IntesisBox DK-RC-KNX-1i User Manual

IntesisBox
®
DK-RC-KNX-1i v2.0
Issue Date: 25/02/2016
r1.0 eng
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
2 / 66
© Intesis Software S.L. 2016 All Rights Reserved.
Information in this document is subject to change without notice. The software described in this document is furnished under a license agreement or nondisclosure agreement. The software may be used only in accordance with the terms of those agreements. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or any means electronic or mechanical, including photocopying and recording for any purpose other than the purchaser’s personal use without the written permission of Intesis Software S.L.
Intesis Software S.L. Milà I Fontanals, 1 bis 08700 Igualada Spain
TRADEMARKS All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
3 / 66
Gateway for integration of Daikin air conditioners into KNX TP-1 (EIB) control systems.
Compatible with VRV and SKY line air conditioners commercialized by Daikin.
Application’s Program Version: 2.0
Order Code: DK-RC-KNX-1i
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
4 / 66
INDEX
1. Presentation .................................................................................................... 6
2. Connection ...................................................................................................... 7
2.1 DK-RC-KNX-1i without DAIKIN Remote Controller ............................................. 7
2.2 DK-RC-KNX-1i with DAIKIN Remote Controller .................................................. 7
3. Configuration and setup .................................................................................... 9
4. ETS Parameters ............................................................................................. 10
4.1 General dialog ............................................................................................ 11
4.1.1 DK-RC-KNX-1i is master in P1/P2 bus ...................................................... 11
4.1.2 Send READs for Control_ objects on bus recovery ..................................... 12
4.1.3 Scene to load on bus recovery / startup ................................................... 12
4.1.4 Disallow control from remote controller .................................................... 12
4.1.5 Enable func “Control_ Lock Control Obj” ................................................... 13
4.1.6 Enable func “Operating Hours Counter” .................................................... 13
4.1.7 Enable object “Error Code [2byte]” .......................................................... 14
4.1.8 Enable object “Error Text Code [14byte]” ................................................. 14
4.2 Mode Configuration dialog ............................................................................ 14
4.2.1 When mode is AUTO Status_ objs report actual operating status ................. 15
4.2.2 Enable use of Heat / Cool bit-type obj ...................................................... 15
4.2.3 Enable PID-Compat. Scaling Mode Objects ............................................... 16
4.2.4 Enable use of + / - object for Mode ......................................................... 16
4.2.5 Enable use of bit-type Mode objects (for control) ...................................... 17
4.2.6 Enable use of bit-type Mode objects (for status)........................................ 17
4.2.7 Enable use of Text object for Mode .......................................................... 18
4.2.8 Enable use of Legacy_ object for Mode .................................................... 18
4.3 Special Modes Configuration dialog ................................................................ 18
4.3.1 Enable use of POWER mode .................................................................... 19
4.3.2 Enable use of ECONOMY mode ................................................................ 20
4.3.3 Enable use of ADDITIONAL HEATING mode .............................................. 21
4.3.4 Enable use of ADDITIONAL COOLING mode .............................................. 21
4.4 Fan Speed Configuration dialog ..................................................................... 23
4.4.1 Available fan speeds in Indoor Unit .......................................................... 23
4.4.2 DPT object type for fanspeed .................................................................. 23
4.4.3 Enable use of +/- object for Fan Speed .................................................... 25
4.4.4 Enable use of bit-type Fan Speed objects (for Control) ............................... 26
4.4.5 Enable use of bit-type Fan Speed objects (for Status) ................................ 26
4.4.6 Enable use of Text object for Fan Speed ................................................... 27
4.4.7 Enable use of Legacy_ obj for Fan Speed ................................................. 27
4.5 Vane Up-Down Configuration dialog ............................................................... 28
4.5.1 Indoor unit has Up-Down Vanes .............................................................. 28
4.5.2 Enable “Control_ Vane U-D Swing” .......................................................... 28
4.5.3 DPT object type for Vane Up-Down .......................................................... 29
4.5.4 Enable use of +/- obj for Vane Up-Down .................................................. 30
4.5.5 Enable use of bit-type Vane U-D objects (for Control) ................................ 31
4.5.6 Enable use of bit-type Vane U-D objects (for Status) ................................. 31
4.5.7 Enable use of Text object for Vane U-D .................................................... 32
4.5.8 Enable use of Legacy_ obj for Vane U-D ................................................... 32
4.6 Temperature Configuration dialog.................................................................. 33
4.6.1 Periodic sending of “Status_ AC Setp” ...................................................... 33
4.6.2 Transmission of “Status_ AC Ret Temp” ................................................... 34
4.6.3 Enable use of +/- obj for Setp Temp ........................................................ 34
4.6.4 Enable limits on Control_ Setpoint obj ..................................................... 35
4.6.5 Ambient temp. ref. is provided from KNX ................................................. 35
4.7 Scene Configuration dialog ........................................................................... 37
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
5 / 66
4.7.1 Enable use of scenes ............................................................................. 37
4.7.2 Scenes can be stored from KNX bus ........................................................ 38
4.7.3 Enable use of bit objects for scene execution ............................................ 39
4.7.4 Scene “x” preset ................................................................................... 39
4.8 Switch-Off Timeouts Configuration dialog ....................................................... 41
4.8.1 Enable use of Open Window / Switch off timeout function .......................... 41
4.8.2 Enable use of Occupancy function ........................................................... 42
4.8.3 Enable use of SLEEP timeout .................................................................. 45
4.9 Binary Input “x” Configuration dialog ............................................................. 46
4.9.1 Enable use of Input “x” .......................................................................... 46
4.9.2 Contact type ......................................................................................... 46
4.9.3 Debounce time ..................................................................................... 46
4.9.4 Disabling function.................................................................................. 47
4.9.5 Function ............................................................................................... 47
5. Specifications ................................................................................................. 55
6. AC Unit Types compatibility. ............................................................................ 56
7. Error Codes ................................................................................................... 57
Appendix A – Communication Objects Table ................................................................ 60
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
6 / 66
1. Presentation
DK-RC-KNX-1i allows a complete and natural integration of DAIKIN air conditioners with KNX control systems.
Compatible with all SKY Air and VRV models commercialized by DAIKIN.
Main features:
Reduced dimensions, quick installation. Direct connection to P1/P2 bus, the bus that connects the AC indoor unit and the wired
remote controller.
Multiple objects for control and status (bit, byte, characters) with KNX standard
datapoint types.
Status objects for every control available. Special Modes available (Power, Economy, Additional Heating and Additional Cooling). Timeout for Open Window and Occupancy. Sleep function also available. Control of the AC unit based in the ambient temperature read by the own AC unit, or in
the ambient temperature read by any KNX thermostat.
Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s
state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
AC unit can be controlled simultaneously by the remote controller of the AC unit and by
KNX.
Up to 5 scenes can be saved and executed from KNX, fixing the desired combination of
Operation Mode, Set Temperature, Fan Speed, Vane Position and Remote Controller Lock in any moment by using a simple switching.
Four potential-free binary inputs provide the possibility to integrate many types of
external devices. Also configurable from ETS, they can be used for switching, dimming, shutter/blind control, and more
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
7 / 66
2. Connection
Connection of the DK-RC-KNX-1i to the AC indoor unit
2.1 DK-RC-KNX-1i without DAIKIN Remote Controller
The DK-RC-KNX-1i can be connected directly to the P1/P2 bus of the indoor unit (no Daikin remote controller -RC from now on- also connected in the P1 P2 bus). If this is the case, DK­RC-KNX-1i must be configured as master (using the ETS software), see connection diagram below.
2.2 DK-RC-KNX-1i with DAIKIN Remote Controller
If a Daikin remote controller (RC) is present and connected to the P1/P2 bus, there are two configuration options:
If we want to use the RC as master, its PCB switch must be set at “M” position and the
DK-RC-KNX-1i must be configured as slave.
If we want to use the RC as slave, its PCB switch must be set at “S” position and the
DK-RC-KNX-1i must be configured as master.
Check compatible Daikin remote controllers in the link provided in section 6.
Figure 2.1 Daikin RC PCB backside, MAIN/SUB switch
Special mention must be made with the use of Daikin’s IR wireless remote controllers, in this case Daikin’s IR must be slave and the DK-RC-KNX-1i must be master, otherwise not all the features will be available from KNX.
Disconnect mains power from the AC unit and use a 2 wire cable with a diameter of 0.75mm2 to 1.25mm2 for the connection of DK-RC-KNX-1i, Daikin’s remote controller and its corresponding indoor unit. Screw the suitably peeled cable ends in the corresponding P1/P2 terminals of each device, as summarized in the Figure 2.2.
Maximum P1/P2 bus length is 500 meter. DAIKIN RC and DK-RC-KNX-1i are polarity insensitive.
Connection of the DK-RC-KNX-1i to the KNX bus:
Disconnect power of the KNX bus. Connect the DK-RC-KNX-1i to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the DK-RC-KNX-1i, respect polarity.
Reconnect power of the KNX bus, and mains power of the AC unit.
S
M
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
8 / 66
Connections diagrams:
DK-RC-KNX-1i without DAIKIN RC
DK-RC-KNX-1i with DAIKIN RC
Figure 2.2 Connections diagrams
Max. 500 m
P1 P2
Connection to P1 P2 bus. Two wires cable.
KNX TP-1 (EIB) bus
P1 P2
DAIKIN
AC Indoor Unit
Remote Control
AC Unit
P2 P1
DK-RC-KNX-1
IntesisBox ®
Internal electronic control board
P2 P1
Connection to P1 P2 bus. Two wires cable.
KNX TP-1
(EIB) bus
AC Indoor Unit
Max. 500 m
AC Unit
P1 P2
DK-RC-KNX-1
IntesisBox ®
Internal electronic control board
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
9 / 66
3. Configuration and setup
This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.
ETS database for this device can be downloaded from:
http://www.intesis.com/down/eib/DK-RC-KNX-1i.zip
Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.
IMPORTANT: Do not forget to select the correct settings of AC indoor unit being connected to the DK-RC-KNX-1i (Fan speed and Vane), this is in "Parameters" of the device in ETS.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
10 / 66
4. ETS Parameters
When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:
Figure 4.1 Default parameter configuration
With this configuration it’s possible to send On/Off (Control_ On/Off), change the AC Mode (Control_ Mode), the Fan Speed (Control_ Fan Speed) and also the Setpoint Temperature (Control_ Setpoint Temperature). The Status_ objects, for the mentioned Control_ objects, are also available to use if needed. Also objects Status_ AC Reference Temp, Status_ Error/Alarm and Status_Error Text Code are shown.
Figure 4.2 Default communication objects
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
11 / 66
4.1 General dialog
Inside this parameter’s dialog it is possible to activate or change the parameters shown in the Figure 4.1.
The first field shows the URL where to download the database (or pr3) and the user manual for the product.
4.1.1 DK-RC-KNX-1i is master in P1/P2 bus
This parameter changes the gateway’s behavior, being able to program it as master or slave in P1 P2 bus.
o If set to “no”, the gateway will work as a slave and it will be necessary to have a BRC
remote controller configured as a master.
o If set to “yes” the gateway will be master of the bus. It is not necessary to have any BRC
remote controller in this case but, if there are, they must be configured as slaves. The next parameter is also shown when selecting DK-RC-KNX-1i as master in P1 P2 bus:
Figure 4.3 Parameter detail
If VRV system, indoor unit is slave of Operating Mode:
VRV indoor units can be configured as master or slave of Operating Mode.
If configured as slave = “yes”, the unit will take the operating mode of the master indoor unit in the system (i.e. if master unit is in Heat mode, slaves will be also in Heat mode).
If configured as slave = “no”, it means is the master unit, then the unit will take the operating mode selected through the BRC or DK-RC-KNX-1i, and the other slave indoor units will adopt this operating mode.
Important: Only ONE indoor unit can be configured as master of operating mode. If
more than one indoor unit is configured as master, the system will not work properly.
There are some compatible Operation Modes that slave indoor units can use while the master indoor unit is operating in another one:
MASTER INDOOR UNIT
SLAVE INDOOR UNIT(s)
Heat
Heat, Fan
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
12 / 66
Cool
Cool, Dry, Fan
Dry
Dry, Cool, Fan
Fan
Fan
Table 4.1 Operating Mode compatibility
4.1.2 Send READs for Control_ objects on bus recovery
When this parameter is enabled, DK-RC-KNX-1i will send READ telegrams for the group addresses associated on its Control_ objects on bus recovery or application reset/start-up.
o If set to “no” the gateway will not perform any action. o If set to “yes” all Control_ objects with both Transmit (T) and Update (U) flags enabled
will send READs and their values will be updated with the response when received.
Figure 4.4 Parameter detail
Delay before sending READs (sec):
With this parameter, a delay can be configured between 0 and 30 seconds for the READs sent by the Control_ objects. This is to give time enough to other KNX devices on the bus to start-up before sending the READs.
4.1.3 Scene to load on bus recovery / startup
This parameter executes a selected scene on bus recovery or startup, only if the selected scene has an enabled preset or values previously saved from KNX bus (see Scene Configuration dialog).
If the gateway is disconnected from the indoor unit (P1 & P2 bus not connected) the scene will not be applied, even when connecting to the indoor unit again.
Figure 4.5 Parameter detail
4.1.4 Disallow control from remote controller
This parameter allows:
1- Having the remote controller always locked, or 2- Decide through a new communication object if the RC is locked or not.
o If set to “yes” all the actions performed through the remote controller will be disabled.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
13 / 66
o If set to “no” the remote controller will work as usually. It also appears a new parameter
and the communication object Control_ Lock Remote Control.
Figure 4.6 Communication object and parameter detail
Enable comm obj “Ctrl_ Remote Lock”:
If set to “no” the object will not be shown.
If set to “yes” the Control_ Lock Remote Control object will appear.
When a “1” value is sent to this communication object, the remote controller
is locked. To be unlocked a “0” value must be sent. The gateway remembers the last value received even if a KNX bus reset/failure happens.
Important: If an initial scene is enabled and it has as Value for Remote Lock
(unchanged) or unlocked, this would unlock the remote controller because the initial scene has priority over the Control_ Lock Remote Control communication object.
4.1.5 Enable func “Control_ Lock Control Obj”
This parameter shows/hide the Control_ Lock Control Obj communication object which, depending on the sent value, locks or unlocks ALL the Control_ communication objects except itself.
o If set to “no” the object will not be shown. o If set to “yes” the Control_ Lock Control Objects object will appear.
When a “1” value is sent to this communication object, all the Control_ objects
will be locked. To unlock a “0” value must be sent, as the gateway remembers the last value received even if a KNX bus reset/failure happens.
4.1.6 Enable func “Operating Hours Counter”
This parameter shows/hides the Status_ Operation Hour Counter communication object which counts the number of operating hours for the DK-RC-KNX-1i.
o If set to “no” the object will not be shown.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
14 / 66
o If set to “yes” the Status_ Operation Hour Counter object will appear.
This object can be read and sends its status every time an hour is counted. The
gateway keeps that count in memory and the status is sent also after a KNX bus reset/failure. Although this object is marked as a Status_ object it also can be written to update the counter when needed. To reset the counter should be written a “0” value.
Important: This object comes by default without the write (W) flag activated.
If is necessary to write on it, this flag must be activated.
Important: This object will also return its status, every time a value is written,
only if it’s different from the existing one.
Important: If the stored value is 0 hours, the gateway will not send the status
to KNX.
4.1.7 Enable object “Error Code [2byte]”
This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.
o If set to “no” the object will not be shown. o If set to “yes” the Status_ Error Code [2byte] object will appear.
This object can be read and also sends the indoor unit error, if occurred, in
numeric format. If a “0” value is shown that means no error.
4.1.8 Enable object “Error Text Code [14byte]”
This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.
o If set to “no” the object will not be shown. o If set to “yes” the Status_ Error Text Code object will appear.
This object can be read and also sends the indoor unit error, if occurred, in text
format. The errors shown have the same format as at the remote controller and
at the error list from the indoor unit manufacturer. If the object’s value is empty
that means no error.
4.2 Mode Configuration dialog
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
15 / 66
Figure 4.7 Default Mode Configuration dialog
All the parameters in this section are related with the different mode properties and communication objects.
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with a “14” value.
4.2.1 When mode is AUTO Status_ objs report actual operating status
This parameter shows the real status of the indoor unit when Auto mode is enabled.
o If set to “no”, when the indoor unit is set to Auto mode, all the Status_ objects concerning
mode will only show Auto enabled.
o If set to “yes”, when the indoor unit is set to Auto mode, all the Status_ objects
concerning mode will show the real mode which the machine is working (Cool, Heat, Dry, Fan). In case of the bitfield objects, also the Status_ Mode Auto will be shown enabled with a “1” value.
4.2.2 Enable use of Heat / Cool bit-type obj
This parameter shows/hides the Control_ and Status_ Mode Cool/Heat communication objects.
o If set to “no” the objects will not be shown. o If set to “yes” the Control_ and Status_ Mode Cool/Heat objects will appear.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
16 / 66
When a “1” value is sent to the Control_ communication object, Heat mode
will be enabled in the indoor unit, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Cool mode
will be enabled in the indoor unit, and the Status_ object will return this value.
4.2.3 Enable PID-Compat. Scaling Mode Objects
This parameter shows/hides the Control_ Mode Cool & On and Control_ Mode Heat & On communication objects.
o If set to “no” the objects will not be shown. o If set to “yes” the Control_ Mode Cool & On and Control_ Mode Heat & On objects will
appear.
These objects provide compatibility with those KNX thermostats that control
the demand of heating or cooling by using scaling (percentage) objects. In these thermostats, the percentage demand is meant to be applied on a fluid valve of the heating / cooling system.
DK-RC-KNX-1i device does not provide individual control on the internal parts
of the indoor unit (as can be its compressor, refrigerant valves, etc). Rather, it provides the same level of control as a (user) remote controller.
Objects “Control_ Mode Cool & On” and “Control_ Mode Heat & On” intend to
bring compatibility between thermostats oriented to the control of custom heating / cooling systems and ready-made AC indoor units, by applying the following logic:
Whenever a non-zero value (>0%) is received at “Control_ Mode Cool
& On”, indoor unit will switch On in COOL mode.
Whenever a non-zero value (>0%) is received at “Control_ Mode Heat
& On”, indoor unit will switch On in HEAT mode.
Lastest updated object will define the operating mode
Indoor unit will switch off only when both objects become zero (0%) –
or when an OFF is requested at object “0. On/Off [DPT_1.001 - 1bit]”
Important: These objects function is only to send On/Off and Cool/Heat to the indoor
unit. The PID (Inverter system) is calculated by the indoor unit itself. Please consider introducing an appropriate PID configuration to the external KNX thermostat to not interfere the indoor unit PID.
4.2.4 Enable use of + / - object for Mode
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
17 / 66
This parameter shows/hides the Control_ Mode +/- communication object which lets change the indoor unit mode by using two different datapoint types.
o If set to “no” the object will not be shown. o If set to “yes” the Control_ Mode +/- object and a new parameter will appear.
Figure 4.8 Parameter detail
DPT type for +/- Mode Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Mode +/- object.
The sequence followed when using this object is shown below:
4.2.5 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type Control_ Mode objects.
o If set to “no” the objects will not be shown. o If set to “yes” the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
To activate a mode by using these objects a “1” value has to be sent.
4.2.6 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type Status_ Mode objects.
Up / Increase
Down / Decrease
DRY
AUTO
HEAT
COOL
FAN
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
18 / 66
o If set to “no” the objects will not be shown. o If set to “yes” the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
When enabled, a mode will return a “1” through its bit-type object.
4.2.7 Enable use of Text object for Mode
This parameter shows/hides the Status_ Mode Text communication object.
o If set to “no” the object will not be shown. o If set to “yes” the Status_ Mode Text object will appear. Also, in the parameters, will be
shown five text fields, one for each mode, that will let modify the text string displayed by the Status_ Mode Text when changing mode.
Figure 4.9 Parameter detail
4.2.8 Enable use of Legacy_ object for Mode
This parameter shows/hides the Legacy_ Mode communication object.
o If set to “no” the object will not be shown. o If set to “yes” the Legacy_ Mode object will appear. This object lets change the indoor
unit mode but it uses a different data type. It is used to maintain compatibility with old gateway models. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Dry mode with a “2” value, Fan mode with a “3” value and Cool mode with a “4” value
4.3 Special Modes Configuration dialog
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
19 / 66
Figure 4.10 Default Special Modes Configuration dialog
The Special Modes can be parameterized through the ETS parameters dialog, and they can be used to give extra functionality.
Important: When executing any of the Special Modes, the real state of the indoor unit
will NOT be shown in KNX.
Important: When the predefined time for the Special Mode is finished or a “0” value is
sent to stop it. The previous state will be recovered.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
received from KNX while any Special Mode is running (“1”), the Special Mode will stop and the previous state will be recovered. The value received will be also applied then.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
modified through the remote controller, the Special Mode will stop WITHOUT recovering the previous state. Then the real indoor unit state will be shown in KNX including the new value received through the remote controller.
4.3.1 Enable use of POWER mode
This parameter shows/hides the Control_ Start Power Mode and Status_ Power Mode communication objects. The Power Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
o If set to “no” the objects will not be shown. o If set to “yes” the Control_ Start Power Mode and Status_ Power Mode objects and new
parameters will appear.
IntesisBox® KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox® is a registered trademark of Intesis Software SL
URL Email tel
http://www.intesis.com info@intesis.com +34 938047134
20 / 66
Figure 4.11 Parameter detail
When a “1” value is sent to the Control_ communication object Power Mode
will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Power Mode
will be disabled, and the Status_ object will return this value.
Important: This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of Power Mode, in minutes, once started.
Setpoint delta increase (HEAT) or decrease (COOL) – in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode, while in Power Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Power Mode.
4.3.2 Enable use of ECONOMY mode
This parameter shows/hides the Control_ Start Econo Mode and Status_ Econo Mode communication objects. The Econo Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
o If set to “no” the objects will not be shown. o If set to “yes” the Control_ Start Econo Mode and Status_ Econo Mode objects and new
parameters will appear.
When a “1” value is sent to the Control_ communication object, EconoMode
will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, EconoMode
will be disabled, and the Status_ object will return this value.
Important: This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of EconoMode, in minutes, once started.
Loading...
+ 46 hidden pages