Where:
SAC - setpoint value currently applied to the indoor unit
Su - setpoint value written at Modbus side (register 4/5)
Tu - external temperature reference written at Modbus side (register 22/23)
TAC - ambient temperature that the indoor unit is using as the reference of its
own control loop (register 5/6)
When INMBSSAM001R000 detects a change in any of the values of
{ Su , Tu , TAC }, it will send the new setpoint (SAC) to the indoor unit.
o After the startup, the value for “external temperature’s reference” (register
22/23) has a value -32768 (0x8000). This value means that no external
temperature reference is being provided through INMBSSAM001R000. In this
scenario, the setpoint value shown in register 4/5 will always be the same as the
current setpoint value of the indoor unit. AC indoor unit will use its own return
path temperature sensor as reference for its control loop.
o When the mechanism of “Virtual Temperature” is applied. The temperature
setpoint’s value shown by the Remote Controller or other Control System from
Samsung connected to the indoor unit may show a different value from the value
shown in register 4/5.
o If it is desired to use the temperature’s reading from the Remote Control as the
external temperature reference (Tu ,register 22/33), the Remote Controller must
be configured as Master, and the Samsung AC indoor unit must have the option
“thermostat sensor in the Remote Controller” as activated. This configuration is
done via a Samsung Remote Controller connected to the indoor unit and must be
done by Samsung authorized installers while the AC is being installed.
o This configuration is done following the instructions from the Service Manual of
Samsung (In Service Mode: Main Menu 1, press [>] button to Sub Menu 2
(=“Function Wireless Remote Control Option setting”); press [>] button data-bit
1 (=“Temperature sensor selection”) set value 1-Wired Remote Controller).This
configuration is done via a Samsung Remote Controller connected to the indoor
unit and must be done by Samsung authorized installers while the AC is being
installed.
o When INMBSSAM001R000 is set as “Master” of F3F4 V1V2 bus, the external
temperature’s sensor connected to Modbus RTU EIA-485 network provides
directly the value currently applied to the indoor unit ( SAC ), and the process of
the Virtual temperature is not applied. In this case, the Remote Controller or any
other Control System connected from Samsung is not able to send the external
temperature reference’s value to the register 22/23.
• AC Real temperature setpoint (R)
(register 23 – In Protocol address / register 24 – in PLC address):
As it has been detailed on the previous point, the real temperature setpoint in the indoor
unit and the temperature setpoint requested from INMBSSAM001R000 might differ
(when a value in register 22/23 – “external temperature reference” is entered). This
register always informs about the current temperature setpoint which is being used by
the indoor unit – it is also includes the temperature setpoint that will be shown by an
additional remote controller from Samsung connected to the indoor unit, if it is present
on the system.