Intesis INMBSSAM001R000 User guide

Compatible with commercial air conditioners by Samsung
USER MANUAL
Issue date: 04/2019 r1.3 ENGLISH
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 23
Modbus RTU (EIA-485) Interface for Samsung air conditioners
Compatible with commercial air conditioners by Samsung
ORDER CODE
LEGACY ORDER CODE
INMBSSAM001R000
SM-RC-MBS-1
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 / 23
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 / 23
INDEX
1. Presentation .......................................................................................................... 5
2. Connection ............................................................................................................ 6
2.1 Connect to the AC indoor unit ............................................................................... 6
2.2 Connection to the EIA-485 bus ............................................................................. 7
3. Quick Start Guide ................................................................................................... 7
4. Modbus Interface Specification ................................................................................ 8
4.1 Modbus physical layer.......................................................................................... 8
4.2 Modbus Registers ................................................................................................ 8
4.2.1 Control and status registers ........................................................................... 8
4.2.2 Configuration Registers................................................................................ 10
4.2.3 Considerations on Temperature Registers ...................................................... 11
4.3 DIP-switch Configuration Interface ...................................................................... 15
4.4 Implemented Functions ..................................................................................... 18
4.5 Device LED indicator ......................................................................................... 18
4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................... 19
5. Electrical and Mechanical features .......................................................................... 20
6. List of supported AC Unit Types. ............................................................................ 21
7. Error Codes ......................................................................................................... 22
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 23
1. Presentation
The INMBSSAM001R000 interfaces allow a complete and natural
integration of Samsung air conditioners into Modbus RTU (EIA-485) networks.
Reduced dimensions. 93 x 53 x 58 mm // 3.7” x 2.1” x 2.3”
Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit of AC.
External power not required.
Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSSAM001R000 devices
can be connected in the same network.
INMBSSAM001R000 is a Modbus slave device.
Direct connection to the AC indoor unit. Up to 16 AC indoor units can be connected to
INMBSSAM001R000, controlling them as one (not individually).
Configuration from both on-board DIP-switches and Modbus RTU.
Total Control and Supervision.
Real states of the AC unit's internal variables.
Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation
of Modbus Repeaters may be required
SCADA
PLC
DDC
BMS
HMI
Controller
etc
Up to 63 AC indoor units*
Modbus RTU EIA-485 network
Modbus RTU
Master
device
INMBSSAM001R000
INMBSSAM001R000 INMBSSAM001R000
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 / 23
2. Connection
The interface comes with 2 plug-in terminal blocks of 2 poles each one, to establish direct connection with the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct connection with the Modbus RTU EIA-485 network.
2.1 Connect to the AC indoor unit
The INMBSSAM001R000 connects directly to the Samsung F3F4 V1V2 bus. This bus is not provided within the interface. Depending on which controllers are available, the recommended connection methods are the following ones (details in Figure 2. 1):
Wired remote control available. Connect the gateway as Slave in parallel with the
wired Remote Controllers (Remote Controller acts as Master).
No remote control available Connect the gateway directly to the F3F4 V1V2 bus of the
indoor unit as Master when there is no Samsung Remote Controller.
Maximum F3F4 V1V2 bus length is 100 m / 328.08 ft. The communication F3F4 V1V2 bus has polarity sensitivity.
Important: If a wired remote controller of the AC manufacturer is connected in the same bus, communication may shut down.
90 mm / 3.5”
MODBUS RTU
EIA-485
Bus
EIA485
A+ B-
F3 F4 V1 V2
AC Unit Power
53 mm / 2.1”
For wall mounting extract the upper and down staples until you hear the "click".
F3 F4 V1V2
AC Indoor Unit
(It is not mandatory to have it in the network)
Max. 100 m / 328.08 ft
Connection to F3F4 V1V2 bus. Four wire cable.
Remote Controller
Samsung
F3 F4
V1 V2
Internal electronic control board
MODBUS RTU
EIA-485
Bus
EIA485
A+ B-
F3 F4 V1 V2
AC Unit Power
AC Indoor Unit
Connection to F3F4 V1V2 bus. Four wire cable.
F3 F4
V1 V2
Internal electronic control board
Max. 100 m / 328.08 ft
53 mm / 2.1”
90 mm / 3.5”
Figure 2. 1 INMBSSAM001R000 connection diagram
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 / 23
2.2 Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block (the one of two poles) of INMBSSAM001R000 and keep the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120 must be present at each end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism (see section 4.6 for more details).
3. Quick Start Guide
1. Disconnect the air conditioning from the Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety instructions given).
3. Connect the F3F4 V1V2 bus between the interface and the AC indoor unit following the
instructions of the diagram. Screw each bare cable end in the corresponding F3F4 V1V2 terminals.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters (see section 4.3).
By default, the interface is set to:
Modbus Slave Address 1 Modbus baud rate 9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be applied.
7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to start communicating.
ON
ON
SW3
SW4
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
8 / 23
4. Modbus Interface Specification
4.1 Modbus physical layer
INMBSSAM001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA­485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit).
4.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
0: Off 1: On
1
2
R/W
AC unit Mode 1
0: Auto 1: Heat 2: Dry 3: Fan 4: Cool
2
3
R/W
AC unit Fan Speed 1
0: Auto 1: Low 2: Mid 3: High
3
4
R/W
AC unit Vane Position 1
0: Auto 10: Swing
4
5
R/W
AC unit Temperature setpoint
1,2,3
-32768 (Initialization value) 18..30ºC (ºC/x10ºC) 65..86ºF
5
6
R
AC unit Temperature reference
1,2,3
-32768 (Initialization value) 10..38ºC (ºC/x10ºC) 50..100ºF
6
7
R/W
Window Contact
0: Closed (Default) 1: Open
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.2.3 for more
information.
3
It is not possible turn to x10 the value shown in Fahrenheit.
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
9 / 23
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
7
8
R/W
INMBSSAM001R000 Disablement 4
0: INMBSSAM001R000 enabled (Default) 1: INMBSSAM001R000 disabled
8
9
R/W
AC Remote Control Disablement 4
0: Remote Controller enabled (Default) 1: Remote Controller disabled
9
10
R/W
AC unit Operation Time 4
0..65535 (hours). Counts the time the AC
unit is in “On” state.
10
11
R
AC unit Alarm Status
0: No alarm condition 1: Alarm condition
11
12
R
Error Code 5
0: No error present 65535(-1 if it is read as signed value): Error
in the communication of INMBSSAM001R000 or Remote Controller with the AC indoor unit.
Any other error present, see the table at the
end of this document.
22
23
R/W
Indoor unit´s ambient temperature from external sensor (at Modbus side)
1,2,3,6
-32768: (Initialization value). No
temperature is being provided from an external sensor.
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,6
When no external temperature is provided,
this read-only register will have the same value as register 5 (PLC addressing). In all cases, it will show the current setpoint in the indoor unit.
Ranges determined by the Manufacturer of
the AC indoor unit: (ºC/x10ºC/ºF)
26
27
R/W
AC unit Left/Right Vane Position
0: Auto (Default) 10: Swing
66
67
R
Return path Temperature
1,2,3
-32768 (Initialization value)
Ranges determined by the Manufacturer of
the AC indoor unit: (ºC/x10ºC/ºF)
97
98
R/W
Block Periodic Sendings
4,7,8
0: Non-blocked (Default value) 1: Blocked
98
99
R/W
Master/Slave (gateway)
0: Slave 1: Master
4
This value is stored in non-volatile memory
5
See section 7 for possible error codes and their explanation
6
See section 4.2.3 for more information
7
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value (values sent on change).
8
This register applies to firmware version 0.3 onwards.
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
10 / 23
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
13
14
R/W
“Open Window” switch-off timeout 9
0..30 (minutes) Factory setting: 30 (minutes)
14
15
R
Modbus RTU baud-rate
2400bps 4800bps 9600bps (Default) 19200bps 38400bps 57600bps 76800bps 115200bps
15
16
R
Modbus Slave Address
1..63
21
22
R
Max number of fan speeds
49
50
R
Device ID: 0x1200
50
51
R
Software version
67
68
R
Number of IUs connected
81
82
R
Error Address
99
100
W
Reset/Reboot device
1: Reset
9
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 23
4.2.3 Considerations on Temperature Registers
AC unit temperature setpoint (R/W)
(register 4 – in Protocol address / register 5 – in PLC address): This is the adjustable temperature setpoint value that must be required by the user. This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A remote controller connected to the Samsung indoor unit will report the same temperature setpoint value as this register, but only will happen when no AC unit´s external reference is provided from INMBSSAM001R000 (see detail for register 22/23 below).
AC unit temperature reference (R)
(register 5 – in Protocol address / register 6 – in PLC address): This register reports the temperature that is currently used by the Samsung indoor unit as the reference of its own control loop. Depending on the configuration of the indoor unit, this value can be the temperature reported by the sensor on the return path of the Samsung indoor unit or the sensor of its remote controller. It is a read-only register (Modbus functions 3 or 4).
AC unit external temperature reference (Modbus) (R/W)
(register 22 – in Protocol address / register 23 – in PLC address): This register allows us to provide an external temperature’s sensor from the Modbus side. Samsung indoor unit does not allow on devices like INMBSSAM001R000 to provide directly temperature to be used as a reference of the control loop of the AC indoor unit. In order to overcome this limitation and enable the usage of an external temperature sensor (i.e.from Modbus side), INMBSSAM001R000 applies the following mechanism (only if “external temperature’s reference” is being used):
o After a couple of values have been entered in the “AC unit external temperature’s
reference” (register 22/23) and “AC unit temperature set point” (register 4/5), INMBSSAM001R000 is going to estimate the temperature chosen implied (e.g. if a “temperature setpoint (register 4/5)” of 22ºC, and an “external temperature reference (register 22/23)” of 20ºC are entered, INMBSSAM001R000 will assume that the user is demanding a +2ºC increase in temperature).
o By knowing at any time the ambient temperature currently used by the indoor
unit to control its own operation (register 5/6), INMBSSAM001R000 can calculate the required temperature setpoint needed to apply the decrease/increase on the real temperature and reach the temperature chosen by the user (following the example above, if INMBSSAM001R000 reads an “ambient temperature” (register 5/6) of 24ºC in the indoor unit, it will apply a final setpoint of 24ºC + 2ºC = 26ºC).
o At this moment, each time that INMBSSAM001R000 detects a change on the
ambient temperature reported by the indoor unit (register 5/6), it will also change the required setpoint, in order to keep the temperature required by the user at any time. If we follow the last example, if INMBSSAM001R000 receives a new temperature´s value coming from the indoor unit of 25ºC, INMBSSAM001R000 will automatically adjust the temperature setpoint required of the AC indoor unit to 25ºC + 2ºC = 27ºC).
o In general, INMBSSAM001R000 is constantly applying the “Virtual Temperature
formula:
SAC = Su – ( Tu – T
AC
)
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
12 / 23
Where:
SAC - setpoint value currently applied to the indoor unit Su - setpoint value written at Modbus side (register 4/5) Tu - external temperature reference written at Modbus side (register 22/23) TAC - ambient temperature that the indoor unit is using as the reference of its
own control loop (register 5/6)
When INMBSSAM001R000 detects a change in any of the values of
{ Su , Tu , TAC }, it will send the new setpoint (SAC) to the indoor unit.
o After the startup, the value for “external temperature’s reference” (register
22/23) has a value -32768 (0x8000). This value means that no external temperature reference is being provided through INMBSSAM001R000. In this scenario, the setpoint value shown in register 4/5 will always be the same as the current setpoint value of the indoor unit. AC indoor unit will use its own return path temperature sensor as reference for its control loop.
o When the mechanism of “Virtual Temperature” is applied. The temperature
setpoint’s value shown by the Remote Controller or other Control System from
Samsung connected to the indoor unit may show a different value from the value shown in register 4/5.
o If it is desired to use the temperature’s reading from the Remote Control as the
external temperature reference (Tu ,register 22/33), the Remote Controller must be configured as Master, and the Samsung AC indoor unit must have the option thermostat sensor in the Remote Controller as activated. This configuration is done via a Samsung Remote Controller connected to the indoor unit and must be done by Samsung authorized installers while the AC is being installed.
o This configuration is done following the instructions from the Service Manual of
Samsung (In Service Mode: Main Menu 1, press [>] button to Sub Menu 2 (=“Function Wireless Remote Control Option setting”); press [>] button data-bit 1 (=Temperature sensor selection) set value 1-Wired Remote Controller).This configuration is done via a Samsung Remote Controller connected to the indoor unit and must be done by Samsung authorized installers while the AC is being installed.
o When INMBSSAM001R000 is set as “Master” of F3F4 V1V2 bus, the external
temperature’s sensor connected to Modbus RTU EIA-485 network provides
directly the value currently applied to the indoor unit ( SAC ), and the process of the Virtual temperature is not applied. In this case, the Remote Controller or any other Control System connected from Samsung is not able to send the external temperature reference’s value to the register 22/23.
AC Real temperature setpoint (R)
(register 23 – In Protocol address / register 24 – in PLC address): As it has been detailed on the previous point, the real temperature setpoint in the indoor
unit and the temperature setpoint requested from INMBSSAM001R000 might differ (when a value in register 22/23 – “external temperature reference” is entered). This register always informs about the current temperature setpoint which is being used by the indoor unit – it is also includes the temperature setpoint that will be shown by an additional remote controller from Samsung connected to the indoor unit, if it is present on the system.
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
13 / 23
Moreover, notice that temperature’s values of all these four registers are expressed according to the temperature´s format configured through its onboard DIP-Switches (See 4.3 -
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
14 / 23
DIP-switch Configuration Interface”). These following formats are possible:
Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a
value “22” in the Modbus register must be interpreted as 22ºC).
Decicelsius value: Value in Modbus register is the temperature value in
decicelsius (i.e. a value “220” in the Modbus register must be interpreted as
22.0ºC).
Fahrenheit value: Value in Modbus register is the temperature value in
Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF (~22ºC).
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
15 / 23
4.3 DIP-switch Configuration Interface
All the configuration values on INMBSSAM001R000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface. The device has DIP-switches SW1, SW3 and SW4 on the following locations:
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC indoor unit’s features
SW1-P1..4
Description
Slave - A Samsung Controller must be present in F3F4 V1V2 bus, configured as Master (Default value)
Master – Samsung Controller not needed in F3F4 V1V2 bus. If it exists, it must be configured as Slave
Not used (Default value)
Not used
Not used (Default value)
Not used
Not used (Default value)
Not used
Table 4.1 SW1: AC indoor unit´s features
EIA485
A+ B-
F3 F4
AC Unit
SW1
SW1
SW4
ON
1 2 3 4
ON
SW3
1 2 3 4
1 2 3 4 5 6 7 8
ON
ON
ON
ON
ON
ON
ON
ON
ON
V1 V2
Power
SW3
SW4
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
16 / 23
SW3/SW4 – Baud rate configuration
SW3-P7..8
SW4-P3
Description
2400bps
4800bps
9600bps (Default value)
19200bps
38400bps
57600bps
76800bps
115200bps
Table 4.2 SW3-SW4: Modbus baud rate
SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination
resistor.
Table 4.3 SW4: Temperature and termination resistor configuration
SW4-P1..2-4
Description
Temperature values in Modbus register are represented in degrees (x1) (Default value)
Temperature values in Modbus register are represented in decidegrees (x10)
Temperature values in Modbus register are represented in Celsius degrees (Default value)
Temperature values in Modbus register are represented in Fahrenheit degrees
EIA-485 bus without termination resistor (Default value)
Internal termination resistor of 120Ω connected to EIA-485 bus
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
17 / 23
SW3 – Modbus Slave address
Table 4.4 SW3: Modbus slave address
Add SW3-P1..6
Add SW3-P1..6
Add SW3-P1..6
Add
SW3-P1..6
Add
SW3-P1..6
0
13
26
39
52
1
14
27
40
53
2
15
28
41
54
3
16
29
42
55
4
17
30
43
56
5
18
31
44
57
6
19
32 45
58
7
20
33 46
59
8
21
34
47
60
9
22
35
48
61
10
23
36 49
62
11 24 37 50 63
12 25 38 51
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
18 / 23
4.4 Implemented Functions
INMBSSAM001R000 implements the following standard Modbus functions:
3: Read Holding Registers 4: Read Input Registers 6: Write Single Register 16: Write Multiple Registers (Despite this function is allowed, the interface does not
allow to write operations on more than 1 register with the same request, this means that length field should be always be 1 when this function is being used in case of writing).
The maximum of registers that can be read in a single request is 100.
4.5 Device LED indicator
The device includes two LED indicators to show all the possible operational states. In the following table there are written the indicators which can be performed and their meaning.
L1 (green LED)
Device status
LED indication
ON / OFF Period
Description
During not normal operation
LED blinking
500ms ON / 500ms OFF
Communication error
During normal operation
LED flashing
100ms ON / 1900ms OFF
Normal operation (configured and working properly)
L2 (red LED)
Device status
LED indication
ON / OFF Period
Description
During not normal operation
LED Pulse
3sec ON / --- OFF
Under voltage
L1 (green LED) & L2 (red LED)
Device status
LED indication
ON / OFF Period
Description
During normal operation
LED Pulse
5sec ON / --- OFF
Device Start-up
During not normal operation
LED alternatively
blinking
500ms ON / 500ms OFF
Flash checksum not OK
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
19 / 23
4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing
mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections.
In order to prevent fail status detected by the receivers, which are listening the bus, when all the transmitters outputs are in three-state (high impedance), it is also required a fail-safe biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the bus when all the transmitters’ outputs are in three-state. This mechanism must be supplied by the Modbus Master.
The INMBSSAM001R000 device includes an on-board terminator resistor of 120Ω that can be connected to the EIA-485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor and/or fail-safe biasing mechanism (Check the technical documentation of the Master device connected to the EIA-485 network in each case).
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
20 / 23
5. Electrical and Mechanical features
Enclosure
Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Color: Light Grey. RAL 7035
Operation Temperature
0ºC to +60ºC
Weight
85 g.
Stock Temperature
-20ºC to +85ºC
Mounting
Wall DIN rail EN60715 TH35.
Operational Humidity
<95% RH, non-condensing
Terminal Wiring (for low-voltage signals)
For terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
Stock Humidity
<95% RH, non-condensing
Modbus RTU port
1 x Serial EIA485 Plug-in screw terminal block (2 poles):
A, B Compatible with Modbus RTU EIA-485 networks
Isolation voltage
1500 VDC
AC unit port
1 x F3F4 bus Plug-in screw terminal block (2 poles):
F3, F4 Compatible with Samsung networks 1 x V1V2 Power screw terminal block (2 poles):
V1, V2
Isolation resistance
1000
Switch 1 (SW1)
1 x DIP-Switch for AC features
Protection
IP20 (IEC60529)
Switch 3 (SW3)
1 x DIP-Switch for Modbus RTU settings
LED indicators
2 x Onboard LED - Operational status
Switch 4 (SW4)
1 x DIP-Switch for extra functions
EIA-485
Port
AC Unit
connections
DIP
Switch SW3
DIP
Switch SW1
LED
Indicators
DIP
Switch SW4
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
21 / 23
6. List of supported AC Unit Types.
A list of Samsung indoor unit model’s references compatible with INMBSSAM001R000 and its available features can be found on this link:
https://www.intesis.com/docs/compatibilities/inxxxsam001r000_compatibility
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
22 / 23
7. Error Codes
Error Code
Modbus
Error in Remote
Controller
Error category
Error Description
0
N/A
INMBSSAM001R000
No active error
101
101
Communication error
Indoor unit communication error
102
102
Communication error
Indoor unit/outdoor unit communication time­out error; errors in more than 6 packets.
121
121
Indoor sensor error
Indoor temperature sensor (open/short).
122
122
Indoor sensor error
Indoor unit evaporator-in sensor (open/short)
128
128
Indoor sensor error
Indoor unit evaporator-in disconnection. (sensor displacement)
129
129
Indoor sensor error
Indoor unit evaporator-out separation.
153
153
Drain diagnostic error
Indoor floating switch secondary detection
201
201
Configuration error
Unit Miss Match indoor/outdoor
202
202
Communication error
Indoor/outdoor communication error (1 min)
203
203
Communication error
Comm. error between indoor/outdoor INV<>MAIN MICOM (1 min)
221
221
Outdoor sensor error
Outdoor temperature sensor error
231
231
Outdoor sensor error
Condenser temperature sensor error
237
237
Outdoor sensor error
Condenser temperature error
251
251
Outdoor sensor error
Inverter Emission temperature sensor error
320
320
Outdoor sensor error
OPL sensor error
402
402
Outdoor sensor error
Detection of outdoor freezing when compressor stop
404
404
Outdoor unit error
Overload Protection of Outdoor when compressor stop
419
419
Control error
EEV Open error (Electronic Evaporation Valve)
422
422
Control error
EEV Close error
425
425
Installation error
Power Cable Miss connection
440
440
Self-diagnostic error
Heating operation blocked
441
441
Self-diagnostic error
Cooling operation blocked
461
461
ODU protection error
Inverter Compressor startup error
462
462
ODU protection error
Inverter total current error / PFC over current error
463
463
ODU protection error
OLP Heat Sink error
464
464
ODU protection error
Inverter IPM over current error
465
465
ODU protection error
Compressor V limit error
466
466
ODU protection error
DC LINK over/low voltage error
467
467
ODU protection error
Inverter compressor rotation error
468
468
ODU protection error
Inverter current sensor error
469
469
ODU protection error
Inverter DC LINK voltage sensor error
471
471
ODU protection error
Inverter OTP error / Inverter EEPROM read/write error
472
472
ODU protection error
AC Zero crossing signal out error
473
473
ODU protection error
Compressor Lock error
474
474
ODU protection error
Heat Sink sensor error
475
475
Self-diagnostic error
Outdoor Fan 2 error
484
484
ODU protection error
PFC Overload error
485
485
ODU protection error
Input current sensor error
500
500
ODU protection error
Heat Sink Over Heat error
554
554
Self-diagnostic error
Gas leak detector
556
556
Configuration error
Outdoor unit Capacity Setup option error
557
557
Configuration error
Option Code Miss match indoor units
601
601
Communication error
Communication error between wired remote and
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
23 / 23
indoor unit. (When communication has stopped for 3 minutes after detecting indoor unit and wired remote control)
602
602
Communication error
Communication error between the Master and Slave wired remote controller. (Only one Master and one Slave can exist).
604
604
Communication error
Tracking 10 or more errors between wired remote control and indoor unit.
606
606
Installation error
-COM1, Com2 crossing connection error.
-When wired remote is connected to indoor unit COM1 (F1, F2) terminals.
607
607
Configuration error
-Multiple Master error. (When using Master remote control).
-Error occurs when two wired remotes are both set as Master in one COM line.
609
609
Configuration error
Indoor unit is not installed. (when the indoor unit is not detected after outside gearing option setting and tracking are finished). In case of using outside gear control.
618
618
Configuration error
-Exceeded maximum no. of installation for indoor units.
-A reset is required after checking the number of indoor unit.
619
619
Configuration error
-Mixed installations for °C/F° indoor unit. (Only detected on master wired remote control).
-Error occurs when mixed indoor units of °C and °F settings are installed.
620
620
Configuration error
-Wired remote control °C/°F setting error.
-This error occurs if the indoor unit is set in °C while the wired remote is set in °F or vice versa.
621
621
Configuration error
This error occurs when the option setting of the Master and Slave wired remote controls are different from each other.
627
627
Configuration error
Slave wired remote control installation error (when two Slave wired remote controls are installed).
EA
EA
Configuration error
Wired remote controller COM2 option setting error.
65535
(-1)
N/A
INMBSSAM001R000
Error in the communication of INMBSSAM001R000 or Remote Controller with the AC unit.
In case to detect an error code not listed, contact your closest Samsung technical support service.
Loading...