This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures or services performed by an unqualified person.
The material in this manual does not supercede manufacturer's installation and operation instructions
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,
that during its lifetime a product may require service. Products should be serviced only by a qualified service technician
who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing
instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATER IALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPL IANCE.
WARNING
G
OODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES.
I
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE W HICH
MAY RESULT.
M
ANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL O R SERVICE HEATING AND A IR CONDITIONING EQUIPMENT.
WARNING
HIGHVOLTAG E
D
ISCONNECT ALL POWER BEFOR E SERVICING OR
INSTALLING THIS UNIT.
BE PR ESENT.
DAMAGE, PERSO NAL INJURY OR DEATH.
FAILURE TO DO SO M AY CAU SE PROPERTY
MULTIPLE POWER SOURCES MAY
2
IMPORTANT INFORMATION
Speci al Warning for Installation of Furnace or Air Handling Units in
Enclosed A reas such as Garage s, Utility Ro oms or Parki ng A r eas
Carbon monoxide producing devices (such as an auto mobile, space
heater, gas water heater, etc.) should not be operated in enclosed areas
such as un ve n tilated garages, ut ility rooms or parking areas because of
the danger of carbon mo noxide (CO) poisoning resulting from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, utility room or parking area and a carbon monoxide producing
device is operated therein, there must be adequate, direct outside
ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which
can occur if a carbon monoxide producing device continues to operate in
the enclosed area. Carbon monoxide emissions can be (re)circu l a ted
throughout the structure if t he furnace or air han dler is operating in any
mode.
CO can cause serious illness in clud ing per man e nt brain dama ge or deat h.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this
product. For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
customerservice@goodmanmfg.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
hac.consumer.affairs@amanahvac.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
3
IMPORTANT INFORMATION
FOR Y OUR S AFETY READ BEFORE OPERATING
If you do not follow these instructions exactly,
a fire or explosion may result causing property
damage, personal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burners. Do not
try to light the burners by hand.
B. BEFORE OPERATING smell around
the appliance area for gas. Be sure to
smell next to the floor because some gas
is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch;
do not use any telephone in your
building.
Immediately call your supplier
from a neighbor's phone. Follow
the gas suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
C. Use only your hand to move the gas
control switch or knob. Never use
tools. If the gas control switch or knob
will not operate, don't try to repair it,
call a qualified service technician.
Force or attempted repair may result in
a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the
appliance.
4. This appliance is equipped with an
automatic ignition system which
automatically lights the burners. Do not
try to light the burners by hand.
5. Remove control access panel.
6. Move the gas control switch or knob
to "OFF ".
GAS CONTROL
SWITCH SHOWN
IN "ON" POSITION
7. Wait five (5) minutes to clear out any
gas. If you then smell gas, STOP!above on this label.
Follow "B" in the safety information
above on this label. If you don't smell
gas, go to the next step.
8. Move the gas control switch or knob
to "ON".
9. Replace control access panel.
10. Turn on all electric power to the
appliance.
11. Set the thermostat to the desired
setting.
12. If the appliance will not operate,
follow the instructions "To Turn Off Gas
To Appliance" and call your service
technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the
appliance if service is to be performed.
3. Remove control access panel.
4. Move the gas control switch or knob
to "OFF". Do not force .
5. Replace control access panel.
WARNING: Improper
alteration, service or
maintenance can
cause injury or
property damage.
Refer to the user's
information manual
provided with this
consult a qualified
or the gas supplier.
This furnace must be
instructions and local
codes. In the absence
of local codes, follow
the National Fuel Gas
Code, ANSI Z223.1.
For indoor installation.
PGB & PGJ
For outdoor
installation only .
If notWARNING:
installed, operated
and maintained in
accordance with the
manufacturer's
instru ctions, this
product could expose
you to substances
in fuel combust ion
which can cause
death or serious
illness and which
are known to the
State of California to
cause cancer, birth
defects or other
reproductive harm.
This product contains
fiberglass insulation.
Fiberglass insu la tion
contains a chemic al
California to cause
cancer.
FOR YOUR SAFETY
other flammable vapors and liquids in the vicinity of this
or any other app liance.
4
Do not store or use gasoline or
0140F00001P
IMPORTANT INFORMATION
CONSIGNES DE SECURITE - LIRE
AVANT D'ALLUMER L'APPAREIL
AVERTISSEMENT: Le non-respect des in structions qui suivent peut
^
entrainer un r i sque d'incendie ou d'explosion causant des dommages,
des blessures ou la mort.
A. Cet appareil comporte pas de veilleuse. Il est muni d'un mecanis m e qui allume
automatiquement le bruleur. N
B. Sentir tout autour de l'appariel AVANT D'ALLUMER afin de deceler toute fuite de gaz.
Assurez-vous de sentir tout pres du plancher car certains gaz sont plus lourds que l'air
et se deposeront sur le plancher.
SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne tentez d'allumer aucun appariel.
Ne touchez pas aux interrupteurs electriques; n'utiliser aucun telephone
dans l'edifice ou vous vous trouvez.
Appelez immediatement votre fournisseur de gaz en utilisant le telephone
d'un voisin et suivez les instructions du fournisseur.
Appelez les pompiers si vous ne parvenez pas a rejoindre votre fournisseur
de gaz.
C. N'utiliser que votre main pour pousser ou tourner le commande du gaz. N'utilisez
jamais d'outils. Si vous ne parvenez pas a pousser ou a t ourner la commande, ne tentez
pas de la reparer; appelez un reparateur qualifie. Forcer la commande ou essayer de la
reparer peut entrainer un risque d'incendie ou d'explosion.
D. N'utilisez pas cet appareil si l'une de ses parties a ete dans l'eau. Si cela se produit,
demandez immediatement a un reparateur qualifie d'insp ecter l'appareil et de remplacer
toute piece du systeme de controle et toute commande de gaz ayant ete dans l'eau.
^^
'allumez paz le bruleur manuellement.
^
^
0140F00002P
1. UN INSTANT! Lisez d'abord les consignes
INSTRUCTIONS DE SERVICE
d e securi te ci-dessus.
2. Reglez le thermostat a son point le plus bas.
3. Coupez l'alimentation electrique de l'appareil.
4. Cet appareil est muni d'un mecanisme qui
allume automatiquement le bruleur. Ne tentez
pa s d'allum er le bruleur manuellement.
5. Retirez le panneau d'acces de la commande.
6. Mettez la commande de gaz a la position
^
ARRET ("OFF").
7. Attendez cinq (5) minutes afin de permettre a
t ou t gaz present d'etre evacue. Si vous sentez
une odeur de gaz a ce moment, ARRETEZ! et
suivez les consignes de securite donnees au
paragraphe B ci-dessus. Si vous ne sentez pas
de gaz, passez a l'etape suivante.
8. Mettez la commande de gaz a la position
MARCHE ("ON").
9. Remettez la panneau d'acces de la commande
en plac e.
10. Retablissez l'alimenation electrique de l'appareil.
11. Reglez le thermostat a le temperature desiree.
12. Si l'appareil ne fonctionne pas, suivez les
instructions intitulees "Arret du gaz" et appelez un
reparateur qualifie ou votre fournisseur de gaz.
1. Reglez le thermostat a son point le plus bas.
2. Coupez l'alimentation electrique de l'appareil si vous devez effectuer un entretien.
3. Retirez le panneau d'acces de la commande.
4. Mettez la commande de gaz a la position ARRET ("OFF").
5. Remettez le panneau d'acces de la commande en p lace.
^
^
^
^
^
^
ARRET DU GAZ
Commande de
gaz en position
"MARCHE"
^
5
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
GMVC960804CNAA
PRODUCT
TYPE :
G: Go od m a n
A: Amana®
Brand
D: A m ana®
Distinctions™
Brand
M: Upflo w/Horizon tal
D: De cidated Downflow
C: Downfl ow/Horiz on tal
H: High Air Flow
FURNACE
TYPE
E: T wo-Stage/
S: Single-Stage /
V: T wo Stage/
Spee d
H: Two Sta ge
Gas Valve -
SUPPLY TYPE
COMMUNICATION FEATURE
C: 4-Wire Communicatio n Ready
X-13 Mot or
Multi-Speed
Varia ble-
Multi-Speed
NOMI NAL I NPUT
040: 40,000 Bt uh
060: 60,000 Bt uh
080: 80,000 Bt uh
100: 100,000 Bt uh
120: 120, 000 B tu h
AFUE
8: 80%
9: 90%
95: 95 %
AIRFLOW
CA PABILITY
@ 0.5" E SP
3: 12 00
4: 16 00
5: 20 00
CABINET
WIDTH
A: 14"
B: 17- 1 /2"
C: 21 "
D: 24 - 1 /2"
MAJOR REVIS ION
A: In itial R e le ase
MI NOR REVI S ION
A: In itial R e le ase
ADDITIONAL
FEA TURE S
N: Natural Gas
X: L o w N O x
6
PRODUCT IDENTIFICATION
MODEL: GMVC96REV AA
Equipment Ty peGoodman Brand Residential Gas Furnace
Heating StagesTwo
Cooling StagesTwo
Control TypeClimateTalk
Blowe r Motor Type4 Wire Variable Speed ECM
GMV C96
Installation Positions
BTUH Input Low Fire (X 1000)
BTUH Input High Fire (X 1000)
A/C Capable Tons
Cabinet Hig ht "
Cabinet Width "
Heating CFM @ 100% Firing Rate
Draft Inducer
Gas Valve
24 VAC Heating Inputs
24 VAC Cooling Input s
Primary He at Exchanger
Accessory Terminals
Gas Line Entry
Revision Attributes
Two Speed
Two Stage
W1 / W2
Y1 / Y2
Alum inized Steel
EAC terminal, Field Powered H UM IN / HUM OUT terminals, Single Hu m termi nal
powered simultaneously with draft inducer, AUX circuit
Left or Right
First revision of 34.5" two stage commu nicating capable up flow furnace
MODEL: AMVC96
Equipment TypeAmana Brand Residential Gas Furnace
Heating StagesTwo
Cooling StagesTwo
Con tro l TypeClimateTalk
Blower Motor Type4 Wire Variable Speed ECM
™ or Conventional 24 Volt
0403BN 0603BN 0803BN 0804CN 1005CN 1205DN
UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R
304560607590
40608080100120
1.5 - 31.5 - 31.5 - 32 - 41.5 - 52 - 5
34.534.534.534.534.534.5
17.517.517.5212124.5
55310591316133718701940
REV AA
™ or Conventional 24 Volt
MODEL: GCVC96REV AA
Equipment Typ eGoodman Brand Residential Gas Furnace
Heating St a ge sTwo
Cooling StagesTwo
Con t rol TypeClimateTalk
™ or Conventional 24 Volt
Blow e r Mo tor Ty p e4 Wire Variable Speed ECM
GCV C9 6
Installati on P ositionsCF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R
BTUH Input Low Fire (X 1000)304560607590
BTUH Input Hi gh Fire (X 1000)40608080100120
A/C Capable Tons 1.5 - 31.5 - 32 - 42 - 42 - 52 - 5
Cabinet Hi ght "34.534.534.534.534.5
Cabinet Width "17.517.5212124.5
Heating CFM @ 100% Firing Rate10599501146132517971827
Draft Inducer
Gas V alve
24 VAC Heating Inputs
24 VAC Cooling Inputs
Primar y Heat Exchanger
Accessory Terminals
Gas L ine Entry
Revisi o n Attr i butes
0403BN 0603BN0803BN 0804CN1005CN 1205DN
Two Speed
Two Stage
W1 / W2
Y1 / Y2
Aluminized Steel
EAC termina l, Field Powered HUM IN / HUM OUT terminals, Single Hum term inal
powe red simultaneously wit h draft inducer, AUX circuit
Left or Right
First revi sion of 34.5" modulating counter fl ow furnace
MODEL: ACVC96REV AA
Equipment Ty peAmana Bra nd Residential Gas Furnac e
Heating StagesTwo
Coo lin g StagesTwo
Cont ro l Ty peClimateTalk
Blowe r M o tor Type4 Wire Variable Speed ECM
™ or Conventional 24 Volt
AMVC96
Ins tallation Positions
BTUH Input Low Fire (X 1000)
BTUH Input High Fi re (X 1000)
A/C Capable Tons
Cabinet Hight "
Cabinet Width "
Heating CFM @ 100% Firing Rate
Draft Inducer
Gas Valve
24 VAC Heating Inputs
24 VAC Cooling Inputs
Primary Heat Exchanger
Accessory Terminals
Gas Line Entry
Revi sion Attributes
0403BN 0603BN0803BN 0804CN1005CN 1205DN
UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R UF, Hor L/R
304560607590
40608080100120
1.5 - 31.5 - 31.5 - 32 - 41.5 - 52 - 5
34.534.534.534.534.534.5
17.517.517.5212124. 5
55310591316133718701940
Two Speed
Two Stage
W1 / W2
Y1 / Y2
Stainless Steel
EAC terminal, Field Powered HUM IN / HUM OUT term i nals, Single Hum terminal
powered simultaneously with draft induce r, AUX circuit
Left or Right
Firs t r evision o f 34.5" two st ag e c o mmunicating c apable u p flow furn ac e
ACVC96
Inst allatio n Positi o n sCF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R CF, Hor L/R
BTUH Input Low Fire (X 1000)304560607590
BTUH Input High Fire (X 1000)40608080100120
A/C Capable Tons 1.5 - 31.5 - 32 - 42 - 42 - 52 - 5
Cabinet Hight "34.534.534. 534.534.5
Cabinet Width "17.517.5212124.5
Heating CFM @ 100% Firing Rate10599501146132517971827
Draft Inducer
Gas Valve
24 VAC Heating Inputs
24 VAC Cooling Inputs
Primary Heat Ex changer
Accessory Terminals
Gas Line Entry
Revision Attributes
0403BN 0603BN 0803BN0804CN 1005CN 1205DN
Two Speed
Two Stage
W1 / W2
Y1 / Y2
Stainless Steel
EAC terminal, Field Powered HUM IN / HUM OUT term in als, Singl e Hum terminal
powered simul taneously with draft inducer, AUX circuit
Left or Right
First revision of 34.5" modulating counter flow furnace
7
PRODUCT IDENTIFICATION
MODE L # MFG #DESCRIPTION
AFE18-60A
AMU1620
AMU1625
AMU2020
AMU2025
GMU1620
GMU1625
GMU2020
GMU2025
ASAS-10
ASAS-11
ASAS-12
ASAS-18
CFSB17
CFSB21
CFSB24
N/A
P1251305F
P1251306F
P1251307F
P1251308F
N/A
P1251301F
P1251302F
P1251303F
P1251304F
N/A
Fo ssil Fuel K it.
above/do wnstream of a gas or f ossil fuel f urnace when used wit h a hea t pump. It will operate
with single and t wo stage hea t pumps and single and two stage f urnaces. The AFE 18-60A
cont rol will tu r n the heat pu mp unit off wh en the f ur nace is turned on. An ant i- short cycle
feature initiates a 3 minute timed off d elay when the compressor goes of f.
Med ia Air Cl eaner.
fur n ac e models. The Amana (A MU*) and Goodman (GMU*) Media Air Cleaner is a high
efficienc y air fil trat ion device designed to r emove dirt, dust , pollen and other microscopic
particles from th e a ir passing thro ugh it. Flexible performance range u p to 2, 000 C FM
capac ity. The air cl eaner should be installed in the system so that all the sy stem air is
circ ulated thr ou gh t he air c leaner . The air cle aner will only remove t he air b orne contaminant s
delivered to it. Maximum per formance is obtained when the syst em blower is set f or
cont in uous operation. Carbon filters (opt io nal) are available.
Electronic Air Cleaner.
Brand furnace models. T he H igh- Efficiency Electronic Air Cleaner i s designed to r emove air
cont aminant s down to .01 micr ons. Car b on filt er s (optional) re move odors. D ual in dic ator
lights show unit operation a t a glance. Electronic pr o ving switch cycles the air c lea ner On/ Off
with the system f an . Durable powder-coat paint finish resists corrosion.
C ounterflow S ubbase K it.
models ACV C9 an d GCVC9. These kits are available for the fo llow ing furnac e wid ths: 17.5"
wide (CFSB17) , 21" w ide (CFS B 21) and 24" wide (CFSB24) . The kits must b e used t o pr event
excessi ve temperat ur e from r eaching combustible mater ials, if the furnace is installed on a
combustible f loor . T his subbase effec tively separate d the furnace base and plenum fro m
combustible materia ls. To ensure safe installation, d o not install the counterf low floor base
directly on car peting, tile, or other combustible material other than wood f looring.
The AFE18-60A cont r o l is designed for use where the i ndoor coil is located
For use with c ur r ent ar c hitect ur al gr ey Goodman® and A mana® B r and
For use with current ar chitectural grey Goodman® and Amana®
For use with select Goodman® and Amana ® B r and 34.5" furnac e
CTK01AA
CTK01BA
CTK01AA
CTK01BA
Communicating Thermostat Kit-
for use with c ompat ible Amana® B rand or Goodman® Brand Air Handlers or Furnaces and
outdoo r split AC or Heat Pump units. T his the r mostat supports up to three stages of he at, two
stages of co oling, dual f uel app lic ations, dehumidification, filter maintenan c e r eminders,
outdoo r temperature display an d advanced menus including diagnostic s. The CT K 01 AA k it
includes a communicating touchscree n thermostat and sub base, 230V-24V 40va
tr an sfor mer, ter minal bloc k s(2), wire jumpers, mounting screws, insta llation manual and
homeowner guide.
Communicating Thermostat Kit-
for use with c ompat ible Amana® B rand or Goodman® Brand Air Handlers or Furnaces and
outdoo r split AC or Heat Pump units. T his the r mostat supports up to three stages of he at, two
stages of co oling, dual f uel app lic ations, dehumidification, filter maintenan c e r eminders,
outdoo r temperature display an d advanced menus including diagnostic s. The CT K 01 B A kit
includes a communicating touchscree n thermostat and sub base, t erminal blocks(2),
installat ion manual and homeowner gui de.
Digit ally communic ating touchscreen thermostat . Designed
Digit ally communic ating touchscreen thermostat . Designed
8
PRODUCT IDENTIFICATION
MODE L # MFG #DES C RIPTI O N
CTK02**
CTK03AA
CTK03AB
CTK04
CTK02**
CTK03AA
CTK03AB
CTK04AA
C ommu nicat ing Thermo st at Kit-
use with compat ibl e Amana ® Brand or Goodman® Bran d Air Handlers or Furnaces
and out door split AC or Heat Pump units. The CTK02** th er mostat featu r es a f ull c o lor
high def ini tion display , advanced programming options including hu midif ic ation control
& heat and cool maximum temperatur e set tings, a USB plug allowing dealer s t he
abilit y to insert pre-progr ammed operat in g par amet ers and dealer info r mat ion by use
of an onlin e da ta entry system.
C ommu nicat ing Thermo st at Kit-
fr o m Honeywell. De signed f or use with c ompat ib le Amana® Brand or Goodman®
Bra nd Air Handlers or Furnaces and outdoor split AC or Heat P ump unit s. The
CTK 0 3AA thermostat featu r es f ull color high definition display and can be used with
RedLINK wireless a ccessor ies.
C ommu nicat ing Thermo st at Kit-
fr o m Honeywell. De signed f or use with c ompat ib le Amana® Brand or Goodman®
Bra nd Air Handlers or Furnaces and outdoor split AC or Heat P ump unit s. The
CTK 0 3AB thermost at fe atures full c o lor hig h definit ion display and ca n be u sed with
RedLI NK wi r ele ss accessor i es and added c apa bilty to c ontrol the HUM IN - HUM OUT
relay.
C ommu nicat ing Thermo st at Kit-
fr o m Honeywell. De signed f or use with c ompat ib le Amana® Brand or Goodman®
Bra nd Air Handlers or Furnaces and outdoor split AC or Heat P ump unit s. The CTK04
thermo stat f eatures full c olo r hi gh definition display and can be used wit h Red LINK
wireless accessories a nd adde d c ap abilty to contr ol the HUM IN - HUM OUT r e lay. Split
system inverter c apabl e.
Digit ally communic a ting t her mostat . Designed for
Digit ally communic a ting t ouc hscr een thermostat
Digit ally communic a ting t ouc hscr een thermostat
Digit ally communic a ting t ouc hscr een thermostat
DCVK-20
(CVENT-2)
DCVK-30
(CVENT-3)
0170K00000S
0170K00001S
DEHUM1
N/A
N/A
N/A
P1227801F
Concentric Vent Kit.
designed to allow terminations of a dir ec t vent furnace to be "concent rically" vented
through a wall or roof. This kit allows a sing le pen etrat ion to support terminations f or
both the vent/flu e and the combustion air intake pipe. The DCVK-20 ( 2") and DCVK-30
(3" ) ki t s are cer tified for models list ed above. See specificat ion sheet s on fut ur e
models for use of the vent k i t.
Side Wall Only Concentric Vent K it
used with 2" - 3" vent systems. The vent k it must ter minat e outside the structure. This
kit is NOT int end ed for use with single pipe (i ndirect vent) insta llations.
Side Wall Only Concentric Vent K it
used only with 2" vent systems. The vent k it must ter minat e ou tside the stru c ture. This
kit is NOT int end ed for use with single pipe (i ndirect vent) insta llations.
Dehumidistat.
fur nac e models. W all mounted, 24 volt humidit y contro l available as a Dehumidistat
used to reduc e t he air flow in the air c onditioning mode when necessar y to lower the
humidity in an occupied home to pr e vent dew build- up associated with high humidity
levels. T his control featur es a moisture-sensitive nylon element and al so provides
positive ON-O FF set tings for manual oper ation. The control is a normally closed switch
that opens on humidity rise causing t he bl ower to switch to a lower speed t o c on trol t h e
humidity within the structure.
For use with Amana® B rand 90% f ur nac e models. This kit is
. F or use with 90% f ur nac e models. This kit is to be
. F or use with 90% f ur nac e models. This kit is to be
For use with Goodman® and Amana® Brand two-stage variable speed
9
PRODUCT IDENTIFICATION
MODEL # MFG #DESCRIPTION
EFR02
HASFK-1
LPLP03
LPM-08
N/A
N/A
N/A
N/A
External Filt er Rack Kit.
speed gas furnace models. This kit is intended to provide a locat ion, external to the furnace
casing, f or installation of a permanent filter. The rack is mount ed over the indoor air blower
compartment area of eit her side panel, and provide filter retention as well as a locat ion f or
att ac hing r et ur n air duc t wor k.
High Altitude Natural Gas Kit.
stage furnac e models. These kits are required when inst alling t he f ur nac es abov e t heir
maximum r ated altit ude. T he or if ic es in the kit have been select ed as a result of t esting wit h t he
American Gas A ssociation. They will pr ovide appropriate der ating at the altit ude listed in the
High Altit ude Char ts as shown in the installations of the kit.
LP Gas Low Pressure Kit.
fur nace produc ts installed on LP gas listed in this manual. This k it includes harness adaptors to
work wit h W hit e- Rodgers single & two stage gas valves,Honeywell single and two-stage gas
v alves, as well as modulating gas valves.
LP Conversion Kit.
models using a Whit e- Rodger s 36J54,, 2-stage gas v alve kit. Includes regulator springs,
1.25mm orifices, instruc tions and a label to show the furnace has been c onverted to L.P.
For use with G oodman® and A mana® Brand 90% upflow variable
Used on selected Goodman® Brand and Amana® B r and 90% two
Designed for applicat ion on Goodman® and A mana® Brand' s gas
For use with Goodman® and Amana® Brand 34.5" 2-stage variable speed
This side wall only vent kit #0170K00000S is to be used with 2” - 3” vent systems. This kit is NOT intended for use with
single pipe (indirect vent) installations.
The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side-byside or with one pipe above the other.
See the section in this manual under "Vent Flue and Combustion Air Pipe Terminations" for more information or consult
the Installation Instructions (IO-635).
0170K00001S
This vent kit is to be used with 2” vent systems. The vent kit must terminate outside the structure and may be installed with
the intake and exhaust pipes located side-by side or with one pipe above the other. This kit is NOT intended for use with
single pipe (indirect vent) installations.
See the section in this manual under "Vent Flue and Combustion Air Pipe Terminations" for more information or consult
the Installation Instructions (IO-805).
Horizontal Installation
12
Vertica l I n s tallatio n
ACCESSORIES
CONCENTRIC VENT CONVERSION KIT
The CVENT-2 (DCVK20) (2") or the CVENT-3 (DCVK-30) (3") is a concentric vent kit approved with furnaces listed in
this manual.
This concentric vent kit allows for vertical or horizontal vent termination. The illustrations give a brief view of the kit and
its application.
See the section in this manual under "Vent Flue and Combustion Air Pipe Terminations" for more information or consult
the Installation and Operating Instructions (IO-619*).
Vent
Maintain 12" (18" for Canada)
minimum clearance above highest
anticipated snow level. Maximum of
Combustion Air
24" above roof.
Roof Boot/Flashing
(Field Supplied)
Support (Field Supplied)
45 Elbow
(Field Supplied)
Vent
Combustion Air
DCVK (Vertical Installation)
AFE18-60A Dual Fuel Accessory
When installing the communicating capable furnace with a
heat pump, the preferred installation would include a communicating thermostat. A communicating thermostat provides control of gas heat and heat pump operation and eliminates the need for a separate dual fuel control. A legacy
dual fuel thermostat could also be used with 24 volt wiring to
control the gas furnace and heat pump. If a communicating
thermostat or legacy dual fuel thermostat are not used, the
AFE18-60A kit must be added to provide control of the equipment. This control is mounted indoors near the furnace and
provides terminals for thermostat, furnace, and heat pump
wiring. The AFE18-60A may be used with or without a separate outdoor thermostat.
CFSB17, 21, 24 Counter Flow Base
The CFSB base must be used when installing a *CVC96
furnace in the vertical position on a combustible floor without a coil under the furnace.
Vent
Combustion Air
Strap
(Field Supplied)
45 Elbow
(Field Supplied)
Combustion Air
Flush to
1" maximum
DCVK (Horizontal Installation)
LPLP03 Low LP Gas Pressure Shut-off Kit
Installation of the LPLP03 kit is recommended on every L.P.
converted furnace to protect the furnace against low L.P.
gas supply pressure. Low L.P. supply pressure can cause
poor combustion and carbon in the heat exchanger. The
LPLP03 kit will open the electrical circuit to the gas valve in
the event of low supply pressure. The kit contains a pressure switch, gas fittings and electrical harness to connect
the switch in series with the gas valve.
LPM-08 LP Conversion Kit
This furnace is factory equipped to operate on Natural Gas
but may be field converted to operate on L.P. gas. To convert a *MVC96 or *CVC96 furnace to operate on L.P. gas,
the LPM-08 conversion kit must be used. The LPM-08 kit
contains a set of 1.25 mm orifices to replace the factory
installed natural gas orifices and a set of springs to convert
the gas valve to L.P. gas.
OT18-60A Outdoor Thermostat
For use in a legacy dual fuel installation to lock-out the heat
pump at a selected temperature.
Vent
13
INST ALLATION CONSIDERA TIONS
Safety
Please adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the furnace.
WARNING
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATI ON, SERV ICE OR MAINTENANCE, R EFER TO THI S
MANUAL.
QUALIFIED INSTALLE R, SERVICE AGENCY OR THE GAS SUPPLIER.
OR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A
F
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERI OUS ILLNESS OR DEATH AN D WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BI RTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO PROTECT
THE ELEC TRICA L COMPON ENTS FROM WAT ER.
Charge (ESD) Precautions
NOTE: Discharge body’s static electricity before touching
unit. An electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and
servicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at
the same electrostatic potential, these steps will help avoid
exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and
uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnace near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in Step 2. Use caution
not to recharge your body with static electricity; (i.e., do
not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded
object, repeat Step 2 before touching control or wires.
4. Discharge any static electricity from your body to ground
before removing a new control from its container. Follow
Steps 1 through 3 if installing the control on a furnace.
Return any old or new controls to their containers before
touching any ungrounded object.
Product Application
This product is designed for use as a residential home gas
furnace. It is not designed or certified for use in mobile home,
trailer, or recreational vehicle applications.
This furnace can be used in the following non-industrial
commercial applications: Schools, Office buildings, Churches,
Retail stores, Nursing homes, Hotels/motels, Common or
office areas. In such applications, the furnace must be installed
with the
Goodman® Brand and Amana® Brand 90% furnaces are
ETL certified appliances and are appropriate for use with
natural or propane gas. (NOTE: If using propane gas, a propane conversion kit is required).
Dual certification means that the combustion air inlet pipe is
optional and the furnace can be vented as a:
To ensure proper installation, operation and servicing, thoroughly read the installation and service manuals for specifics pertaining to the installation, servicing and application of
this product.
POSSIBLE PROPERTY DAMAGE, PERSONAL IN JURY OR DEATH DUE TO FIRE,
EXPLOSION, SMOKE, S OOT, CONDENSTAION, E LECTRICAL SHOCK OR CARBON
MONOXIDE MAY RESULT FROM IM PROPER INSTALLATION, RE PAIR, OPERATI ON,
OR MAINTENANCE OF THI S PRODUCT.
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJ URY OR DEATH D UE TO FIRE,
DO NOT INSTALL T HIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL
VEHICLE.
To ensure proper furnace operation, install, operate, maintain and service the furnace in accordance with the installation, operation and service instructions, all local building
codes and ordinances. In their absence, follow the latest
edition of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1), and/or CAN/CGA B149 Installation Codes, local
plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
installation instructions.
Non-direct vent (single pipe) central forced air furnace
in which combustion air is taken from the installation
area or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which
all combustion air supplied directly to the furnace burners through a special air intake system outlined in
this manual and the installation instructions.
WARNING
WARNING
American National Standards Institute
1430 Broadway
New York, NY 10018
14
INST ALLATION CONSIDERA TIONS
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning Contractors of America.
Location Requirements and Considerations
WARNING
O PREVENT POSSIBLE EQUI PMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FO LLOWING BULLET P OINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in the
Combustion and Ventilation Air Requirements section in this
manual or the installation instructions for details.
•Centrally locate the furnace with respect to the proposed or existing air distribution system.
•Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
•If the furnace is installed in an application where the
typical operating sound level of a furnace is deemed
objectionable, an optional sound reduction kit is available. Consult your local distributor for more details.
•Provide provisions for venting combustion products
outdoors through a proper venting system. Special
consideration should be given to vent/flue pipe routing
and combustion air intake pipe when applicable.
90% Furnaces: Refer to the Vent/Flue Pipe and Com-
bustion Air Pipe -Termination Locations section in this
manual or the installation instructions for appropriate
termination locations. Also for 90% furnaces, refer to
the Vent/Flue Pipe and Combustion Air Pipe -Termi-nation Locations section in this manual or the installation instructions to determine if the piping system
from furnace to termination can be accomplished
within the guidelines given. NOTE: The length of flue
and/or combustion air piping can be a limiting factor
in the location of the furnace.
•Locate the 90% furnace so that the condensate can
be piped at a downward slope away from the furnace
to the drain. Do not locate the furnace or its condensate drainage system in any area subject to below
freezing temperatures without proper freeze protection. Refer to the Condensate Drain Lines and Trap
section in this manual or the installation instructions
for further details.
•Set the 90% furnace on a level floor to enable proper
condensate drainage. If the floor becomes wet or damp
at times, place the furnace above the floor on a concrete base sized approximately 1-1/2" larger than the
base of the furnace. Refer to the Horizontal Applica-tions and Considerations section in this manual or
the installation instructions for leveling of horizontal
furnaces.
•Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material. The only combustible material allowed is wood.
•A special accessory subbase must be used for upright counterflow unit installations over any combustible material (including wood). Refer to subbase instructions for installation details. (NOTE: A subbase
will not be required if an air conditioning coil is located
beneath the furnace between the supply air opening
and the combustible floor.
•Exposure to contaminated combustion air will result
in safety and performance-related problems. Do not
install the furnace where the combustion air is exposed to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
•Isolate a non-direct furnace from an area contaminated
by any of the above substances. This protects the
non-direct vent furnace from airborne contaminants.
To ensure that the enclosed non-direct vent furnace
has an adequate supply of combustion air, vent from
a nearby uncontaminated room or from outdoors. Refer to the Combustion and Ventilation Air Require-ments section in this manual or the installation instructions for details.
•If the furnace is used in connection with a cooling
unit, install the furnace upstream or in parallel with
the cooling unit coil. Premature heat exchanger failure will result if the cooling unit coil is placed in the
return air of the furnace.
15
INST ALLATION CONSIDERA TIONS
•If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source
are located not less than 18 inches (457 mm) above
the floor. Protect the furnace from physical damage
by vehicles.
•If the furnace is installed horizontally, the furnace access doors must be vertical so that the burners fire
horizontally into the heat exchanger. Do not install
the unit with the access doors on the “up/top” or “down/
bottom” side of the furnace.
Clearances and Accessibility
Installations must adhere to the clearances to combustible
materials to which this furnace has been design certified.
The minimum clearance information for this furnace is provided on the unit’s clearance label. These clearances must
be permanently maintained. Refer to Specification Sheet for
minimum clearances to combustible materials. Clearances
must also accommodate an installation’s gas, electrical,
and drain trap and drain line connections. If the alternate
combustion air intake or vent/flue connections are used on
a 90% furnace, additional clearances must be provided to
accommodate these connections. Refer to Vent Flue Pipeand Combustion Air Pipe section in this manual or the installation instructions for details. NOTE: In addition to the
required clearances to combustible materials, a minimum
of 24 inches service clearance must be available in front of
the unit.
A furnace installed in a confined space (i.e., a closet or
utility room) must have two ventilation openings with a total
minimum free area of 0.25 square inches per 1,000 BTU/hr
of furnace input rating. One of the ventilation openings must
be within 12 inches of the top; the other opening must be
within 12 inches of the bottom of the confined space. In a
typical construction, the clearance between the door and
door frame is usually adequate to satisfy this ventilation requirement.
Furnace Suspension
If suspending the furnace from rafters or joist, use 3/8"
threaded rod and 2”x2”x1/8” angle iron as shown in the following figure. If the furnace is installed in a crawl space it
must also be suspended from the floor joist or supported by
a concrete pad. Never install the furnace on the ground or
allow it to be exposed to water. The length of rod will depend
on the application and the clearances necessary.
3/8" DIAMETER
THREADED ROD
HOLD DOWN
NUTS
SUPPORT
NUTS
GAS PIPING
2"X2"X1/8" ANGLE IRON
(3 PLACES)
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting
system serving other appliances, the venting system may
be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the
American National Standard/National Standard of Canada for
Gas-Fired Central Furnaces ANSI Z21.47, latest edition,
CSA-2.3b, latest edition Section 1.23.1.
The following steps shall be followed with each appliance connected to
the venting system placed in operation, while any other appliances
connected to the venting system are not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal pitch,
c. In so far as practical, close all building doors and windows and all
d. Follow the lighting instructions. Place the appliance being in-
e. Test for draft hood equipped spillage at the draft hood relief
f. After it has been determined that each appliance connected to the
g . If improper venting is observed during any of the above tests, the
Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or
CSA B149 Installation Codes.
PROVIDE 8" MINIMUM CLEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BLOWER REMOVAL.
ASSURE FURNACE IS LEVEL FROM
END TO END.
90% FURNACES MAKE SURE
ON
THE UNIT HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE.
CONDENSATE
DRAIN
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL.
(6 PLACES)
ALTERNATE
GAS PIPING
POSITION AS CLOSE AS POSSIBLE
TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMOVAL.
90% Suspended Furnace Shown
as required by the National Fuel Gas Code, ANSI Z223.1 or the
CSA B149 Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition;
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close fireplace dampers;
spected in operation. Adjust thermostat so appliance shall operate continuously;
opening after 5 minutes of main burner operation. Use the flame
of a match or candle;
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and any
other gas burning appliance to their previous conditions of use;
common venting system must be corrected.
16
INST ALLATION CONSIDERA TIONS
If resizing is required on any portion of the venting system,
use the appropriate table in Appendix G in the latest edition
of the National Fuel Gas Code ANSI Z223.1 and/or CSA B149
Installation Codes.
Thermostat Requirements
The optional CTK0*** thermostat kit may be used with
ComfortNet™ compatable furnaces (ACVC, AMVC, GCVC,
GMVC models). Refer to System Operation - ComfortNet™System for details.
NOTE: A single-stage thermostat with only one heating
stage can be used to control a two-stage furnace. The application of a single-stage thermostat does not offer "true"
thermostat driven two-stage operation, but provides a timed
transition from low to high fire. The furnace will run on low
stage for a fixed period of time before stepping up to high
stage to satisfy the thermostat's call for heat. The delay
period prior to stepping up can be set at either 5 or 10 minutes through the DIP switch adjacent to the Heat Off delay
DIP switches on the integrated control module. To use a
single-stage thermostat, turn off power to the furnace, move
the thermostat selection jumper on the integrated contro
module from the "two-stage" position to the "single-stage"
position, turn power back on. Refer to DIP switch charts on
pages 41 & 42.
NOTE: A single-stage thermostat with only one heating stage
may be used to control ComfortNet™ compatible furnaces
(ACVC, AMVC, GCVC, GMVC models). The application of
a single-stage thermostat does not offer “true” thermostatdriven two-stage operation, but provides a timed transition
from low to high fire. The furnace will run on low stage for a
fixed period of time before stepping up to high stage to satisfy the thermostat’s call for heat. The delay period prior to
stepping up can be set at either a fixed 5 minute time delay
or a load based variable time between 1 and 12 minutes
(AUTO mode). If the AUTOmode is selected, the control
averages the cycle times of the previous three cycles and
uses the average to determine the time to transition from
low stage to high stage.
To use a single-stage thermostat, turn off power to the furnace, move the thermostat selection DIP switch to the OFF
position. Set the desired transition time by setting the transition delay DIP switch to the desired ON/OFF position. Turn
power back on. Refer to DIP switch charts on pages 41 &
42.
Dehumidistat Requirements
A dehumidistat can be used in conjunction with the twostage variable speed furnace to lower the humidity in the
conditioned space. The dehumidistat will improve dehumidification of the conditioned air by prompting the furnace to
reduce the speed of the circulator blower during operation in
the cooling mode. To be compatible with these furnaces, a
dehumidistat must operate on 24 VAC and utilize a switch
which opens on humidity rise. Refer to Electrical Connec-tions - 24 Volt Dehumidistat Wiring section in this manual
or the installation instructions for correct installation procedure.
Thermostat and Dehumidistat Location
In an area having good air circulation, locate the thermostat
and dehumidistat (if applicable) about five feet high on a vibration-free inside wall. Do not install the thermostat or dehumidistat where it may be influenced by any of the following:
•Drafts, or dead spots behind doors, in corners, or un-
•Hot or cold air from registers.
•Radiant heat from the sun.
•Light fixtures or other appliances.
•Radiant heat from a fireplace.
•Concealed hot or cold water pipes, or chimneys.
•Unconditioned areas behind the thermostat and de-
Consult the instructions packaged with the thermostat and
dehumidistat for mounting instructions and further precautions.
COMBUSTION AND VENTILATION AIR
REQUIREMENTS
OSSIBLE PROPERTY DAMAGE, PERSONAL I NJURY OR DEATH MAY OCCUR
P
IF THE FURNACE I S NOT PR OVIDED WITH ENOUGH FRESH AIR FOR PROPER
COMBUSTION AND VENTIL ATION OF F LUE GASES. MOST HOMES REQUI RE
OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA.
Improved construction and additional insulation in buildings
have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped
in reducing heating/cooling costs but have created a problem supplying combustion and ventilation air for gas fired
and other fuel burning appliances. Appliances that pull air
out of the house (clothes dryers, exhaust fans, fireplaces,
etc.) increase the problem by starving appliances for air.
When the furnace is installed as a direct vent (2-pipe) furnace, no special provisions for air for combustion are required. However, if this furnace is to be installed in the same
space with other gas appliances, such as a water heater,
ensure there is an adequate supply of combustion and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1
(Section 9.3), or CAN/CGA B149 Installation Codes (Sections 7.2, 7.3, or 7.4), or applicable provisions of the local
building codes for determining the combustion air requirements for the appliances.
der cabinets.
humidistat, such as an outside wall.
WARNING
17
INST ALLATION CONSIDERA TIONS
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors
such as attics or crawl spaces.
The following information on air for combustion and ventilation
is reproduced from the National Fuel Gas Code NFPA 54/ANSI
Z223.1 Section 9.3.
9.3* Air for Combustion and Ventilation.
9.3.1 General.
9.3.1.1 Air for combustion, ventilation, and dilution of flue gases for
appliances installed in buildings shall be obtained by application of one
of the methods covered in 9.3.2 through 9.3.6. Where the requirements
of 9.3.2 are not met, outdoor air shall be introduced in accordance with
methods covered in 9.3.3 through 9.3.6.
Exception No. 1: This provision shall not apply to direct vent appliances.
9.3.1.2 Appliances of other than natural draft design and other than
Category 1 vented appliances shall be provided with combustion, ventilation, and dilution air in accordance with the appliance manufacturer’s
instructions.
9.3.1.3 Appliances shall be located so as not to interfere with proper
circulation of combustion, ventilation, and dilution air.
9.3.1.4 Where used, a draft hood or a barometric draft regulator shall be
installed in the same room or enclosure as the appliance served so as to
prevent any difference in pressure between the hood or regulator and the
combustion air supply.
(2) For fan-assisted appliances, calculate using the following equation:
Required Volume
where:
I
other
I
fan
ACH=air change per hour (percent of volume of space exchanged
(3) For purposes of this calculation, an infiltration rate greater than
0.60 ACH shall not be used in the equations in 9.3.2.2(1) and
9.3.2.2(2).
9.3.2.3 Indoor Opening Size and Location. Openings used to connect
indoor spaces shall be sized and located in accordance with the following:
(1)*Combining spaces on the same story. Each opening shall have a
minimum free area of 1 in.
input rating of all appliances in the space but not less than 100 in.
(0.60m2). One opening shall commence within 12 in. (300 mm) of
the top, and one opening shall commence within 12 in. (300 mm) of
the bottom, of the enclosure [see Figure A.9.3.2.3(1)]. The mini-
mum dimension of air openings shall be not less than 3 in. (80 mm).
NOTE: Each opening must have
a free area of not less than one
square inch per 1000 BTU of
the total input rating of all equipment in the enclosure, but not
less than 100 square inches.
3
> ________ _________
fan
15 ft
ACH1000 Btu/hr
I
fan
()
=all appliances other than fan-assisted input in Btu per
hour
=fan-assisted appliances input in Btu per hour
per hour, expressed as a decimal)
2
/1000Btu/hr (2200 mm2/kW) of the total
Chimney or Gas Vent
2
9.3.1.5 Makeup air requirements for the operation of exhaust fans, kitchen
ventilation systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion air requirements.
9.3.2 Indoor Combustion Air . The required volume of indoor air shall
be determined in accordance with the method in 9.3.2.1 or 9.3.2.2 except that where the air infiltration rate is known to be less than 0.40
ACH, the method in 9.3.2.2 shall be used. The total required volume
shall be the sum of the required volume calculated for all appliances
located within the space. Rooms communicating directly with the space
in which the appliances are installed through openings not furnished
with doors, and through combustion air openings sized and located in
accordance with 9.3.2.3, are considered a part of the required volume.
9.3.2.1* Standard Method. The minimum required volume shall be 50
ft 3 per 1,000/Btu/hour (4.8m3/kW).
9.3.2.2* Known Air Infiltration Rate Method. Where the air infiltration rate of a structure is known, the minimum required volume shall be
determined as follows:
(1) For appliances other than fan-assisted, calculate using the following
equation:
Required Volume
> ________ _________
other
3
21 ft
I
other
ACH1000 Btu/hr
(
)
Opening
Water
Heater
Furnace
Opening
Figure A.9.2.3.3.(1) All Combustion Air from Adjacent
Indoor Spaces through Indoor Combustion Air Openings.
(2) Combining spaces in different stories. The volumes of spaces in
different stories shall be considered as communicating spaces where
such spaces are connected by one or more openings in doors or
floors having a total minimum free area of 2 in.2/1000 Btu/hr (4400
mm2/kW) of total input rating of all appliances.
9.3.3 Outdoor Combustion Air. Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with the methods in 9.3.3.1 or 9.3.3.2. The minimum dimension of air openings shall
not be less than 3 in. (80 mm).
9.3.3.1 Two Permanent Openings Method. Two permanent openings, one commencing within 12 in. (300 mm) of the top and one commencing within 12 in. (300 mm) of the bottom, of the enclosure shall be
provided. The openings shall communicate directly, or by ducts, with
the outdoors or spaces that freely communicate with the outdoors, as
follows:
18
INST ALLATION CONSIDERA TIONS
A
(1)*Where directly communicating with the outdoors or where commu-
nicating to the outdoors through vertical ducts, each opening shall
have a minimum free area of 1 in.
total input rating of all appliances in the enclosure. [See Figure
A.9.3.3.1(1)(a) and Figure A.9.3.3.1(1)(b).]
Chimney or Gas Vent
Water
Heater
Furnace
lternate
air inlet
Ventilation louvers for
unheated crawl space
Figure A.9.3.3.1(1)(a) All Combustion Air Fr om Outdoors -
Inlet Air from Ventilated Crawl Space and Outlet Air
to Ventilated Attic.
2
/4000 Btu/hr (550 min2/kW) of
Ventilation louvers
(each end of attic)
NOTE: The inlet and outlet a ir
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.
Outlet Air
Inlet Air
9.3.3.2* One Permanent Opening Method. One permanent openings, commencing within 12 in. (300 mm) of the top of the enclosure,
shall be provided. The appliance shall have clearances of at least 1 in. (25
mm) from the sides and back and 6 in. (150 mm) from the front of the
appliance. The opening shall directly communicate with the outdoors or
shall communicate through a vertical or horizontal duct to the outdoors
or spaces that freely communicate with the outdoors (see FigureA.9.3.3.2) and shall have a minimum free area of the following:
(1) 1 in.
appliances located in the enclosure, and
(2) Not less than the sum of the areas of all vent connectors in the
space.
Chimney or Gas Vent
NOTE: The air duct openings
must have a free a r ea o f not
less than one square inch per
2000 BTU of the total input
rating of all equipment in the
enclosure*.
Furnace
Water
Heater
Outlet air duct
Inlet air duct
Figure A.9.3.3.1(2) All Combustion Air From Outdoors
through Horizontal Ducts.
2
/3000 Btu/hr (700 mm2 per kW) of the total input rating of all
Chimney or Gas Vent
Ventilation louvers
(each end of attic)
NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipmen t
in the enclosure.
Outlet Air
Water
Heater
Furnace
Inlet air duct
[ends 1 ft (300 mm)
above floor]
Figure A.9.3.3.1(1)(b) All Combustion Air
From Outdoors through Ventilated Attic.
(2)*Where communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 in.2/2000 Btu/hr
(1100 min2/kW) of total input rating of all appliances in the enclosure. [See Figure A.9.3.3.1(2).]
NOTE: The single opening must have
a free area of not less than one
square inch per 30 00 BT U o f
the total in p ut rat i ng of all equipment in th e enclosure, but not less than
the sum of the areas of all vent
connecto rs in the confined space.
Chimney or Gas Vent
Water
Heater
Furnace
Opening
Alternate
Opening
Location
Figure A.9.3.3.2 All Combustion Air
From Outdoors through Single Combustion Air Opening.
9.3.4 Combination Indoor and Outdoor Combustion Air. The use of
a combination of indoor and outdoor combustion air shall be in accordance with (1) through (3) (see example calculation in Annex J]:
(1) Indoor Openings: Where used, openings connecting the interior
spaces shall comply with 9.3.2.3.
(2) Outdoor Opening(s) Location. Outdoor opening(s) shall be located
in accordance with 9.3.3.
(3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be
calculated in accordance with the following:
(a) The ratio of the interior spaces shall be the available volume of
all communicating spaces divided by the required volume.
(b) The outdoor size reduction factor shall be 1 minus the ratio of
interior spaces.
19
INST ALLATION CONSIDERA TIONS
(c) The minimum size of outdoor opening(s) shall be the full size
of outdoor opening(s) calculated in accordance with 9.3.3,
multiplied by the reduction factor. The minimum dimension
of air openings shall not be less than 3 in. (80 mm).
9.3.8.4 Ducts shall not serve both upper and lower combustion air
openings where both such openings are used. The separation between
ducts servicing upper and lower combustion air openings shall be maintained to the source of combustion air.
9.3.5 Engineered Installations. Engineered combustion air installations shall provide an adequate supply of combustion, ventilation, and
dilution air and shall be approved by the authority having jurisdiction.
9.3.6 Mechanical Combustion Air Supply. Where all combustion air
is provided by a mechanical air supply system, the combustion air shall
be supplied form outdoors at the minimum rate of 0.35 ft3/min per 1000
Btu/hr (0.034 m
space.
9.3.6.1 Where exhaust fans are installed, additional air shall be provided
to replace the exhausted air.
9.3.6.2 Each of the appliances served shall be interlocked to the mechanical air supply system to prevent main burner operation where the
mechanical air supply system is not in operation.
9.3.6.3 Where combustion air is provided by the building’ s mechanical
ventilation system, the system shall provide the specified combustion
air rate in addition to the required ventilation air.
9.3.7 Louvers, Grilles, and Screens.
9.3.7.1 Louvers and Grilles. The required size of openings for com-
bustion, ventilation, and dilution air shall be based on the net free area of
each opening. Where the free area through a design of louver or grille or
screen is known, it shall be used in calculating the size opening required
to provide the free area specified. Where the louver and grille design and
free area are not known, it shall be assumed that wood louvers will have
25 percent free area, and metal louvers and grilles will have 75 percent
free area. Nonmotorized louvers and grilles shall be fixed in the open
position.
3
/min per kW) for all appliances located within the
9.3.8.5 Ducts shall not be screened where terminating in an attic space.
9.3.8.6 Horizontal upper combustion air ducts shall not slope down-
ward toward the source of combustion air.
9.3.8.7 The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or
factory built chimney shall not be used to supply combustion air.
Exception: Direct vent appliances designed for installation in a solid
fuel-burning fireplace where installed in accordance with the
manufacture’s installation instructions.
9.3.8.8 Combustion air intake openings located on the exterior of the
building shall have the lowest side of the combustion air intake openings
located at least 12 in. (300 mm) vertically from the adjoining grade level.
Horizontal Applications and Considerations
Horizontal applications, in particular, may dictate many of
the installation’s specifics such as airflow direction, ductwork connections, flue and/or combustion air pipe connections, etc. The basic application of this furnace as a horizontal furnace differs only slightly from an upright installation. When installing a furnace horizontally, additional consideration must be given to the following:
9.3.7.2 Minimum Scree Mesh Size. Screens shall not be smaller than
1/4 in. mesh.
9.3.7.3 Motorized Louvers. Motorized louvers shall be interlocked
with the appliance so they are proven in the full open position prior to
main burner ignition and during main burner operation. Means shall be
provided to prevent the main burner form igniting should the louver fail
to open during burner startup and to shut down the main burner if the
louvers close during burner operation.
9.3.8 Combustion Air Ducts. Combustion air ducts shall comply with
9.3.8.1 through 9.3.8.8.
9.3.8.1 Ducts shall be constructed of galvanized steel or a material having equivalent corrosion resistance, strength, and rigidity.
Exception: Within dwellings units, unobstructed stud and joist spaces
shall not be prohibited from conveying combustion air, provided that not
more than one fireblock is removed.
9.3.8.2 Ducts shall terminate in an unobstructed space, allowing free
movement of combustion air to the appliances.
9.3.8.3 Ducts shall serve a single space.
90% Horizontal Furnace Shown
20
INST ALLATION CONSIDERA TIONS
Installation Positions
*MVC96 models may be installed up flow or horizontally
with left or right side down. *CVC96 models may be installed
down flow or horizontally with left or right side down. Do not
install any furnace on its back.
Horizontal Installations
1. Horizontal installations require 5.5" under the furnace
to accommodate the drain trap.
2. Horizontal furnaces must be installed with ¾” slope from
back to front to permit condensate flow towards the
front of the furnace.
When installing a *MVM97 horizontally with the left side
down, there are two options for connecting the vent pipe to
the furnace.
1. Venting may be connected to the furnace vent pipe fitting on the original top (now the end) of the furnace
2. The internal vent pipe and elbow may be removed from
the furnace to permit the vent to exit the top (original
side) of the furnace. If this option is used, an RF000142
Vent-Drain coupling must be used to keep condensate
from collecting in the inducer assembly.
Refer to the following instructions and illustration.
1. Remove screws from vent flange.
2. Remove internal elbow and vent pipe.
3. Cut pipe 2 1/2” from flange.
4. Remove cabinet plug adjacent to inducer outlet and install an original cabinet vent hole.
5. Install RF000142 coupling on inducer outlet.
6. Install flanged vent section removed in step 2 & secure
with clamps.
7. Secure flange to cabinet using screws removed in step
1.
E
R
E
H
T
U
C
Vent/Flue Pipe Cuts
R 000142F
Insert flange. Cut 2 ½” long.
90% Furnace Recommended Installation Positions
NOTE: Alternate "vertical" piping connections can not be
used when an upflow 90% furnace is installed with supply
air discharging to the right or when a counterflow furnace is
installed with supply discharging to the left. In this case,
use the standard flue and combustion air piping connections
21
INST ALLATION CONSIDERA TIONS
Alternate Electrical and Gas Line Connections
The furnaces have provisions allowing for electrical and gas
line connections through either side panel. In horizontal applications the connections can be made either through the
“top” or “bottom” of the furnace.
Drain Pan
A drain pan must be provided if the furnace is installed above
a conditioned area. The drain pan must cover the entire area
under the furnace (and air conditioning coil if applicable).
Freeze Protection
If the drain trap and drain line will be exposed to temperatures near or below freezing, adequate measures must be
taken to prevent condensate from freezing. NOTE: The use
of insulation and/or heat tape is recommended. Failure to
provide proper condensate drainage can result in property
damage.
Propane Gas and/or High Altitude Installations
WARNING
P
OSSIBLE PRO PERTY DA MAGE, PERSO NAL IN JURY OR DEATH MAY OCCUR IF
THE CORRECT CONV ERSI ON KITS ARE NOT IN STALLE D.
MUST BE APPLIE D TO I NSURE SAFE AN D PROPER FURNAC E OPERAT ION.
CONVERSIONS MUS T BE PERFORMED BY A QUALIF IE D INSTA LLER OR SERV ICE
AGENCY.
THE APPROPRIATE KI TS
ALL
WARNING
UPON COMPLETION OF THE FURNA CE INSTALLATIO N, CAREFULLY I NSPECT THE
ENTIRE FLUE SYSTEM BO TH INSIDE AND OUTSIDE THE FURNACE TO ASS URE IT
IS PROPERLY SEALED.
PERSONAL INJURY OR DE ATH DUE TO EXPOS URE TO FLUE PRODUCTS,
INCLUDING CARBON MONOXIDE.
LEAKS IN THE FLUE SYSTEM CAN RESULT IN SERIOUS
A condensing gas furnace achieves its high level of efficiency
by extracting almost all of the heat from the products of
combustion and cooling them to the point where condensation takes place. Because of the relatively low flue gas temperature and water condensation requirements, PVC pipe is
used as venting material.
This furnace must not be connected to Type B, BW, or L
vent or vent connector, and must not be vented into any
portion of a factory built or masonry chimney except when
used as a pathway for PVC as described later in this section. Never common vent this appliance with another appliance or use a vent which is used by a solid fuel appliance.
It is the responsibility of the installer to follow the manufacturers’ recommendations and to verify that all vent/flue piping and connectors are compatible with furnace flue products. Additionally, it is the responsibility of the installer to
ensure that all piping and connections possess adequate
structural integrity and support to prevent flue pipe separation, shifting, or sagging during furnace operation.
This furnace is shipped from the factory configured for natural gas at standard altitude. Propane gas installations require an orifice change to compensate for the energy content difference between natural and propane gas.
High altitude installations may require both a pressure switch
and an orifice change. These changes are necessary to compensate for the natural reduction in the density of both the
gas fuel and the combustion air at higher altitude.
Refer to the Accessories Charts in this manual or product
Specification Sheet for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe
and proper furnace operation. All conversions must be performed by a qualified installer, or service agency.
VENT/FLUE PIPE AND COMBUSTION AIR PIPE
WARNING
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY INJURY OR
DEATH.
CAREFULLY READ AND FOLLOW ALL INSTRUCTIONS GIVEN IN THIS
SECTION.
Materials and Joining Methods
WARNING
T
O AVOID BODILY INJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS MUST BE
KEPT AWAY FROM ALL IGNITION SOURCES (I.E., SPARKS, OPEN FLAMES, AND
EXCESSIVE HEAT) AS THEY ARE COMBUSTIBLE LIQUIDS.
CEMENT VAPORS OR CONTACT WITH SKIN AND/ OR EYES.
A
VOID BREATHING
Precautions should be taken to prevent condensate from
freezing inside the vent/flue pipe and/or at the vent/flue pipe
termination. It is our recommendation that all vent/flue piping
exposed to temperatures below 35°F for extended periods
of time should be insulated with 1/2” thick closed cell foam.
Also all vent/flue piping exposed outdoors in excess of the
terminations shown in this manual (or in unheated areas)
should be insulated with 1/2” thick closed cell foam. Inspect
piping for leaks prior to installing insulation.
The following bullets and diagram describe the restrictions
concerning the appropriate location of vent/flue pipe and combustion air intake pipe (when applicable) terminations. Refer to the installation instructions for specific details on termination construction.
•All terminations must be located at least 12 inches
above ground level or the anticipated snow level.
•Vent terminations must terminate at least 3 feet above
any forced air inlet located within 10 feet.
22
INST ALLATION CONSIDERA TIONS
NOTE: This provision does not apply to the combus-
tion air intake termination of a direct vent application.
•The vent termination of a non-directvent application
must terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window, or gravity
air inlet into any building.
•The vent termination of a direct vent application must
terminate at least 12 inches from any opening through
which flue gases may enter a building (door, window,
or gravity air inlet).
•The vent termination of vent pipe run vertically through
a roof must terminate at least 12 inches above the
roof line (or the anticipated snow level) and be at least
12 inches from any vertical wall (including any anticipated snow build up).
•A vent termination shall not terminate over public walkways or over an area where condensate or vapor could
create a nuisance or hazard or could be detrimental
to the operation of regulators, relief valves, or other
equipment.
•The combustion air intake termination of a direct vent
application should not terminate in an area which is
frequently dusty or dirty.
NOTE: In Canada, CAN B149.1 Fuel Gas Code takes precedence over the preceding termination restrictions.
OTHER THAN
COMBUSTION AIR
TERMINATION INTAKE
NON-DIRECT VENT
VENT/FLUE TERMINATION
NO TERMINATIONS
ABOVE WALKWAY
3"
GRADE OR HIGHEST
ANTICIPATED
SNOW LEVEL
FORCED AIR
INLET
10'
12"
12"
DIRECT VENT
VENT/FLUE TERMINATION
12"
VENT/FLUE TERMINATION
4'
4'
12"
NON-DIRECT VENT
90% Furnace Vent Termination Clearances
Direct Vent Installations
On upflow units secure the combustion air intake pipe directly to the air intake coupling. On counterflow units secure the combustion air intake pipe to the air intake coupling using the rubber coupling and worm gear hose clamps
provided with the unit. The counterflow rubber coupling allows service removal of air intake piping internal to the furnace blower compartment. The combustion air intake pipe
can also be secured directly to the counterflow unit air intake pipe coupling.
Non-Direct Vent Installations
A minimum of one 90° elbow must be installed on the combustion air intake “coupling” to guard against inadvertent
blockage.
HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORAT A LOAD. WHEN THE
T
RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET,
EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD-SUPPLI ED
VENT/FLUE PIPING, AS DAMAGE CAN RESULT IN LEAKS CAUSING BODILY
INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES, INCLUDING CARBON
MONOXIDE.
Vent/Flue Pipe Lengths (Non-Direct Vent) and Diameters
Refer to the following table for applicable length, elbows,
and pipe diameter for construction of the vent/flue pipe system of a non-direct vent installation. In addition to the vent/
flue pipe, a single 90° elbow must be secured to the combustion air intake to prevent inadvertent blockage. The tee
or elbows used in the vent/flue termination must be included
when determining the number of elbows in the piping system.
Vent/Flue and Combustion Air Pipe Lengths and Diameters
Refer to the following table for applicable length, elbows,
and pipe diameter for construction of the vent/flue and combustion air intake pipe systems of a non-direct vent (single
pipe) installation. The number of elbows tabulated represents the number of elbows and/or tees in each (Vent/Flue
& Combustion Air Intake) pipe. Elbows and/or tees used in
the terminations must be included when determining the number of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a
finished ceiling or other area where dripping of condensate
will be objectionable, insulation of the combustion air pipe
may be required. Use 1/2” thick closed cell foam insulation
such as Armaflex or Insultube where required.
Vent/Flue Pipe Terminations
The vent/flue pipe may terminate vertically, as through a roof,
or horizontally, as through an outside wall.
Vertical vent/flue pipe termination should be as shown in the
following figures. Refer to Vent/Flue Pipe and CombustionAir Pipe - Termination Locations section in this manual or
the installation instructions for details concerning location
restrictions. The penetration of the vent through the roof must
be sealed tight with proper flashing such as is used with a
plastic plumbing vent.
WARNING
23
INST ALLATION CONSIDERA TIONS
Horizontal vent/flue pipe terminations should be as shown in
the following figure. Refer to Vent/Flue Pipe and Combus-tion Air Pipe - Termination Locations section in this manual
or the installation instructions for details concerning location restrictions. A 2 3/8" diameter wall penetration is required for 2" diameter pipe while a 3 1/2" diameter hole is
required for 3" diameter pipe. To secure the pipe passing
through the wall and prohibit damage to piping connections,
a coupling should be installed on either side of the wall and
solvent cemented to a length of pipe connecting the two
couplings. The length of pipe should be the wall thickness
plus the depth of the socket fittings to be installed on the
inside and outside of the wall. The wall penetration should
be sealed with silicone caulking material.
In a basement installation, the vent/flue pipe can be run between joist spaces. If the vent pipe must go below a joist
and then up into the last joist space to penetrate the header,
two 45° elbows should be used to reach the header rather
than two 90° elbows.
NOTE: Terminate both pipes in the same pressure zone
(same side of roof, no major obstacle between pipes, etc).
TEE (OPTIONAL)
COMBUSTION AIR INTAKE
(OPTIONAL)
*Not required for
single pipe installation
E
N
I
L
F
O
O
R
INTAKE
SCREEN
OPTIONAL
12” MIN TO ROOF OR HIGHEST
ANTICIPATED SNOW LEVEL
6
9
12” MIN
HEIGHT DIFFERENCE
BETWEEN
INT AKE AND VENT
”
3
-
.
X
A
M
”
.
N
I
M
90% Furnace Horizontal Termination (Single Pipe)
Direct Vent (Dual Pipe) Piping
Direct vent installations require both a combustion air intake and a vent/flue pipe. The pipes may be run horizontally
and exit through the side of the building or run vertically and
exit through the roof of the building. The pipes may be run
through an existing unused chimney; however, they must
extend a minimum of 12 inches above the top of the chimney. The space between the pipes and the chimney must
be closed with a weather tight, corrosion resistant flashing.
Both the combustion air intake and a vent/flue pipe terminations must be in the same atmospheric pressure zone. Refer to Vent/Flue and Combustion Air Pipe - Termination Lo-cations or Concentric Vent Termination section in this manual
or the installation instructions for specific details on termination construction.
*MVC9 6/*CVC 9 6 Direct Vent (2 - Pipe) and N on-Direct Vent (1- Pip e)
Unit Input
(Btu)
12" MINIMUM
VENT/FLUE TEE
90° ELBOW TURNED
12" MINIMUM ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
OR
DOWN
Above Highest Anticipated Snow Level
Maximum Allowable Length of Vent/Flue Pipe
& Comb u stion Air Pipe (ft )
Pipe Size
(4)
(in .)
12345678
Number of Elbows
(1) (2)
(3) (5)
(6)
ELBOWS
STRAIGHT
24
40,000
60,000
80,000 "B" 2 or 2 1/2 7570656055504540
80,000 "B"3200193186179172165158151
80,000 "C" 2 or 2 1/2 252015105N/A N /A N/A
80,000 "C"3200193186179172165158151
100,0002 or 2 1/2 252015105N/A N /A N /A
100,0003200193186179172165158151
120,0002 or 2 1/2 4540353025201510
120,00039590858075706560
2
or 2 1/2
2
or 2 1/2
120115110105100959085
9590858075706560
Loading...
+ 55 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.