Intesis INMBSFGL001I000 User guide

Fujitsu Air Conditioning
Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu
USER MANUAL
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 21
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 / 21
Gateway for the integration of a Fujitsu air conditioning unit in ModBus RTU enabled monitoring and control systems.
Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu.
ORDER CODE
LEGACY ORDER CODE
INMBSFGL001I000
FJ-AC-MBS-1
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 / 21
INDEX
1 Presentation .......................................................................................................................................................... 5
2 Connection ............................................................................................................................................................ 6
Connect to the AC indoor unit ....................................................................................................................... 6
Connection to the EIA-485 bus ..................................................................................................................... 6
3 Quick Start Guide .................................................................................................................................................. 7
4 Modbus Interface Specification ............................................................................................................................. 8
Modbus physical layer ................................................................................................................................... 8
Modbus Registers ......................................................................................................................................... 8
4.2.1 Control and status registers ................................................................................................................... 8
4.2.2 Configuration Registers ....................................................................................................................... 10
4.2.3 Considerations on Temperature Registers .......................................................................................... 10
DIP-switch Configuration Interface .............................................................................................................. 12
Implemented Functions ............................................................................................................................... 14
Device LED indicator ................................................................................................................................... 14
EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................................................... 15
5 Mechanical & electrical characteristics ............................................................................................................... 16
6 AC Unit Types compatibility ................................................................................................................................ 17
7 Error codes .......................................................................................................................................................... 18
Intesis Codes ............................................................................................................................................... 18
RAC and VRF J-II / V-II / VR-II series ......................................................................................................... 18
VRF V / S / J Series .................................................................................................................................... 21
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 21
1 Presentation
The INMBSFGL001I000 interfaces allow a complete and natural integration of Fujitsu air conditioners into Modbus RTU (EIA-485) networks.
Reduced dimensions. 93 x 53 x 58 mm
3.7” x 2.1” x 2.3”
Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit of AC.
External power not required.
Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSFGL001I000 devices can be connected
in the same network.
INMBSFGL001I000 is a Modbus slave device.
Direct connection to the AC indoor unit.
Configuration from both on-board DIP-switches and Modbus RTU.
Total Control and Supervision.
Real states of the AC unit's internal variables.
Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation of Modbus Repeaters may
be required
SCADA
PLC
DDC
BMS
HMI
Controller
etc
Up to 63 AC indoor units*
Modbus RTU
EIA-485 network
Modbus RTU
Master device
INMBSFGL001I000
INMBSFGL001I000
INMBSFGL001I000
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 / 21
2 Connection
The interface comes with cable + connectors for direct connection to the AC indoor unit, and with a plug-in terminal block of 3 poles for connection to a Modbus RTU EIA-485 network.
Connect to the AC indoor unit
The INMBSFGL001I000 connects directly to the indoor unit internal control board. In the control board locate the socket connector marked as CN65.
Figure 2.1 INMBSFGL001I000 connection diagram
Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block of INMBSFGL001I000 and keep the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120 must be present at each end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism.
CN65
AC indoor unit
Electronic control board
200 mm / 7.9”
40 mm / 1.6”
Connection cable provided with the interface
90 mm / 3.5”
53 mm / 2.1”
Use this hole to attach the cable using the staple and the screw provided with the interface
Fixing screw
ModBus RTU
EIA-485
Bus
AC Unit
B A SG
EIA485
For wall mounting, extract the upper and lower staples until you listen the "click".
SW1
SW2
SW3
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 / 21
3 Quick Start Guide
1. Disconnect the air conditioning from Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions of the diagram below or install it inside the AC indoor unit (respect the safety instructions given).
3. Connect to CN65 between the interface and the AC indoor unit following the instructions of the diagram.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the current installation’s parameters:
By default, the interface is set to:
Modbus Slave Address ➔ 1 ▪ Modbus baud rate ➔ 9600 bps
These parameters can be modified from DIP-Switches (see for further information). NOTE: All changes on the DIP-Switch configuration require a system power cycle to be applied.
7. Connect the AC system to Mains Power. IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to start
communicating.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
8 / 21
4 Modbus Interface Specification
Modbus physical layer
INMBSFGL001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit).
Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
0: Off ▪ 1: On
1
2
R/W
AC unit Mode 1
0: Auto ▪ 1: Heat ▪ 2: Dry ▪ 3: Fan ▪ 4: Cool
2
3
R/W
AC unit Fan Speed 1
0: Auto ▪ 1: Quiet ▪ 2: Low ▪ 3: Med ▪ 4: High
3
4
R/W
AC unit Vane Position 1
1: Position-1 (Horizontal) ▪ 2: Position-2 (Horizontal) ▪ 3: Position-3 (Medium) ▪ 4: Position-4 (Vertical) ▪ 10: Swing
4
5
R/W
AC unit Temperature Setpoint
1,2,3,4
-32768 (Initialization value) ▪ 16..30 (ºC) (0 = undetermined) ▪ 61..86 (ºF) (0 = undetermined)
5
6
R
AC unit Temperature reference
1,2,3,4
18..30 (ºC) (0 = undetermined) ▪ 64,4..86 (ºF) (0 = undetermined) ▪ 0x8000 There is no temperature sent from the Remote
controller
6
7
R/W
Window Contact
0: Closed (Default) ▪ 1: Open
7
8
R/W
INMBSFGL001I000 Disablement 5
0: INMBSFGL001I000 enabled (Default value) ▪ 1: INMBSFGL001I000 disabled
8
9
R/W
AC Remote Control Disablement 5
0: Remote Control enabled (Default value) ▪ 1: Remote Control disabled
9
10
R/W
AC unit Operation Time
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit.
3
It is not possible turn to x10 the value shown in Fahrenheit.
4
See section 4.2.3 CONSIDERATIONS ON TEMPERATURE REGISTERS for more information
5
This value is stored in non-volatile memory
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
9 / 21
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0..65535 (hours). Counts the time the AC unit is in “On”
state.
10
11
R
AC unit Alarm Status
0: No alarm condition ▪ 1: Alarm condition
11
12
R
Error Code 6
0: No error present ▪ 65535(-1 if it is read as signed value): Error in the
communication of INMBSFGL001I000 or Remote Controller with the AC unit.
Any other value, see the table at the end of this
document.
22
23
R/W
Indoor unit´s ambient temperature from external sensor (at Modbus side)
1,2,3,4
-32768: (Initialization value). No temperature is being
provided from an external sensor.
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,4
When no external temperature is provided, this read-
only register will have the same value as register 5 (PLC addressing). In all cases, it will show the current setpoint in the indoor unit.
16..31ºC (ºC/x10ºC) ▪ 60..92ºF
24
25
R
Current AC max setpoint
1,2,3
-32768 (Initialization value) ▪ Ranges are specific from Manufacturer
25
26
R
Current AC min setpoint
1,2,3
-32768 (Initialization value) ▪ Ranges are specific from Manufacturer
26
27
R/W
AC unit Horizontal Vane Position 1
0: Auto (Default) ▪ 1: Position 1 ▪ 5: Position 5 ▪ 10: Swing
31
32
R
Window status (feedback)
0: Not active (Default value) ▪ 1: Active (Window is open)
36
37
R/W
External On/Off disablement:
0: Not active (Default value) ▪ 1: Active
40
41
R
Window contact ON/OFF disablement:
0: Window contact is disabled (not working) ▪ 1: Window contact is enabled (in use)
43
44
W
Filter reset:
1: Reset
44
45
R
Filter status
0: Off ▪ 1: Lit
56
57
R/W
Antifreeze operation
0: Disabled 1: Enabled
64
65
R/W
Economy
0: Disabled ▪ 1: Enabled
65
66
R
Input reference temperature
1,2,3
6
See section 7 ERROR CODES for possible error codes and their explanation
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
10 / 21
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0x8000: No temperature’s value is being provided from
an external sensor. No virtual temperature is being applied.
Any other: (ºC/x10ºC/ºF)
66
67
R
Return path temperature
1,2,3
-32768 (Initialization value) ▪ Ranges are specific from Manufacturer
97
98
R/W
Block Periodic Sendings
5,7
0: Non-blocked (Default value) ▪ 1: Blocked
98
99
R
Master/Slave (gateway’s role)
0: Slave ▪ 1: Master
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
13
14
R/W
“Open Window” switch-off timeout 8
0..30 (minutes) ▪ Factory setting: 30 (minutes)
14
15
R
Modbus RTU baud-rate
2400bps ▪ 4800bps ▪ 9600bps (Default) ▪ 19200bps ▪ 38400bps ▪ 57600bps ▪ 76800bps ▪ 115200bps
15
16
R
Modbus Slave Address
1..63
49
50
R
Device ID: 0x0D00
50
51
R
Software version
99
100
W
Reset
1: Reset
4.2.3 Considerations on Temperature Registers
AC unit Temperature Setpoint (R/W) (register 5 in PLC addressing): This is the adjustable temperature setpoint meant to be required by the user. This register can be read (Modbus function 3 or 4) or written (modbus functions 5 or 16). A remote controller connected to the 3-wire bus of the Fujitsu indoor unit will report the same temperature setpoint value as this register.
AC unit external reference temperature (R/W) (register 23 in PLC addressing): This register allows providing an external temperature reference from Modbus side. If an external temperature is provided through this register, indoor unit will use it as reference for its temperature control loop.
o This register will have no effect in those Fujitsu RAC / domestic line splits Air-Conditioning units –
this is, those models requiring an additional communication accessory enabling communication with INMBSFGL001I000.
o For this temperature to take effect it is required that the Fujitsu AC indoor unit is configured in such
a way that it uses the “thermostat sensor in the remote controller” (this is, INMBSFGL001I000 will act as thermostat sensor providing a temperature sensor reading).
7
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”, commands from Modbus will only
be sent to the AC system if they differ from the previous value.
8
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 21
o This configuration is done via a Fujitsu remote controller connected to the indoor unit (Function
number “42” – setting value “1” / operation of Thermosensor button) and must be done by Fujitsu authorized installers at the time of the installation of the AC.
o Register value after INMBSFGL001I000 startup is -32768, which means that no temperature
reference is provided to the AC indoor unit. In that case, AC indoor unit will use its own return path temperature sensor as reference for its control loop.
o Virtual temperature mechanism will be activated once the first temperature value is received on
register 23 – in PLC addressing:
SAC = Su – (Tu – SU)
Where: SAC - setpoint value currently applied to the indoor unit Su - setpoint value Tu - external temperature reference written at BACnet side
When INMBSFGL001I000 detects a change in any of the values of {Su, Tu}, it will send the new setpoint (SAC) to the indoor unit.
Moreover, notice that temperature’s values of all these four registers are expressed according to the temperature´s format configured through its onboard DIP-Switches (See sectin 4.3 for details). These following formats are possible:
Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a value “22” in the Modbus register must be interpreted as 22ºC).
Tenths of value: Value in Modbus register is the temperature value in decicelsius (i.e. a value “220” in the Modbus register must be interpreted as 22.0ºC).
Fahrenheit value: Value in Modbus register is the temperature value in Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF (~22ºC).
NOTE
Fujitsu General cannot guarantee the Room Temperature object value is consistently equal to the current actual room temperature.
The Room Temperature is only allowed for displaying, it cannot be used for controlling other equipment.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
12 / 21
DIP-switch Configuration Interface
All the configuration values on INMBSFGL001I000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface. The device has DIP-switches SW1, SW2 and SW3 on the following locations:
*Consider OFF as
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC configuration + Modbus baud rate
AC Configuration
Modbus Baud rate
SW1-P1…5
Description
SW1-P6..8
Description
Not used (default value)
Low Power mode (default value)
2400bps
Not used
High Performance mode
4800bps
Not used (default value)
9600bps (Default value)
Not used
19200bps
Not used (default value)
38400bps
Not used
57600bps
Not used (default value)
76800bps
Not used
115200bps
Table 4.1 SW1: AC Configuration + Modbus baud rate
SW1
B A SG
EIA 485
SW3
SW2
ON ON
ON
SW1
1 2 3
1 2 3 4 5 6 7 8
SW3
SW2
ON
ON
ON
ON
ON
1 2 3 4 5 6 7 8
AC Unit
L1 L2
AC Unit
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
13 / 21
SW2 – Modbus Slave address + Degrees/tenths of degrees (x10) + Temp. magnitude (ºC/ºF)
Table 4.2 SW2: Modbus slave address
Table 4.3 SW2: Degrees / tenths of degrees (x10) + Temperature magnitude (ºC/ºF)
Add SW2-P1..6
Add SW2-P1..6
Add SW2-P1..6
Add SW2-P1..6
Add SW2-P1..6
0
13
26
39
52
1
14
27
40
53
2
15
28
41
54
3
16
29
42
55
4
17
30
43
56
5
18
31
44
57
6
19
32 45
58
7
20
33
46
59
8
21
34 47
60
9
22
35
48
61
10
23
36
49
62
11 24 37 50 63
12 25 38 51
SW2-P7-8
Description
Temperature values in ModBus register are represented in degrees (x1) (default value)
Temperature values in ModBus register are represented in tenths of degrees (x10)
Temperature values in ModBus register are represented in Celsius degrees (default value)
Temperature values in ModBus register are represented in Fahrenheit degrees
ON SAB
ON SAB
ON SAB
ON SAB
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
14 / 21
SW3 – Termination resistor + BUS polarization configuration
Table 4.4 SW3: Temperature and termination resistor configuration
Implemented Functions
INMBSPAN001R000 implements the following standard Modbus functions:
3: Read Holding Registers 4: Read Input Registers 6: Write Single Register 16: Write Multiple Registers (Despite this function is allowed, the interface does not allow to write operations
on more than 1 register with the same request, this means that length field should be always be 1 when this function is being used in case of writing)
Device LED indicator
The device includes two LED indicators to show all the possible operational states. In the following table there are written the indicators which can be performed and their meaning.
L1 (green LED)
Device status
LED indication
ON / OFF Period
Description
During not normal operation
LED blinking
500ms ON / 500ms OFF
Communication error
During normal operation
LED flashing
100ms ON / 1900ms OFF
Normal operation (configured and working properly)
L2 (red LED)
Device status
LED indication
ON / OFF Period
Description
During not normal operation
LED Pulse
3sec ON / --- OFF
Under voltage
L1 (green LED) & L2 (red LED)
Device status
LED indication
ON / OFF Period
Description
During normal operation
LED Pulse
5sec ON / --- OFF
Device Start-up
During not normal operation
LED alternatively blinking
500ms ON / 500ms OFF
EEPROM failure
SW3-P1..3
Description
EIA-485 bus without termination resistor (Default value).
Internal termination resistor of 120Ω connected to EIA-485 bus.
No BUS polarization (default value).
BUS polarization active.
ON
ON
ON
ON
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
15 / 21
EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections. To prevent fail status detected by the receivers, which are listening” the bus, when all the transmitters outputs are
in three-state (high impedance), it is also required a fail-safe biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the bus when all the transmitters’ outputs are in three-state. This mechanism must be supplied by the Modbus Master.
The INMBSFGL001I000 device includes an on-board terminator resistor of 120Ω that can be connected to the EIA­485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor and/or fail-safe biasing mechanism (Check the technical documentation of the Master device connected to the EIA-485 network in each case).
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
16 / 21
5 Mechanical & electrical characteristics
Enclosure
Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Color: Light Grey. RAL 7035
Operation Temperature
0ºC to +70ºC
Weight
85 g.
Stock Temperature
-20ºC to +85ºC
Mounting
Wall DIN rail EN60715 TH35.
Operational Humidity
<95% RH, non-condensing
Terminal Wiring (for low-voltage signals)
For terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
Stock Humidity
<95% RH, non-condensing
ModBus RTU port
1 x EIA485 Plug-in screw terminal block (2 poles +
GND) with 120 Ω resistor termination and
polatization selectable by switch.
Isolation voltage
1500 VDC
AC unit port
1 x Specific connector Specific cable included
Isolation resistance
1000 MΩ
Switch 1 (SW1)
1 x DIP-Switch for Air Conditioner Unit + ModBus baud rate
Protection
IP20
Switch 3 (SW3)
1 x DIP-Switch for ModBus RTU slave address + temperature magnitude (ºC/ºF) and scale (x1/x10).
LED indicators
2 x Onboard LED - Operational status
53 mm
93 mm
58 mm
AC Unit
connection
DIP
Switch SW3
LED
Indicator
DIP
Switch SW1
DIP
Switch SW2
ModBus RTU Port
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
17 / 21
6 AC Unit Types compatibility
Please, check compatibility list at to know which Fujitsu units are compatible with our gateway.
https://www.intesis.com/docs/compatibilities/inxxxfgl001i000_compatibility
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
18 / 21
7 Error codes
Intesis Codes
Error Code
Modbus
Error in Remote
Controller
Error Description
0
N/A
No active error
65535
(-1)
N/A
Error in the communication of INMBSFGL001I000 or Remote Controller with the AC unit
RAC and VRF J-II / V-II / VR-II series
Error Code
Modbus
Error in Remote
Controller
System
Error Description
0
00
Wired remote controller error
1
01
Indoor signal error
2
02
Indoor room temperature sensor error
3
03
Indoor room temperature sensor error
4
04
Indoor heat exchanger temperature sensor (middle) error
5
05
Indoor heat exchanger temperature sensor (middle) error
6
06
Outdoor heat exchanger temperature sensor (outlet) error
7
07
Outdoor heat exchanger temperature sensor (outlet) error
8
08
Power voltage error
9
09
Float switch operated
10
0A
Outdoor temperature sensor error
11
0b
Outdoor temperature sensor error
12
0C
Outdoor discharge pipe temperature sensor error
13
0d
Outdoor discharge pipe temperature sensor error
14
0E
Heat sink thermistor (Inverter) error
15
0F
Discharge temperature error
17
11
Indoor unit EEPROM error
18
12
Indoor fan error
19
13
Indoor signal error
20
14
Outdoor EEPROM error
21
15
RAC
Compressor temperature sensor error
22
16
Inverter and
Pressure switch abnormal, Pressure sensor error
23
17
Non Inverter
IPM protection
24
18
CT error
25
19
Active filter error
INV voltage protection
26
1A
Compressor location error
27
1b
Outdoor fan error
28
1C
Outdoor unit computer communication error
29
1d
2-way valve temperature sensor error
30
1E
3-way valve temperature sensor error
31
1F
Connected indoor unit error
32
20
Indoor MANUAL AUTO switch error
33
21
reverse VDD permanent stop protection
34
22
VDD permanent stop protection
36
24
Excessive high pressure protection on cooling
37
25
P.F.C. circuit error
38
26
Indoor signal error
39
27
Indoor signal error
40
28
Indoor heat exchanger temperature sensor (inlet) error
41
29
Outdoor heat exchanger temperature sensor (middle) error
42
2A
Power supply frequency detection error
43
2b
Compressor temperature error
44
2C
4-way valve error
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
19 / 21
Error Code
Modbus
Error in Remote
Controller
System
Error Description
45
2d
Heat sink thermistor P.F.C. error
46
2E
Indoor unit damper error
Inverter error
47
2F
RAC
Low pressure error
48
30
Inverter and
Refrigerant circuit address set-up error
49
31
Non Inverter
Master unit, Slave unit set-up error
50
32
Connected the indoor number set-up error
51
33
P.F.C. printed circuit board error
52
34
Indoor fan 2 error
53
35
Control box thermistor error
54
36
Indoor unit CT error
55
37
Indoor fan motor 1 driving circuit error
56
38
Indoor fan motor 2 driving circuit error
117
11
Serial communication error between indoor/outdoor units
118
12
Remote controller communication error
119
13
Communication error between outdoor units
120
14
Network communication error
121
15
Scan error
122
16
Peripheral unit communication error
123
17
Electricity charge apportionment error
133
21
Indoor unit initial setting error
134
22
Indoor unit capacity abnormal
135
23
Incompatible series connection error
136
24
Connection unit number error
137
25
Connection pipe length error
138
26
RAC
Indoor unit address setting error
139
27
Inverter
Master/slave unit setting error
140
28
Models G
Other setting error
141
29
series
Connection unit number error in wired remote controller system
149
31
Indoor unit power supply abnormal
150
32
VRF
Indoor unit main PCB error
151
33
J-II/V-II/VR-II
Indoor unit display PCB error
152
34
Series
Power relay error
153
35
Indoor unit manual auto switch error
154
36
Heater relay error
155
37
Indoor unit transmission PCB error
156
38
Network convertor PCB error
157
39
Indoor unit power supply circuit error
158
3A
Indoor unit communication circuit (wired remote controller) error
165
41
Indoor unit room temp. thermistor error
166
42
Indoor unit heat ex. temp. thermistor error
167
43
Humidity sensor error
168
44
Light sensor error
169
45
Gas sensor error
170
46
Float sensor error
171
47
Water temperature sensor error
172
48
Warm water flow rate sensor error
173
49
Heater sensor error
181
51
Indoor unit fan motor 1 error
182
52
Indoor unit coil (expansion valve) error
183
53
Indoor unit water drain abnormal
184
54
Air cleaning function error
185
55
Filter cleaning function error
186
56
Water circulation pump error
187
57
Indoor unit damper error
188
58
Indoor unit intake grille position error
189
59
Indoor unit fan motor 2 error
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
20 / 21
Error Code
Modbus
Error in Remote
Controller
System
Error Description
195
5U
Indoor unit miscellaneous error
197
61
Outdoor unit power supply abnormal
198
62
Outdoor unit main PCB error
199
63
Outdoor unit inverter PCB error
200
64
Outdoor unit active filter/PFC circuit error
201
65
Outdoor unit IPM error
202
66
Convertor distinction error
203
67
Outdoor unit power short interruption error (protective operation)
204
68
Outdoor unit magnetic relay error
205
69
Outdoor unit transmission PCB error
206
6A
Outdoor unit display PCB error
213
71
Outdoor unit discharge temp. thermistor error
214
72
Outdoor unit compressor temp. thermistor error
215
73
Outdoor unit heat ex. temp. thermistor error
216
74
Outside air temp. thermistor error
217
75
Outdoor unit suction gas temp. thermistor error
218
76
Outdoor unit operating valve thermistor error
219
77
Outdoor unit heat sink temp. thermistor error
220
78
Expansion valve temperature sensor error
229
81
Receiver liquid level detection sensor error
230
82
Outdoor unit sub-cool heat ex. gas temp. thermistor error
231
83
Outdoor unit liquid pipe temp. thermistor error
232
84
RAC
Outdoor unit current sensor error
233
85
Inverter
Fan motor current sensor error
234
86
Models G
Outdoor unit pressure sensor error
235
87
series
Oil sensor error
245
91
Outdoor unit compressor 1 error
246
92
Outdoor unit compressor 2 error
247
93
VRF
Outdoor unit compressor start up error
248
94
J-II/V-II/VR-II
Outdoor unit trip detection
249
95
Series
Outdoor unit compressor motor control error
250
96
Open loop error (Field-weakening relevant)
251
97
Outdoor unit fan motor 1 error
252
98
Outdoor unit fan motor 2 error
253
99
Outdoor unit 4-way valve error
254
9A
Outdoor unit coil (expansion valve) error
259
9U
Outdoor unit miscellaneous error
261
A1
Outdoor unit discharge temperature 1 error
262
A2
Outdoor unit discharge temperature 2 error
263
A3
Outdoor unit compressor temperature error
264
A4
Outdoor unit pressure error 1
265
A5
Outdoor unit pressure error 2
266
A6
Outdoor unit heat exchanger temperature error
267
A7
Suction temperature abnormal
268
A8
Poor refrigerant circulation
269
A9
Current overload error
270
AA
Outdoor unit special operation error
271
AC
Ambient temperature error
272
AF
Out of the possible operation range
273
AJ
Freeze protection operated
277
C1
Peripheral unit main PCB error
278
C2
Peripheral unit transmission PCB error
279
C3
Peripheral unit PCB 1 error
280
C4
PCB 2 error
281
C5
PCB 3 error
282
C6
PCB 4 error
283
C7
PCB 5 error
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
21 / 21
Error Code
Modbus
Error in Remote
Controller
System
Error Description
284
C8
Peripheral unit input device error
285
C9
Display device error
286
CA
EEPROM error
287
CC
Peripheral unit sensor error
288
CF
Peripheral unit external connector error (USB memory)
289
CJ
Other parts error
293
F1
RAC
System tool software error
294
F2
Inverter
System tool adaptor error
295
F3
Models G
System tool interface error
296
F4
series
System tool environment error
309
J1
RB unit error
310
J2
Branch boxes error
311
J3
VRF
Total heat exchanging, ventilation unit error
312
J4
J-II/V-II/VR-II
Domestic hot water unit error
313
J5
Series
Zone control interface error
VRF V / S / J Series
Error Code
Modbus
Error in Remote
Controller
System
Error Description
0
00
No Error 2 02
Model information Error
4
04
Power frequency Error
6
06
VRF
EEPROM access Error
7
07
V / S / J
EEPROM deletion Error
9
09
Series
Room sensor Error
10
0A
Heat Ex. Middle Sensor Error
11
0b
Heat Ex. Inlet sensor Error
12
0C
Heat Ex. Outlet sensor Error
13
0d
Blower temperature thermistor Error
17
11
Drain Error
18
12
Room temperature Error
19
13
Indoor fan motor Error
20
18
VRF
Standard wired remote Error
V / S / J
Standard wired token Error
31
1F
Series
Network communication Error
32
20
Node setting error
33
21
Communication Error between Main PCB & Transmission PCB
34
32
Outdoor unit Error
In case you detect an error code not listed, contact your nearest Fujitsu technical support service for more information on the error meaning.