
Compatible with Digital Inverter & VRF lines
USER MANUAL
Issue date: 04/2019 r2.7 ENGLISH

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Modbus RTU (EIA-485) Interface for Toshiba air
conditioners
Compatible with Digital Inverter & VRF lines

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks
of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility
or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product
development. The information in this document shall therefore not be construed as a commitment on the
part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no
commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only
intended to help improve understanding of the functionality and handling of the product. In view of the wide
range of possible applications of the product, and because of the many variables and requirements associated
with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for
actual use based on the data, examples or illustrations included in this document nor for any damages incurred
during installation of the product. Those responsible for the use of the product must acquire sufficient
knowledge in order to ensure that the product is used correctly in their specific application and that the
application meets all performance and safety requirements including any applicable laws, regulations, codes
and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility
for any problems that may arise as a result from the use of undocumented features or functional side effects
found outside the documented scope of the product. The effects caused by any direct or indirect use of such
aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
INDEX
1. Presentation .......................................................................................................... 5
2. Connection ............................................................................................................ 6
2.1 Connect to the AC indoor unit ............................................................................... 6
2.2 Connection to the EIA-485 bus ............................................................................. 6
3. Quick Start Guide ................................................................................................... 7
4. Modbus Interface Specification ................................................................................ 8
4.1 Modbus physical layer.......................................................................................... 8
4.2 Modbus Registers ................................................................................................ 8
4.2.1 Control and status registers ........................................................................... 8
4.2.2 Configuration Registers................................................................................ 10
4.3 Modbus Registers for Advanced Functions ............................................................ 10
4.3.1 Advanced registers for Indoor Unit status ...................................................... 10
4.3.2 Advanced registers for Outdoor Unit Status on VRF-SMMSi Systems .................. 11
4.3.3 Advanced registers for Outdoor Unit Status on VRF-SHRM/SMMS Systems ...... 13
4.3.4 Advanced registers for Outdoor Unit Status on RAV Systems ............................ 14
4.3.5 Advanced registers for Indoor Unit Type and Refresh Time adjustment .............. 15
4.3.6 Considerations on Temperature Registers ...................................................... 16
4.4 DIP-switch Configuration Interface ...................................................................... 18
4.5 Implemented Functions ..................................................................................... 21
4.6 Device LED indicator ......................................................................................... 21
4.7 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................... 22
5. Electrical and Mechanical features .......................................................................... 23
6. List of supported AC Unit Types. ............................................................................ 24
7. Error Codes ......................................................................................................... 25

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
1. Presentation
The INMBSTOS001R000 interfaces allow a complete and natural
integration of Toshiba air conditioners into Modbus RTU (EIA-485)
networks.
Compatible with Digital Inverter & VRF lines.
Reduced dimensions. 93 x 53 x 58 mm
3.7” x 2.1” x 2.3”
• Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit of AC.
• External power not required.
• Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSTOS001R000 devices
can be connected in the same network.
INMBSTOS001R000 is a Modbus slave device.
• Direct connection to the AC indoor unit. Up to 16 AC indoor units can be connected to
INMBSTOS001R000, controlling them as one (not individually).
• Configuration from both on-board DIP-switches and Modbus RTU.
• Total Control and Supervision.
• Real states of the AC unit's internal variables.
• Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation
of Modbus Repeaters may be required
• SCADA
• PLC
• DDC
• BMS
• HMI
• Controller
• etc
Up to 63
AC indoor
units*
Modbus RTU
EIA-485 network
INMBSTOS001R000
INMBSTOS001R000

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2. Connection
The interface comes with a plug-in terminal block of 2 poles to establish direct connection with
the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct
connection with the Modbus RTU EIA-485 network.
2.1 Connect to the AC indoor unit
The INMBSTOS001R000 connects directly to the Toshiba AB Bus, which is not provided within
the interface. The recommended connection’ methods are the following ones (details in Figure
2. 1):
• Wired remote control available.
• No remote control available
Maximum AB bus length is 500 m / 1,640.42 ft. The bus has no polarity sensitivity.
Important: If a wired remote controller of the AC manufacturer is connected in the same bus,
communication may shut down.
2.2 Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block of INMBSTOS001R000 and keep
the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is
1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus.
A terminator resistor of 120Ω must be present at each end of the bus to avoid signal reflections.
The bus needs a fail-safe biasing mechanism (see section 4.7 for more details).
(It is not mandatory to have it in the network)
Internal
electronic
control board
Internal
electronic
control board
90 mm / 3.5”
53 mm / 2.1”
For wall mounting
extract the upper
and down staples
until you hear the
"click".
Figure 2. 1 INMBSTOS001R000 connection diagram

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3. Quick Start Guide
1. Disconnect the air conditioning from the Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety
instructions given).
3. Connect the AB bus between the interface and the AC indoor unit following the
instructions of the diagram. Screw each bare cable end in the corresponding AB
terminals of each device.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters (see section 4.4).
By default, the interface is set to:
▪ Modbus Slave Address ➔ 1
▪ Modbus baud rate ➔ 9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be
applied.
7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to
start communicating.

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4. Modbus Interface Specification
4.1 Modbus physical layer
INMBSTOS001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485
line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).
4.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian
notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
AC unit On/Off
▪ 0: Off
▪ 1: On
AC unit Mode 1
▪ 0: Auto
▪ 1: Heat
▪ 2: Dry
▪ 3: Fan
▪ 4: Cool
AC unit Fan Speed 1
▪ 0: Auto
▪ 1: Low
▪ 2: Mid
▪ 3: High
AC unit Vane Position 1
▪ 1: POS1 (Horizontal)
▪ 2: POS2 (Horizontal)
▪ 3: POS3 (Medium)
▪ 4: POS4 (Vertical)
▪ 5: POS5 (Vertical)
▪ 6: POS6
▪ 7: POS7
▪ 10: Swing
AC unit Temperature Setpoint
1,2,3
▪ -32768 (Initialization value)
▪ 16..32ºC (ºC/x10ºC)
▪ 61..90ºF
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.3.6 for more
information.
It is not possible turn to x10 the value shown in Fahrenheit.

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
AC unit Temperature reference
1,2,3
▪ -32768: Initial value. Value invalid, which
comes from the IU’s sensor. If the value that
is shown in register 22 (23 PLC) is valid, the
address is going to take this value.
▪ Ranges are specific from Manufacturer
(ºC/x10ºC/ºF)
Window Contact
▪ 0: Closed (Default)
▪ 1: Open
INMBSTOS001R000 Disablement 4
▪ 0: INMBSTOS001R000 enabled (Default)
▪ 1: INMBSTOS001R000 disabled
AC Remote Control Disablement 4
▪ 0: Remote Control enabled (Default)
▪ 1: Remote Control disabled
AC unit Operation Time 4
▪ 0..65535 (hours). Counts the time the AC
unit is in “On” state.
AC unit Alarm Status
▪ 0: No alarm condition
▪ 1: Alarm condition
Error Code 5
▪ 0: No Error active
▪ 65535 (-1): Error in the communication of
INMBSTOS001R000 with the AC indoor unit.
▪ Any other error present, see the table at the
end of this document.
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
1,2,3,6
▪ -32768: Initialization value. No temperature
is being provided from an input sensor.
There’s no input sensor.
▪ Any other: (ºC/x10ºC/ºF)
AC Real temperature setpoint
1,2,3,6
▪ There’s no Virtual Temperature. The value
equals to the value of register 5 (6 PLC). The
value which is introduced by the user is the
one that the machine uses (the external
sensor is able to write directly over the
machine to do this operation).
▪ Ranges are specific from Manufacturer
(ºC/x10ºC/ºF)
Block Periodic Sendings
4,7,8
▪ 0: Non-blocked (Default value)
▪ 1: Blocked
This value is stored in non-volatile memory
See section 7 for possible error codes and their explanation
See section 4.3.6 for more information
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value.
This register applies to firmware version 2.3 onwards

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
“Open Window” switch-off timeout 9
▪ 0..30 (minutes)
▪ Factory setting: 30 (minutes)
Modbus RTU baud-rate 10
▪ 2400bps
▪ 4800bps
▪ 9600bps (Default)
▪ 19200bps
▪ 38400bps
▪ 57600bps
▪ 76800bps
▪ 115200bps
Modbus Slave Address
▪ 1..63
While the initialization is ongoing, some Modbus registers indicate an undetermined value. Once
the normal operation starts, they acquire its corresponding value. It is important to keep in
mind that any change done during the initialization process will not have effect until it has been
finished.
4.3 Modbus Registers for Advanced Functions
4.3.1 Advanced registers for Indoor Unit status
These registers are only available when the indoor unit’s type selected on SW1 is different from
the default value. Please, check the Section 4.4 for more information.
NOTE: IU stands for Indoor Unit’s index
Register Address
(Protocol address)
Register Address
(PLC address)
Indoor Unit exist
▪ 0: Doesn’t exist
▪ 1: Exist
Indoor Unit address
▪ MSB – OU address ; LSB – IU
address
Indoor Unit defrost
▪ 0: Off
▪ 1: On
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
The range 38400bps-115200bps applies to firmware version 2.3 onwards

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(Protocol address)
Register Address
(PLC address)
Indoor Unit filter alarm
▪ 0: No alarm
▪ 1: Alarm
Indoor Unit 11hermos ON.
▪ 0: Cool
▪ 1: Heat
Room temperature (During
Control)
▪ x1 ºC
Room temperature (Remote
Controller)
▪ x1 ºC
Indoor suction temperature (TA)
▪ x1 ºC
Indoor fan coil temperature (TCJ)
▪ x1 ºC
Indoor fan coil temperature
(TC2)
▪ x1 ºC
Indoor fan coil temperature
(TC1)
▪ x1 ºC
Indoor discharge temperature
(TF)
▪ x1 ºC
▪ Only for VRF systems
Revolutions indoor fan
▪ RPS
▪ Only for RAV systems
Indoor PMV opening
▪ x1, x10 Pulses
▪ Only for VRF systems
Running hours indoor fan
▪ x100 hours
▪ Only for RAV systems
Time filtersign
▪ Hours
▪ Only for RAV systems
Estimated supply air temperature
▪ x1 ºC
▪ Only for RAV systems
4.3.2 Advanced registers for Outdoor Unit Status on VRF-SMMSi Systems
These registers are only available when the indoor unit’s type selected on SW1 is different from
the default value. Please, check section 4.4 for more information.
Register Address
(protocol address)
Register Address
(PLC address)

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
High-pressure sensor detention
pressure (Pd)
▪ X100 Mpa
Low-pressure sensor detention
pressure (Ps)
▪ X100 Mpa
Compressor 1 discharge
temperature (Td1)
▪ x1 ºC
Compressor 2 discharge
temperature (Td2)
▪ x1 ºC
Compressor 3 discharge
temperature (Td3)
▪ x1 ºC
Suction temperature (TS)
▪ x1 ºC
Outdoor fan coil temperature 1
(TE1)
▪ x1 ºC
Outdoor fan coil temperature 2
(TE2)
▪ x1 ºC
Temperature at liquid side (TL)
▪ x1 ºC
Outside ambient temperature
(TO)
▪ x1 ºC
PMV1 + 2 opening
▪ x1 Pulse
Compressor 1 current (I1)
▪ x10 A
Compressor 2 current (I2)
▪ x10 A
Compressor 3 current (I3)
▪ x10 A
Outdoor fan current (Ifan)
▪ x10 A
Compressor 1 revolutions
▪ x10 RPS
Compressor 2 revolutions
▪ x10 RPS
Compressor 3 revolutions
▪ x10 RPS
Outdoor fan mode
▪ x1 mode
Compressor IPDU 1 heat sink
temperature
▪ x1 ºC
Compressor IPDU 2 heat sink
temperature
▪ x1 ºC
Compressor IPDU 3 heat sink
temperature
▪ x1 ºC

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
Outdoor fan IPDU heat sink
temperature
▪ x1 ºC
Heating/cooling recovery
controlled ∗5
▪ 0: Normal
▪ 1: Recovery controlled
Pressure release ∗5
▪ 0: Normal
▪ 1: Recovery controlled
Discharge temperature release ∗5
▪ 0: Normal
▪ 1: Recovery controlled
Follower unit release (U2/U2/U4
outdoor units) ∗5
▪ 0: Normal
▪ 1: Recovery controlled
Outdoor unit horsepower
▪ x1 HP
4.3.3 Advanced registers for Outdoor Unit Status on VRF-SHRM/SMMS
Systems
These registers are only available when the indoor unit’s type selected on SW1 is different from
the default value. Please, check section 4.4 for more information
Register Address
(protocol address)
Register Address
(PLC address)
Td1-Compressor 1 Discharge
Temp.
▪ x1 ºC
Td2-Compressor 2 Discharge
Temp.
▪ x1 ºC
Pd – High Pressure Sensor
▪ Mpa
Ps – Low Pressure Sensor
▪ Mpa
TS – Suction Temp.
▪ x1 ºC
TE – Outdoor Heat Exchanger
Temp.
▪ x1 ºC
TL – Liquid Temp.
▪ x1 ºC
TO – Outside ambient
temperature
▪ x1 ºC
TU – Low Pressure Saturated
Temp.
▪ x1 ºC

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
PMV1 + 2 Opening
▪ 0..100
Compressor 1, 2
▪ 0: Off
▪ 1: On
4.3.4 Advanced registers for Outdoor Unit Status on RAV Systems
These registers are only available when the indoor unit’s type selected on SW1 is different from
the default value. Please, check section 4.4 for more information
Register Address
(protocol address)
Register Address
(PLC address)
Outdoor Unit duty
▪ 0..15
TE temperature (evaporator)
▪ x1 ºC
TO temperature outdoor
▪ x1 ºC
Compressor discharge
temperature
▪ x1 ºC
Suction temperature TS
▪ x1 ºC
Temperature thyristor THS
▪ x1 ºC
Temperature at liquid side TL
▪ x1 ºC
Compressor revolutions
▪ RPS
Revolutions lowest Fan
▪ RPS
Revolutions upper Fan
▪ RPS
Running hours compressor
▪ x100 hours

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.3.5 Advanced registers for Indoor Unit Type and Refresh Time adjustment
Register Addr
(protocol address)
Register Addr
(PLC address)
Indoor Unit Type
▪ 0: Not defined (extra signals
disabled)
▪ 1: RAV
▪ 2: VRF (SMMSi)
▪ 3: VRF (SHRM/SMMS)
Refresh Time Adjust
▪ 1..4
Refresh Time Adjust
This parameter indicates the cadence when reading priority signals.
Priorities are defined as follows and can’t be modified:
0: Update on start-up
1: High priority
2: Low priority
The higher the value, the fastest the priority signals are going to update.
The cadence is defined by:
1: One high priority signal and one low priority signal’s poll.
2: Two high priority signals and one low priority signal’s poll.
3: Three high priority signals and one low priority signal’s poll.
4: Four high priority signals and one low priority signal’s poll.

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.3.6 Considerations on Temperature Registers
• AC unit temperature setpoint (R/W)
(register 4 – in Protocol address / register 5 – in PLC address):
This is the adjustable temperature setpoint value that must be required by the user.
This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16).
A remote controller connected to the Toshiba indoor unit will report the same
temperature setpoint value as this register.
• AC unit temperature reference (R)
(register 5 – in Protocol address / register 6 – in PLC address):
This register reports the temperature that is currently used by the Toshiba indoor unit as
the reference of its own control loop.
If the value on the register 22 is valid (different from 0x8000), it will report the value
from this register. If not, it will show the indoor unit reference temperature.
It is a read-only register (Modbus functions 3 or 4).
Depending on the mode selected, the register shows a different value:
Heat Mode:
Temperature reference = Ambient temperature +0.5ºC
Dry Mode / Fan Mode / Cool mode:
Temperature reference = Ambient temperature -0.5ºC
When the mode changes from Heat to anyone else, or from anyone else to Heat, the
register updates the value using the intervals +0.5ºC/-0.5ºC
• AC unit external temperature reference (Modbus) (R/W)
(register 22 – in Protocol address / register 23 – in PLC address):
This register reports the temperature from an external sensor in the Modbus side. If
valid value is received, the Modbus register will indicate a 0x8000 value.
This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16).
• AC Real temperature setpoint (R)
(register 23 – In Protocol address / register 24 – in PLC address):
This register will show the same value as in register 4 (protocol address). The reference
temperature from the remote controller is sent directly to the AC unit to be applied in the
control loop.
It is a read-only register (Modbus functions 3 or 4).
Moreover, notice that temperature’s values of all these four registers are expressed according to
the temperature´s format configured through its onboard DIP-Switches (See “4.4 -

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
DIP-switch Configuration Interface”). These following formats are possible:
• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a
value “22” in the Modbus register must be interpreted as 22ºC)
• Decicelsius value: Value in Modbus register is the temperature value in
decicelsius (i.e. a value “220” in the Modbus register must be interpreted as
22.0ºC)
• Fahrenheit value: Value in Modbus register is the temperature value in
Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72 ºF
(~22ºC).

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.4 DIP-switch Configuration Interface
All the configuration values on INMBSTOS001R000 can be written and read from Modbus
interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW3 and SW4 on the following locations:
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC indoor unit’s features
Indoor Unit type not defined (Default value)
Machine type: VRF-SMMS/SHRM
Esclavo del bus A B (Valor por defecto)- Debe existir un mando Toshiba configurado como Header
en el bus AB
Slave of bus A B (Default value) – A Toshiba Controller must be present in the AB bus, configured
as Header.
Maestro del bus A B - No es necesario un mando Toshiba en bus AB. Si lo hay, debe ser configurado
como Follower.
Master of bus A B –Toshiba Remote Controller is not necessary to have it in the bus AB. If it exists, it
must be configured as Follower.
Table 4.1 SW1: AC indoor unit´s features

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW3/SW4 – Baud rate configuration
Table 4.2 SW3-SW4: Modbus baud rate
SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination
resistor.
Table 4.3 SW4: Temperature and termination resistor configuration
Temperature values in Modbus register are represented in degrees (x1) (Default value)
Temperature values in Modbus register are represented in Decidegrees (x10)
Temperature values in Modbus register are represented in Celsius degrees (Default value)
Temperature values in Modbus register are represented in Fahrenheit degrees
EIA-485 bus without termination resistor (Default value)
Internal termination resistor of 120Ω connected to EIA-485 bus

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW3 – Modbus Slave address
Table 4.4 SW3: Modbus slave address

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.5 Implemented Functions
INMBSTOS001R000 implements the following standard Modbus functions:
▪ 3: Read Holding Registers
▪ 4: Read Input Registers
▪ 6: Write Single Register
▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not
allow to write operations on more than 1 register with the same request, this means that
length field should be always be 1 when this function is being used in case of writing)
4.6 Device LED indicator
The device includes two LED indicators to show all the possible operational states. In the
following table there are written the indicators which can be performed and their meaning.
L1 (green LED)
During not normal
operation
Normal operation (configured and
working properly)
During not normal
operation
L1 (green LED) & L2 (red LED)
During not normal
operation
LED alternatively
blinking

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.7 EIA-485 bus. Termination resistors and Fail-Safe Biasing
mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal
reflections.
In order to prevent fail status detected by the receivers, which are “listening” the bus, when all
the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe
biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the bus
when all the transmitters’ outputs are in three-state. This mechanism must be supplied by the
Modbus Master.
The INMBSTOS001R000 device includes an on-board terminator resistor of 120Ω that can be
connected to the EIA-485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor
and/or fail-safe biasing mechanism (Check the technical documentation of the Master device
connected to the EIA-485 network in each case).

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5. Electrical and Mechanical features
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh):
93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”
Color: Light Grey. RAL 7035
Wall
DIN rail EN60715 TH35.
Terminal Wiring
(for low-voltage
signals)
For terminal: solid wires or stranded wires
(twisted or with ferrule)
1 core: 0.5mm2… 2.5mm2
2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
1 x Serial EIA485 Plug-in screw terminal
block (2 poles):
A, B
Compatible with Modbus RTU EIA-485
networks
1 x AB bus Plug-in screw terminal block
(2 poles):
A, B
Compatible with Toshiba networks
1 x DIP-Switch for AC features
1 x DIP-Switch for Modbus RTU settings
2 x Onboard LED - Operational
status
1 x DIP-Switch for extra functions

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6. List of supported AC Unit Types.
A list of Toshiba indoor unit model references compatible with INMBSTOS001R000 and their
available features can be found in:
https://www.intesis.com/docs/compatibilities/inxxxtos001rx00_compatibility

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Error in
Remote
Controller
Central Controller
Issues
Duplicated setting of control address
Central control number of units mis-matched
Incorrect wiring of central control
Incorrect connection of central control
System Controller fault, error in transmitting
comms signal, i/door or o/door unit not
working, wiring fault
System Controller fault, error in receiving
comms signal, i/door or o/door unit not
working, wiring fault, CN1 not connected
correctly
Batch alarm by local controller
Transmission error from adaptor to unit
Reception error to adaptor from unit
Duplicate central address in adaptor
Duplicate adaptor address
Mix of PAC & GHP type units on adaptor
Incorrect address setting in adaptor
Host terminal software failure
Host terminal hardware failure
Host terminal processing failure
Host terminal communication failure
Reception error of S-DDC from host terminal
Initialization failure of S-DDC
Configuration change detected by adaptor
Addressing and
Communication
Problems
Remote control detecting error from indoor unit,
Address not set/Auto address failed. Check
interconnecting wiring etc. Re-address system.
Remote detecting error from indoor unit,
Indoor unit detecting error from remote,
Indoor seeing error from outdoor. Qty of i/d
units connected are less than qty set. Check; all
i/d units are ON, reset turn off all units wait
5min power up
Indoor unit detecting error from outdoor unit,
Error in sending comms signal
Outdoor unit detecting error from indoor unit,
Error in receiving comms signal
Outdoor unit detecting error from indoor unit,
Error in sending comms signal
Incorrect setting indoor/controller, Indoor
address duplicated
Incorrect setting indoor/controller, Remote
address duplicated or IR wireless controller not
disabled
Indoor unit detecting error from ‘option’ plug,
Error in sending comms signal
Indoor unit detecting error from ‘option’ plug,
Error in receiving comms signal
Auto addressing failed, Auto address connector
CN100 shorted during auto addressing
Indoor unit failed to send signal to remote

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Setting Failure, Duplication of master indoor
units
Auto addressing failed, Number of indoor units
connected are less than number set
Auto addressing failed, Number of indoor units
connected are more than number set
Addressing and
Communication
Problems
Group control wiring error, Main indoor unit not
sending signal for sub indoor units
Group control wiring error, Main indoor unit not
receiving signal for sub indoor units
Outdoor header units quantity error
Auto addressing failed, No indoor units
connected
Sending error in communication between
outdoor units
Auto addressing failed, Error on sub outdoor
unit
Auto addressing failed, Error on outdoor unit
address setting
Auto addressing failed, Quantity of main and
sub outdoor units do not correspond to the
number set on main outdoor unit P.C.B.
Follower outdoor unit error
Auto addressing failed, Sub outdoor unit not
receiving comms for main outdoor unit
Between units, Comms failure with MDC, does
E31 remain after power is re-instated? If so
replace PCB. & power PCB
Indoor Heat Exch inlet temp sensor failure (E1)
Indoor Heat Exch freeze temp sensor failure
(E2)
Indoor Heat Exch outlet temp sensor failure
(E3)
Outdoor Discharge temp sensor failure (TD) or
(DISCH1)
Outdoor Discharge temp sensor failure
(DISCH2)
Outdoor Heat Exch temp sensor failure (C1) or
(EXG1)
Outdoor Heat Exch temp sensor failure (C2) or
(EXL1)
Outdoor Air temp sensor failure (TO)
Indoor inlet temp sensor failure
Indoor outlet temp sensor failure
Outdoor Intake sensor failure (TS)
GHP – Cooling water temperature sensor failure
Outdoor temp. sensor misconnection (TE1,TL)
Outdoor High pressure sensor failure
GHP - Cooling water temperature sensor fault
GHP - Exhaust gas temperature sensor fault
GHP Clutch coil temperature fault
Outdoor Heat Exch temp sensor failure (EXG2)
Outdoor Heat Exch temp sensor failure (EXL2)
Clock Function (RTC) fault
Compressor Fault, Over current (Comp1)
Compressor Fault, Locked rota current detected
(Comp1)
Compressor Fault, No current detected (Comp1)

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Comp-1 case thermo operation
Compressor Fault, Discharge temp not detected
(Comp1)
Compressor Fault, Low Pressure trip
Compressor Fault, Low oil level
Compressor Fault, Oil sensor Fault (Comp1)
Compressor Fault, Over current (Comp2)
Compressor Fault, Locked rota current detected
(Comp2)
Compressor Fault, No current detected (Comp2)
Comp-2 case thermo operation
Compressor Fault, Discharge temp not detected
(Comp2)
Oil level detection circuit error / Magnet switch
error /
Overcurrent relay error
Compressor Fault, Over current (Comp3)
Compressor Fault, Locked rota current detected
(c.3)
Compressor Fault, No current detected (Comp3)
Compressor Fault, Discharge temp not detected
(Comp3)
Compressor Fault, Oil sensor fault (Comp2)
Compressor Fault. Oil sensor (connection
failure)
Compressor Fault. IPM trip (IMP current on
temperature)
Setting Error, Indoor unit group setting error
Setting Error, Indoor/outdoor unit type/model
miss-matched
Duplication of main indoor unit address in group
control
Duplication of outdoor unit system address
2 or more controllers have been set as 'priority'
in one system - shown on controllers set as
'priority'
2 or more controllers have been set as 'priority'
in one system - shown on controllers not set as
'priority'
Group wiring connected on and individual indoor
unit
Indoor unit address/group not set
Indoor unit capacity code not set
Outdoor unit capacity code not set
Group control wiring incorrect
Indoor unit type setting error, capacity
Water heat exch. unit setting failure
Miss-match of outdoor unit with different
refrigerant
Water heat exch. unit duplicated address
Duplicated central control addresses
Maximum number of outdoor units exceeded
Auxiliary interlock in indoor unit
Indoor unit fault, Fan motor thermal overload
Outdoor unit fault, Compressor motor thermal
overload, over or under voltage

Intesis
TM
INMBSTOS001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Outdoor unit fault, Compressor discharge
temperature too high (Comp1) over 111 ºC.
Low on ref gas, exp. valve, pipework damage.
Outdoor unit fault, High pressure trip
Outdoor unit fault, Open phase on power
supply. Check power on each phase, inverter
PCB, control PCB
Indoor unit fault, Ceiling panel incorrectly wired
Indoor unit fault, Condensate float switch
opened
GHP - Water Heat exch. low temp (frost
protection) fault
Indoor unit fault, Fan DC motor fault
Outdoor liquid back detection error
Input from leak detector (If fitted)
Refrigerant loss, high discharge temp and EEV
wide open and low compressor current draw.
Outdoor unit fault, Open phase on compressor
power supply
Outdoor unit fault, Compressor discharge
temperature too high (Comp2) over 111ºC. Low
on ref gas, exp. valve, pipework damage.
Outdoor unit fault, By-pass valve failure
Outdoor unit fault, 4 way valve failure, i/door
temp rises in cooling or fills in heating. Check
wiring, coil, PCB output, valve operation.
Ref gas, high temp/pressure fault, heat exch.
temp high C2, 55-60 ºC, cooling over-load,
sensor fault.
Outdoor unit fan motor fault, fan blade
jammed, check connections, does fan turn
freely, motor resistance 30-40ohm on each
pair, no fan fault, yes PCB fault.
Outdoor unit fault, Compressor overcurrent check winding resistance, Inverter failure check internal resistance term HIC + & - to
UVW 200-300Kohm or more
Outdoor unit fault, Inverter circuit fault - Motorcurrent Detection Circuit (MDC) fault, check
comp windings, sensors C1 & TS, if ok possible
PCB failure.
Indoor unit fault, System controller detected
fault on sub indoor unit
Simultaneous operation multi control fault,
Group controller fault
Error in the communication of
INMBSTOS001R000 with the AC unit
In case to detect an error code not listed, contact your closest Toshiba technical support
service.