The CA3059 and CA3079 zero-voltage switches are monolithic silicon integrated circuits designed to control a thyristor
in a variety of AC power switching applications for AC input
voltages of 24V, 120V, 208/230V, and 277V at 50Hz-60Hz
and 400Hz. Each of the zero-voltage switches incorporates
4 functional blocks (see the Functional Block Diagram) as
follows:
1. Limiter-Power Supply - Permits operation directly from an
AC line.
2. Differential On/Off Sensing Amplifier - Tests the condition
of external sensors or command signals. Hysteresis or
proportional-control capability may easily be implemented in this section.
3. Zero-Crossing Detector - Synchronizes the output pulses
of the circuit at the time when the AC cycle is at zero voltage point; thereby eliminating radio-frequency interference (RFI) when used with resistive loads.
4. Triac Gating Circuit - Provides high-current pulses to the
gate of the power controlling thyristor.
In addition, the CA3059 provides the following important
auxiliary functions (see the Functional Block Diagram).
1. A built-in protection circuit that may be actuated to remove
drive from the triac if the sensor opens or shorts.
2. Thyristor firing may be inhibited through the action of an
internal diode gate connected to Terminal 1.
3. High-power dc comparator operation is provided by over-
Ordering Information
PART NUMBERTEMPERATUREPACKAGE
CA3059-55
CA3079-55
o
C to +125oC14 Lead Plastic DIP
o
C to +125oC14 Lead Plastic DIP
riding the action of the zero-crossing detector. This is accomplished by connecting Terminal 12 to Terminal 7.
Gate current to the thyristor is continuous when Terminal
13 is positive with respect to Terminal 9.
The CA3059 and CA3079 are supplied in 14 lead dual-inline plastic packages.
At distance 1/16” ± 1/32” (1.59 ± 0.79) from case
for 10 seconds max
CAUTION: Stresses above those listed in “Absolute Maximum Ratings” may cause permanent damage to the device. This is a stress only rating and operation
of the device at these or any other conditions above those indicated in the ope rational sections of this specification is not implied.
Electrical SpecificationsT
= +25oC, For all Types, Unless Otherwise Specified. All voltages are measured with respect to
A
Terminal 7. For Operating at 120V
, 50-60Hz (AC Line Voltage) (Note 1)
RMS
PARAMETERSSYMBOLTEST CONDITIONSMINTYPMAXUNITS
DC SUPPLY VOLTAGE (Figure 2A, 2B, 2C)
Inhibit ModeAt 50/60HzV
At 400HzR
At 50/60HzR
Pulse ModeAt 50/60HzV
At 400HzR
At 50/60HzR
Gate Trigger Current (Figures 3, 4A)I
Terminal 4
GT
RS = 8kΩ, IL = 06.16.57V
S
= 10kΩ, IL = 0-6.8-V
S
= 5kΩ, IL = 0-6.4-V
S
RS = 8kΩ, IL = 066.47V
S
= 10kΩ, IL = 0-6.7-V
S
= 5kΩ, IL = 0-6.3-V
S
Terminals 3 and 2 Connected,
-105-mA
VGT = 1V
PEAK OUTPUT CURRENT (PULSED) (Figures 4, 5)
With Internal Power Supply
Figure 4a, 4b
Terminal 4
With External Power Supply
Figure 5a, 5b, 5c
Terminal 4
Inhibit Input Ratio (Figure 6)V
I
OM
I
OM
9/V2
Terminal 3 open, Gate Trigger
Voltage (VGT) = 0
Terminals 3 and 2 Connected, Gate
Trigger Voltage (V
PULSE DURATION AFTER ZERO CROSSING (50-60Hz) (Figure 7A)
For Positive dv/dtt
For Negative dv/dtt
P1
N1
EXT
= 0, R
= ∞-50-µs
EXT
-60-µs
C
OUTPUT LEAKAGE CURRENT (Figure 8)
Inhibit ModeI
4
-0.00110µA
INPUT BIAS CURRENT (Figure 9)
CA3059I
I
-2201000nA
CA3079-2202000nA
Common-mode Input Voltage RangeV
CMR
Terminals 9 and 13 Connected-1.5 to 5-V
C
5
Specifications CA3059, CA3079
Electrical SpecificationsT
= +25oC, For all Types, Unless Otherwise Specified. All voltages are measured with respect to
A
Terminal 7. For Operating at 120V
, 50-60Hz (AC Line Voltage) (Note 1) (Continued)
RMS
PARAMETERSSYMBOLTEST CONDITIONSMINTYPMAXUNITS
SENSITIVITY (Note 3) (Figures 4(a), 11)
Pulse Mode∆V
Terminal 12 open-6-mV
13
NOTES:
1. The values given in the Electrical Characteristics Chart at 120V also apply for operation at input voltages of 208/230V, and 277V, except
for Pulse Duration. However, the series resistor (R
for the specified input voltage.
) must have the indicated value, shown in the chart in the Functional Block Diagram,
S
2. Pulse Duration in 50Hz applications is approximately 15% longer than shown in Figure 7(b).
3. Required voltage change at Terminal 13 to either turn OFF the triac when ON or turn ON the triac when OFF.
This chart gives the range of voltages which can be applied to the terminals listed horizontally with respect to the terminals listed vertically.
For example, the voltage range of horizontal Terminal 6 to vertical Terminal 4 is 2V to -10V.
NOTES:
1. Resistance should be inserted between Terminal 5 and external supply or line voltage for limiting current into Terminal 5 to less than
50mA.
2. Resistance should be inserted between Terminal 14 and external supply for limiting current into Terminal 14 to less than 2mA.
3. For the CA3079 indicated terminal is internally connected and, therefore, should not be used.
4. Voltages are not normally applied between these terminals; however, voltages appearing between these terminals are safe, if the specified voltage limits between all other terminals are not exceeded.
5. For CA3079 (0V to -10V).
6
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.