
USER MANUAL
Issue date: 05/2020 r1.7 ENGLISH

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Modbus RTU (EIA-485) Interface for LG air conditioners

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks
of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility
or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product
development. The information in this document shall therefore not be construed as a commitment on the
part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no
commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only
intended to help improve understanding of the functionality and handling of the product. In view of the wide
range of possible applications of the product, and because of the many variables and requirements associated
with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for
actual use based on the data, examples or illustrations included in this document nor for any damages incurred
during installation of the product. Those responsible for the use of the product must acquire sufficient
knowledge in order to ensure that the product is used correctly in their specific application and that the
application meets all performance and safety requirements including any applicable laws, regulations, codes
and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility
for any problems that may arise as a result from the use of undocumented features or functional side effects
found outside the documented scope of the product. The effects caused by any direct or indirect use of such
aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
INDEX
1. Presentation .......................................................................................................... 5
2. Connection ............................................................................................................ 6
2.1 Connect to the AC indoor unit ............................................................................... 6
2.2 Connection to the EIA-485 bus ............................................................................. 7
3. Quick Start Guide ................................................................................................... 7
4. Modbus Interface Specification ................................................................................ 8
4.1 Modbus physical layer.......................................................................................... 8
4.2 Modbus Registers ................................................................................................ 8
4.2.1 Control and status registers ........................................................................... 8
4.2.2 Configuration Registers................................................................................ 10
4.2.3 Considerations on Temperature Registers ...................................................... 11
4.3 DIP-switch Configuration Interface ...................................................................... 14
4.4 Implemented Functions ..................................................................................... 17
4.5 Device LED indicator ......................................................................................... 17
4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................... 18
5. Mechanical and electrical features .......................................................................... 19
6. List of supported AC Unit Types. ............................................................................ 20
7. Error Codes ......................................................................................................... 21

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
1. Presentation
The INMBSLGE001R000 interfaces allow a complete and natural integration of
LG air conditioners into Modbus RTU (EIA-485) networks.
Reduced dimensions. 93 x 53 x 58 mm
3.7” x 2.1” x 2.3”
Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit of AC.
• External power not required.
• Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSLGE001R000 devices
can be connected in the same network.
INMBSLGE001R000 is a Modbus slave device.
• Direct connection to the AC indoor unit.
• Configuration from both on-board DIP-switches and Modbus RTU.
• Total Control and Supervision.
• Real states of the AC unit's internal variables.
• Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation
of Modbus Repeaters may be required
• SCADA
• PLC
• DDC
• BMS
• HMI
• Controller
• etc
Up to 63
AC indoor
units*
Modbus RTU
EIA-485 network
INMBSLGE001R000
INMBSLGE001R000

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2. Connection
The interface comes with a plug-in terminal block of 3 poles to establish direct connection with
the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct
connection with the Modbus RTU EIA-485 network.
2.1 Connect to the AC indoor unit
The INMBSLGE001R000 connects directly to the LG BYR Bus, which is not provided within the
interface. Depending on which controllers are available, the recommended connection’ methods
are the following ones (details in Figure 2. 1):
• Wired remote control available. Connect the gateway as Slave in parallel with the
wired Remote Controllers (Controller acts as Master).
• No remote control available Connect the gateway directly to the BYR bus of the
indoor unit as Master when there is no LG Remote Controller.
Maximum BYR bus length is 50 m / 164.04 ft. The bus has no polarity sensitivity.
Important: If a wired remote controller of the AC manufacturer is connected in the same bus,
communication may shut down.
For wall mounting
extract the upper
and down staples
until you hear the
"click".
GND (3) B
Data (2) Y
Power (1) R
Internal electronic
control board
Internal electronic
control board
GND (3) B
Data (2) Y
Power (1) R
Attention: Type A units don’t allow to install a Remote Controller and
INMBSLGE001R000 together.
Figure 2. 1 INMBSLGE001R000 connection diagram

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2.2 Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block (the one of two poles) of
INMBSLGE001R000 and keep the polarity on this connection (A+ and B-). Make sure that the
maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not
allowed in the case of the EIA-485 bus. A terminator resistor of 120Ω must be present at each
end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism (see
section 4.6 for more details).
3. Quick Start Guide
1. Disconnect the air conditioning from the Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety
instructions given).
3. Connect the BYR bus between the interface and the AC indoor unit following the
instructions of the diagram. Screw each bare cable end in the corresponding BYR
terminals of each device.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters.
By default, the interface is set to:
▪ Modbus Slave Address ➔ 1
▪ Modbus baud rate ➔ 9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be
applied.
7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to
start communicating.

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4. Modbus Interface Specification
4.1 Modbus physical layer
INMBSLGE001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485
line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).
4.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian
notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
AC unit On/Off
▪ 0: Off
▪ 1: On
AC unit Mode 1
▪ 0: Auto
▪ 1: Heat
▪ 2: Dry
▪ 3: Fan
▪ 4: Cool
AC unit Fan Speed 1
▪ 0: Auto
▪ 1..7: Pos. 1 .. Pos. 7
AC unit Vane Position 1
▪ 0: No Swing
▪ 1..4: Pos. 1 .. Pos. 4
▪ 10: Swing
▪ 11: Swirl
AC unit Temperature Setpoint
1,2,3
▪ -32768 (Initialization value)
▪ 16..30ºC (ºC/x10ºC)
▪ 61..86ºF
AC unit Temperature reference
1,2,3
▪ -32768 (Initialization value)
▪ 10..38ºC (ºC/x10ºC)
▪ 50..100ºF
Window Contact
▪ 0: Closed (Default)
▪ 1: Open
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.2.3 for more
information.
It is not possible turn to x10 the value shown in Fahrenheit.

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
INMBSLGE001R000 Disablement 4
▪ 0: INMBSLGE001R000 enabled (Default)
▪ 1: INMBSLGE001R000 disabled
AC Remote Control Disablement 4
▪ 0: Remote Controller enabled (Default)
▪ 1: Remote Controller disabled
AC unit Operation Time 4
▪ 0..65535 (hours). Counts the time the AC
unit is in “On” state.
AC unit Alarm Status
▪ 0: No alarm condition
▪ 1: Alarm condition
Error Code 5
▪ 0: No error present
▪ 65535(-1 if it is read as signed value): Error
in the communication of INMBSLGE001R000
or Remote Controller with the AC unit.
▪ If any error is present, see the table at the
end of this document.
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
1,2,3,6
▪ -32768: (Initialization value). No
temperature is being provided from an
external sensor.
▪ Any from Manufacturer: (ºC/x10ºC/ºF)
AC Real setpoint temperature
1,2,3,6
▪ When no external temperature is provided,
this read-only register will have the same
value as register 5 (PLC addressing). In all
cases, it will show the current setpoint in the
indoor unit.
▪ Any from Manufacturer: (ºC/x10ºC/ºF)
Current AC max setpoint
1,2,3
▪ -32768 (Initialization value)
▪ Any from Manufacturer: (ºC/x10ºC/ºF)
Current AC min setpoint
1,2,3
▪ -32768 (Initialization value)
▪ Any from Manufacturer: (ºC/x10ºC/ºF)
AC unit Left/Right Vane Position 1
▪ 0: Auto (Default)
▪ 1..9: Pos. 1 .. Pos. 9
▪ 10: Swing
Up/Down Vane Position
▪ 1: Pulse
Status (feedback)
▪ 0: Not active (Default value)
▪ 1: Active (A window is open)
Compressor Status
▪ 0: Off
▪ 1: To Off
▪ 2: To On
▪ 3: On
This value is stored in non-volatile memory
See section 7 for possible error codes and their explanation
See section 4.2.3 for more information

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
Compressor on Time 4
▪ 0..65535 (hours). Counts the time the
Compressor is in “On” state.
Input Ref. Temperature (feedback)
1,2,3
▪ -32768 (Initialization value)
▪ Any from Manufacturer: (ºC/x10ºC/ºF)
Block Periodic Sendings
4,7,8
▪ 0: Non-blocked (Default value)
▪ 1: Blocked
Master/Slave (gateway’s role)
▪ 0: Slave
▪ 1: Master
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
“Open Window” switch-off timeout 9
▪ 0..30 (minutes)
▪ Factory setting: 30 (minutes)
Modbus RTU baud-rate
▪ 2400bps
▪ 4800bps
▪ 9600bps (Default)
▪ 19200bps
▪ 38400bps
▪ 57600bps
▪ 76800bps
▪ 115200bps
Modbus Slave Address
▪ 1..63
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value.
This register applies to firmware version 1.7 onwards
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.2.3 Considerations on Temperature Registers
• AC unit temperature setpoint (R/W)
(register 4 – in Protocol address / register 5 – in PLC address):
This is the adjustable temperature setpoint value that must be required by the user. This
register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A
remote controller connected to the LG indoor unit will report the same temperature
setpoint value as this register, but only will happen when no AC unit´s external
reference is provided from INMBSLGE001R000 (see detail for register 22/23 below).
• AC unit temperature reference (R)
(register 5 – in Protocol address / register 6 – in PLC address):
This register reports the temperature that is currently used by the LG indoor unit as the
reference of its own control loop. Depending on the configuration of the indoor unit, this
value can be the temperature reported by the sensor on the return path of the LG indoor
unit or the sensor of its remote controller. It is a read-only register (Modbus functions 3
or 4).
• AC unit external temperature reference (Modbus) (R/W)
(register 22 – in Protocol address / register 23 – in PLC address):
This register allows us to provide an external temperature’s sensor from the Modbus
side. LG indoor unit does not allow on devices like INMBSLGE001R000 to provide directly
temperature to be used as a reference of the control loop of the AC indoor unit. In order
to overcome this limitation and enable the usage of an external temperature sensor
(i.e.from Modbus side), INMBSLGE001R000 applies the following mechanism (only if
“external temperature’s reference” is being used):
o After a couple of values have been entered in the “AC unit external temperature’s
reference” (register 22/23) and “AC unit temperature set point” (register 4/5),
INMBSLGE001R000 is going to estimate the temperature chosen implied (e.g. if a
“temperature setpoint (register 4/5)” of 22ºC, and an “external temperature
reference (register 22/23)” of 20ºC are entered, INMBSLGE001R000 will assume
that the user is demanding a +2ºC increase in temperature).
o By knowing at any time the ambient temperature currently used by the indoor
unit to control its own operation (register 5/6), INMBSLGE001R000 can calculate
the required temperature setpoint needed to apply the decrease/increase on the
real temperature and reach the temperature chosen by the user (following the
example above, if INMBSLGE001R000 reads an “ambient temperature” (register
5/6) of 24ºC in the indoor unit, it will apply a final setpoint of 24ºC + 2ºC =
26ºC).
o At this moment, each time that INMBSLGE001R000 detects a change on the
ambient temperature reported by the indoor unit (register 5/6), it will also
change the required setpoint, in order to keep the temperature required by the
user at any time. If we follow the last example, if INMBSLGE001R000 receives a
new temperature´s value coming from the indoor unit of 25ºC,
INMBSLGE001R000 will automatically adjust the temperature setpoint required of
the AC indoor unit to 25ºC + 2ºC = 27ºC).
o In general, INMBSLGE001R000 is constantly applying the “Virtual Temperature”
formula:
SAC = Su – ( Tu – T
AC
)

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Where:
SAC - setpoint value currently applied to the indoor unit
Su - setpoint value written at Modbus side (register 4/5)
Tu - external temperature reference written at Modbus side (register 22/23)
TAC - ambient temperature that the indoor unit is using as the reference of its
own control loop (register 5/6)
When INMBSLGE001R000 detects a change in any of the values of
{ Su , Tu , TAC }, it will send the new setpoint (SAC) to the indoor unit.
o After the startup, the value for “external temperature’s reference” (register
22/23) has a value -32768 (0x8000). This value means that no external
temperature reference is being provided through INMBSLGE001R000. In this
scenario, the setpoint value shown in register 4/5 will always be the same as the
current setpoint value of the indoor unit. AC indoor unit will use its own return
path temperature sensor as reference for its control loop.
o When the mechanism of “Virtual Temperature” is applied. The temperature
setpoint’s value shown by the Remote Controller or other Control System from LG
connected to the indoor unit may show a different value from the value shown in
register 4/5.
o If it is desired to use the temperature’s reading from the Remote Control as the
external temperature reference (Tu ,register 22/33), the Remote Controller must
be configured as Master, and the LG AC indoor unit must have the option
“thermostat sensor in the Remote Controller” as activated. This configuration is
done via a LG Remote Controller connected to the indoor unit and must be done
by LG authorized installers while the AC is being installed.
o When INMBSLGE001R000 is set as “Master” of BYR bus, the external
temperature’s sensor connected to Modbus RTU EIA-485 network provides
directly the value currently applied to the indoor unit ( SAC ), and the process of
the Virtual temperature is not applied. In this case, the Remote Controller or any
other Control System connected from LG is not able to send the external
temperature reference’s value to the register 22/23.
• AC Real Setpoint temperature (R)
(register 23 – In Protocol address / register 24 – in PLC address):
As it has been detailed on the previous point, the real temperature setpoint in the indoor
unit and the temperature setpoint requested from INMBSLGE001R000 might differ (when
a value in register 22/23 – “external temperature reference” is entered). This register
always informs about the current temperature setpoint which is being used by the indoor
unit – it is also includes the temperature setpoint that will be shown by an additional
remote controller from LG connected to the indoor unit, if it is present on the system.

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Moreover, notice that temperature’s values of all these four registers are expressed according to
the temperature´s format configured through its onboard DIP-Switches (See “4.3 - DIP-switch
Configuration Interface”). These following formats are possible:
• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a
value “22” in the Modbus register must be interpreted as 22ºC).
• Decicelsius value: Value in Modbus register is the temperature value in
decicelsius (i.e. a value “220” in the Modbus register must be interpreted as
22.0ºC).
• Fahrenheit value: Value in Modbus register is the temperature value in
Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF
(~22ºC).

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.3 DIP-switch Configuration Interface
All the configuration values on INMBSLGE001R000 can be written and read from Modbus
interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW3 and SW4 on the following locations:
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC indoor unit’s features
Slave - A LG Controller must be present in BYR bus, configured as Master (Default value)
Master – LG Controller not needed in BYR bus. If it exists, it must be configured as Slave
Error Type_B – Machine must be Type B (Default value)
Error Type_A – Machine must be Type A
Min. ambient temperature not applied (Default value)
Min. ambient temperature applied
Keep the switch into this position (Default value)
Do not turn the switch into this position (not applicable)
Table 4.1 SW1: AC indoor unit´s features

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW3/SW4 – Baud rate configuration
Table 4.2 SW3-SW4: Modbus baud rate
SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination
resistor.
Table 4.3 SW4: Temperature and termination resistor configuration
Temperature values in Modbus register are represented in degrees (x1) (Default value)
Temperature values in Modbus register are represented in decidegrees (x10)
Temperature values in Modbus register are represented in Celsius degrees (Default value)
Temperature values in Modbus register are represented in Fahrenheit degrees
EIA-485 bus without termination resistor (Default value)
Internal termination resistor of 120Ω connected to EIA-485 bus

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW3 – Modbus Slave address
Table 4.4 SW3: Modbus slave address

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.4 Implemented Functions
INMBSLGE001R000 implements the following standard Modbus functions:
▪ 3: Read Holding Registers
▪ 4: Read Input Registers
▪ 6: Write Single Register
▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not
allow to write operations on more than 1 register with the same request, this means that
length field should be always be 1 when this function is being used in case of writing)
4.5 Device LED indicator
The device includes two LED indicators to show all the possible operational states. In the
following table there are written the indicators which can be performed and their meaning.
L1 (green LED)
During not normal
operation
Normal operation (configured and
working properly)
During not normal
operation
L1 (green LED) & L2 (red LED)
During not normal
operation
LED alternatively
blinking

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing
mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal
reflections.
In order to prevent fail status detected by the receivers, which are “listening” the bus, when all
the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe
biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the bus
when all the transmitters’ outputs are in three-state. This mechanism must be supplied by the
Modbus Master.
The INMBSLGE001R000 device includes an on-board terminator resistor of 120Ω that can be
connected to the EIA-485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor
and/or fail-safe biasing mechanism (Check the technical documentation of the Master device
connected to the EIA-485 network in each case).

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5. Mechanical and electrical features
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh):
93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”
Color: Light Grey. RAL 7035
Wall
DIN rail EN60715 TH35.
Terminal Wiring
(for low-voltage
signals)
For terminal: solid wires or stranded wires
(twisted or with ferrule)
1 core: 0.5mm2… 2.5mm2
2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
1 x Serial EIA485 Plug-in screw terminal
block (2 poles):
A, B
Compatible with Modbus RTU EIA-485
networks
1 x BYR bus Plug-in screw terminal block
(3 poles):
B, Y, R
Compatible with LG networks
1 x DIP-Switch for AC features
1 x DIP-Switch for Modbus RTU settings
2 x Onboard LED - Operational
status
1 x DIP-Switch for extra functions

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6. List of supported AC Unit Types.
A list of LG indoor unit model’s references compatible with INMBSLGE001R000 and its available
features can be found on this link:
https://www.intesis.com/docs/compatibilities/inxxxlge001r000_compatibility

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Indoor unit pipe in sensor fault
Communication fault between wired remote controller and indoor unit
Communication fault between indoor unit and outdoor unit
Indoor unit pipe out sensor fault
Indoor unit mode runs on opposite to outdoor unit
BLDC motor signal fault or motor lock
HEX middle point sensor fault
heater terminal block sensor fault
No communication response from sub PCB to main PCB
No communication response from main PCB to sub PCB
AC input is over current (RMS)
DC link low or high voltage
High pressure or low pressure switch on
Over current at compressor input
Discharge temperature is high at inverter compressor
Discharge temperature is high at constant speed compressor
High pressure is too high
Compression ratio is too low
Communication fault between PFC and inverter PCB
Discharge sensor at inverter compressor is fault
Low pressure sensor is fault
High pressure sensor is fault
Air sensor at outdoor unit is fault
HEX sensor at outdoor unit is fault
Compressor suction sensor is fault
Discharge sensor at constant speed compressor is fault
HEX outlet sensor at outdoor unit is fault
IPM temperature sensor is fault
Missing phase among 3 phase
No communication from inverter PCB detected at main PCB
Communication fault between indoor and outdoor unit
Reverse phase is detected
No communication from main PCB detected at inverter PCB

Intesis
TM
INMBSLGE001R000
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Wrong outdoor unit combination
Inverter EEPROM memory fault
Outdoor pipe temperature is too high
IPM temperature is too high
IPM temperature sensor is fault
Fan locked or fan start failure
CT sensor of constant speed compressor 1 is fault
CT sensor of constant speed compressor 2 is fault
Function error of outdoor 4way valve (reversing valve)
Fan DC link voltage is high
Fan input voltage is high
Inlet temperature sensor of external PCB is fault
Outlet temperature sensor of external PCB is fault
No Communication from slave is detected
Communication fault between fan and inverter PCB
Fan DC link voltage is low
Sub-cooling inlet pipe sensor fault
Sub-cooling outlet pipe sensor fault
No communication from external PCB is detected at main PCB
Over / low current at constant speed compressor 1
Over / low current at constant speed compressor 2
Communication fault between main and sub micom in external PCB
Hydro-kit water temperature sensor fault
Inverter PCB heat sink temperature is high
Inverter PCB heat sink temperature sensor fault
Fan PCB heat sink temperature is high
Fan PCB heat sink temperature sensor fault
Fault at liquid pipe sensor of Heat Recovery (HR) unit
Fault at sub-cooling inlet pipe sensor of Heat Recovery (HR) unit
Fault at sub-cooling outlet pipe sensor of Heat Recovery (HR) unit
No communication from outdoor unit is detected at the Heat Recovery
(HR) unit
HR unit addresses are duplicated
No response from outdoor unit modem at indoor unit modem
No response from outdoor unit at outdoor unit modem
Error in the communication of INMBSLGE001R000 or Remote Controller
with the AC unit.
In case to detect an error code not listed, contact your closest LG technical support service.