Intesis INMBSDAI001R000 User guide

Compatible with VRV and SKY line air conditioners commercialized by Daikin
USER MANUAL
Issue date: 10/2020 r3.8 ENGLISH
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 25
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 / 25
Modbus RTU (EIA-485) Interface for Daikin air conditioners
Compatible with VRV and SKY line air conditioners commercialized by Daikin
ORDER CODE
LEGACY ORDER CODE
INMBSDAI001R000
DK-RC-MBS-1
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 / 25
INDEX
1. Presentation .......................................................................................................... 5
2. Connection ............................................................................................................ 6
2.1 Connect to the AC indoor unit ............................................................................... 6
2.2 Connection to the EIA-485 bus ............................................................................. 7
3. Quick Start Guide ................................................................................................... 7
4. Modbus Interface Specification ................................................................................ 8
4.1 Modbus physical layer.......................................................................................... 8
4.2 Modbus Registers ................................................................................................ 8
4.2.1 Control and status registers ........................................................................... 8
4.2.2 Configuration Registers................................................................................ 10
4.2.3 Considerations on Temperature Registers ...................................................... 11
4.3 DIP-switch Configuration Interface ...................................................................... 14
4.4 Implemented Functions ..................................................................................... 17
4.5 Device LED indicator ......................................................................................... 17
4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism ...................... 18
5. Electrical and Mechanical features .......................................................................... 19
6. List of supported AC Unit Types. ............................................................................ 20
7. Error Codes ......................................................................................................... 21
8. Annex 1: Master/Slave of Operation Mode ............................................................... 25
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 25
1. Presentation
The INMBSDAI001R000 interfaces allow a complete and natural integration of Daikin air conditioners into Modbus RTU (EIA-485) networks.
Compatible with all SKY Air and VRV models commercialized by Daikin. Check the Section 6 to obtain more information.
Reduced dimensions. 93 x 53 x 58 mm
3.7” x 2.1” x 2.3”
Quick and easy installation.
Mountable on DIN rail, wall, or even inside the indoor unit on some models of AC.
External power not required.
Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSDAI001R000 devices
can be connected in the same network.
INMBSDAI001R000 is a Modbus slave device.
Direct connection to the AC indoor unit. Up to 16 AC indoor units can be connected to
INMBSDAI001R000, controlling them as one (not individually).
Configuration from both on-board DIP-switches and Modbus RTU.
Total Control and Supervision.
Real states of the AC unit's internal variables.
Allows simultaneous use of the AC’s remote controls and Modbus RTU.
* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation of
Modbus Repeaters may be required
SCADA
PLC
DDC
BMS
HMI
Controller
etc
Up to 63
AC indoor units*
Modbus RTU
EIA-485 network
Modbus RTU
Master
device
INMBSDAI001R000
INMBSDAI001R000 INMBSDAI001R000
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 / 25
Connection to P1P2 bus. Two wire cable.
90 mm
3.5”
53 mm / 2.1
90 mm
3.5”
53 mm / 2.1
2. Connection
The interface comes with a plug-in terminal block of 2 poles to establish direct connection with the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct connection with the Modbus RTU EIA-485 network.
2.1 Connect to the AC indoor unit
The INMBSDAI001R000 connects directly to the Daikin P1P2 Bus, which is not provided within the interface. Depending on which controllers are available, the recommended connection methods are the following ones (details in Figure 2. 1):
Wired remote control available. Connect the gateway as Slave in parallel with the wired
remote controllers (Controller acts as Master).
Infrared remote control available. Connect the gateway as Master in parallel with the
infrared remote controller (Infrared Remote Control as Slave).
No remote control available Connect the gateway directly to the P1P2 bus of the indoor
unit as Master when there is no Daikin Remote Controller.
Maximum P1 P2 bus length is 500 meters / 1,640.42 ft . The bus has no polarity sensitivity.
Important: If a wired remote controller of the AC manufacturer is connected in the same bus, communication may shut down.
Max. 500m / 1,640.42 ft
Max. 500m / 1,640.42 ft
Figure 2. 1 INMBSDAI001R000 Connection diagrams
AC Indoor Unit
MODBUS
RTU
EIA-485
EIA485
A+ B-
P1 P2
AC Unit
For wall mounting extract the upper and lower staples until you hear the "click".
P1 P2
DAIKIN
Internal electronic control
Remote Controller
P2 P1
MODBUS RTU
EIA-485
Bus
EIA485
A+ B-
P1 P2
AC Unit
AC Indoor Unit
Internal electronic control
Connection to P1P2 bus. Two wire cable.
P2 P1
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 / 25
2.2 Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block (the one of two poles) of INMBSDAI001R000 and keep the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120 must be present at each end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism (see section 4.6 for more details).
3. Quick Start Guide
1. Disconnect the air conditioning from the Mains Power.
2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions
of the diagram below or install it inside the AC indoor unit (respect the safety instructions given).
3. Connect the P1P2 bus between the interface and the AC indoor unit following the
instructions of the diagram. Screw each bare cable end in the corresponding P1P2 terminals of each device.
4. Connect the EIA-485 bus to the connector EIA485 of the interface.
5. Close the AC indoor unit.
6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters (see section 4.3).
By default, the interface is set to:
Modbus Slave Address 1 Modbus baud rate 9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be applied.
7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to start communicating.
ON
ON
SW3
SW4
IntesisTM INMBSDAI001R000
User’s Manual r3.8 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
8 / 25
4. Modbus Interface Specification
4.1 Modbus physical layer
INMBSDAI001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit).
4.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the standard Modbus big endian notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
0: Off 1: On
1
2
R/W
AC unit Mode 1
0: Auto 1: Heat 2: Dry 3: Fan 4: Cool
2
3
R/W
AC unit Fan Speed 1
0: Auto 1: Low 2: Mid 3: High
3
4
R/W
AC unit Vane Position 1
1: Position-1 (Horizontal) 2: Position-2 (Horizontal) 3: Position-3 (Medium) 4: Position-4 (Vertical) 5: Position-5 (Vertical) 10: Swing
4
5
R/W
AC unit Temperature Setpoint
1,2,3
-32768 (Initialization value) 16..31ºC (ºC/x10ºC) 61..92ºF
5
6
R
AC unit Temperature reference
1,2,3
-32768 (Initialization value) 10..38ºC (ºC/x10ºC) 50..100ºF
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 0 for more information.
3
It is not possible turn to x10 the value shown in Fahrenheit.
Loading...
+ 17 hidden pages