Fujitsu Air Conditioning
Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu
USER MANUAL
Issue date: 05/2021 r1.3 ENGLISH

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any
inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for
any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product
development. The information in this document shall therefore not be construed as a commitment on the part of
HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment
to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only
intended to help improve understanding of the functionality and handling of the product. In view of the wide range
of possible applications of the product, and because of the many variables and requirements associated with any
particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on
the data, examples or illustrations included in this document nor for any damages incurred during installation of the
product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the
product is used correctly in their specific application and that the application meets all performance and safety
requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will
under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of
undocumented features or functional side effects found outside the documented scope of the product. The effects
caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility
issues and stability issues.

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Gateway for the integration of a Fujitsu air conditioning unit in
ModBus RTU enabled monitoring and control systems.
Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu.

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
INDEX
1 Presentation .......................................................................................................................................................... 5
2 Connection ............................................................................................................................................................ 6
Connect to the AC indoor unit ....................................................................................................................... 6
Connection to the EIA-485 bus ..................................................................................................................... 6
3 Quick Start Guide .................................................................................................................................................. 7
4 Modbus Interface Specification ............................................................................................................................. 8
Modbus physical layer ................................................................................................................................... 8
Modbus Registers ......................................................................................................................................... 8
4.2.1 Control and status registers ................................................................................................................... 8
4.2.2 Configuration Registers ....................................................................................................................... 10
4.2.3 Considerations on Temperature Registers .......................................................................................... 10
DIP-switch Configuration Interface .............................................................................................................. 12
Implemented Functions ............................................................................................................................... 14
Device LED indicator ................................................................................................................................... 14
EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................................................... 15
5 Mechanical & electrical characteristics ............................................................................................................... 16
6 AC Unit Types compatibility ................................................................................................................................ 17
7 Error codes .......................................................................................................................................................... 18
Intesis Codes ............................................................................................................................................... 18
RAC and VRF J-II / V-II / VR-II series ......................................................................................................... 18
VRF V / S / J Series .................................................................................................................................... 21

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
1 Presentation
The INMBSFGL001I000 interfaces allow a complete and natural integration
of Fujitsu air conditioners into Modbus RTU (EIA-485) networks.
Reduced dimensions. 93 x 53 x 58 mm
3.7” x 2.1” x 2.3”
Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit of AC.
• External power not required.
• Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSFGL001I000 devices can be connected
in the same network.
INMBSFGL001I000 is a Modbus slave device.
• Direct connection to the AC indoor unit.
• Configuration from both on-board DIP-switches and Modbus RTU.
• Total Control and Supervision.
• Real states of the AC unit's internal variables.
• Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation of Modbus Repeaters may
be required
• PLC
• DDC
• BMS
• HMI
• Controller
Up to 63 AC
indoor units*

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 Connection
The interface comes with cable + connectors for direct connection to the AC indoor unit, and with a plug-in terminal
block of 3 poles for connection to a Modbus RTU EIA-485 network.
Connect to the AC indoor unit
The INMBSFGL001I000 connects directly to the indoor unit internal control board. In the control board locate the
socket connector marked as CN65.
Figure 2.1 INMBSFGL001I000 connection diagram
Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block of INMBSFGL001I000 and keep the polarity on this
connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star
typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120Ω must be present at each end
of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism.
Connection cable
provided with the
interface
Use this hole to
attach the cable
using the staple and
the screw provided
with the interface
For wall mounting,
extract the upper and
lower staples until you
listen the "click".

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 Quick Start Guide
1. Disconnect the air conditioning from Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions of the diagram below
or install it inside the AC indoor unit (respect the safety instructions given).
3. Connect to CN65 between the interface and the AC indoor unit following the instructions of the diagram.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the current installation’s
parameters:
By default, the interface is set to:
▪ Modbus Slave Address ➔ 1
▪ Modbus baud rate ➔ 9600 bps
These parameters can be modified from DIP-Switches (see for further information).
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be applied.
7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to start
communicating.

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 Modbus Interface Specification
Modbus physical layer
INMBSFGL001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs
8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps,
9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1
communication (8 data bits, no parity and 1 stop bit).
Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
AC unit On/Off
▪ 0: Off
▪ 1: On
AC unit Mode 1
▪ 0: Auto
▪ 1: Heat
▪ 2: Dry
▪ 3: Fan
▪ 4: Cool
AC unit Fan Speed 1
▪ 0: Auto
▪ 1: Quiet
▪ 2: Low
▪ 3: Med
▪ 4: High
AC unit Vane Position 1
▪ 1: Position-1 (Horizontal)
▪ 2: Position-2 (Horizontal)
▪ 3: Position-3 (Medium)
▪ 4: Position-4 (Vertical)
▪ 10: Swing
AC unit Temperature Setpoint
1,2,3,4
▪ -32768 (Initialization value)
▪ 16..30 (ºC) (0 = undetermined)
▪ 61..86 (ºF) (0 = undetermined)
AC unit Temperature reference
1,2,3,4
▪ 18..30 (ºC) (0 = undetermined)
▪ 64,4..86 (ºF) (0 = undetermined)
▪ 0x8000 There is no temperature sent from the Remote
controller
Window Contact
▪ 0: Closed (Default)
▪ 1: Open
INMBSFGL001I000 Disablement 5
▪ 0: INMBSFGL001I000 enabled (Default value)
▪ 1: INMBSFGL001I000 disabled
AC Remote Control Disablement 5
▪ 0: Remote Control enabled (Default value)
▪ 1: Remote Control disabled
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for this register.
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit.
It is not possible turn to x10 the value shown in Fahrenheit.
See section 4.2.3 CONSIDERATIONS ON TEMPERATURE REGISTERS for more information
This value is stored in non-volatile memory

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
▪ 0..65535 (hours). Counts the time the AC unit is in “On”
state.
AC unit Alarm Status
▪ 0: No alarm condition
▪ 1: Alarm condition
Error Code 6
▪ 0: No error present
▪ 65535(-1 if it is read as signed value): Error in the
communication of INMBSFGL001I000 or Remote
Controller with the AC unit.
▪ Any other value, see the table at the end of this
document.
Indoor unit´s ambient temperature from external
sensor (at Modbus side)
1,2,3,4
▪ -32768: (Initialization value). No temperature is being
provided from an external sensor.
▪ Any other: (ºC/x10ºC/ºF)
AC Real temperature setpoint
1,2,3,4
▪ When no external temperature is provided, this read-
only register will have the same value as register 5 (PLC
addressing). In all cases, it will show the current setpoint
in the indoor unit.
▪ 16..31ºC (ºC/x10ºC)
▪ 60..92ºF
Current AC max setpoint
1,2,3
▪ -32768 (Initialization value)
▪ Ranges are specific from Manufacturer
Current AC min setpoint
1,2,3
▪ -32768 (Initialization value)
▪ Ranges are specific from Manufacturer
AC unit Horizontal Vane Position 1
▪ 0: Auto (Default)
▪ 1: Position 1
▪ …
▪ 5: Position 5
▪ 10: Swing
Window status (feedback)
▪ 0: Not active (Default value)
▪ 1: Active (Window is open)
External On/Off disablement:
▪ 0: Not active (Default value)
▪ 1: Active
Window contact ON/OFF disablement:
▪ 0: Window contact is disabled (not working)
▪ 1: Window contact is enabled (in use)
Filter status
▪ 0: Off
▪ 1: Lit
Antifreeze operation
▪ 0: Disabled
▪ 1: Enabled
Economy
▪ 0: Disabled
▪ 1: Enabled
Input reference temperature
1,2,3
See section 7 ERROR CODES for possible error codes and their explanation

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
▪ 0x8000: No temperature’s value is being provided from
an external sensor. No virtual temperature is being
applied.
▪ Any other: (ºC/x10ºC/ºF)
Return path temperature
1,2,3
▪ -32768 (Initialization value)
▪ Ranges are specific from Manufacturer
Block Periodic Sendings
5,7
▪ 0: Non-blocked (Default value)
▪ 1: Blocked
Master/Slave (gateway’s role)
▪ 0: Slave
▪ 1: Master
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
“Open Window” switch-off timeout 8
▪ 0..30 (minutes)
▪ Factory setting: 30 (minutes)
Modbus RTU baud-rate
▪ 2400bps
▪ 4800bps
▪ 9600bps (Default)
▪ 19200bps
▪ 38400bps
▪ 57600bps
▪ 76800bps
▪ 115200bps
Modbus Slave Address
▪ 1..63
4.2.3 Considerations on Temperature Registers
• AC unit Temperature Setpoint (R/W) (register 5 – in PLC addressing): This is the adjustable temperature
setpoint meant to be required by the user. This register can be read (Modbus function 3 or 4) or written
(modbus functions 5 or 16). A remote controller connected to the 3-wire bus of the Fujitsu indoor unit will
report the same temperature setpoint value as this register.
• AC unit external reference temperature (R/W) (register 23 – in PLC addressing): This register allows
providing an external temperature reference from Modbus side. If an external temperature is provided
through this register, indoor unit will use it as reference for its temperature control loop.
o This register will have no effect in those Fujitsu RAC / domestic line splits Air-Conditioning units –
this is, those models requiring an additional communication accessory enabling communication with
INMBSFGL001I000.
o For this temperature to take effect it is required that the Fujitsu AC indoor unit is configured in such
a way that it uses the “thermostat sensor in the remote controller” (this is, INMBSFGL001I000 will
act as thermostat sensor providing a temperature sensor reading).
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”, commands from Modbus will only
be sent to the AC system if they differ from the previous value.
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
o This configuration is done via a Fujitsu remote controller connected to the indoor unit (Function
number “42” – setting value “1” / operation of Thermosensor button) and must be done by Fujitsu
authorized installers at the time of the installation of the AC.
o Register value after INMBSFGL001I000 startup is -32768, which means that no temperature
reference is provided to the AC indoor unit. In that case, AC indoor unit will use its own return path
temperature sensor as reference for its control loop.
o Virtual temperature mechanism will be activated once the first temperature value is received on
register 23 – in PLC addressing:
SAC = Su – (Tu – SU)
Where:
SAC - setpoint value currently applied to the indoor unit
Su - setpoint value
Tu - external temperature reference written at BACnet side
When INMBSFGL001I000 detects a change in any of the values of {Su, Tu}, it will send the new
setpoint (SAC) to the indoor unit.
Moreover, notice that temperature’s values of all these four registers are expressed according to the temperature´s
format configured through its onboard DIP-Switches (See sectin 4.3 for details). These following formats are possible:
• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a value “22” in the
Modbus register must be interpreted as 22ºC).
• Tenths of value: Value in Modbus register is the temperature value in decicelsius (i.e. a value “220”
in the Modbus register must be interpreted as 22.0ºC).
• Fahrenheit value: Value in Modbus register is the temperature value in Fahrenheit (i.e. a value “72”
in the Modbus register must be interpreted as 72ºF (~22ºC).
NOTE
• Fujitsu General cannot guarantee the Room Temperature object value is consistently equal to the current
actual room temperature.
• The Room Temperature is only allowed for displaying, it cannot be used for controlling other equipment.

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
DIP-switch Configuration Interface
All the configuration values on INMBSFGL001I000 can be written and read from Modbus interface. Otherwise, some
of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW2 and SW3 on the following locations:
*Consider OFF as
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC configuration + Modbus baud rate
Low Power mode
(default value)
Table 4.1 SW1: AC Configuration + Modbus baud rate

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW2 – Modbus Slave address + Degrees/tenths of degrees (x10) + Temp. magnitude (ºC/ºF)
Table 4.2 SW2: Modbus slave address
Table 4.3 SW2: Degrees / tenths of degrees (x10) + Temperature magnitude (ºC/ºF)
Temperature values in ModBus register are represented in degrees (x1) (default value)
Temperature values in ModBus register are represented in tenths of degrees (x10)
Temperature values in ModBus register are represented in Celsius degrees (default value)
Temperature values in ModBus register are represented in Fahrenheit degrees

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
SW3 – Termination resistor + BUS polarization configuration
Table 4.4 SW3: Temperature and termination resistor configuration
Implemented Functions
INMBSPAN001R000 implements the following standard Modbus functions:
▪ 3: Read Holding Registers
▪ 4: Read Input Registers
▪ 6: Write Single Register
▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not allow to write operations
on more than 1 register with the same request, this means that length field should be always be 1 when this
function is being used in case of writing)
Device LED indicator
The device includes two LED indicators to show all the possible operational states. In the following table there are
written the indicators which can be performed and their meaning.
L1 (green LED)
During not normal
operation
Normal operation (configured and
working properly)
During not normal
operation
L1 (green LED) & L2 (red LED)
During not normal
operation
LED alternatively
blinking
EIA-485 bus without termination resistor (Default value).
Internal termination resistor of 120Ω connected to EIA-485 bus.
No BUS polarization (default value).

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections.
To prevent fail status detected by the receivers, which are “listening” the bus, when all the transmitters’ outputs are
in three-state (high impedance), it is also required a fail-safe biasing mechanism. This mechanism provides a safe
status (a correct voltage level) in the bus when all the transmitters’ outputs are in three-state. This mechanism must
be supplied by the Modbus Master.
The INMBSFGL001I000 device includes an on-board terminator resistor of 120Ω that can be connected to the EIA485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor and/or fail-safe
biasing mechanism (Check the technical documentation of the Master device connected to the EIA-485 network in
each case).

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 Mechanical & electrical characteristics
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh):
93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”
Color: Light Grey. RAL 7035
Wall
DIN rail EN60715 TH35.
Terminal Wiring
(for low-voltage
signals)
For terminal: solid wires or stranded wires (twisted
or with ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
1 x EIA485 Plug-in screw terminal block (2 poles +
GND) with 120 Ω resistor termination and
polatization selectable by switch.
1 x Specific connector
Specific cable included
1 x DIP-Switch for Air Conditioner Unit + ModBus
baud rate
1 x DIP-Switch for ModBus RTU slave address +
temperature magnitude (ºC/ºF) and scale (x1/x10).
2 x Onboard LED - Operational status

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 AC Unit Types compatibility
Please, check compatibility list at to know which Fujitsu units are compatible with our gateway.
https://www.intesis.com/docs/compatibilities/inxxxfgl001i000_compatibility

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 Error codes
Intesis Codes
Error in
Remote
Controller
Error in the communication of INMBSFGL001I000 or Remote Controller with the AC
unit
RAC and VRF J-II / V-II / VR-II series
Error in
Remote
Controller
Wired remote controller error
Indoor room temperature sensor error
Indoor room temperature sensor error
Indoor heat exchanger temperature sensor (middle) error
Indoor heat exchanger temperature sensor (middle) error
Outdoor heat exchanger temperature sensor (outlet) error
Outdoor heat exchanger temperature sensor (outlet) error
Outdoor temperature sensor error
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Outdoor discharge pipe temperature sensor error
Heat sink thermistor (Inverter) error
Discharge temperature error
Compressor temperature sensor error
Pressure switch abnormal, Pressure sensor error
Compressor location error
Outdoor unit computer communication error
2-way valve temperature sensor error
3-way valve temperature sensor error
Connected indoor unit error
Indoor MANUAL AUTO switch error
reverse VDD permanent stop protection
VDD permanent stop protection
Excessive high pressure protection on cooling
Indoor heat exchanger temperature sensor (inlet) error
Outdoor heat exchanger temperature sensor (middle) error
Power supply frequency detection error
Compressor temperature error

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Error in
Remote
Controller
Heat sink thermistor P.F.C. error
Refrigerant circuit address set-up error
Master unit, Slave unit set-up error
Connected the indoor number set-up error
P.F.C. printed circuit board error
Control box thermistor error
Indoor fan motor 1 driving circuit error
Indoor fan motor 2 driving circuit error
Serial communication error between indoor/outdoor units
Remote controller communication error
Communication error between outdoor units
Network communication error
Peripheral unit communication error
Electricity charge apportionment error
Indoor unit initial setting error
Indoor unit capacity abnormal
Incompatible series connection error
Connection unit number error
Connection pipe length error
Indoor unit address setting error
Master/slave unit setting error
Connection unit number error in wired remote controller system
Indoor unit power supply abnormal
Indoor unit main PCB error
Indoor unit display PCB error
Indoor unit manual auto switch error
Indoor unit transmission PCB error
Network convertor PCB error
Indoor unit power supply circuit error
Indoor unit communication circuit (wired remote controller) error
Indoor unit room temp. thermistor error
Indoor unit heat ex. temp. thermistor error
Water temperature sensor error
Warm water flow rate sensor error
Indoor unit fan motor 1 error
Indoor unit coil (expansion valve) error
Indoor unit water drain abnormal
Air cleaning function error
Filter cleaning function error
Water circulation pump error
Indoor unit intake grille position error
Indoor unit fan motor 2 error

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Error in
Remote
Controller
Indoor unit miscellaneous error
Outdoor unit power supply abnormal
Outdoor unit main PCB error
Outdoor unit inverter PCB error
Outdoor unit active filter/PFC circuit error
Convertor distinction error
Outdoor unit power short interruption error (protective operation)
Outdoor unit magnetic relay error
Outdoor unit transmission PCB error
Outdoor unit display PCB error
Outdoor unit discharge temp. thermistor error
Outdoor unit compressor temp. thermistor error
Outdoor unit heat ex. temp. thermistor error
Outside air temp. thermistor error
Outdoor unit suction gas temp. thermistor error
Outdoor unit operating valve thermistor error
Outdoor unit heat sink temp. thermistor error
Expansion valve temperature sensor error
Receiver liquid level detection sensor error
Outdoor unit sub-cool heat ex. gas temp. thermistor error
Outdoor unit liquid pipe temp. thermistor error
Outdoor unit current sensor error
Fan motor current sensor error
Outdoor unit pressure sensor error
Outdoor unit compressor 1 error
Outdoor unit compressor 2 error
Outdoor unit compressor start up error
Outdoor unit trip detection
Outdoor unit compressor motor control error
Open loop error (Field-weakening relevant)
Outdoor unit fan motor 1 error
Outdoor unit fan motor 2 error
Outdoor unit 4-way valve error
Outdoor unit coil (expansion valve) error
Outdoor unit miscellaneous error
Outdoor unit discharge temperature 1 error
Outdoor unit discharge temperature 2 error
Outdoor unit compressor temperature error
Outdoor unit pressure error 1
Outdoor unit pressure error 2
Outdoor unit heat exchanger temperature error
Suction temperature abnormal
Poor refrigerant circulation
Outdoor unit special operation error
Ambient temperature error
Out of the possible operation range
Freeze protection operated
Peripheral unit main PCB error
Peripheral unit transmission PCB error
Peripheral unit PCB 1 error

Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Error in
Remote
Controller
Peripheral unit input device error
Peripheral unit sensor error
Peripheral unit external connector error (USB memory)
System tool software error
System tool adaptor error
System tool interface error
System tool environment error
Total heat exchanging, ventilation unit error
Domestic hot water unit error
Zone control interface error
Error in
Remote
Controller
Heat Ex. Middle Sensor Error
Heat Ex. Inlet sensor Error
Heat Ex. Outlet sensor Error
Blower temperature thermistor Error
Standard wired remote Error
Standard wired token Error
Network communication Error
Communication Error between Main PCB & Transmission PCB
In case you detect an error code not listed, contact your nearest Fujitsu technical support service for more information
on the error meaning.