INMBSRTR0320000
Modbus RTU to Modbus TCP Router
Order Codes:
INMBSRTR0320000 (32 full-load devices)
The Intesis INMBSRTR0320000 Router has been specially designed
to route messages between Modbus RTU and Modbus TCP networks.
Intesis acts as a transparent gateway between Modbus RTU and
Modbus TCP networks, making its configuration simple and fast. It
makes accessible Modbus RTU devices, its registers and resources to
a Modbus TCP client BMS or controller. When the gateway receives a
Modbus TCP packet from the TCP network, it simply routes the packet
to the serial port.
Modbus TCP devices are connected through the Ethernet port, while
Modbus RTU devices are connected to the serial port of the gateway.
Configuration project is done through Intesis MAPS.
• Support for up to 5 simultaneous Modbus TCP Clients
• Support for up to 32 full-load RTU devices
• Modbus diagnose signals available in both MAPS and as Modbus
registers
• Configuration through IP
• Onboard LED indicators to provide easy to check communication
status on both the Ethernet and serial ports
• Includes Intesis MAPS with automatic updates for both Intesis
MAPS and Gateway’s firmware
• UL certification
![](/html/a9/a98a/a98ab71bed909289c6a1ec79b6ed1c6ae4dc9a5f522aafdbf08cc7826971c2da/bg2.png)
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 115.2kbps
Data Types
&
Functions
supported
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 93x53x58 mm
Recommended space for installation (dxwxh): 100x60x70mm
Color: Light Grey. RAL 7035
Wall.
DIN rail EN60715 TH35.
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
9-24VDC +/-10% Max.: 205mA
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
5 to 95%, no condensation
ELECTRICAL & MECHANICAL FEATURES
Modbus Protocol is a de facto standard, truly open and the most widely used network protocol in the
industrial manufacturing environment.
Modbus is used in multiple applications to monitor and program devices; to communicate between
intelligent devices, sensors and instruments; to monitor field devices using PCs and HMIs.
But Modbus is not only an industrial protocol. Building, infrastructure, transportation and energy
applications also make use of its benefits.
For further information visit www.modbus.org
70mm (h)