Drives 1 x 32W Spiral CFL Lamp
Input Voltage: 120Vac
High Frequency Operation
Lamp Filament Preheating
Lamp Fault Protection with Auto-Restart
Low AC Line/Brownout Protection
IRS2530D DIM8TM HVIC Ballast Controller
2. Overview
The 3 way dimming system widely adopted in the US with conventional filament lamps
consists of a light bulb that has a modified Edison screw type base which allows 3
connections to be made to a special lamp socket that also has 3 connections.
Standard Edison Screw
Base
Live
Neutral
Figure 2.1: Three way dimming Edison screw base
The 3 way dimming light bulb has two filaments inside which produce different light
outputs when connected to the AC line. These filaments are connected in series such that
the mid point goes to the line common and the two ends can be connected to the live
3 Way Dimming Edison
Screw Base
Live 1 Live 2
Neutral
www.irf.com
RD0803
- 2 -
either independently or both together. Thus with an external switch that has four positions,
it is possible to obtain 3 different light levels or to switch off.
3 Way Dimming Switch
3 Way Dimming Light Bulb
Live
120V AC Line
Neutral
1 2
0
Figure 2.2: Three way dimming filament lamp system
3 0
1 2
3
40W Filament60W Filament
Figure 2.2 shows how the live and the neutral connect for 4 different configurations
(position 0, 1, 2, and 3). The flow of current for each position is also shown with colored
arrow; no current flows for position 0 (switch off), red arrow for position 1, blue arrow for
position 2, and magenta arrow for position 3. In position 1, the current will flow through
the 40W filament resistor (the lowest dimming level). In position 2, the current will flow
through the 60W filament resistor (intermediate dimming level). In position 3, current
will flow through both filaments, and the system will be at the maximum dimming level.
Existing Ballast Solution
There are in existence CFL ballast designs that provide three way dimming based on
the same switching arrangement shown above. A common approach is a system
whereby the line voltage is full wave rectified when one live input is connected and a
voltage doubler circuit comes into operation when the other live input is connected or
both are connected together thereby having two DC bus voltages in the ballast during
dim level settings. This type of design also operates at two different frequencies, a low
frequency (typically 40-45kHz) when both live inputs are connected providing a high
lamp current and a higher frequency (for example 70-75kHz) when either of the two
lives is connected alone which will produce a lower lamp current. In this way the
following combinations are achieved:
1. Low DC bus (150V) / high frequency ….. minimum output
2. High DC bus (300V) / high frequency …... medium output
3. High DC bus (300V) / low frequency …… maximum output
This approach has some serious drawbacks:
Firstly, since the ballast must be designed to give 100% light output for the lamp when
the bus voltage is 300V and the frequency is 40kHz, it is not easy to achieve
satisfactory preheat and ignition when the bus voltage is at 150V because of the
limitations in the peak voltage that the output circuit is able to produce from a 150Vpp
half bridge voltage.
www.irf.com
RD0803
- 3 -
One strategy that has been used is to omit the preheating phase and steer the
oscillator frequency to resonance during ignition using feedback from the output circuit.
This ensures that at switch-on the highest possible ignition voltage will be applied to the
lamp. In this way the lamp will ignite in whichever position the 3 way switch is set.
Such a scheme could reliably ignite the lamp when the DC bus is at 300V, however
without correct preheating the ignition voltage of the lamp and consequently the peak
current in the MOSFET half bridge during ignition will be higher. Also the life of the
lamp is substantially reduced when there is no preheat due to far greater stress
occurring on the cathodes at the point of ignition.
Ignition when the DC bus voltage is at 150V is very difficult. Tests indicated that
sweeping the frequency down through resonance sometimes failed to produce
sufficient ignition voltage leaving the ballast in open circuit running mode. The
conclusion from this is that the ballast needs to oscillate at resonance for an extended
period of time in order for the lamp to ignite at 150V considering that the output inductor
and capacitor have been designed to produce 100% lamp power at 300VDC bus when
the frequency is 40-45kHz.
Many CFL ballast designs do not incorporate a current sense and shutdown function to
protect the circuit in the case of ignition failure and so the ballast would eventually fail if
left switched on due to the high MOSFET switching losses causing thermal destruction.
This would not matter with and integrated ballast / lamp type product when the lamp
has failed.
It has also been observed that hard switching occurs at the MOSFET half bridge when
the DC bus voltage is low in position 1 since when the ballast is running it will be close
to resonance, bearing in mind that the resonant frequency shifts downwards in run
mode. Hard switching is very undesirable because of the high peak currents that occur
when each MOSFET switches on. This has been shown to result in a higher rate of
field failures in ballasts due to MOSFET failure.
The conclusion is that the approach to design described above is unable to provide a
reliable ballast.
The dimming level can also be controlled by simply changing the frequency. By
changing the frequency between 3 defined settings, however, it was found to be
extremely difficult to set a point where the dim level is 50%. The problem with this is
that the lamp current against ballast frequency characteristic of the system exhibits a
very sharp knee such that as the frequency increases the lamp current is gradually
reduced up to a point at which a small increase of frequency will result in a very large
reduction in the lamp current.
www.irf.com
RD0803
- 4 -
Ballast / Lamp Operati ng Characteristic
Lamp
Current
Ballast Running
Frequency
Figure 2.3: Lamp current against ballast frequency
To obtain 50% output, the frequency would have to be very precisely set. This is not
practical since the tolerances of the output inductor, capacitor and oscillator timing
components do not allow this. Even if each ballast was individually adjusted in
production variations in lamp behavior over temperature would mean that under some
conditions the lamp arc would extinguish at this setting leaving the system in
permanent preheat which would burn out the cathodes eventually.
This explains why the 150VDC bus solution has been adopted in some designs as this
allows 50% output to be achieved without this problem. However as discussed in the
previous section this approach is not without some major disadvantages.
IRPLCFL4 Reference Design
It is however necessary in order to create a reliable design to include a closed loop
feedback system that controls the lamp current by adjusting the ballast frequency from
a VCO (voltage controlled oscillator) driven by the output of an error amplifier that
senses the lamp arc current directly and compares it with a reference. This has been
used in the IRPLCFL4 reference design “A 3 Way Dimming CFL Ballast” and has been
demonstrated to be capable of controlling the lamp output down to approximately 10%
arc current maintaining stability. This also compensates for tolerances in the
components of the circuit or the lamp.
www.irf.com
RD0803
- 5 -
∑
Regulated Lamp Current Control System
VCO
&
DRIVER
+
Lamp Arc Current
Reference
-
Figure 2.4: Closed loop lamp arc current regulation
Many of the design issues described above have also been overcome in the ballast
circuit of reference design IRPLCFL4. The design, however, required two additional
operational amplifiers and additional circuitry since it is based on the IR2156 control IC,
which does not incorporate the necessary dimming circuitry. This circuit therefore has a
relatively high component count.
L1
L2
COMMON
R4
R5
R1
L1
C1 C2
R2
L2
D1D2
C3
R6
C4
D3
R7
R8
C7
D4
5
6
R10
R12
2
3
IC1a
R11
R9
8
4
R3
R15
7
NC
VCC
VDC
R16
RT
R17
RPH
CT
CPH
C9C10C11
C8
1
IC1b
C20
D7
R18
D8
IC2
IR2156
VB
14
HO
13
VS
12
LO
11
CS
10
SD
9
COM
8
C6
1
2
3
4
5
6
7
Q1
L3
R19
C13
Q2
D10
C19
R20
C5
C14
R21
R13
C15
D9
R9
C16
C12
L3a
C17
C18
L3b
D5
D6
R14
Figure 2.5: IRPLCFL4 Circuit Schematic
The component count for the IRPLCFL4 design shown in figure 2.5 is 56 parts.
www.irf.com
RD0803
- 6 -
New Solution: IRPLCFL8U
A completely new approach has been developed that overcomes all of the above
limitations. The IRPLCFL8U reference design kit consists of a dimming Fluorescent
ballast, with a 3 way dimming switch, driving a single 32W CFL lamp. The design
contains an EMI filter and a dimming ballast control circuit using the
IRS2530D(
50 parts. This demo board is intended to help with the evaluation of the IRS2530D
dimming ballast control IC, demonstrate PCB layout techniques and serve as an aid in
the development of production ballasts using the IRS2530D.
DIM8
TM
). The component count for the IRPLCFL8U, shown in figure 3.1, is
www.irf.com
RD0803
- 7 -
3. Circuit Schematic
SPIRAL
CFL LAMP
CH1
LRES : B
CDC
LRES:A
RLMP2
MHS
RHO
VB
HO
8
7
RVCC2RVCC1
CVCC1
RS1
RS2
IRS2530D
1
2
VCC
COM
CVCC2
CRES
CSNUB
RLO
CBS
LO
VS
6
3
DIM
VCO
CVCO
CDIM
CH2
DCP2
MLS
RLMP1
5
4
RVCO
CCPH
RCS
LRES :C
DCP1
RFB
CFB
RDIM
RPU
D2
D1
C3
R2
PL2
PL1
L2
R1
L1
Q1
Q2
R3
R4
C1C2
DZ1
R5R6
C4
COMMON
DZ2
C5
R7
D4
D3
Figure 3.1: IRPLCFL8U Circuit Schematic
www.irf.com
RD0803
- 8 -
4. Electrical Characteristics
Parameter Units Dimming Level Value
Lamp Type 32W CFL
Maximum 31
Input Power [W]
Input Current [mArms]
Lamp Running Voltage [Vpp]
Lamp Running Current [mArms]
Start Frequency [kHz] 115
Run Frequency [kHz]
Preheat Time [s] 0.5
Input AC Voltage Range [VACrms] 60 - 180
Ballast turn-off voltage [VACrms] 60
TABLE 4.1: Ballast Parameters.
Intermediate 22
Minimum 15
Maximum 386
Intermediate 260
Minimum 175
Maximum 370
Intermediate 540
Minimum 630
Maximum 190
Intermediate 80
Minimum 27
Maximum 42
Intermediate 59
Minimum 60
5. Fault Protection Characteristics
Fault Protection Ballast Restart Operation
Brown-out Non-ZVS Increase
frequency
Upper filament broken Crest Factor Over Current Deactivates Lamp exchange
Lower filament broken Crest Factor Over Current Deactivates Lamp exchange
Lamp removed Crest Factor Over Current Deactivates Lamp inserted
Failure to ignite VVCOFLT+ Deactivates Lamp exchange
No lamp VLOSD- Does not
start
End of life Crest Factor Over Current Deactivates Lamp exchange
TABLE 5.1: Fault Protections Characteristics.
Line voltage
increase
Lamp inserted
www.irf.com
RD0803
- 9 -
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.