heat insulation for the connection pipes of the indoor unit and the out­door unit is bad.
Make sure that heat insulation for the thick and thin pipes is good. Heat insulation must also be provided for the joint andthe exposed part of the copper pipe .
Block of outdoor heat ex­changer
Clean the dust accumulated on the surface of the heat exchanger.
Air filter were blocked
Clean the filter
Fan speed was set too slow
To set the fan speed to high or middle speed
Air circulation is insufficient
Fan rotation speed becomes low
Capacitor damage
Motor damage
Replace the capaci­tor
Replace the motor
The installation position of the outdoor unit is not appropriate.
Good ventilation must be provided for the installation position of the outdoor unit.
The outdoor temperature is too high.
Properly install the rainproof plate or the sunproof plate. If the maximum cool air still can not meet the requirement, it is sug­gested to replace the air conditioner.
Keep certain air tightness indoors, try not to use electricalappliance with large quantity of heat
The air tightness is not enough. People come in and out too frequently. There are heating devices indoors.
Poor COOL(HEAT) operation
40
The indoor fan motor is burned or breaks or has the heat protector malfunction.
Replace the fan motor or the defective part.
Wrong connection
Make the correction connection based on the circuit drawing.
The fan capacitor has open circuit or is damaged.
The fan does not run when it is set to supply air.
Replace the fan capacitor of the same type and same specification.
The outdoor fan motor is damaged.
Replace the fan motor
Wrong connection
Make the correct connection based on the circuit drawing
The outdoor fan capacitor is damaged.
Replace the fan capacitor
Malfunction of compressor
Replace the compressor
Breakage of running capacitor of compressor
Replace the capacitor
The voltage is too low or too high.
Manostat is recommended.
Wrong wir
e connection
Connect the circuit diagram correctly
The built-in heat protector of the motor breaks frequently because the motor is abnormal.
Replace the fan motor
Adjust the volume of the refrigerant
The refrigerant is not enough or is too much.
Replace the capillary
The capillary is blocked and the tem­perature rises.
The compressor does not run smoothly or is stuck. The air discharge valve is damaged
Replace the compressor
The protector itself has malfunction. Replace the protector
The compres­sor is too hot and leads to the action of the protector.
The protector itself has malfunction.
Use the multimeter to check whether the contact of the compressor is on when it is not overheated. If it is not on, then replace the protector
In the cooling and heating mode, the compressor runs, but the out­door fan does not run.
In the cooling and heating mode, the outdoor fan runs, but the compressor
does not run.
41
Adjust fan location
Fan of indoor unit contacts other parts
Foreign object in indoor unit
Take out the foreign object
Adjust support washer of compressor, and tighten loosen screws
Touch of pipeline of outdoor unit Separate the touching pipeline.
Abnormal sound and shake
Touch of inner plates
1. Tighten connect screw.
2. Stick absorbing clay between plates.
Louver of outdoor unit touched outer case.
Adjust location of louver.
Abnormal sound inside compressor
Change compressor
Drainage pipe blocked or broken Change drainage pipe
Re-wrap and make it tight.
Wrap of refrigerant pipe joint is not close enough.
Water leakage
Change controller
Wire loose or wrong connection
In cool, heat mode, the outdoor unit and compres­sor will not run.
Correctly wire according to the drawing
Improper setting of temperature
Adjust setting temp.
Controller malfunction (IC2003 broken, creepage of parallel capaci­tor of relay loop, relay is broken etc.)
First, check whether the connection is wrong. If no, replace the parts
The swing fan does not run.
The torque of the swing motor is not enough
Wrong connection
The controller is damaged(IC2003 is damaged, the swing relay can not close, etc)
Compressor shakes too much
42
43
44
45
Simply
N
Y
N
Y
N
Y
N
Y
N
Y
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the voltage on the two ends of electrolytic
capacitor
Voltage higher than 200V?
Fault with the voltage
testing circuit on
control panel AP1
Replace the control
panel AP1
Measure the AC voltage between terminal
L and N on wiring board
XT(power supply)
Voltage within 210VAC~250VAC?
Shut down the power and repair the power supply to restore the range 210VAC~250VAC
power on and restart the unit
If the fault is eliminated?
Shut down the power and wait 20 mi
nutes;
or use DC voltmeter to measure the voltage on the two ends of capacitor , until the voltage is lower than 20V
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
reactor L
is normal?
Connect the reactor Laccording to Elec­trical Wiring Diagr­am correctly
Re-energize and turn on the unit
If the fault is eliminated?
End
Replace the control
panel AP1
46
Energize and
switch on
IPM protection
occurs after the machine has run for a
p
eriod of time?
Use AC voltmeter to measure the voltage between terminal L and N on the wiring board XT)
If the voltage between terminal L and N on wiring board XT is within 210VAC~250VAC?
Check the supply voltage and restore it to
210VAC~250VAC
Voltage between
the two ends of celectrolytic
capacitor is
Restart the unit. Before protection occurs, use DC voltmeter to
measure the voltage
between the two
ends of electrolytic
capacitor on control
panel AP1
If the unit can
work
normally?
Please confirm:
1. If the indoor and outdoor heat exchangers are dirty? If they are
obstructed by other
objects which affect
the heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting in that the system
pressure is too high
and exceeds the
permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system pressure is too high?
5. Other conditions resulting in that the system pressure becomes too high.
The connection
of capacitor C2
is loose.
Reconnect the capacitor C2 according to Electrical Wiring Diagram. Then, Restart the unit.
Stop the unit and disconnect the power supply. Wait 20 minutes, or use DC voltmeter to measure the voltage
between the two ends of
capacitor C2, until the
voltage is lower than 20V
Replace the capacitor C2. Then, energize and start the unit.
Replace the
control panel AP1
Take corrective actions according to Technical Service Manual, and
then energize and start
the unit.
If there is any
abnormality
described above?
Replace the
control panel AP1
If the connection between AP1 and COMP is unsecure or the connection order is wrong?
Connect the control panel
A
P1 and compressor COMP correctly according to the Electrical Wiring Diagram. Then, energize and start the unit.
Use ohmmeter to measure the resistance between the three terminals on compressor COMP, and compare the measurements with the
compressor resistance on
Service Manual.
If the
resistance is
normal?
Use ohmmeter to measure the resistance between the two
terminals of compressor
COMP and copper tube.
Replace the compressor
COMP
Resistance higher
than 500MΩ?
Replace the
control panel
AP1
END
Y N
Y
N
Y
If the unit can
work normallv?
Y
If the unit can
work normally?
Y
N
Y
N
If the unit can
work normally?
Y
Y
N
N
If the unit can
work
normally?
Y
Y
N
N
N
Y
higher than 250V
Remove the wires on the two ends of capacitor C2. Then, use capacitance meter to measure the capacitor C2. Verify as per the Parameters Sheet.
Stop the unit and disconnect the power supply. Then, check the connection of capacitor C2 according to Electrical Wiring Diagram.
If capacitor C2 is failed?
Refer to the Electrical Wiring Diagram and check if the connection between AP1 and COMP is loose and if the connection order is correct.
47
End
Y
N
Y
N
Y
N
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
Normal protection, please operate it after the outdoor ambient temp­erature is normalized.
Improve the heat dissipation environ­ment of the unit
Does the outdoor fan work normally?
1. Check if the fan terminal OFAN is connected correctly
2. Resistance between any two terminals is measure by an ohm gauge and should be less than 1K Ohm.
Replace the control panel
AP1
Replace the fan
capacitor C1
Replace the outdoor fan
48
Y
N
Y
N
N
Y
Y
N
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Restart it up after 3 minutes
Does startup fail?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Connect the wires as per the connection diagram
Replace the control panel AP1
If the fault is eliminated?
Replace the
compressor
End
49
Out of step occurs once the
unit is powered on.
Is stop time of the
compressor longer than
3 minutes?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
direction?
Connect the
wires correctly
Replace the control
panel AP1
If the fault is eliminated?
Replace the compressor
End
Out of step occurs in
operation
Is the outdoor fan working
normally?
Is the outdoor unit blocked
by foreign objects?
Replace the
control panel AP1
If the fault is eliminated?
Replace the compressor
End
Check if the fan terminal
OFAN is connected correctly
Remove foreign objects
Replace the fan
capacitor C1
Replace the outdoor fan
50
20 minutes after the
complete unit is
powered off
Is the terminal FA for the
electronic expansion valve
connected correctly?
Connect the
wires correctly
Resistances between the first four pins close to the terminal hole and the fifth pin are almost the same, less than 100 ohm.
Replace the electronic
expansion valve
If the fault is eliminated?
If the fault is eliminated?
Replace the
control panel
AP1
Coolant leakage, refilling
the coolant
End
51
Y
Y
N
N
N
N
N
N
Y
Y
Y
Start
Check wiring of the reactor (L) of the outdoor unit and the PFC capacitor
Whether there is any
damage or
short-circuit?
Replace it as per the
wiring diagram and
reconnect the wires
If the fault is eliminated?
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
The capacitor is
short circuited and
the capacitor should be repla­ced
Restart the unit
If the fault is eliminated?
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the reactor by an ohm gauge
Whether there is any damage
or short-circuit?
Replace the reactor
Restart the unit
If the fault is eliminated?
Replace the control
panel AP1
End
Y
52
Y
N
Y
N
N
Y
N
N
Y
N
Y
N
Y
Y
Start
Did the equipment operate
normally before the failure
occurs?
The AP1 voltage detection circuit is at fault
Check wiring inside of the indoor and outdoor
units
Are wires broken?
Check the communication
circuit of the outdoor unit
If the fault is eliminated?
The communication
circuit is abnormal
Replace the main board of
the indoor unit
End
If the fault is eliminated?
Replace the main board
AP1 of the outdoor unit
If the fault is eliminated?
Is the connection right?
Check the wiring of the indoor and outdoor units with reference to the
wiring diagram
Correctly connect the
corresponding wires for
the indoor and outdoor units with reference to
the wiring diagram
53
54
Y
Y
Y
Y
Y
N
N
N
N
Start
Measure voltage at the
Test 10 position as
shown in the diagram
with a voltmeter
Value jumping
Measure voltage at the
Test 15 position as
shown in the diagram
with a voltmeter
Value jumping
Measure voltage at the
Test 11 position as
shown in the diagram
with a voltmeter
Value jumping
Measure voltage at the
Test 12 position as
shown in the diagram
with a voltmeter
Value jumping
The communication
circuit of the outdoor
unit is normal
End
Fault with
outdoor unit
55
56
57
58
59
60
61
2
Handle
2. Remove top cover
1.Remove big handle
Top panel
1 Before disassembly.
Remove the connection screw fixing the big handle and then remove the handle.
Remove connection screws connecting the top cover plate with the front panel and the right side plate, and then remove the top panel.
62
3.Remove grille and front panel
4.Remove axial flow blade
5.Remove right side plate
Remove connection screws between the front grille and the front panel. Then remove the front grille. Remove connection screws connecting the front panel with the chassis and the motor support, and then remove the front panel.
Remove the nut fixing the blade and then remove the axial flow blade.
Remove connection screws connecting the right side plate with the valve support and the electric box. Then remove the right side plate.
Grille
Panel
Axial flow blade
Right side plate
63
Remove the 2 screws fixing the cover of elec­tric box. Lift to remove the cover. Loosen the wire and disconnect the terminal. Lift to re­move the electric box assy.
6.Remove electric box assy
Electric box assy
Unscrew the fastening nut of the 4-way Valve Assy coil and remove the coil. Wrap the 4­way Valve Assy with wet cotton and unsolder the 4 weld spots connecting the 4-way Valve Assy to take it out.(Note: Refrigerant should be discharged firstly.) Welding process should be as quickly as possible and keep wrapping cotton wet all the time. Be sure not to burn out the lead-out wire of compressor.
7.Remove 4-way valve assy
8.Remove capillary sub-assy
Unsolder weld point of capillary Sub-assy, valve and outlet pipe of condensator. Then remove the capillary Sub-assy. Do not block the capillary when unsoldering it. (Note: be­fore unsoldering,discharg
e refrigerants
completely)
4-way Valve Assy
Capillary Sub-assy
64
Remove the 4 tapping screws fixing the motor. Pull out the lead-out wire and remove the motor. Remove the 2 tapping screws fixing the motor support. Lift motor support to re­move it.
9.Remove motor and motor support
Motor
Motor support
10.Remove clapboard sub-assy
Loosen the screws of the Clapboard Sub-Assy . The Clapboard Sub-Assy has a hook on the lower side. Lift and pull the Clapboard Sub-Assy to remove.
Clapboard Sub-Assy
65
11.Remove Compressor
1 Remove the 2 screws fixing the gas valve.
Unsolder the welding spot connecting gas valve and air return pipe and remove the gas valve. (Note: it is necessary to warp the gas valve when unsoldering the welding spot.) Remove the 2 screws fixing liquid valve. Unsolder the weld­ing spot connecting liquid valve and remove the liquid valve.
2 Remove the 3 footing screws of the compressor
and remove the compressor.
Compressor
Gas valve
Liquid valve
66
Loading...