Intra Automation ITA-T1S Technical Information

Page 1
THE EXPERT IN LEVEL AND FLOW
LEVEL
Magnetic Level Sensing
Transmitter
Type: ITA-T1S
02/2011
Page 2
ITA-T1S Technical Information Intra-Automation
- 1 -
Intra-Automation
Technical Information
02/2011
Technical details subject to be changed
Please send your comments regarding this brochure to:
info@intra-automation.de
Page 3
Intra-Automation GmbH Technical Information ITA-T1S
- 2 -
ITA-T1S
Magnetic Level Sensing
Transmitter
List of contents: Chapt. Description Page
1 Characteristics 2 Functional Principle 3 Indicator 4 Interface Measurement 5 Techncal Data 6 Float Types 7 Transmitter 8 Order Code
Page 4
ITA-T1S Technical Information Intra-Automation
- 3 -
1 Characteristics
Simple and rugged construction
Applicable for liquids with density   0,5 kg/dm³
Measuring length 300 up to 6000 mm (11,8 up to 236“)
Applicable for small storage reservoir
Pressure rating up to PN40 (300 lbs)
Temperature range up to 130 °C (166 °F)
Material of transmitter housing: Aluminium or stainless steel
Protection class: IP65 NEMA 4X)
Different sensor-tube materials available
Sensor tube available in Plastic material
Current output: 4…20 mA (optional: HART)
2 Functional Principle
The level sensing transmitter type ITA-T1S will be installed vertically on the top of a tank. Different types of tank-connections are available (see order code). The electrical connection between level sensor and transmitter is done on factory side (3-wire).
A float follows directly the changes of liquid level and moves along the guide tube. Inside the float a permanent magnet system is installed. This magnetic field operates directly to the reed switches inside the sensor tube. While the reed-switches are activated the result will be a change in the resistance load which corresponds directly to the level.
The transmitter (f.e. type INT5333 or TMT182) allocates to the actual level a current output between 4 and 20 mA.
If required on customer side the movement of the float can be reduced by using adjustable float stops.
3 Indicator
Measured values can be displayed directly on site by the optionally available LCD digital 4 ½ digit indicator. The indicator is freely configurable by means of a DIP-switch. Values in between 0 and 19999 can be indicated. When supplied, the device has been configured to the clients’ requests. If no requests have been received, the configuration is 0-100 %.
For indication of the measured value the DigiFlow 520 can be connected directly to the sensor type ITA-T1S. The DigiFlow 520 shows the actual value in most of all engineering units (see fig. 3). Linearization of various tank shapes can be done in the indicator.
fig. 2 Digital indicator (at site)
Abb. 1 Schematische Darstellung zur Anordnung der Reedkontakte
fig. 3 DigiFlow 520
Page 5
Intra-Automation GmbH Technical Information ITA-T1S
- 4 -
4 Interface Measurement
The level measurement of liquids with different densities in one tank – interface measurement- is a big problem for a lot of competitors. In this case it is important to measure the level of two liquids in one tank (see fig. 4). This function will be solved while using the ITA-T1S. Depending on the difference of density the float will be designed to measure the interface.
5 Technical Data
Level sensing transmitter : ITA-T1S Measuring range : 0,3…6 m Resolution :
5, 10 or 20 mm
Ambient temperature Aluminium electronic housing
: -20…+40 °C (-4…+104 °F)
Stainless steel elec. housing
: -20…+40 ° C (-4…+104 °F) Pysical data of liquid Temperature
: -10…+100 °C (14…212 °F Density
: min. 0,5 kg/dm³ Pressure
: max. PN40 (300 lbs) Prot. class DIN 40050 / IEC 144 : IP65 (NEMA 4X) Cables : Cable glands Aluminium housing
: M20x1,5 (optional ½“ NPT) Stainless steel housing
: M20x1,5 (optional ½“ NPT) EExd-housing
: ½“ NPT-F Current output : 4..20 mA (optional HART) Threaded tank connection : R ½“ or ½“ NPT-M Flanged tank connection : DN50, DN100 / PN16 & PN50 or 2“, 4“ / 150 & 300 lbs RF
Materials Transmitter housing
: Aluminium Special housing
: Stainless steel EExd-housing
: Aluminium/epoxy coated Housing for digital LCD-indicator
: Aluminium Flange
: CS, SS (Option ECTFE-coating) PP, PVC, PVDF Thread
: SS Sensor tube
: CS, SS (Option ECTFE-coating) PP, PVC, PVDF Float
: See „Float Types“
fig. 4 Typical Application
Page 6
ITA-T1S Technical Information Intra-Automation
- 5 -
Optional Digital Indicator Display
: 4 ½ digits
Power supply
: 2,9 VDC (Two-wire-version)
Current input
: +3,8…+20,4 mA
Load
:
190
Counter-Resolution
: 19,999
Frequency
: 2,5 readings per second
Precision
:
0,01 % (of span) + 2 counts
Temperature drift
:
max. 0,6 counts/°C
Operational temperature
: 0…+50°C
Rel. humidity
: max. 95 %
6 Float types
Type
1)
Form Dimensions
[mm]
Material Min.
Density
[kg/dm³]
Max. Op. Pressure
[bar @ 20°C]
Max. Medium
temperatur
[°C]
A Spherical
52
1.4571 316Ti
0,7 40 -40…+100
B Spherical
80
3.7035
Titanium
0,6 17 -40…+100
C Cylinder
80 x 35
1.4571 316Ti
0,5 13 -40…+100
D Cylinder
44 x 52
1.4571 316Ti
0,8 25 -40…+100
E Cylinder
50 x 120
PVC 0,55 10 0…+60
F Cylinder
50 x 120
PP 0,5 10 0…+60
Y Spherical
65
Hastelloy 0,7 6 -40…+100
1) other types on request
Type: A, B und Y Type C Type D Type E Type F
7 Transmitter
Type
Current
output
[mA]
Power
supply
[VDC]
Min/Max-values
current output
[mA]
Operating
temperature
[°C (°F)]
Min. and max.
resistance
[]
Approval
T1 4…20 8…35 4…20
-20…+85
(-4…+185)
50
6000
---
T2 4…20 8…28 4…20
-20…+85
(-4…+185)
50
6000
Ex II 1 G EEx ia IIC
T1…T6
T3 4…20 10..30 4…20
-40…+85
(-40…+185)
0…400
0…2000
Ex II 1 G EEx ia IIC
T4…T6
T4
4…20
Hart
13…30
3,8 oder 22 (selectable)
-40 (-40)… +85 (+185) +70 (+158) +55 (+131)
0…400
0…4000
Ex II 1 G EEx ia IIC
T4…T6
Page 7
Intra-Automation GmbH Technical Information ITA-T1S
- 6 -
8 Order Code
Code Description ITA-T1S
Continous Level Sensing Element for vertical tank-mounting
Material Guide tube / Measuring length in mm Material Resolution S10-L____mm
316SS 10 mm
S05-L____mm
316SS 5 mm
S20-L____mm
316SS 20 mm
T10-L____mm
Titanium 10 mm
T05-L____mm
Titanium 5 mm
T20-L____mm
Titanium 20 mm
P10-L____mm
PP 10 mm
P05-L____mm
PP 5 mm
P20-L____mm
PP 20 mm
V10-L____mm
PVC 10 mm
V05-L____mm
PVC 5 mm
V20-L____mm
PVC 20 mm
H10-L____mm
Hastelloy 10 mm
H05-L____mm
Hastelloy 5 mm
H20-L____mm
Hastelloy 20 mm
Tank connection Material Type Dimensions CR01
CS Nipple R ½“
CN01
CS Nipple ½“ NPT
CF11
CS Blind flange DN50 PN16
CF12
CS Blind flange DN100 PN16
CF21
CS Blind flange 2“150# RF
CF22
CS Blind flange 4“ 150# RF
SR01
316SS Nipple R ½“
SN01
316SS Nipple ½“ NPT
SF11
316SS Blind flange DN50 PN16
SF12
316SS Blind flange DN100 PN16
SF21
316SS Blind flange 2“150# RF
SF22
316SS Blind flange 4“ 150# RF
TF11
Titanium Blind flange DN50 PN16
TF12
Titanium Blind flange DN100 PN16
TF21
Titanium Blind flange 2“150# RF
TF22
Titanium Blind flange 4“ 150# RF
PF11
PP Blind flange DN50 PN16
PF12
PP Blind flange DN100 PN16
PF21
PP Blind flange 2“150# RF
PF22
PP Blind flange 4“ 150# RF
VF11
PVC Blind flange DN50 PN16
VF12
PVC Blind flange DN100 PN16
VF21
PVC Blind flange 2“150# RF
VF22
PVC Blind flange 4“ 150# RF
HF11
316SS/Hastelloy-plated Blind flange DN50 PN16
HF12
316SS/Hastelloy-plated Blind flange DN100 PN16
HF21
316SS/Hastelloy-plated Blind flange 2“150# RF
HF22
316SS/Hastelloy-plated Blind flange 4“ 150# RF
9999
others, please specify
(continued on page 7)
Page 8
ITA-T1S Technical Information Intra-Automation
- 7 -
(Continuation)
Float Dimension
[mm]
min. Density
[kg/dm³]
max. Pressure
[bar] Material
A
52 0,70 40 316SS
B
80 0,60 17 Titanium
C
80x35 0,50 13 316SS
D
44x52 0,80 25 316SS
E
50x120 0,50 10 PVC
F
50x120 0,55 10 PP
G
65 0,70 6 Hastelloy
Electronic housing A
Standard, IP65, material: die-cast Aluminium, painted
I**
Incl. digital display, IP66, housing material: die-cast Aluminium
S
Standard, IP65, material: 316SS
E
Flame proof, IP66, material: die-cast Aluminium / epoxy coated
9
others, please specify
Head transmitter M10
Transmitter type: INT5333A
M11
Transmitter type: INT5333A with Exd housing
M12
Transmitter type: INT5333A with stainless steel housing
M20
Transmitter type: INT5333B intrinsically safe
M22
Transmitter type: INT5333B intrinsically safe with stainless steel housing
M30
Transmitter type: INT5335A SMART/HART technology
M31
Transmitter type: INT5335D Ex proof with SMART/HART technology
M32
Transmitter type: INT5335D Ex proof with SMART/HART technology and with stainless steel housing
M40
Transmitter type: INT5350A Profibus PA/FOUNDATION Fieldbus technology
M41
Transmitter type: INT5350A Ex proof with Profibus PA/FOUNDATION Fieldbus technology
M42
Transmitter type: INT5350A Ex proof with Profibus PA/FOUNDATION Fieldbus technology and with stainless steel housing
99
others
ATEX-approval 00
without
Ex*
II 1/2G EEx d IIC T4…T6 / EEx ia IIC T4…T6 *only in combination with electronic housing type „E“ and transmitter type „T2“ to „T4“. ** ATEX-approval EEx d for digital display in preparation!
Order code: ITA-T1S-
-L____mm- - - - -
Page 9
Intra-Automation GmbH Technical Information ITA-T1S
- 8 -
Besides the products covered by this brochure, Intra-Automation GmbH also manufactures other hig h­quality and high precision instruments for industrial measurement tasks. For more information, please contact us (contact details on the backside of this brochure).
Flow measurement
Itabar®-Flow Sensor IntraSonic IS210 Ultrasonic Flow Meter
Level measurement
ITA-mag. Level Gauge MAGLINK Level Indicator
Other Measurement Tasks:
DigiFlow Flow and Level Computers IntraCon Digital Controllers IntraDigit Digital Indicators / Meters
Page 10
ITA-T1S Technical Information Intra-Automation
- 9 -
International Headquarters: Sales Office for the BENELUX:
Intra-Automation GmbH B.V. Intra-Automation HTP Otto-Hahn-Str. 20 PO Box 10 41515 Grevenbroich 4730 AA Oudenbosch GERMANY THE NETHERLANDS
+49 – (0) 21 81 / 7 56 65-0 +31 – (0)165 – 32 22 01 +49 – (0) 21 81 / 6 44 92 +31 – (0)165 – 32 29 70
info@intra-automation.de info@intra-automation.nl
www.intra-automation.com
Loading...