IBOX-MBS-DALI
DALI to Modbus Server Protocol Converter
Order Code: IBMBSDAL0640000
Installation Sheet rev.1.2
Intesis Software S.L.U. © 2018
SAFETY INSTRUCTIONS
! WARNING
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any other equipment connected to it.
IntesisBox must be installed by accredited electrician or similar technical personnel, following all the safety instructions given here and in accordance always with the country legislation for installation of electric equipment.
IntesisBox cannot be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust.
IntesisBox must only be installed in a restricted access location. In case of wall mount, fix firmly IntesisBox on a not vibrating surface
following the instructions next. In case of DIN rail mount fix IntesisBox properly to the DIN rail following
the instructions below. Mounting on DIN rail inside a metallic cabinet properly connected to
earth is recommended. Disconnect always power of any wires before manipulating and
connecting them to IntesisBox. A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rated is to be used. Respect always the expected polarity of power and communication
cables when connecting them to IntesisBox. Supply always a correct voltage to power IntesisBox, see details of
voltage range admitted by the device in the technical characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries according to the instructions. Battery replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without routing to the outside plant, all communication ports are considered for indoor only.
This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with static levels above 4 kV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before touching the unit.
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to IntesisBox.
Disconnect power of any bus or communication cable before connecting it to IntesisBox.
Mount IntesisBox on the wall or DIN rail following the instruction given below, respecting the safety instructions given above.
Connect a NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply to IntesisBox, respect the polarity if DC power or Line and Neutral if AC power. Apply always a voltage within the range admitted by IntesisBox and of enough power (see technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V­6A.
Connect the communication cables to IntesisBox, see details on the user's manual.
Power IntesisBox and the rest of devices connected to it.
Wall Mount
1. Separate the fixing clips in the bottom of the box, pushing them to the outside until hear the "click" which indicates that now the clips are in position for wall mount, see in the figure below.
2. Use the holes of the clips to fix the box in the wall using screws. Use the template below for the wall wholes.
Clips in their original position Clips in position for wall mount
(for DIN rail mount)
DIN Rail Mount
With the clips of the box in their original position, insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail, using a small screwdriver and following the steps in the figure below.
Press
Press
Press
DIN Rail
1 2 3
Owner’s Record
The model and serial numbers are located on the rear of the gateway. Record these numbers in the space provided below. Refer to them whenever you contact upon your gateway dealer or support team regarding this product.
Model No.
Serial No.
CONFIGURATION
Use the Configuration Tool to configure the gateway. See instructions to download and install the latest version at:
http://intesisbox.com/intesis/software/intesisbox_maps_installer.exe
Use the Ethernet connection or the Console Port (mini USB type B connector included) to get communication between the gateway and the configuration tool.
Follow the instructions of the user's manual for more details.
2 / 4
This information is subject to change without prior notice
email: info@intesisbox.com web: www.intesisbox.com phone: +34 938047134
Enclosure
Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 90x88x56 mm Recommended space for installation (dxwxh): 130x100x100mm Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm Capacity: 3V / 225mAh Type: Manganese Dioxide Lithium
Mounting
Wall. DIN rail EN60715 TH35.
Console Port
Mini Type-B USB 2.0 compliant 1500VDC isolation
Terminal Wiring
(for power supply and low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
USB port
Type-A USB 2.0 compliant Only for USB flash storage device (USB pen drive) Power consumption limited to 150mA (HDD connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth 24VDC
Push Button
Button A: Check the user manual Button B: Check the user manual
Operation Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45 2 x Ethernet LED: port link and activity
Operational Humidity
5 to 95%, no condensation
Port A
1 x DALI port (Plug-in screw terminal block orange 2 poles)
1500VDC isolation from other ports DALI power consumption: 240mA Voltage rating: 16VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Protection
IP20 (IEC60529)
LED Indicators
10 x On board LED indicators
2 x Error (red) / Power LED 2 x Ethernet Link / Speed 2 x Port A TX/RX 2 x Port B TX/RX 1 x Button A indicator 1 x Button B indicator
Switch A
(SWA)
1 x DIP-Switch for PORT A configuration:
Reserved for future use
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Modbus RTU 1500VDC isolation from other ports (except PORT B: EIA485)
1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
A, B, SGND (Reference ground or shield) 1500VDC isolation from other ports (except PORT B: EIA485)
Switch B
(SWB)
1 x DIP-Switch for serial EIA485 configuration:
Position 1:
ON: 120 Ω termination active Off: 120 Ω termination inactive
Position 2-3:
ON: Polarization active Off: Polarization inactive
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table below). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the AC power supply to earth, and make sure the same power supply is not supplying any other device.
Ethernet / Modbus TCP / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual for more information). DHCP is enabled by default. When disabled, default IP is 192.168.100.246.
PortA / DALI
Connect the DALI bus to connectors A4 (+), A3 (-) of gateway’s PortA. IntesisBox provides 16VDC (+/­2%) DALI voltage to the bus.
PortB / Modbus RTU
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of gateway’s PortB. Respect the polarity. Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor of 120 . The gateway has an internal bus biasing circuit that incorporates the termination resistor. If you install the gateway in one of the ends of the bus, then do not install an additional termination resistor in that end.
Connect the serial cable EIA232 coming from the external serial device to the EIA232 connector of gateway’s PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used. Details of the pinout can be seen in the user's manual. Respect the maximum distance of 15 meters.
Console Port Connect a mini-type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
Port B
USB
EIA 232
B1 B2 B3
SW B
SW A
Ethernet Port
Port A
A1 A2
A3 A4
Power
Run / Error
Eth.Link/Spd PortA TX/RX
PortB TX/RX
Button A
Button B
Console
- +
www.intesisbox.com
Power Supply
DALI
Ethernet Modbus TCP
USB storage
Modbus RTU EIA232
Modbus RTU EIA485
Console Port
100 mm (h)
100 mm (w)
130 mm (d)