TAC - ambient temperature that the indoor unit is using as the reference of its
own control loop (register 5/6)
When INMBSHIT001R000 detects a change in any of the values of
{ Su , Tu , TAC }, it will send the new setpoint (SAC) to the indoor unit.
o After the startup, the value for “external temperature’s reference” (register
22/23) has a value -32768 (0x8000). This value means that no external
temperature reference is being provided through INMBSHIT001R000. In this
scenario, the setpoint value shown in register 4/5 will always be the same as the
current setpoint value of the indoor unit. AC indoor unit will use its own return
path temperature sensor as reference for its control loop.
o When the mechanism of “Virtual Temperature” is applied. The temperature
setpoint’s value shown by the Remote Controller or other Control System from
Hitachi connected to the indoor unit may show a different value from the value
shown in register 4/5.
o If it is desired to use the temperature’s reading from the Remote Control as the
external temperature reference (Tu ,register 22/33), the Remote Controller must
be configured as Master, and the Hitachi AC indoor unit must have the option
“thermostat sensor in the Remote Controller” as activated. This configuration is
done via a Hitachi Remote Controller connected to the indoor unit and must be
done by Hitachi authorized installers while the AC is being installed.
o When INMBSHIT001R000 is set as “Master” of AB bus, the external temperature’s
sensor connected to Modbus RTU EIA-485 network provides directly the value
currently applied to the indoor unit ( SAC ), and the process of the Virtual
temperature is not applied. In this case, the Remote Controller or any other
Control System connected from Hitachi is not able to send the external
temperature reference’s value to the register 22/23.
o AC Real temperature setpoint (R)
(register 23 – In Protocol address / register 24 – in PLC address):
As it has been detailed on the previous point, the real temperature setpoint in the indoor
unit and the temperature setpoint requested from INMBSHIT001R000 might differ (when
a value in register 22/23 – “external temperature reference” is entered). This register
always informs about the current temperature setpoint which is being used by the indoor
unit.
Moreover, notice that temperature’s values of all these four registers are expressed according to
the temperature´s format configured through its onboard DIP-Switches (See “3.3 - DIP-switch
Configuration Interface”). These following formats are possible:
• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a
value “22” in the Modbus register must be interpreted as 22ºC)
• Decicelsius value: Value in Modbus register is the temperature value in
decicelsius (i.e. a value “220” in the Modbus register must be interpreted as
22.0ºC)
• Fahrenheit value: Value in Modbus register is the temperature value in
Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF
(~22ºC).
3.3 DIP-switch Configuration Interface