Intertek GPG 16 SEER, M SERIES Installation Instructions Manual

INSTALLATION INSTRUCTIONS GPG 16 SEER “M” SERIES
SINGLE PACKAGE GAS-ELECTRIC HEATING & COOLING UNITS
Affix this manual and Users Information
Manual adjacent to the unit.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this In­stallation Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to edu­cate the customer on its safe use.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of self contained package air conditioner and heating units. See the Specification Sheets applicable to your model for information regarding accessories.
*NOTE: Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual.
This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central F urnaces
Goodman Manufacturing Company, L.P.
IOG-3012 3/15
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
© 2015 Goodman Manufacturing Company, L.P.
INDEX
REPLACEMENT PARTS............................................ 3
O
RDERING PARTS ............................................ 3
SAFETY INSTRUCTIONS ......................................... 3
UNIT LOCATION ................................................... 4
A
LL INSTALLATIONS:.......................................... 4
G
ROUND LEVEL INSTALLATIONS ONLY:........................ 4
R
OOFTOP INSTALLATIONS ONLY:.............................. 5
R
OOF CURB INSTALLATIONS ONLY: ........................... 5
GENERAL INFORMATION ........................................ 5
TRANSPORTATION DAMAGE ................................... 5
RIGGING DETAILS ................................................. 6
GAS PIPING ........................................................ 6
H
IGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) ....... 6
P
IPING ........................................................ 6
G
AS PIPING CHECKS.......................................... 7
PROPANE GAS INSTALLATIONS ................................ 7
T
ANKS AND PIPING ........................................... 8
ELECTRICAL WIRING ............................................. 8
T
HERMOSTAT LOCATION ...................................... 8
S
INGLE STAGE THERMOSTAT .................................. 9
UNIT VOLTAGE ............................................. 10
H
EAT ANTICIPATOR SETTING ................................ 10
CIRCULATING AIR AND FILTERS .............................. 1 1
A
IRFLOW CONVERSION...................................... 11
D
UCTWORK ................................................. 11
F
ILTERS .................................................... 11
VENTING.......................................................... 11
I
NSTALLATION - FLUE HOOD EXHAUST...................... 11
NSTALLATION - COMBUSTION AIR INTAKE HOOD ........... 12
I
CONDENSATE DRAIN ........................................... 12
C
ONDENSATE DRAIN CONNECTION........................... 12
NORMAL SEQUENCES OF OPERATION ...................... 12
H
EATING ................................................... 12
C
OOLING ................................................... 12
F
AN ONLY .................................................. 13
STARTUP, ADJUSTMENTS, AND CHECKS ................... 1 3
H
EATING STARTUP.......................................... 13
COOLING STARTUP ......................................... 16
TROUBLESHOOTING ........................................... 17
I
GNITION CONTROL ERROR CODES .......................... 17
F
AULT RECALL ............................................. 17
A
BNORMAL OPERATION - HEATING ......................... 17
INTERNAL CONTROL FAILURE ............................. 17
EXTERNAL LOCKOUT ..................................... 17
PRESSURE SWITCH STUCK OPEN ......................... 17
PRESSURE SWITCH STUCK CLOSED ....................... 18
PRIMARY LIMIT .......................................... 18
FLAME DETECTED WITH GAS VALVE CLOSED ............. 18
LOW FLAME SIGNAL ..................................... 18
A
BNORMAL OPERATION - COOLING ......................... 18
SHORT CYCLE COMPRESSOR DELA Y ....................... 18
HIGH PRESSURE SWITCH/LOSS OF CHARGE SWITCH ...... 18
MAINTENANCE................................................... 19
F
ILTER REPLACEMENT OR CLEANING ........................ 19
ABINET FINISH MAINTENANCE ............................. 19
C
C
LEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)........ 19
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS .19
F
LAME SENSOR (QUALIFIED SERVICER ONLY) ............... 19
F
LUE PASSAGES (QUALIFIED SERVICER ONLY).............. 19
C
LEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) ... 19
M
AIN BURNER FLAME (QUALIFIED SERVICER ONLY) ........ 19
C
LEANING BURNERS ........................................ 20
ACCESSORIES AND FUNCTIONAL PARTS ................... 20
SHEET METAL ACCESSORIES ................................. 20
F
UNCTIONAL PARTS ........................................ 20
G
ENERAL INFORMATION..................................... 20
APPENDIX ........................................................ 21
GNITION CONTROL DIAGNOSTIC INDICATOR CHART ........ 21
I
H
EATING TIMING CHART ................................... 21
C
OOLING TIMING CHART ................................... 21
UNIT DIMENSIONS .......................................... 22
W
IRING DIAGRAM .......................................... 23
M
INIMUM CLEARANCES ..................................... 24
R
ECOMMENDED FILTER SIZES ............................... 24
B
LOWER PERFORMANCE .................................... 25
S
TART-UP CHECKLIST ................................ 27 - 28
2
REPLACEMENT PARTS ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WA Y
HOUSTON, TEXAS 77040
(713) 254-4729
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
TO THE OWNER
A warranty certificate is provided with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it when necessary.
Keep this literature in a safe place for future reference.
3
Advertenci a e spe cia l p ara la insta l aci ón de calentad o res ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio .
RISQUE D'E MPO ISO N NEM EN T AU
MONOXYDE DE CARBONE
Cett e v entilation est nécessaire pour éviter le danger d'in t oxication au CO pouvant survenir si un appareil produisant du monoxyde de carbon e continue de fonction ne r au sein de la zone confinée.
Le monoxyde de des
dommages permanents au cerveau et meme la mort.
carbone peut causer des maladies graves telles que
CO can cause serious illness including perm anent brain damag e or death.
B10259-216
Las emis ion es de monóxido de carbono pueden circ ula r a través del aparat o c uando se opera en cualquier modo.
El monóx i do de carbono puede causar enfermedades seve ra s como daño cerebral permanente ó muerte.
B10259-216
UNIT LOCATION
IMPORTANT NOTE: Remove wood shipping rails prior to installa-
tion of the unit.
ALL INSTALLATIONS:
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted level.
• The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
• To avoid possible corrosion of the heat exchanger, do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds.
To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual
fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see appendix). These clearances must be permanently maintained.
The combustion air inlet and flue outlet hoods on the unit
must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems.
When the unit is heating, the temperature of the return air
entering the unit must be between 50° F and 100° F.
B10259-216
GROUND LEVEL INSTALLATIONS ONLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runoff of water
from higher ground can collect in the unit.
Outside Slab Installation
4
ROOFTOP INSTALLATIONS ONLY:
NOTE: To ensure proper condensate drainage, unit must be installed in a level position.
To avoid possible property damage or personal injury, the roof must
have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on Class A,
Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for service
personnel should be provided.
ROOF CURB INSTALLATIONS ONLY:
Sufficient structural support must be determined prior to locating
and mounting the curb and package unit.
Rooftop Installation
Ductwork must be constructed using industry guidelines. The duct
work must be placed into the roof curb before mounting the package unit.
Curb insulation, cant strips, flashing and general roofing material are furnished by the
contractor.
GENERAL INFORMATION
This unit is approved for outdoor installation ONLY. Rated performance is achieved after 72 hours of operation. unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.goodmanmfg.com for Goodman® brand products. Within the website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Rated performance is delivered at the specified airflow. See outdoor
Roof Curb Installation
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
TRANSPORTATION DAMAGE
Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately .
Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
5
3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. d. Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier. The carrier
is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.
RIGGING DETAILS
IMPORTANT NOTE: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions.
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.
GAS PIPING
IMPORTANT NOTE: This unit is factory set to operate on natural gas at
the altitudes shown on the rating plate.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of a factory authorized conversion kit. Contact your distributor or refer to the specification sheet for your model for a listing of approved LP gas conversion kit(s). Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas.
The minimum supply pressure should not vary from that shown in the Inlet Gas Pressure table because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.
INLET GAS PRESSURE
Natural Min. 5.0" W.C., Max. 10.0" W.C.
Propane Min. 11.0" W.C., Max. 13.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in T able Above.
Rigging
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)
IMPORTANT NOTE: The gas/electric units naturally derate with altitude. Do not attempt to increase the firing rate by changing
orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate. Contact your distributor or refer to the specification sheet for your model for listing of approved high altitude conversion kit(s). Refer to the Installation Manual provided with the high altitude kit for altitude adjustments.
NOTE: No changes are required up to 2,000 feet. Use the appropriate high altitude kit above 2,000 feet.
PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not
undersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously.
6
The rating plate is stamped with the model number, type of gas and gas
g
)
input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Natural Gas Connection
Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:
1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.
2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
5. Use two pipe wrenches when making connection to the gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8. The unit must be connected to the building piping by one of the following methods:
• Rigid metallic pipe and fittings
• Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)
• Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment
• In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact
GROMMET
with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage)
NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based
CFH =
Heatin
Nominal Black Pipe Size (inches)
1/2 3/4
on 0.60 Specific Gravity Gas)
1
1 1/4 1 1/2
BTUH Furnace Input
Va lu e o f Gas (BTU/Cubic Foot
GROUND JO INT UNION (INSTALLED AHEAD OF GAS VALVE)
DRIP LEG
Proper Piping Practice
MANUAL SHUT-OFF VALVE
GAS PIPING CHECKS
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.
PROPANE GAS INSTALLATIONS
IMPORTANT NOTE: Propane gas conversion kits must be installed to convert units to propane gas. Contact the distributor or refer to the specification sheet for your model for the correct LP conversion kit(s).
7
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58). For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appl iances
in operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.
First Stage Regulator
5 to 15 P SIG (20 PSIG Max.)
Continuous
11" W.C.
TANKS AND PIPING
Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
See Typical Propane Gas Piping figure for typical piping arrangement.
Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR
PIPE OR
TUBING
LENGTH,
FEET
30 309 700 1,303 2,205 3,394 1,843 3,854 40 265 599 1,115 1,887 2,904 1,577 3,298 50 235 531 988 1,672 2,574 1,398 2,923 60 213 481 896 1,515 2,332 1,267 2,649 70 196 446 824 1,394 2,146 1,165 2,437 80 182 412 767 1,297 1,996 1,084 2,267
90 171 386 719 1,217 1,873 1,017 2,127 100 161 365 679 1,149 1,769 961 2,009 150 130 293 546 923 1,421 772 1,613 200 111 251 467 790 1,216 660 1,381 250 90 222 414 700 1,078 585 1,224 300 89 201 378 634 976 530 1,109 350 82 185 345 584 898 488 1,020 400 76 172 321 543 836 454 949
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130 To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
NOMINAL PIPE SIZE,
SCHEDULE 4 0
Sizing Between Single or Second Stage Regulator and Appliance* Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Dr op at 11" W.C. Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING
LENGTH,
FEET
10 49 110 206 348 539 291 608 1,146 2,353 3,525 20 34 76 141 239 368 200 418 788 1,617 2,423 30 27 61 114 192 296 161 336 632 1,299 1,946 40 23 52 97 164 253 137 284 541 1,111 1,665 50 20 46 86 146 224 122 255 480 985 1,476 60 19 42 78 132 203 110 231 436 892 1,337
80 16 36 67 113 174 94 198 372 764 1,144 100 14 32 59 100 154 84 175 330 677 1,014 125 12 28 52 89 137 74 155 292 600 899 150 11 26 48 80 124 67 141 265 544 815 200 10 22 41 69 106 58 120 227 465 697 250 9 19 36 61 94 51 107 201 412 618 300 8 18 33 55 85 46 97 182 374 560 350 7 16 30 51 78 43 89 167 344 515 400 7 15 28 47 73 40 83 156 320 479
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1- 1/4" 1-1/2"
200 PSIG Maximum
Second Stage Regulator
Typical Propane Gas Piping
NOMINAL PIPE SIZE,
SCHEDULE 40
ELECTRICAL WIRING THERMOSTAT LOCATION
Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation.
Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions.
Propane Gas Pipe Sizing
8
All units have two stages of heating and two stages of mechanical cooling. Units which will have economizers may use thermostats with two or three stages of cooling. All units can use single stage or multi-stage thermostats. Refer to figures later in this section for wiring.
Thermostat
R
CY1
Y2
Two-Stage Heating
with
Two-Stage Cooling
The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. The low voltage wiring must be connected between the unit control panel and the room thermostat.
SINGLE STAGE THERMOSTAT
To use a single stage thermostat, move jumper located to the left of the terminal strip labeled “Stage Delay” from NONE to “5” or “10” minutes. This selection will cause the control to run on low stage for the selected time (5 or 10 minutes) then shift to HIGH ST AGE. This option controls both cooling and heating modes. If the jumper is not moved, only low-stage cool and low-stage heat will operate.
W1
W2
R C W1W2
Two-Stage Heating with Two-Stage Cooling
G
I
ntegrated
GY1Y2
Thermostat Diagram
Control Module
5 MINUTE DELAY PERIOD WI TH JUMPER IN THIS POSITION
10 MINUTE DELAY PERIO D WITH JUMPER IN THIS POSITION
Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof.
Two-Stage Heating (timed) and Two-Stage Cooling (timed)
with Single Stage Thermostat Diagram
9
Loading...
+ 19 hidden pages