INBACEIP***0000
EtherNet/IP to BACnet IP & MS/TP Server gateway
Order Code: INBACEIP***0000
** stands for the Intesis gateway capacity and varies depending on the specific gateway acquired
Installation Sheet rev.1.0
HMS Industrial Networks S.L.U ©
! WARNING
Follow carefully this safety and installation instructions.
Improper work may lead to serious harmful for your health
and may damage seriously the Intesis gateway and/or any
other equipment connected to it too.
The Intesis gateway must be installed by accredited electrician or
similar technical personnel, following all the safety instructions given
here and in accordance always with the country legislation for
installation of electric equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct
solar radiation, water, high relative humidity or dust.
The Intesis gateway must only be installed in a restricted access
location.
To mount in DIN rail, fix the Intesis device properly to the DIN rail
following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to
earth is recommended.
Disconnect always power of any wires before manipulating and
connecting them to the Intesis gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rated is to be used.
Respect always the expected polarity of power and communication
cables when connecting them to the Intesis device.
Supply always a correct voltage to power the Intesis gateway, see
details of voltage range admitted by the device in the technical
characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type.
Dispose of Used Batteries according to the instructions. Battery
replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without
routing to the outside plant, all communication ports are considered for
indoor only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels
above 4 kV, precautions should be taken when the device is mounted
outside an enclosure. When working in an enclosure (ex. making
adjustments, setting switches etc.) typical anti-static precautions
should be observed before touching the unit.
Safety instructions in other languages can be found at:
https://intesis.com/docs/manuals/v6-safety
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the
Intesis device.
Disconnect power of any bus or communication cable before
connecting it to the Intesis device.
Mount the Intesis device in a vertical position on the DIN rail following
the instruction given below, respecting the safety instructions given
above.
IMPORTANT: Connect a NEC Class 2 or Limited Power Source (LPS)
and SELV rated power supply to the Intesis gateway, respect the
polarity if DC power or Line and Neutral if AC power. This power
supply must not be shared with other devices. Apply always a
voltage within the range admitted by the Intesis gateway and of enough
power (see technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V6A.
Connect the communication cables to the gateway, see details on the
user's manual.
Power the gateway and the rest of devices connected to it.
DIN Rail Mount
With the clips of the box in their original position, insert first the box
in the upper edge of the DIN rail and later insert the box in the down
part of the rail, using a small screwdriver and following the steps in
the figure below.
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B
connector included) for communication between the gateway and the
configuration tool. See CONNECTIONS below and follow instructions
of the user’s manual for more details.
The serial number is located at the rear of the gateway.
Record this information in the space provided below.
Refer to it whenever you contact upon your gateway
dealer or support team regarding this product.
Serial No.
![](/html/90/9032/903262992cbf5ba5eadbf3a92216161334d3e3f89626b9e733926730de4cac03/bg2.png)
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL http://www.intesis.com
Plastic, type ABS (UL 94 V-0)
Net dimensions (dxwxh): 90x160x58 mm
Recommended space for installation (dxwxh): 130x160x100mm
Color: Light Grey. RAL 7035
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
Type-A USB 2.0 compliant
Only for USB flash storage device (USB pen
drive)
Power consumption limited to 150mA (HDD
connection not allowed)
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC +/-10% Max.: 580mA
Button A: Check the user manual
Button B: Check the user manual
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
5 to 95%, no condensation
1 x Serial EIA485 (Plug-in screw terminal block 2 poles)
A, B
1 x Plug-in screw terminal block green (2 poles)
SGND (Reference ground or shield)
1500VDC isolation from other ports
1 x DIP-Switch for PORT A configuration:
Position 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive
Position 2-3:
ON: Polarization active
Off: Polarization inactive
8 x On board LED indicators
1 x Error LED
1 x Power LED
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
1 x EIA232 (SUB-D9 male connector)
Reserved for future use
1 x EIA485 port (Plug-in screw terminal block 3 poles)
Reserved for future use
1 x DIP-Switch for serial EIA485 configuration:
Reserved for future use
2 x Ethernet 10/100 Mbps RJ45
4 x Ethernet LED: 2 x port link and 2 x activity
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage
applied is within the range admitted (check table below). The power supply
can be connected to earth but only through the negative terminal, never
through the positive terminal. Functional Earth shall be connected to the
installation Earth.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of
the building, contact the network administrator and make sure traffic on the
port used is allowed through all the LAN path (check the gateway user
manual for more information). With factory settings, after powering up the
gateway, DHCP will be enabled for 30 seconds. After that time, if no IP is
provided by a DHCP server, the default IP 192.168.100.246 will be set.
PortA / BACnet MS/TP
Connect the EIA485 bus to connectors A3 (+), A4 (-) and A1 or A2 (SNGD)
of gateway’s PortA. Respect the polarity. Remember the characteristics of
the standard EIA485 bus: maximum distance of 1200 meters, maximum 32
devices connected to the bus, and in each end of the bus it must be a
termination resistor of 120 Ω. The gateway has an internal bus biasing circuit
that incorporates the termination resistor. If you install the gateway in one of
the ends of the bus, then do not install an additional termination resistor in
that end.
PortB: Reserved for future use.
Port C / EtherNet/IP
Connect the cables coming from the network to the EtherNet/IP connectors
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow
communication between the Configuration Software and the gateway.
Remember that Ethernet connection is also allowed. Check the user manual
for more information. To be used only during the configuration stage.
USB
Only used by debugging services. It can connect a USB storage device (not
a HDD) if required. Check the user manual for more information.
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation