Installation Instructions
Use the software LinkBoxBacnet to configure IntesisBox. Follow User’s Manual instructions for detail on the configuration process.
See instructions to download and install the latest version of LinkBoxBacnet and
its user's manual at
http://www.intesis.com/down/bacnet/linkboxbacnet.html
IntesisBox must be installed by accredited electrician or similar technical personnel, following all the safety instructions
given here, and in accordance always with the country legislation for installation of electric equipment.
IntesisBox can not be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust.
IntesisBox must only be installed in a restricted access location.
In case of wall mount, fix firmly IntesisBox on a not vibrating surface following the instructions below.
In case of DIN rail mount fix IntesisBox properly to the DIN rail following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to earth is recommended.
Disconnect always power of any wires before manipulating and connecting them to IntesisBox.
Respect always the expected polarity of power and communication cables when connecting them to IntesisBox.
Supply always a correct voltage to power IntesisBox, within voltage range admitted (230Vac +/ -10%).
This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with
static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure. When working in
an enclosure (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before
touching the unit
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your
health and also may damage seriously the IntesisBox and/or any other equipment connected to it.
Disconnect the mains power and power of any bus or communication cable before connecting it to IntesisBox.
Mount IntesisBox on the wall or DIN rail following the instruction given below, respecting the safety instructions given
above.
Connect the mains power cable to the supply voltage terminal block of IntesisBox.
Circuit-breaker must be used before the mains power cable. Rating 250V-6A
Connect the communication cables to IntesisBox, see details on the user's manual.
Power IntesisBox and the rest of devices connected to it.
After power-on, DALI bus LED (at the left side of DALI connector) should be ON, signalling that there is DALI bus voltage.
If DALI bus LED is OFF, you should check the DALI communication line for a possible short-circuit.
If your DALI installation is already operative, communication at DALI side can be tested by pressing the DALI test button:
Pressing once the button, the ballasts will switch ON (DALI led will start flashing)
Pressing again the button, the ballasts will switch OFF (DALI led will toggle to ON)
Pressing again the button, the ballasts will switch ON, and remain ON until their value is changed from BACnet side
(DALI led will toggle to OFF, signaling that the test has ended).

IntesisBox
®
BACnet/IP Server – DALI
The information in this document may change without previous notice.
http://www.intesis.com
info@intesis.com
+34 938047134
1. Separate the fixing clips in the bottom of the box, pushing them to the outside until hearing the "click"
which indicates that now the clips are in position for wall mount, see in the figure below.
2. Drill 3 holes in the wall following as a guide the distances shown below. Use the holes of the clips
to fix the box in the wall, using screws.
With the clips of the box in their original position, insert first the box in the upper edge of the DIN rail. Then insert
the box in the down part of the rail, using a small screwdriver, following the steps in the figure below.
Clips in their original position, for DIN-rail mounting
Clips in wall-mount position
IntesisBox
®
www.intesis.com

IntesisBox
®
BACnet/IP Server – DALI
The information in this document may change without previous notice.
http://www.intesis.com
info@intesis.com
+34 938047134
________________________________________________________________________________________
Notes:
1. BACnet/IP connection: Use a crossover ethernet CAT5 cable if connecting directly to a BACnet/IP controller, or a straight ethernet CAT5
cable if connecting to a hub or switch of the LAN in the installation. If communicating through a LAN you might need to contact the network
administrator to make sure UDP traffic and port used for BACnet/IP (default is 47808) are allowed throughout the LAN path between
IntesisBox and your BACnet client.
DALI connection: Connect DALI bus to the DALI connector of IntesisBox. IntesisBox provides 15Vdc (+/-2%) DALI voltage to the bus.
2. Use the software LinkBoxBacnet to configure IntesisBox. Consult user's manual for details.
LinkBoxBacnet
Only needed for
configuration,
configuration can also be
done using Ethernet
See Note 2
Ethernet / BACnet/IP
(and IntesisBox configuration)
See Note 1
IntesisBox
®
www.intesis.com
Console cable 1,8 m.
Standard DB9 Female - DB9 Male.
(supplied with IntesisBox)

IntesisBox
®
BACnet/IP Server – DALI
The information in this document may change without previous notice.
http://www.intesis.com
info@intesis.com
+34 938047134
Technical characteristics
Plastic, type PC (UL 94 V-0).
Dimensions: 159mm 105mm x 58mm.
230Vac +/-10% 6W
(3-pole plug-in terminal block – line, neutral and earth)
Terminal wiring
(for power supply
and low-voltage
signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm2… 2.5mm2
2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
Wall.
DIN rail EN60715 TH35.
15Vdc +/-2% 250mA.
(DALI bus is powered from IntesisBox)
1 x DALI electrically isolated (2-pole plug-in terminal block). SELV
Ethernet port
(BACnet/IP, device
config)
1 x Ethernet 10Base-T (RJ45).
1 x Power indicator.
2 x DALI activity (Tx, Rx).
2 x Ethernet link & activity (LNK, ACT).
1 x DALI bus power
1 x DALI test1
EIA232. DB9 female connector (DCE). SELV
Via Ethernet or serial console port.2
Allows upgrades via console port.
25-90% at 50ºC, non condensing
Protection
Compliant with RoHS directive (2002/95/CE).
CE conformity to EMC directive (2004/108/EC) and Low-voltage
directive (2006/95/EC)
EN 61000-6-2
EN 61000-6-3
EN 60950-1
EN 50491-3
1
DALI test push-button and LED are meant to perform a quick test of your DALI line and connected ballasts.
2
Standard cable DB9male-DB9female 1,8 meters long is supplied with the device for connection to a PC COM port for
configuring and monitoring the device using the serial port (Ethernet is also possible). The configuration software, compatible
with Windows® operating systems, is also supplied.

IntesisBox
®
BACnet/IP Server – DALI
The information in this document may change without previous notice.
http://www.intesis.com
info@intesis.com
+34 938047134
External dimensions
Free space recommended in the install location of the device, with spacing enough for external connections.