IntesisBox Modbus Server-DALI Installation Manual

IntesisBox
®
Modbus Server – DALI
Installation Manual
2
The information in this document may change without previous notice.
Doc. Rev.0
URL
email
tel
http://www.intesis.com info@intesis.com +34 938047134
1 / 5
Safety Instructions
WARNING
Installation Instructions
Configuration and Setup
IntesisBox must be installed by accredited electrician or similar technical personnel, following all the safety instructions
given here, and in accordance always with the country legislation for installation of electric equipment.
IntesisBox can not be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust.  IntesisBox must only be installed in a restricted access location.  In case of wall mount, fix firmly IntesisBox on a not vibrating surface following the instructions below.  In case of DIN rail mount fix IntesisBox properly to the DIN rail following the instructions below.  Mounting on DIN rail inside a metallic cabinet properly connected to earth is recommended.  Disconnect always power of any wires before manipulating and connecting them to IntesisBox.  Respect always the expected polarity of power and communication cables when connecting them to IntesisBox.  Supply always a correct voltage to power IntesisBox, within voltage range admitted (230Vac +/ -10%).  This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with
static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before touching the unit
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any other equipment connected to it.
Disconnect the mains power and power of any bus or communication cable before connecting it to IntesisBox.  Mount IntesisBox on the wall or DIN rail following the instruction given below, respecting the safety instructions given
above.
Connect the mains power cable to the supply voltage terminal block of IntesisBox.  Circuit-breaker must be used before the mains power cable. Rating 250V-6A  Connect the communication cables to IntesisBox, see details on the user's manual.  Power IntesisBox and the rest of devices connected to it.  After power-on, DALI bus LED (at the left side of DALI connector) should be ON, signalling that there is DALI bus voltage.
If DALI bus LED is OFF, you should check the DALI communication line for a possible short-circuit.
If your DALI installation is already operative, communication at DALI side can be tested by pressing the DALI test button:
Pressing once the button, the ballasts will switch ON (DALI led will start flashing)  Pressing again the button, the ballasts will switch OFF (DALI led will toggle to ON)  Pressing again the button, the ballasts will switch ON, and remain ON until their value is changed from Modbus side
(DALI led will toggle to OFF, signaling that the test has ended).
IntesisBox
®
Modbus Server – DALI
Installation Manual
2
The information in this document may change without previous notice.
Doc. Rev.0
URL
email
tel
http://www.intesis.com info@intesis.com +34 938047134
2 / 5
Wall mounting
DIN rail mounting
Bottom view of the box
Clips in their original position, for DIN-rail mounting
Clips in wall-mount position
Top view of the box
97,5 mm
114 mm
Ø 3 mm
IntesisBox
®
www.intesis.com
23 mm
79 mm
DIN Rail
(EN60715 TH35)
1 2 3
Side view of the box
IntesisBox
®
Modbus Server – DALI
Installation Manual
2
The information in this document may change without previous notice.
Doc. Rev.0
URL
email
tel
http://www.intesis.com info@intesis.com +34 938047134
3 / 5
Connections
DALI Bus
See Note 1
Alimentación
230V ac
PC Console
IntesisBox
®
www.intesis.com
- +
N L
POWER
230VAC 6W
DALI
Modbus RTU
master EIA232
See Note 2
Console Cable 1,8 m. Standard DB9 Female ­DB9 Male. Supplied with IntesisBox
LinkBoxMB
Only needed for configuration, also it can be done using Ethernet
See Note 3
Modbus RTU
master EIA485
See Note 2
Ethernet Modbus TCP
ModBusTCP master
(and IntesisBox configuration)
See Note 2
- +
Modbus RTU
IntesisBox
®
Modbus Server – DALI
Installation Manual
2
The information in this document may change without previous notice.
Doc. Rev.0
URL
email
tel
http://www.intesis.com info@intesis.com +34 938047134
4 / 5
Technical characteristics
Enclosure
Plastic, type PC (UL 94 V-0). Dimensions: 159mm 105mm x 58mm.
Color
Light Grey / RAL 7035.
Supply Voltage
230Vac +/-10% 6W (3-pole plug-in terminal block – line, neutral and earth)
Terminal wiring (for power supply and low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.5mm2 3 cores: not permitted
Mounting
Wall. DIN rail EN60715 TH35.
DALI bus power source
15Vdc +/-2% 250mA. (DALI bus is powered from IntesisBox)
DALI port
1 x DALI electrically isolated (2-pole plug-in terminal block). SELV
Ethernet port (Modbus TCP, device config)
1 x Ethernet 10Base-T (RJ45). Modbus RTU ports
1 x Serial EIA232 (DB9 male DTE). SELV 1 x Serial EIA485 (Plug-in screw terminal block 2 poles). SELV
LED indicators
1 x Power indicator. 2 x DALI activity (Tx, Rx). 2 x Ethernet link & activity (LNK, ACT). 2 x Modbus RTU serial port activity (Tx, Rx). 1 x DALI bus power 1 x DALI test1
Push buttons
1 x DALI test1
Console port
EIA232. DB9 female connector (DCE). SELV
Configuration
Via Ethernet or serial console port.2
Firmware
Allows upgrades via console port.
Operational temperature
0°C to +60°C
Operational humidity
25-90% at 50ºC, non condensing Protection
IP20 (IEC60529).
RoHS conformity
Compliant with RoHS directive (2002/95/CE).
Norms and standards
CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC) EN 61000-6-2 EN 61000-6-3 EN 60950-1 EN 50491-3
IntesisBox
®
Modbus Server – DALI
Installation Manual
2
The information in this document may change without previous notice.
Doc. Rev.0
URL
email
tel
http://www.intesis.com info@intesis.com +34 938047134
5 / 5
Dimensions
AC mains
power
DALI port
159 mm
105 mm
58 mm
Ethernet port
Serial console
port
Modbus RTU EIA232/EIA485
167 mm
130 mm
100 mm