Intesis KNX User Manual

Gateway for integration of LG air conditioners into KNX TP-
1 (EIB) control systems
Compatible with VRF air conditioners commercialized by LG
Application’s Program Version: 1.4
USER MANUAL
Issue date: 07/2020 r1.7 ENGLISH
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 54
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 / 54
Gateway for integration of LG air conditioners into KNX TP-1 (EIB) control systems.
Compatible with VRF air conditioners commercialized by LG.
Application’s Program Version: 1.4
ORDER CODE
LEGACY ORDER CODE
INKNXLGE001R000
LG-RC-KNX-1i
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 / 54
INDEX
1. Presentation .................................................................................................... 6
2. Connection ...................................................................................................... 7
INKNXLGE001R000 with LG Remote Controller.................................................. 7
3. Configuration and setup .................................................................................... 7
4. ETS Parameters ............................................................................................... 8
General dialog .............................................................................................. 8
4.1.1 LG protocol type ..................................................................................... 9
4.1.2 INKNXLGE001R000 is master in bus (3-wire) .............................................. 9
4.1.3 Send READs for Control_ objects on bus recovery ....................................... 9
4.1.4 Scene to load on bus recovery / startup ................................................... 10
4.1.5 Disallow control from remote controller .................................................... 10
4.1.6 Enable func “Control_ Lock Control Obj” ................................................... 10
4.1.7 Enable func “Operating Hours Counter” .................................................... 11
4.1.8 Enable object “Error Code [2byte]” .......................................................... 11
4.1.9 Enable object “Error Text Code [14byte]” ................................................. 12
Mode Configuration dialog ............................................................................ 12
4.2.1 Indoor unit has HEAT mode .................................................................... 13
4.2.2 Indoor unit has AUTO mode.................................................................... 13
4.2.3 Enable “Mode Cool/Heat” objects ............................................................ 13
4.2.4 Enable PID-Compat. Scaling Mode Objects (for Control) ............................. 13
4.2.5 Enable use of + / - object for Mode ......................................................... 14
4.2.6 Enable use of bit-type Mode objects (for control) ...................................... 15
4.2.7 Enable use of bit-type Mode objects (for status)........................................ 15
4.2.8 Enable use of Text object for Mode .......................................................... 15
Special Modes Configuration dialog ................................................................ 16
4.3.1 Enable use of POWER mode .................................................................... 16
4.3.2 Enable use of ECONOMY mode ................................................................ 17
4.3.3 Enable use of ADDITIONAL HEATING mode .............................................. 18
4.3.4 Enable use of ADDITIONAL COOLING mode .............................................. 19
Fan Speed Configuration dialog ..................................................................... 19
4.4.1 Available fanspeeds in Indoor Unit ........................................................... 20
4.4.2 Indoor unit has AUTO fan speed .............................................................. 20
4.4.3 DPT object type for Fan Speed ................................................................ 20
4.4.4 Enable use of +/- object for Fan Speed .................................................... 21
4.4.5 Enable “Fan Speed Man/Auto” objects (for Control and Status) ................... 22
4.4.6 Enable use of bit-type Fan Speed objects (for Control) ............................... 22
4.4.7 Enable use of bit-type Fan Speed objects (for Status) ................................ 22
4.4.8 Enable use of Text object for Fan Speed ................................................... 23
Vanes Up-Down Configuration dialog ............................................................. 23
4.5.1 Indoor unit has U-D Vanes ..................................................................... 23
4.5.2 Indoor unit has Vanes Swirl (for U-D vanes) ............................................. 24
4.5.3 Indoor unit has L-R Vanes ...................................................................... 24
4.5.4 Indoor unit has Vanes Swirl (for U-D vanes) ............................................. 25
Temperature Configuration dialog.................................................................. 25
4.6.1 Periodic sending of “Status_ AC Setp” ...................................................... 25
4.6.2 Transmission of “Status_ AC Ref Temp” ................................................... 26
4.6.3 Enable use of +/- object for Setpoint Temp .............................................. 26
4.6.4 Enable limits on Control_ Setpoint obj ..................................................... 27
4.6.5 Ambient temp. ref. is provided from KNX ................................................. 27
Scene Configuration dialog ........................................................................... 28
4.7.1 Enable use of scenes ............................................................................. 29
4.7.2 Scenes can be stored from KNX bus ........................................................ 29
4.7.3 Enable use of bit objects for scene execution ............................................ 30
4.7.4 Scene “x” preset ................................................................................... 30
Switch-Off Timeouts Configuration dialog ....................................................... 32
4.8.1 Enable use of Open Window / Switch off timeout function .......................... 32
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 54
4.8.2 Enable use of Occupancy function ........................................................... 33
4.8.3 Enable use of SLEEP timeout .................................................................. 36
Binary Input “x” Configuration dialog ............................................................. 36
4.9.1 Enable use of Input “x” .......................................................................... 36
4.9.2 Contact type ......................................................................................... 37
4.9.3 Debounce time ..................................................................................... 37
4.9.4 Disabling function.................................................................................. 37
4.9.5 Function ............................................................................................... 37
5. Specifications ................................................................................................. 45
6. AC Unit Types compatibility ............................................................................. 46
7. Error Codes ................................................................................................... 47
8. Appendix A – Communication Objects Table ...................................................... 49
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 / 54
1. Presentation
INKNXLGE001R000 allows a complete and natural integration of LG air conditioners with KNX control systems.
Compatible with VRF Series air conditioners commercialized by LG.
Main features:
Reduced dimensions, quick installation.
Multiple objects for control and status (bit, byte, characters…) with KNX standard
datapoint types.
Status objects for every control available.
Timeout for Open Window and Occupancy. Sleep function also available.
Control of the AC unit based in the ambient temperature read by the own AC unit, or in
the ambient temperature read by any KNX thermostat.
AC unit can be controlled simultaneously by the wired remote control of the AC unit and
by KNX.
Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s
state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
Up to 5 scenes can be saved and executed from KNX, fixing the desired combination of
Operation Mode, Set Temperature, Fan Speed, Vane Position and Remote Controller Lock in any moment by using a simple switching.
Four binary inputs for potential-free contacts provide the possibility to integrate many
types of external devices. Also configurable from ETS, they can be used for switching, dimming, shutter/blind control, and more
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 / 54
2. Connection
Connection of the INKNXLGE001R000 to the AC indoor unit
The INKNXLGE001R000 can be connected directly to the RYB bus of the indoor unit (no LG remote controller -RC from now on- connected in the RYB bus) or with the LG RC. See connection diagram below.
Figure 2.1 INKNXLGE001R000 connection diagrams
INKNXLGE001R000 with LG Remote Controller
Connection of the INKNXLGE001R000 to the KNX bus:
Disconnect power of the KNX bus. Connect the INKNXLGE001R000 to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the INKNXLGE001R000, respect polarity.
Reconnect power of the KNX bus, and mains power of the AC unit.
3. Configuration and setup
This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.
ETS database for this device can be downloaded from:
https://intesis.com/products/ac-interfaces/lg-gateways/lg-knx-inputs-vrf-lg-rc-knx-1i
Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.
Important: Do not forget to select the correct settings of AC indoor unit being connected
to the INKNXLGE001R000. This is in "Parameters" of the device in ETS.
AC Indoor Unit
R Y B
LG bus max length 50 m
Longitud máxima del bus de LG 50 m
GND (3) B Data (2) Y
Power (1) R
Internal electronic
control board
KNX TP-1
(EIB) bus
R Y B
AC Unit
Free potential
binary inputs
COM
IN4 IN3 IN2
IN1
Attention: The LG Type A units do not allow a remote controller and INKNXLGE001R000 device installed together.
Control Panel
(It is not mandatory to have it in the network)
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
8 / 54
4. ETS Parameters
When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:
Figure 4.1 Default parameter configuration
With this configuration it’s possible to send On/Off (Control_ On/Off), change the AC Mode (Control_ Mode), the Fan Speed (Control_ Fan Speed) and also the Setpoint Temperature (Control_ Setpoint Temperature). The Status_ objects, for the mentioned Control_ objects, are also available to use if needed. Also objects Status_ AC Return Temp and Status_ Error/Alarm are shown.
Figure 4.2 Default communication objects
General dialog
Inside this parameter’s dialog it is possible to activate or change the parameters shown in the Figure 4.1.
The first field shows the URL where to download the database and the user manual for the product.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
9 / 54
4.1.1 LG protocol type
This parameter is used to differentiate between the Type A and Type B units. Please, leave it in Type B (as per default). 1
4.1.2 INKNXLGE001R000 is master in bus (3-wire)
This parameter changes the gateway’s behavior, being able to program it as master or slave in LG bus.
o If set to “No”, the gateway will work as a slave. o If set to “Yes” the gateway will be master of the bus. It is not necessary to have any
remote controller in this case but, if there are, they must be configured as slaves. The next parameter is also shown when selecting INKNXLGE001R000 as master in LG bus:
Figure 4.3 Parameter detail
Apply “Min Ambient Temp”:
If set to “Yes”, the minimum ambient temperature set on the LG system will apply.
4.1.3 Send READs for Control_ objects on bus recovery
When this parameter is enabled, INKNXLGE001R000 will send READ telegrams for the group addresses associated on its Control_ objects on bus recovery or application reset/start-up.
o If set to “No” the gateway will not perform any action. o If set to “Yes” all Control_ objects with both Transmit (T) and Update (U) flags enabled
will send READs and their values will be updated with the response when received.
Figure 4.3 Parameter detail
Delay before sending READs (sec):
With this parameter, a delay can be configured between 0 and 30 seconds for the READs sent by the Control_ objects. This is to give time enough to other KNX devices on the bus to start-up before sending the READs.
1
Type A should be use only under very specific circumstances. Contact HMS Networks before selecting A type.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
10 / 54
4.1.4 Scene to load on bus recovery / startup
This parameter executes a selected scene on bus recovery or startup, only if the selected scene has an enabled preset or values previously saved from KNX bus (see Scene Configuration dialog).
If the gateway is disconnected from the indoor unit the scene will not be applied, even when connecting to the indoor unit again.
Figure 4.4 Parameter detail
4.1.5 Disallow control from remote controller
This parameter allows:
1- Having the remote controller always locked, or 2- Decide through a new communication object if the RC is locked or not.
o If set to “Yes” all the actions performed through the remote controller will be disabled. o If set to “No” the remote controller will work as usually. It also appears a new parameter
and the communication object Control_ Lock Remote Control.
Figure 4.5 Communication object and parameter detail
Enable comm obj “Ctrl_ Remote Lock”:
If set to “No” the object will not be shown.
If set to “Yes” the Control_ Lock Remote Control object will appear.
When a “1” value is sent to this communication object, the remote controller
is locked. To be unlocked a “0” value must be sent. The gateway remembers the last value received even if a KNX bus reset/failure happens.
Important: If an initial scene is enabled and it has as Value for Remote Lock
(unchanged) or unlocked, this would unlock the remote controller because the initial scene has priority over the Control_ Lock Remote Control communication object.
4.1.6 Enable func “Control_ Lock Control Obj”
This parameter shows/hide the Control_ Lock Control Obj communication object which, depending on the sent value, locks or unlocks ALL the Control_ communication objects except itself.
28
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 54
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Lock Control Objects object will appear.
When a “1” value is sent to this communication object, all the Control_ objects
will be locked. To unlock a “0” value must be sent, as the gateway remembers the last value received even if a KNX bus reset/failure happens.
4.1.7 Enable func “Operating Time Counter”
This parameter shows/hides the Status_ Operation Hour Counter and Status_ Operation Sec Counter communication objects which counts the number of operating hours or seconds for the INKNXLGE001R000.
o If set to “No” objects will not be shown. o If set to “Yes” the Status_ Operation Sec Counter object and an additional parameter for
the Status_ Operation Hour Counter selection will appear.
These objects can be read and sends its status every time an hour/second is
counted. The gateway keeps that count in memory and the status is sent also after a KNX bus reset/failure. Although this object is marked as a Status_ object it also can be written to update the counter when needed. To reset the counter should be written a “0” value.
Important: This object comes by default without the write (W) flag activated.
If is necessary to write on it, this flag must be activated.
Important: This object will also return its status, every time a value is written,
only if it’s different from the existing one.
Important: If the stored value is 0 hours, the gateway will not send the status
to KNX.
4.1.8 Enable object “Error Code [2byte]”
This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.
29
81
82
73
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
12 / 54
o If set to “No” the object will not be shown. o If set to “Yes” the Status_ Error Code [2byte] object will appear.
This object can be read and also sends the indoor unit error, if occurred, in
numeric format. If a “0” value is shown that means no error.
4.1.9 Enable object “Error Text Code [14byte]”
This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.
o If set to “No” the object will not be shown. o If set to “Yes” the Status_ Error Text Code object will appear.
This object can be read and also sends the indoor unit error, if occurred, in text
format. The errors shown have the same format as at the remote controller and
at the error list from the indoor unit manufacturer. If the object’s value is empty
that means no error.
Mode Configuration dialog
Figure 4.6 Default Mode Configuration dialog
All the parameters in this section are related with the different mode properties and communication objects.
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with a “14” value.
74
1
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
13 / 54
4.2.1 Indoor unit has HEAT mode
This parameter has to be used to indicate if the indoor unit has the heat mode available.
o If set to “No”, the indoor unit doesn’t have the heat mode available. o If set to “Yes”, the infoor unit has the heat mode available.
Important: Read the documentation of your indoor unit to check if it has HEAT mode
available.
4.2.2 Indoor unit has AUTO mode
This parameter has to be used to indicate if the indoor unit has the auto mode available.
o If set to “No”, the indoor unit doesn’t have the auto mode available. o If set to “Yes”, the infoor unit has the auto mode available.
Important: Read the documentation of your indoor unit to check if it has AUTO mode available.
4.2.3 Enable “Mode Cool/Heat” objects
This parameter shows/hides the Control_ and Status_ Mode Cool/Heat communication objects.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ and Status_ Mode Cool/Heat objects will appear.
When a “1” value is sent to the Control_ communication object, Heat mode
will be enabled in the indoor unit, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Cool mode
will be enabled in the indoor unit, and the Status_ object will return this value.
4.2.4 Enable PID-Compat. Scaling Mode Objects (for Control)
This parameter shows/hides the Control_ Mode Cool & On and Control_ Mode Heat & On communication objects.
o If set to “No” the objects will not be shown.
2
54
3
4
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
14 / 54
o If set to “Yes” the Control_ Mode Cool & On and Control_ Mode Heat & On objects will
appear.
These objects provide compatibility with those KNX thermostats that control
the demand of heating or cooling by using scaling (percentage) objects. In these thermostats, the percentage demand is meant to be applied on a fluid valve of the heating / cooling system.
INKNXLGE001R000 device does not provide individual control on the internal
parts of the indoor unit (as can be its compressor, refrigerant valves, etc.). Rather, it provides the same level of control as a (user) remote controller.
Objects “Control_ Mode Cool & On” and “Control_ Mode Heat & On” intend to
bring compatibility between thermostats oriented to the control of custom heating / cooling systems and ready-made AC indoor units, by applying the following logic:
Whenever a non-zero value (>0%) is received at “Control_ Mode Cool
& On”, indoor unit will switch On in COOL mode.
Whenever a non-zero value (>0%) is received at “Control_ Mode Heat
& On”, indoor unit will switch On in HEAT mode.
Latest updated object will define the operating mode
Indoor unit will switch off only when both objects become zero (0%) –
or when an OFF is requested at object “0. On/Off [DPT_1.001 - 1bit]”
* Important: These objects function is only to send On/Off and Cool/Heat to the indoor
unit. The PID (Inverter system) is calculated by the indoor unit itself. Please consider introducing an appropriate PID configuration to the external KNX thermostat to not interfere the indoor unit PID.
4.2.5 Enable use of + / - object for Mode
This parameter shows/hides the Control_ Mode +/- communication object which lets change the indoor unit mode by using two different datapoint types.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Mode +/- object and a new parameter will appear.
Figure 4.7 Parameter detail
DPT type for +/- Mode Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Mode +/- object.
10
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
15 / 54
The sequence followed when using this object is shown below:
Important: Read the documentation of your indoor unit to check if it has HEAT
mode available.
4.2.6 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type Control_ Mode objects.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
To activate a mode by using these objects a “1” value has to be sent.
4.2.7 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type Status_ Mode objects.
o If set to “No” the objects will not be shown. o If set to “Yes” the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
When enabled, a mode will return a “1” through its bit-type object.
4.2.8 Enable use of Text object for Mode
This parameter shows/hides the Status_ Mode Text communication object.
Up / Increase
Down / Decrease
* If available
5
6
7
8
9
53
54
55
56
57
58
DRY
AUTO
HEAT*
COOL
FAN
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
16 / 54
o If set to “No” the object will not be shown. o If set to “Yes” the Status_ Mode Text object will appear. Also, in the parameters, will be
shown five text fields, one for each mode, that will let modify the text string displayed by the Status_ Mode Text when changing mode.
Figure 4.8 Parameter detail
Special Modes Configuration dialog
Figure 4.9 Default Special Modes Configuration dialog
The Special Modes can be parameterized through the ETS parameters dialog, and they can be used to give extra functionality.
Important: When executing any of the Special Modes the real state of the indoor unit
will NOT be shown in KNX.
Important: When the predefined time for the Special Mode is finished or a “0” value is
sent to stop it; the previous state will be recovered.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
received from KNX while any Special Mode is running (“1”), the Special Mode will stop and the previous state will be recovered. The value received will be also applied then.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
modified through the remote controller, the Special Mode will stop WITHOUT recovering the previous state. Then the real indoor unit state will be shown in KNX including the new value received through the remote controller.
4.3.1 Enable use of POWER mode
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
17 / 54
This parameter shows/hides the Control_ Power Mode and Status_ Power Mode communication objects. The Power Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Power Mode and Status_ Power Mode objects and new
parameters will appear.
Figure 4.10 Parameter detail
When a “1” value is sent to the Control_ communication object Power Mode
will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Power Mode
will be disabled, and the Status_ object will return this value.
Important: This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of Power Mode, in minutes, once started.
Setpoint delta increase (HEAT) or decrease (COOL) – in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode, while in Power Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Power Mode.
4.3.2 Enable use of ECONOMY mode
This parameter shows/hides the Control_ Econo Mode and Status_ Econo Mode communication objects. The Econo Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
30
77
31
78
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
18 / 54
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Econo Mode and Status_ Econo Mode objects and new
parameters will appear.
When a “1” value is sent to the Control_ communication object, EconoMode
will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, EconoMode
will be disabled, and the Status_ object will return this value.
Important: This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of EconoMode, in minutes, once started.
Setpoint delta increase (HEAT) or decrease (COOL) – in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode, while in EconoMode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in EconoMode.
4.3.3 Enable use of ADDITIONAL HEATING mode
This parameter shows/hides the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode communication objects. The Additional Heating Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode
objects and new parameters will appear.
When a “1” value is sent to the Control_ communication object, Additional
Heating Mode will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Additional
Heating Mode will be disabled, and the Status_ object will return this value.
Important: This mode will ALWAYS turn on the indoor unit in Heat mode.
Action time for this mode (minutes):
32
79
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
19 / 54
Duration of Additional Heating Mode, in minutes, once started.
Setpoint temp for this mode (ºC):
Setpoint temperature that will be applied while in Additional Heating Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Additional Heating Mode.
4.3.4 Enable use of ADDITIONAL COOLING mode
This parameter shows/hides the Control_ Start Additional Cool Mode and Status_ Additional Cool Mode communication objects. The Additional Heating Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Start Additional Cool Mode and Status_ Additional Cool Mode
objects and new parameters will appear.
When a “1” value is sent to the Control_ communication object, Additional
Cooling Mode will be enabled, and the Status_ object will return this value.
When a “0” value is sent to the Control_ communication object, Additional
Cooling Mode will be disabled, and the Status_ object will return this value.
Important: This mode will ALWAYS turn on the indoor unit in Cool mode.
Action time for this mode (minutes):
Duration of Additional Cooling Mode, in minutes, once started.
Setpoint temp for this mode (ºC):
Setpoint temperature that will be applied while in Additional Cooling Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Additional Cooling Mode.
Fan Speed Configuration dialog
33
80
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
20 / 54
Figure 4.11 Default Fan Speed Configuration dialog
All the parameters in this section are related with the Fan Speed properties and communication objects.
4.4.1 Available fanspeeds in Indoor Unit
With this parameter you select the number of fan speeds available in your indoor unit. Please check that information in your indoor unit manual.
4.4.2 Indoor unit has AUTO fan speed
With this parameter you select if your indoor unit has or not AUTO fan speed mode. Please check that information in your indoor unit manual.
4.4.3 DPT object type for Fan Speed
With this parameter is possible to change de DPT for the Control_ Fan Speed and Status_ Fan Speed byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
Important: The communication objects shown in this section may be different depending
on the number of fan speeds available, although they all share the same communication object number.
o When “Enumerated [DPT 5.010]” is selected, Control_ Fan Speed and Status_ Fan
Speed communication objects for this DPT will appear.
The first fan speed will be selected if a “1” is sent to the Control_ object. The second one will be selected sending a “2”; the third one will be selected sending a “3”.
The Status_ object will always return the value for the fan speed selected.
11
59
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
21 / 54
Important: If a “0” value is sent to the Control_ object, the minimum fan speed will
be selected. If a value bigger than “3” is sent to the Control_ object, then the maximum fan speed will be selected.
o When “Scaling [DPT 5.001]” is selected, Control_ Fan Speed and Status_ Fan Speed
communication objects for this DPT will appear.
The next table shows the range of values that can be sent through the Control_ object and the value returned by the Status_ object.
Important: Read the documentation of your indoor unit to check how many fan speeds
are available.
4.4.4 Enable use of +/- object for Fan Speed
This parameter shows/hides the Control_ Fan Speed +/- communication object which lets increase/decrease the indoor unit fan speed by using two different datapoint types.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Fan Speed +/- object and a new parameter will appear.
Figure 4.13 Parameter detail
DPT type for +/- Fan Speed Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Fan Speed +/- object.
Does +/- sequence include fan speed Auto?
This parameter includes or excludes the auto mode for the fan speed in the list of available speeds.
11
63
Fan Speed 1
Fan Speed 2
Fan Speed 3
Control_
0% - 49%
50% - 82%
83% - 100%
Status_
33%
67%
100%
17
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
22 / 54
Roll-over Speed at upper/lower limit
This parameter lets choose if roll-over will be enabled (“Yes”) or disabled (“No”) for the Control_ Fan Speed +/- object.
4.4.5 Enable “Fan Speed Man/Auto” objects (for Control and Status)
This parameter shows/hides the bit-type Control_ Fan Speed Man/Auto and the Status_ Fan Speed Man/Auto objects.
4.4.6 Enable use of bit-type Fan Speed objects (for Control)
This parameter shows/hides the bit-type Control_ Fan Speed objects.
o If set to “No” the objects will not be shown. o If set to “Yes” the Control_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 will
appear. To activate a Fan Speed by using these objects a “1” value has to be sent.
4.4.7 Enable use of bit-type Fan Speed objects (for Status)
This parameter shows/hides the bit-type Status_ Fan Speed objects.
o If set to “No” the objects will not be shown. o If set to “Yes” the Status_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 will
appear. When a Fan Speed is enabled, a “1” value is returned through its bit-type object.
Up / Increase
Down / Decrease
12
60
13
14
15
16
61
62
63
64
FS 4
AUTO
FS 3
FS 1
FS 2
Only if Roll-over is enabled
Only if Roll-over is enabled
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
23 / 54
4.4.8 Enable use of Text object for Fan Speed
This parameter shows/hides the Status_ Fan Speed Text communication object.
o If set to “No” the object will not be shown. o If set to “Yes” the Status_ Fan Speed Text object will appear. Also, in the parameters,
will be shown five text fields, one for each Fan Speed, that will let modify the text string displayed by the Status_ Fan Speed Text when changing a fan speed.
Figure 4.14 Parameter detail
Vanes Up-Down Configuration dialog
Figure 4.15 Vanes Up-Down Configuration dialog
All the parameters in this section are related with the Vanes Up-Down/Left-Right properties and communication objects.
4.5.1 Indoor unit has U-D Vanes
This parameter lets choose if the unit has Up-Down Vanes available or not.
Figure 4.16 Parameter detail
o If set to “No” all the parameters and communication objects for the Up-Down Vanes will
not be shown.
65
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
24 / 54
o If set to “Yes” all the parameters and communication objects (if enabled in the
parameters dialog) for the Up-Down Vanes will be shown.
Important: Read the documentation of your indoor unit to check if Up-Down Vanes are
available.
4.5.2 Indoor unit has Vanes Swirl (for U-D vanes)
This parameter lets choose if the unit has Swirl mode available or not.
Figure 4.16 Parameter detail
o If set to “No” all the parameters and communication objects for the Up-Down Swirl Vanes
will not be shown.
o If set to “Yes” all the parameters and communication objects (if enabled in the
parameters dialog) for the Up-Down Swirl Vanes will be shown.
Important: Read the documentation of your indoor unit to check if Swirl mode is
available.
4.5.3 Indoor unit has L-R Vanes
This parameter lets choose if the unit has Up-Down Vanes available or not.
Figure 4.16 Parameter detail
o If set to “No” all the parameters and communication objects for the Up-Down Vanes will
not be shown.
o If set to “Yes” all the parameters and communication objects (if enabled in the
parameters dialog) for the Up-Down Vanes will be shown.
18
66
19
67
20
68
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
25 / 54
Important: Read the documentation of your indoor unit to check if Up-Down Vanes are
available.
4.5.4 Indoor unit has Vanes Swirl (for U-D vanes)
This parameter lets choose if the unit has Swirl mode available or not.
Figure 4.16 Parameter detail
o If set to “No” all the parameters and communication objects for the Left-Right Swirl Vanes
will not be shown.
o If set to “Yes” all the parameters and communication objects (if enabled in the
parameters dialog) for the Up-Down Swirl Vanes will be shown.
Important: Read the documentation of your indoor unit to check if Swirl mode is
available.
Temperature Configuration dialog
Figure 4.20 Default Temperature Configuration dialog
All the parameters in this section are related with the Temperature properties and communication objects.
4.6.1 Periodic sending of “Status_ AC Setp”
21
69
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
26 / 54
This parameter lets change the interval of time (in seconds, from 0 to 255) at the end of which the AC setpoint temperature is sent to the KNX bus. For a “0” value, the AC setpoint temperature will ONLY be sent on change. The AC setpoint temperature is sent through the communication object Status_ AC Setpoint Temp.
Figure 4.21 Parameter detail
Important: In case the ambient temperature is provided from KNX, the setpoint
temperature returned from this object, will be the one resulting from the formula shown in the section “4.6.4 Ambient temp. ref. is provided from KNX”.
4.6.2 Transmission of “Status_ AC Ref Temp”
This parameter lets to you choose if the AC return temperature will be sent “only cyclically”, “only on change” or “cyclically and on change”. The AC return temperature is sent through the communication object Status_ AC Ref Temp.
71:
Figure 4.22 Parameter detail
“Status_ AC SetTemp” periodic sending time (in sec)
This parameter will only be available for the “only cyclically” and “cyclically and on change” options, and lets you change the interval of time (in seconds, from 1 to
255) at the end of which the AC return temperature is sent to the KNX bus.
4.6.3 Enable use of +/- object for Setpoint Temp
This parameter shows/hides the Control_ Setpoint Temp +/- communication object which lets change the indoor unit setpoint temperature by using two different datapoint types.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Setpoint Temp +/- object and a new parameter will appear.
70
22
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
27 / 54
Figure 4.22 Parameter detail
DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Setpoint Temp +/- object.
4.6.4 Enable limits on Control_ Setpoint obj
This parameter enables to define temperature limits for the Control_ Setpoint Temperature object.
Figure 4.23 Parameter detail
o If set to “No” the setpoint temperature limits for the Control_ Setpoint Temperature
object will be the default: 16ºC for the lower limit and 30ºC for the upper limit.
o If set to “Yes” it is possible to define temperature limits for the Control_ Setpoint
Temperature object.
Control_ Set Temp Lower limit (ºC)
This parameter lets to define the lower limit for the setpoint temperature.
Control_ Set Temp Upper limit (ºC)
This parameter lets to define the upper limit for the setpoint temperature.
Important: If a setpoint temperature above the upper defined limit (or below the lower
defined limit) is sent through the Control_ Setpoint Temperature object, it will be ALWAYS applied the limit defined.
Important: When limits are enabled, any setpoint temperature sent to the AC (even
through scenes, special modes, etc.) will be limited.
4.6.5 Ambient temp. ref. is provided from KNX
This parameter shows/hides the Control_ Ambient Temperature communication object which lets use an ambient temperature reference provided by a KNX device.
Up / Increase
Down / Decrease
16ºC
19ºC
30ºC
28ºC
(Upper limit)
(Lower limit)
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
28 / 54
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Ambient Temperature object will appear. Meant to be enabled
when you want the temperature provided by a KNX sensor to be the reference ambient temperature for the air conditioner. Then, the following formula applies for calculation of real Control_ Setpoint Temperature sent to the AC unit:
As an example, consider the following situation:
User wants: 19ºC (“KNX Setp. Temp.”) User sensor (a KNX sensor) reads: 21ºC (“KNX Amb Temp.”) Ambient temp. read by LG system is: 24ºC (“AC Ret. Temp”)
In this example, the final setpoint temperature that INKNXLGE001R000 will send out to the indoor unit (shown in “Setp. Temp.”) will become 24ºC – (21ºC - 19ºC) = 22ºC. This is the setpoint that will actually be requested to LG unit.
This formula will be applied as soon as the Control_ Setpoint Temperature and Control_ Ambient Temperature objects are written at least once from the KNX installation. After that, they are kept always consistent.
Note that this formula will always drive the AC indoor unit demand in the right direction, regardless of the operation mode (Heat, Cool or Auto).
Scene Configuration dialog
Figure 4.24 Parameter detail
All the parameters in this section are related with the Scene properties and communication objects. A scene contains values of: On/Off, Mode, Fan speed, Vane position, Setpoint Temperature and Remote Controller Disablement.
24
AC Setp. Temp: AC indoor unit setpoint temperature AC Ret. Temp: AC indoor unit return temperature KNX Amb. Temp.: Ambient temperature provided from KNX KNX Setp. Temp: Setpoint temperature provided from KNX
“AC Setp. Temp” = “AC Ret. Temp” - (“KNX Amb. Temp.” - “KNX Setp. Temp”)
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
29 / 54
4.7.1 Enable use of scenes
This parameter shows/hides the scene configuration parameters and communication objects.
Figure 4.25 Parameter detail
o If set to “No” the scene parameters and communication objects will not be shown. o If set to “Yes” the scene parameters and communication objects will be shown. To
execute a scene through the byte-type object, a value from “0” to “4” has to be sent, correponding each one to a different scene (i.e. 0 = Scene 1; 4 = Scene 5).
4.7.2 Scenes can be stored from KNX bus
This parameter shows/hides the Control_ Save/Exec Scene and all the Control_ Store Scene (if enabled) communication objects.
o If set to “No” the communication objects will not be shown. o If set to “Yes” the communication objects and a new parameter will appear. To store a
scene through the byte-type object, a value from “128” to “132” has to be sent to the object, correponding each one to a different scene (i.e. 128 = Scene 1; 132 = Scene
5).
Figure 4.26 Parameter detail
Enable use of bit objects for storing scenes (from bus)
If set to “No” the objects will not be shown.
If set to “Yes” the Control_ Store Scene objects for storing scenes will appear. To store a scene by using these objects, a “1” value has to be sent to the scene’s object
we want to store (i.e. to store scene 4, a “1” has to be sent to the Control_ Store Scene 4 object).
34
34
35
36
37
38
39
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
30 / 54
4.7.3 Enable use of bit objects for scene execution
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.
Figure 4.27 Parameter detail
o If set to “No” the communication objects will not be shown. o If set to “Yes” the communication objects will appear. To execute a scene by using these
objects, a “1” value has to be sent to the scene’s object we want to execute (i.e. to execute scene 4, a “1” has to be sent to the Control_ Execute Scene 4 object).
4.7.4 Scene “x” preset
This parameter lets define a preset for a scene (the following description is valid for all the scenes).
Figure 4.28 Parameter detail
o If set to “No” the preset for the scene “x” will be disabled. o If set to “Yes” the preset will be enabled. When a scene is executed the values configured
in the preset will be aplied.
Important: If a scene’s preset is enabled, will not be possible to modify (store) the scene
from the KNX bus.
Figure 4.29 Parameter detail
40
41
42
43
44
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
31 / 54
Scene “x” / Value for On-Off
This parameter lets choose the power of the indoor unit when the scene is executed. The following options are available: “ON”, “OFF” or (unchanged).
Scene “x” / Value for Mode
This parameter lets choose the mode of the indoor unit when the scene is executed. The following options are available: “AUTO (if available)”, “HEAT (if available)“, “COOL”, “FAN”, “DRY”, or “(unchanged)”.
Scene “x” / Value for Fan Speed
This parameter lets choose the fan speed of the indoor unit when the scene is executed. The following options are available: “FAN SPEED AUTO (if available)”, FAN SPEED 1”, FAN SPEED 2”, FAN SPEED 3”, “FAN SPEED 4 (if available)”, or “(unchanged)”.
Scene “x” / Value for Vane U-D (if available)
This parameter lets choose the vane position of the indoor unit when the scene is executed. The following options are available: “VANES U-D OFF”, “VANES U-D SWING”, “VANES U-D SWIRL (if available)” or “(unchanged)”.
Scene “x” / Value for Vane L-R (if available)
This parameter lets choose the vane position of the indoor unit when the scene is executed. The following options are available: “VANES L-R OFF”, “VANES L-R SWING”, “VANES L-R SWIRL (if available)” or “(unchanged)”.
Scene “x” / Value for Setpoint Temp (ºC)
This parameter lets choose the setpoint temperature of the indoor unit when the scene is executed. The following options are available: from “16ºC” to “30ºC” (both included) or “(unchanged)”.
Scene “x” / Value for Remote Lock
This parameter lets choose the remote controller status of the indoor unit when the scene is executed. The following options are available: “Locked (remote not allowed)”, “unlocked (remote allowed)or “(unchanged)”.
Important: If any preset value is configured as “(unchanged)”, the execution of
this scene will not change current status of this feature in the AC unit.
Important: When a scene is executed, Status_ Current Scene object shows the
number of this scene. Any change in previous items does Status_ Current Scene show
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
32 / 54
“No Scene”. Only changes on items marked as “(unchanged)” will not disable current scene.
Switch-Off Timeouts Configuration dialog
Figure 4.30 Default Switch-Off Timeouts Configuration dialog
All the parameters in this section are related with the timeout properties and communication objects.
4.8.1 Enable use of Open Window / Switch off timeout function
This parameter shows/hides the Control_ Switch Off Timeout communication object which lets Start/Stop a timeout to switch off the indoor unit.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Switch Off Timeout object and new parameters will appear.
If a “1” value is sent to this object, and the indoor unit is already turned on, the switch­off timeout will begin. If a “0” value is sent to this object, the switch-off timeout will stop.
Figure 4.31 Parameter detail
AC switch-off timeout (min)
This parameter lets select how much time (in minutes) to wait before switching off the indoor unit.
25
25
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
33 / 54
DPT for Window / Switch-off timeout
This parameter lets choose between the datapoints 0-Open / 1-Closed Window
[DPT_1.009] and 0-Stop / 1-Start Timeout [DPT_1.010] for the Control_ Switch Off Timeout.
Disallow On/Off operation while window is Open
If set to “No”, On/Off commands while the window is open will be accepted.
If a “1” value is sent to the Control_ Switch Off Timeout object the switch-off
timeout period will begin again.
If a “0” value is sent to the Control_ Switch Off Timeout object, no action will
be performed.
If set to “Yes”, On/Off commands, while the window is open, will be saved (but not applied). These commands will be used in the next parameter if set to “Yes”.
Reload last On/Off val once window is closed?
If set to “No”, once the switch-off timeout is stopped, any value will be reloaded.
If set to “Yes”, once the switch-off timeout is stopped, the last On/Off value sent will be reloaded.
If a “1” value is sent to the Control_ Switch Off Timeout object after the timeout
period, the indoor unit will turn on.
If a “0” value is sent to the Control_ Switch Off Timeout after the timeout
period, no action will be performed.
4.8.2 Enable use of Occupancy function
This parameter shows/hides the Control_ Occupancy communication object which lets apply different parameters to the indoor unit depending on the presence/no presence in the room.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Occupancy object and new parameters will appear. If a “1”
value is sent to this object (no room occupancy), the timeout will begin. If a “0” value is sent to this object, the timeout will stop.
Figure 4.32 Parameter detail
26
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
34 / 54
Timeout to apply action (minutes)
This parameter lets choose how much time to wait (in minutes) before executing the action specified in the next parameter (“Action after timeout elapsed”). This time is considered as a part of the occupancy.
Action after timeout elapsed
When Switch-Off is selected, once the timeout has elapsed, the indoor unit will be turned off.
When Apply Preset Delta is selected, once the timeout has elapsed, a delta temperature will be applied in order to save energy (decreasing the setpoint when in Heat mode, or increasing the setpoint when in Cool mode). Also new parameters will appear.
Figure 4.33 Parameter detail
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature (increase or decrease) that will be applied when the timeout has elapsed.
Important: When there is occupancy again after the application of a delta, the same
delta will be applied inversely. (i.e. In a room with AC in cool mode and 25ºC setpoint temperature, a +2ºC delta is applied after the occupancy timeout, setting the setpoint at 27ºC because there is no occupancy in the room. If the setpoint is raised to 29ºC during that period, when the room is occupied again, a -2ºC delta will be applied and the final setpoint temperature will then be 27ºC).
Enable secondary timeout
If set to “No” nothing will be applied.
If set to “Yes”, a new timeout will be enabled and two new parameters will appear.
Figure 4.34 Parameter detail
Timeout to apply action (minutes)
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
35 / 54
This parameter lets choose how much time to wait (in minutes) before
executing the action specified in the next parameter (“Action after timeout elapsed”).
Action after timeout elapsed
When Switch-Off is selected, once the timeout has elapsed, the indoor unit will turn off.
When Apply Preset Delta is selected, once the timeout configured is extinguished, a delta temperature will be applied (decreasing the setpoint when in Heat mode, or increasing the setpoint when in Cool mode). Also new parameters will appear.
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature that will be applied when the timeout is extinguished.
Important: When there is occupancy again after the application
of a delta, the same delta will be applied inversely as explained above.
Disallow On/Off operation while not Occupied
If set to “No”, On/Off commands while the window is open will be accepted.
If set to “yes”, once Switch-Off action has been executed, On/Off commands will be saved (but not applied). These commands will be used in the next parameter if set to “yes”.
Figure 4.35 Parameter detail
Consider that the countdown time (transitional time between occupancy and non­occupancy) is considered as a part of the occupancy status as explained before.
Reload last On/Off value when Occupied
If set to “No”, once the switch-off timeout has elapsed, any value will be reloaded.
If set to “Yes”, once the switch-off timeout has elapsed, the last On/Off value will be reloaded.
If a “1” value is sent to the Control_ Occupancy object after the timeout period,
the indoor unit will turn on.
If a “0” value is sent to the Control_ Occupancy after the timeout period no
action will be performed.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
36 / 54
4.8.3 Enable use of SLEEP timeout
This parameter shows/hides the Control_ Sleep Timeout communication object which lets start a timeout to automatically turn off the indoor unit.
o If set to “No” the object will not be shown. o If set to “Yes” the Control_ Sleep Timeout object and a new parameter will appear. If a
“1” value is sent to this object the switch-off timeout will begin. If a “0” value is sent to this object, the switch-off timeout will stop.
Figure 4.36 Parameter detail
Timeout to apply action (minutes)
This parameter lets select how much time (in minutes) to wait before switching off the AC unit.
Binary Input “x” Configuration dialog
Figure 4.37 Binary Input Configuration dialog
All the parameters in this section are related with the binary inputs properties and communication objects.
4.9.1 Enable use of Input “x”
This parameter enables the use of the Input “x” and shows/hides the Status_ Inx communication object(s) which will act as configured in the “Function” parameter.
27
84
86
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
37 / 54
o If set to “No” the objects will not be shown. o If set to “Yes” the Status_ Inx object(s) and new parameters will appear.
4.9.2 Contact type
This parameter lets choose the behavior that will have the binary input depending on if the contact is normally open or normally closed.
o There are two possible options to configure the contact type: “NO: Normally Open” and
“NC: Normally Closed”.
4.9.3 Debounce time
This parameter lets choose a debounce time (in milliseconds) that will be applied to the contact.
4.9.4 Disabling function
This parameter shows/hides the Control_ Disable Input x communication object which will let disable/enable the input x.
o If set to “No” any object will be shown. o When “DPT 1.003: 0-Disable; 1-Enable is selected, the input can be disabled using
the value “0” and enabled using the value “1”.
o When “DPT 1.002: 1-True (Disable); 0-False (Enable) is selected, the input can be
disabled using the value “1” and enabled using the value “0”.
4.9.5 Function
This parameter lets choose the function that will have the binary input. There are 7 different functions available: Switching, Dimming, Shutter/Blind, Value, Execute Scene (internal), Occupancy (internal) and Window Contact (internal).
o When “Switching” is selected the communication object and new parameters for the
Input “x” will appear as shown below.
88
90
45
45
84
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
38 / 54
Figure 4.38 Parameter detail
Send telegram after bus recovery
This parameter lets select if the Binary Input “x” will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled).
When “No action” is selected, no telegram will be sent after a bus recovery.
When “Current status” is selected, the binary input will send a telegram with
its current status after a bus recovery. Also a new parameter will appear (see below).
When “On” is selected, the binary input will send a telegram with a “1” value
after a bus recovery. Also a new parameter will appear (see below).
When “Off” is selected, the binary input will send a telegram with a “0” value
after a bus recovery. Also a new parameter will appear (see below).
Figure 4.39 Parameter detail
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
Value on rising edge
This parameter lets select the value that the Binary Input “x” will send on a rising edge
(contact activated).
When Onis selected, the binary input will always send telegrams with a “1”
value.
When Offis selected, the binary input will always send telegrams with a “0”
value.
When “Toggle (On/Off)” is selected, the binary input will send a “1” value
after a “0” value and viceversa.
When “No action” is selected, the binary input will not perform any action.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
39 / 54
Value on falling edge
This parameter lets select the value that the Binary Input “x” will send on a falling
edge (contact deactivated).
When “On” is selected, the binary input will always send telegrams with a “1”
value.
When “Off” is selected, the binary input will always send telegrams with a “0”
value.
When “Toggle (On/Off)” is selected, the binary input will send a “1” value
after a “0” value and viceversa.
When “No action” is selected, the binary input will not perform any action.
Cyclical sending
This parameter lets enable/disable cyclical sending when a determined condition is met.
When When output value is Onis selected, everytime a “1” value is sent,
it will be sent cyclically. Also a new parameter will appear (see below).
When When output value is Offis selected, everytime a “0” value is sent,
it will be sent cyclically. Also a new parameter will appear (see below).
When “Always” is selected, the binary input will send any value cyclically. Also
a new parameter will appear (see below).
When “Never” is selected, cyclical sending will be disabled.
Period for cyclical sending (seconds)
This parameter lets configure a time (in seconds) for the cyclical sending.
Figure 4.40 Parameter detail
o When Dimmingis selected the communication objects and new parameters for the
Input “x” will appear as shown below.
86
87
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
40 / 54
Figure 4.41 Parameter detail
Send telegram after bus recovery
This parameter lets select if the Binary Input “x” will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled).
When “No action” is selected, no telegram will be sent after a bus recovery.
When “On” is selected, the binary input will send a telegram with a “1” value
after a bus recovery. Also a new parameter will appear (see below).
When “Off” is selected, the binary input will send a telegram with a “0” value
after a bus recovery. Also a new parameter will appear (see below).
Figure 4.42 Parameter detail
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
Mode for short (long) operation
This parameter lets select the value that the Binary Input “x” will send on a rising edge (contact activated), for a short and a long operation.
When “On (increase)is selected, the binary input will always send telegrams
with a “1” value for a short operation, and an “increase step” for a long operation.
When “Off (decrease)is selected, the binary input will always send
telegrams with a “0” value for a short operation, and an “decrease step” for a long operation.
When “Toggle: On/Off (increase/decrease)” is selected: o For the short operation the binary input will send a “1” value after a “0”
value and viceversa.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
41 / 54
o For the long operation the binary input will send an “increase step” after
a “decrease step” and viceversa.
Important: Note that the first long operation in toggle depends on the last short
operation, meaning that after a “1” value will be sent a “decrease step” and after a “0” value will be sent an “increase step”.
Important: The time period between a short and a long operation is defined in the
parameter “Short/long operation limit (x100ms)”.
Increasing step
This parameter lets select the increasing step value (in %) that will be sent for a long operation.
Decreasing step
This parameter lets select the decreasing step value (in %) that will be sent for a long operation.
Short/long operation limit (x100ms)
This parameter lets introduce the time period difference for the short and the long operation.
Cycl. send. period in long oper. (x100ms)
This parameter lets configure a time (in seconds) for the cyclical sending of a long operation.
o When “Shutter/Blind” is selected the communication objects and new parameters for
the Input “x” will appear as shown below.
Figure 4.43 Parameter detail
Send telegram after bus recovery
88
89
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
42 / 54
This parameter lets select if the Binary Input “x” will send a telegram, or not, after a
bus recovery and the type of telegram sent (if enabled).
When “No action” is selected, no telegram will be sent after a bus recovery.
When Move Upis selected, the binary input will send a telegram with a 0
value after a bus recovery. Also a new parameter will appear (see below).
When “Move Downis selected, the binary input will send a telegram with a
1 value after a bus recovery. Also a new parameter will appear (see below).
Figure 4.44 Parameter detail
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
Operation
This parameter lets select the value that the Binary Input “x” will send on a rising edge
(contact activated).
When “Up” is selected, the binary input will always send telegrams with a “0”.
When Downis selected, the binary input will always send telegrams with a
1value.
When “Toggle (Up/Down)is selected the binary input will send a “0” value
after a “1” value and viceversa.
Method
This parameter lets select the working method for the shutter/blind.
When “Step-Move-Step” is selected: On a rising edge (contact activated) a
step/stop telegram will be sent and will begin a time called T1. If a falling edge occurs (contact deactivated) during the T1, no action will be performed.
If the rising edge is maintained longer than T1, a move telegram will be sent and will start a time called T2. If a falling edge occurs during the T2, a step/stop telegram will be sent. If a falling edge occurs after T2 no action will be performed.
When “Move-Step” is selected: On a rising edge a move telegram will be sent
and will begin the T2 time. If a falling edge occurs during the T2, a step/stop telegram will be sent. If a falling edge occurs after T2 no action will be performed.
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
43 / 54
Important: The T1 time have to be defined in the “Short/long operation limit
(x100ms)” parameter. Also the T2 time have to be defined in the “Vanes adjustment time (x100ms)” parameter.
Short/long operation limit (x100ms)
This parameter lets introduce the time period difference for the short and the long operation (T1 time).
Vanes adjustment time (x100ms)
This parameter lets introduce the time period for the vanes adjustment/blind movement (T2 time).
o When “Value” is selected the communication objects and new parameters for the Input
“x” will appear as shown below.
Figure 4.45 Parameter detail
Send telegram after bus recovery
This parameter lets select if the Binary Input “x” will send a telegram, or not, after a
bus recovery and the type of telegram sent (if enabled).
When “No action” is selected, no telegram will be sent after a bus recovery.
When “Fixed value” is selected, the binary input will send a telegram with the
same value configured in the “Value on rising edge” parameter. Also a new
parameter will appear (see below).
Figure 4.46 Parameter detail
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
DPT to be sent
91
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
44 / 54
This parameter lets select the DPT type for the value that will be defined in the next parameter. This value will be sent on a rising edge (contact activated).
Figure 4.47 Parameter detail
Value on rising edge (when contact activated)
This parameter lets define a value for the DTP type configured in the “DPT to be sent” parameter. This value will be sent on a rising edge (contact activated).
o When Execute Scene (internal)is selected, the binary input “x” will activate the scene
defined in the next parameter, on a rising edge (contact activated).
Figure 4.48 Parameter detail
Scene when contact is activated
This parameter lets choose the scene that will be activated on a rising edge. This scene MUST be defined in the Scene Configuration dialog as a preset.
o When “Occupancy (internal)” is selected, the binary input “x” will have the same
behavior as configured in the parameter “Enable use of Occupancy function” inside the “Switch-Off Timeouts Configuration” dialog.
Figure 4.49 Parameter detail
o When “Window Contact (internal)” is selected, the binary input “x” will have the same
behavior as configured in the parameter “Enable use of Open Window / Switch off timeout function” inside the “Switch-Off Timeouts Configuration” dialog.
Figure 4.50 Parameter detail
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
45 / 54
5. Specifications
Envelope
Plastic, type ABS (UL 94 V-0). 2,5 mm thickness
Dimensions
71 X 71 X 27 mm
Weight
70g
Color
White, RAL 9010
Power supply
29V DC, 7mA Supplied through KNX bus.
LG AB Bus
Voltage: 13-15V Current: 10mA
LED indicators
1 x KNX programming.
Push buttons
1 x KNX programming.
Binary inputs
4 x Potential-free binary inputs. Signal cable length: 5m unshielded, may be extended up to 20m with twisted. Compliant with the following standards: IEC61000-4-2 : level 4 - 15kV (air discharge) - 8kV (contact discharge) MIL STD 883E-Method 3015-7 : class3B
Configuration
Configuration with ETS.
Operating Temperature
From -25ºC to 60ºC
Storage Temperature
From -40ºC to 85ºC
Isolation Voltage
2500V
RoHS conformity
Compliant with RoHS directive (2002/95/CE).
Certifications
CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC) EN 61000-6-1; EN 61000-6-3; EN 60950-1; EN 50491-3; EN 50090­2-2; EN 50428; EN 60669-1; EN 60669-2-1
71 mm
71 mm
27 mm
Programming LED
AC Indoor unit RYB bus connection
KNX bus
connection
Programming button
Binary inputs
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
46 / 54
6. AC Unit Types compatibility
A list of LG indoor unit model references compatible with INKNXLGE001R000 and their available features can be found in:
https://www.intesis.com/docs/compatibilities/inxxxlge001r000_compatibility
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
47 / 54
7. Error Codes
Error in
KNX
Remote
Control Error
Error Description
1
1
Room air sensor fault
2
2
Indoor unit pipe in sensor fault
3
3
communication fault between wired remote controller and indoor unit
4
4
Drain pump fault
5
5
Communication fault between indoor unit and outdoor unit
6
6
Indoor unit pipe out sensor fault
7
7
Indoor unit mode runs on opposite to outdoor unit
8
8
N/A 9 9
EEPROM memory fault
10
10
BLDC motor signal fault or motor lock
11
11
HEX middle point sensor fault
12
12
heater terminal block sensor fault
13
13
N/A
14
14
N/A
15
15
N/A
16
16
N/A
17
17
Outlet air sensor fault
18
18
Return air sensor fault
19
19
No communication response from sub PCB to main PCB
20
20
No communication response from main PCB to sub PCB
21
21
IPM fault
22
22
AC input is over current (RMS)
23
23
DC link low or high voltage
24
24
High pressure or low pressure switch on
25
25
High/low input voltage
26
26
Compressor start failure
27
27
PSC/PFC fault
28
28
DC link high voltage
29
29
Over current at compressor input
32
32
Discharge temperature is high at inverter compressor
33
33
Discharge temperature is high at constant speed compressor
34
34
High pressure is too high
35
35
Low pressure is too low
36
36
Compression ratio is too low
39
39
Communication fault between PFC and inverter PCB
40
40
CT sensor fault
41
41
Discharge sensor at inverter compressor is fault
42
42
Low pressure sensor is fault
43
43
High pressure sensor is fault
44
44
Air sensor at outdoor unit is fault
45
45
HEX sensor at outdoor unit is fault
46
46
Compressor suction sensor is fault
47
47
Discharge sensor at constant speed compressor is fault
48
48
HEX outlet sensor at outdoor unit is fault
49
49
IPM temperature sensor is fault
50
50
Missing phase among 3 phase
51
51
Over combination ratio
52
52
No communication from inverter PCB detected at main PCB
53
53
Communication fault between indoor and outdoor unit
54
54
Reverse phase is detected
57
57
No communication from main PCB detected at inverter PCB
59
59
Wrong outdoor unit combination
60
60
Inverter EEPROM memory fault
61
61
Outdoor pipe temperature is too high
Intesis
TM
KNX – LG VRF lines
User's manual r1.7 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
48 / 54
62
62
IPM temperature is too high
65
65
IPM temperature sensor is fault
67
67
Fan locked or fan start failure
69
69
CT sensor of constant speed compressor 1 is fault
70
70
CT sensor of constant speed compressor 2 is fault
71
71
PFC CT sensor fault
72
72
Fuction error of outdoor 4way valve.(reversing valve)
73
73
DC peak current is over
74
74
Unbalance at 3 phase
75
75
Fan CT sensor fault
76
76
Fan DC link voltage is high
77
77
Fan input voltage is high
78
78
Fan hall sensor fault
79
79
Fan motor start failure
86
86
Main PCB EEPROM is fault
87
87
Fan PCB EEPROM is fault
88
88
PFC PCB EEPROM is fault
90
90
Inlet temperature sensor of external PCB is fault
91
91
Outlet temperature sensor of external PCB is fault
104
104
No Communication from slave is detected
105
105
Communication fault between fan and inverter PCB
106
106
Fan PCB IOM fault
107
107
Fan DC link voltage is low
113
113
Liquid pipe sensor fault
114
114
Subcooling inlet pipe sensor fault
115
115
Subcooling outlet pipe sensor fault
116
116
Oil level sensor fault
145
145
No communication from external PCB is detected at main PCB
151
151
4 way valve failure
153
153
Upper HEX sensor fault
154
154
Bottom HEX sensor fault
173
173
Over / low current at constant speed compressor 1
174
174
Over / low current at constant speed compressor 2
182
182
Communication fault betwen main and sub micom in external PCB
187
187
Hydrokit water temperature sensor fault
190
190
Inverter PCB heak sink temperature is high
191
191
Inverter PCB heat sink temperature sensor fault
193
193
Fan PCB heak sink temperature is high
194
194
Fan PCB heat sink temperature sensor fault
200
200
Auto piping failure
201
201
Fault at liquid pipe sensor of HR unit
202
202
Fault at subcooling inlet pipe sensor of HR unit
203
203
Fault at subcooling outlet pipe sensor of HR unit
204
204
No communication from outdoor unit is detected at HR unit
205
205
HR unit addresses are duplicated
237
237
No response from outdoor unit modem at indoor unit modem
238
238
No response from outdoor unit at outdoor unit modem
Please, check your LG manual for a better understating of the error codes present in the associated Communication Object.
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
49 / 54
8. Appendix A – Communication Objects Table
TOPIC
OBJECT
NUMBER
NAME
LENGTH
DATAPOINT TYPE
FLAGS
FUNCTION
DPT_NAME
DPT_ID
R W T
U
On/Off
0
Control_ On/Off
1 bit
DPT_Switch
1.001
W T 0 - Off; 1-On
Mode
1
Control_ Mode
1 byte
DPT_HVACContrMode
20.105
W T 0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
2
Control_ Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
W T 0 - Cool; 1 - Heat;
3
Control_ Mode Cool & On
1 byte
DPT_Scaling
5.001
W T 0% - Off; 0.1%-100% - On + Cool
4
Control_ Mode Heat & On
1 byte
DPT_Scaling
5.001
W T 0% - Off; 0.1%-100% - On + Heat
5
Control_ Mode Auto
1 bit
DPT_Bool
1.002
W T 1 - Auto
6
Control_ Mode Heat
1 bit
DPT_Bool
1.002
W T 1 - Heat
7
Control_ Mode Cool
1 bit
DPT_Bool
1.002
W T 1 - Cool
8
Control_ Mode Fan
1 bit
DPT_Bool
1.002
W T 1 - Fan
9
Control_ Mode Dry
1 bit
DPT_Bool
1.002
W T 1 - Dry
10
Control_ Mode +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Mode +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
Fan Speed
11
Control_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
W T
0%-49% - Speed 1; 50%-82% - Speed 2; 83%-100% - Speed 3;
Control_ Fan Speed / 3 Speeds
1 byte
DPT_Enumerated
5.010
W T 1 - Speed 1; 2 - Speed 2; 3 Speed 3;
Control_ Fan Speed / 4 Speeds
1 byte
DPT_Scaling
5.001
W T
0%-37% - Speed 1; 38%-62% - Speed 2; 63%-87% - Speed 3; 88%-100% - Speed 4;
Control_ Fan Speed / 4 Speeds
1 byte
DPT_Enumerated
5.010
W T
1- Speed 1; 2- Speed 2; 3- Speed 3; 4- Speed 4;
12
Control_ Fan Speed Man/Auto
1 bit
DPT_Bool
1.002
W T 0 – Manual; 1 – Auto
13
Control_ Fan Speed 1
1 bit
DPT_Bool
1.002
W T 1 – Set Fan Speed 1
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
50 / 54
Fan Speed
14
Control_ Fan Speed 2
1 bit
DPT_Bool
1.002
W T 1 – Set Fan Speed 2
15
Control_ Fan Speed 3
1 bit
DPT_Bool
1.002
W T 1 – Set Fan Speed 3
16
Control_ Fan Speed 4
1 bit
DPT_Bool
1.002
W T 1 – Set Fan Speed 3
17
Control_ Fan Speed +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Fan Speed +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
Vanes
Up-Down
18
Control_ Vanes U-D Swing
1 bit
DPT_Bool
1.002
W T 0 - Off; 1 - Swing
19
Control_ Vanes U-D Swirl
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 - Swirl
Vanes
Left-Right
20
Control_ Vanes L-R Swing
1 bit
DPT_Bool
1.002
W T 0 - Off; 1 - Swing
21
Control_ Vanes L-R Swirl
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 - Swirl
Temperature
22
Control_ Setpoint Temperature
2 byte
DPT_Value_Temp
9.001
W T (ºC)
23
Control_ Setpoint Temp +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Setpoint Temp +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
24
Control_ Ambient Temperature
2 byte
DPT_Value_Temp
9.001
W T (ºC)
Timeout
25
Control_ Window Contact Status
1 bit
DPT_OpenClose
1.009
W T 0 - Open; 1 - Closed
Control_ Switch Off Timeout
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
26
Control_ Occupancy
1 bit
DPT_Occupancy
1.018
W T 0 - Not Occupied; 1 - Occupied
27
Control_ Sleep Timeout
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
Locking
28
Control_ Lock Remote Control
1 bit
DPT_Bool
1.002
W T 0 - Unlock; 1 - Lock
29
Control_ Lock Control Objects
1 bit
DPT_Bool
1.002
W T 0 - Unlock; 1 - Lock
Special Modes
30
Control_ Power Mode
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
31
Control_ Econo Mode
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
32
Control_ Additional Heat
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
51 / 54
33
Control_ Additional Cool
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
Scenes
34
Control_ Save/Exec Scene
1 byte
DPT_SceneControl
18.001
W T
0 to 4 - Exec. Scene 1 to 5; 128 to 132 - Save Scene 1 to 5
35
Control_ Store Scene1
1 bit
DPT_Bool
1.002
W 1 - Store Scene
36
Control_ Store Scene2
1 bit
DPT_Bool
1.002
W 1 - Store Scene
37
Control_ Store Scene3
1 bit
DPT_Bool
1.002
W 1 - Store Scene
38
Control_ Store Scene4
1 bit
DPT_Bool
1.002
W 1 - Store Scene
39
Control_ Store Scene5
1 bit
DPT_Bool
1.002
W 1 - Store Scene
40
Control_ Execute Scene1
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
41
Control_ Execute Scene2
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
42
Control_ Execute Scene3
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
43
Control_ Execute Scene4
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
44
Control_ Execute Scene5
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
Binary Input
Disabling
45
Control_ Disable Input 1
1 bit
DPT_Bool
1.002
W T 0 - False; 1 - True
Control_ Disable Input 1
1 bit
DPT_Enable
1.003
W T 0 - Disable; 1 - Enable
46
Control_ Disable Input 2
1 bit
DPT_Bool
1.002
W T 0 - False; 1 - True
Control_ Disable Input 2
1 bit
DPT_Enable
1.003
W T 0 - Disable; 1 - Enable
47
Control_ Disable Input 3
1 bit
DPT_Bool
1.002
W T 0 - False; 1 - True
Control_ Disable Input 3
1 bit
DPT_Enable
1.003
W T 0 - Disable; 1 - Enable
48
Control_ Disable Input 4
1 bit
DPT_Bool
1.002
W T 0 - False; 1 - True
Control_ Disable Input 4
1 bit
DPT_Enable
1.003
W T 0 - Disable; 1 - Enable
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
52 / 54
On/Off
50
Status_ On/Off
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
Mode
51
Status_ Mode
1 byte
DPT_HVACContrMode
20.105
R T 0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
52
Status_ Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
R T 0 - Cool; 1 - Heat
53
Status_ Mode Auto
1 bit
DPT_Bool
1.002
R T 1 - Auto
54
Status_ Mode Heat
1 bit
DPT_Bool
1.002
R T 1 - Heat
55
Status_ Mode Cool
1 bit
DPT_Bool
1.002
R T 1 - Cool
56
Status_ Mode Fan
1 bit
DPT_Bool
1.002
R T 1 - Fan
57
Status_ Mode Dry
1 bit
DPT_Bool
1.002
R T 1 - Dry
58
Status_ Mode Text
14 byte
DPT_String_8859_1
16.001
R T ASCII String
Fan Speed
59
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
W T
33% - Speed 1; 67% - Speed 2; 100% - Speed 3;
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Enumerated
5.010
W T 1 - Speed 1; 2 - Speed 2; 3 Speed 3;
Status_ Fan Speed / 4 Speeds
1 byte
DPT_Scaling
5.001
W T
25% - Speed 1; 50% - Speed 2; 75% - Speed 3; 100% - Speed 4;
Status_ Fan Speed / 4 Speeds
1 byte
DPT_Enumerated
5.010
W T 1- Speed 1; 2- Speed 2; 3- Speed 3; 4- Speed 4;
60
Status_ Fan Speed Manual/Auto
1 bit
DPT_Bool
1.002
R T 0 – Manual; 1 - Auto
61
Status_ Fan Speed 1
1 bit
DPT_Bool
1.002
R T 1 – Fan is in speed 1
62
Status_ Fan Speed 2
1 bit
DPT_Bool
1.002
R T 1 – Fan is in speed 2
63
Status_ Fan Speed 3
1 bit
DPT_Bool
1.002
R T 1 - Fan is in Speed 3
64
Status_ Fan Speed 4
1 bit
DPT_Bool
1.002
R T 1 - Fan is in Speed 4
65
Status_ Fan Speed Text
14 byte
DPT_String_8859_1
16.001
R T ASCII String
Vanes
Up-Down
66
Status_ Vanes U-D Swing
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 - Swing
67
Status_ Vanes U-D Swirl
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 – Swirl
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
53 / 54
Vanes
Left-Right
68
Status_ Vanes L-R Swing
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 - Swing
69
Status_ Vanes L-R Swirl
1 bit
DPT_Bool
1.002
W T 0 – Off; 1 - Swirl
Temperature
70
Status_ AC Setpoint Temp
2 byte
DPT_Value_Temp
9.001
R T (ºC)
71
Status_ AC Ambient Ref Temp
2 byte
DPT_Value_Temp
9.001
R T (ºC)
Error
72
Status_ Error/Alarm
1 bit
DPT_Alarm
1.005
R T 0 - No Alarm; 1 - Alarm
73
Status_ Error Code
2 byte
Enumerated
R T 0 - No Error; Any other see user's manual
74
Status_ Error Text code
14 byte
DPT_String_8859_1
16.001
R T 2 char LG Error; Empty - none
Locking
75
Status_ Lock Remote Control
1 bit
DPT_Bool
1.002
R T 0 - Unlocked; 1 – Locked
76
Status_ Lock Control Objects
1 bit
DPT_Bool
1.002
R T 0 - Unlocked; 1 - Locked
Special
Modes
77
Status_ Power Mode
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
78
Status_ Econo Mode
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
79
Status_ Additional Heat
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
80
Status_ Additional Cool
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
Counter
81
Status_ Operation Hour Counter
2 byte
DPT_TimePeriodHrs
7.007
R T Number of operating hours
82
Status_ Operation Sec Counter
4 byte
DPT_LongDeltaTimeSec
13.100
R T Number of operating seconds
Scene
83
Status_ Current Scene
1 byte
DPT_SceneNumber
17.001
R T 0 to 4 - Scene 1 to 5; 63 - No Scene
Binary Inputs
84
86
88
90
Status_ Inx - Switching
1 bit
DPT_Switch
1.001
R T 0 - Off; 1-On
Status_ Inx – Dimming - On/Off
1 bit
DPT_Switch
1.001
R T 0 - Off; 1 - On
Status_ Inx – Shut/Blind - Step
1 bit
DPT_ShutterBlinds
1.023
R T 0 – Step Up; 1 – Step Down
Status_ Inx – Value
1 byte
DPT_Value_1_Ucount
5.010
R T 1 byte unsigned value
85
87
Status_ Inx – Value
2 byte
DPT_Value_2_Ucount
7.001
R T 2 byte unsigned value
Status_ Inx – Value
2 byte
DPT_Value_2_Count
8.001
R T 2 byte signed value
Intesis
TM
KNX – LG AC
User's manual 1.6 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
54 / 54
89
91
Status_ Inx – Value
2 byte
DPT_Value_Temp
9.001
R T Temperature (ºC)
Status_ Inx – Value
4 byte
DPT_Value_4_Ucount
12.001
R T 4 byte unsigned value
Status_ Inx – Dimming – Step(%)
1 bit
DPT_Control_Dimm.
3.007
R T Dimming step
Status_ Inx - Shut/Blind -Move
1 bit
DPT_ShutterBlinds
1.023
R T 0 – Move Up; 1 – Move Down
Loading...