s the structure feature of split unit, concerning the comfort, in heating mode, when compressor stops, the indoor ambient
temperature is higher than preset temperature for 3 .
2. Check parameters to effectively make judgment and control
Insert the outdoor discharge temp sensor into corresponding temp sensor jacket of discharge pipe in order to protect safe and
reliable operation of the unit, so that the control system can accurately detect the discharge temp as well as effectively control
and protect it. Otherwise, the unit will stop and display the trouble of “outdoor discharge temp sensor failure ( not be inserted
correctly)” which can be recovered by pressing ON/OFF button.
3. Cooling Mode
3.1 Conditions and processes of cooling operation:
3.1.1 If the compressor stops, and [Tpreset – (Tindoor ambient – ΔTcooling indoor ambient temperature compensation)] ≤0.5 ,
start up the unit for cooling operation;
3.1.2 During cooling operation, if 0
≤ [Tpreset – (Tindoor ambient –ΔTcooling indoor ambient temperature compensation)]< 2 ,
keep the cooling operation;
3.1.3 During cooling operation, if 2
≤ [Tpreset – (Tindoor ambient –ΔTcooling indoor ambient temperature compensation)], the
cooling operation will stop after reaching to the setting temperature.
3.2 Temperature setting range
3.2.1 If Toutdoor ambient ≥ [Tlow-temperature cooling], the temperature can be set at: 16~30
(Cooling at roomemperature);
3.2.2 If Toutdoor ambient < [Tlow-temperature cooling], the temperature can be set at: 25~30
(Cooling at low temperature),
that is, the minimum setting temperature to be judged by outdoor unit is 25
.
4. Dry Mode
4.1 Conditions and processes of dry operation: same as the cooling mode;
4.2 The temperature setting range is: 16~30
;
5. Fan Mode
5.1 The compressor, outdoor fan and four-way valve are switched off;
5.2 The temperature setting range is: 16~30
.
6. Heating Mode
6.1. Conditions and processes of heating operation: (Tindoor ambient is the actual detection temperature of indoor
environment temp sensor, ΔTheating indoor ambient temperature compensation is the indoor ambient temperature compensation
during heating operation)
6.1.1 If the compressor stops, and [(Tindoor ambient –ΔTheating indoor ambient temperature compensation) –Tpreset]≤ 0.5
,
start the unit to enter into heating operation;
6.1.2 During heating operation, if 0
≤ [(Tindoor ambient –ΔTheating indoor ambient temperature compensation)–Tpreset] < 2 ,
keep the heating operation;
6.1.3 During heating operation, if 2
≤ [(Tindoor ambient –ΔTheating indoor ambient temperature compensation)–Tpreset], the
heating operation will stop after reaching the setting temperature.
6.2 The temperature setting range in this mode is: 16~30
.
7. Defrosting Control (heating)
7.1 After the time for defrosting is judged to be satisfied, if the temperature for defrosting is satisfied for continuous 3minutes, the
defrosting operation will start.
7.2 Start defrosting: Compressor stops and starts up 55S later;
7.3 Finish of Defrosting: Compressor stops and starts up 55S later;
7.4 The defrosting operation can exit when any of the conditions below is satisfied:
7.4.1 Toutdoor pipe≥ 12
;
7.4.2 Toutdoor ambient
-5 , and the Toutdoor pipe≥ 6 last more than 80S;
7.4.3The continuous running time of defrosting reaches.
8. Compressor Control
8.1. The frequency of compressor will be controlled according to the relationship of ambient temperature and preset temperature
as well as changing speed of ambient temperature;
8.2 Start the compressor after starting cooling, heating, dry operation, and the outdoor fan for 5s;
8.3 When the unit is off, in safety stops and switching to fan mode, the compressor will stop immediately;
8.4 In all modes: once the compressor starts up, it will not be allowed to stop within 7 min. (Note: except the cases that require
stop of the compressor such as fault protection, remote shutdown, mode switching etc.);
6.2.2 Functions of Outdoor Unit