International Comfort Products Corporation NTG3/FBF, NTN3/NBF, NTC6/GNE, NDN3/NDF, NDN6/GDE Installation Instructions Manual

...
NTG3/FBF & NTC6/GNE NTN3/NBF & NTN6/NNE NDN3/NDF & NDN6/GDE
SAFETY REQUIREMENTS
Recognize safety information. This is the safety--alert symbol alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards, those that will result in severe personal injury or death. WARNING signifies a hazard that could result in personalinjury or death. CAUTION is used to identify unsafe practices that could result in minor personal injury or product and property damage.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) NFPA No. 54/ANSIZ223.1. In Canada, refer to the current edition of the National Standard Canada CAN/CGA--B149.1-- and .2--M91 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start--up and adjust­ment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
!
. When you see this symbol on the furnace and in instructions manuals be
Manufactured by:
International Comfort Products Corporation (USA)
Lewisburg, TN USA 37091
Table of Contents
1.Safe Installation Requirements 3................
2. Installation 4...............................
3. Combustion & Ventilation Air 7.................
4. Gas Vent Installation 9.......................
5. Horizontal Venting 10.........................
6. Masonry Chimney Venting with Optional Kit 11......
7. Gas Supply and Piping 12......................
Electric Shock Hazard
Turn Off All Power Before Servicing.
Failure to do so can result in death, personal injury and/or property damage.
Printed in U.S.A. LP1 3/4/2002 441 01 2603 02
8. Electrical Wiring 15.........................
9. Ductwork and Filter (Upflow/Horizontal) 16......
10. Ductwork and Filter (Downflow) 17............
11. Checks and Adjustments 19.................
12. Furnace Maintenance 21....................
13. Tech Support and Parts 22..................
!
Fire or Explosion hazard. This furnace is not designed for use in mobile
homes, trailers or recreational vehicles. Such use could result in death, bodily injury
and/or property damage.
START--UP CHECK SHEET
(Keep this page for future reference)
Dealer Name:
Address: Business Card Here
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Type of Gas: Natural: LP:
Blower Motor H.P.:
Supply Voltage:
Limit Opens at...(°F) or(°C)
Limit Closes at...(°F) or(°C)
Which blower speed tap is used?
(Heating)
(Cooling)
Drip--Leg Upstream of Gas Valve? YES NO
Condensate Drain Connected? YES NO
Condensate Drain Trapped? YES NO
Horizontal Condensate Switch Installed? YES NO
Blower Speed Checked? YES NO
All Electrical Connections Tight? YES NO
Gas Valve OK? YES NO
Measured Line Pressure When Firing Unit:
Calculated Firing Rate:(See Checks and Adjustments Sec-
tion).
Measured Manifold Pressure:
Temperature of Supply Air: (°F) or(°C)
Temperature of Return Air: (°F) or(°C)
Rise (Supply Temp.--Return Temp.): (°F) or(°C)
Filter Type and Size:
Fan “Time ON” Setting:
Fan “Time OFF” Setting:
Manual Gas Shut--Off Upstream
of Furnace/Drip--Leg? YES
Dealer Comments:
2
NO
Thermostat OK? YES NO
Subbase Level? YES NO
Anticipator Set? YES NO Set At?:
Breaker On? YES NO
Date of Installation:
Date of Start--Up:
441 01 2603 02
1. Safe Installation Requirements
!
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in this manual is intended for use by a qualified service technician who is experienced in such work, who is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, death, personal injury and/or property damage.
NOTE: This furnace is design certified by the American Gas
Association and the Canadian Gas Association for installation in the United States and Canada. Refer to the appropriate codes, along with this manual, for proper installation.
· This furnace is NOT approved for installation in mobile
homes, trailers or recreation vehicles.
· Do NOT use this furnace as a construction heater or to heat
a building that is under construction.
· Use only the Type of gas approved for this furnace (see
Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation. (Furnace can be converted to L.P. gas with approved kit.)
· Do NOT use open flame to test for gas leak.
· Ensure adequate combustion and ventilation air is provided
to the furnace.
B. There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire extinguisher and smoke detectors listed by Under­writers Laboratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any detec-
tors and makes no representations regarding any brand or type of detector.
C. Toensuresafe and efficient operation of your unit, you should
do the the following:
1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and the haz­ards involved with gas and electricity.
2. Do not use this unit if any part has been under water. Im­mediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.
3. Neverobstruct the vent grilles, or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases.
Carbon monoxide or “CO” is a colorless and odorless gas produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
· Seal supply and return air ducts.
· The vent system MUST be checked to determine that it is
the correct type and size.
· Install correct filter type and size.
· Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
· It is the suggestion of the manufacturer to install fire and
carbon monoxide detectors.
Safety Rules
Your unit is built to provide many years of safe and dependable service providing it is properly installedand maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission recom-
mends that users of gas--burning appliances install carbon monoxide detectors. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas--fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas--fired fireplaces, wood fireplaces, and several other items. Carbon monoxide can cause serious bodily inju­ry and/or death. Therefore, to help alert people of potentially dangerous carbon monoxide levels, you should have carbon monoxide detectors listed by a nationally recognized agency (e.g. Underwriters Laboratories or International Approval Services) installed and maintained in the building or dwelling (see Note below).
441 01 2603 02
Freezing Temperatures and Your Structure
!
Freeze warning.
Turn off water system.
If your unit remains shut off during cold weather the water pipes could freeze and burst, resulting in serious water damage.
Your unit is equipped with safety devices that may keep it from op­erating if sensors detect abnormal conditions suchas clogged ex­haust flues.
If the structure will be unattended during cold weather you should take these precautions.
1. Turn off main s upply water into the structure and drain the water lines if possible. Open faucets in appropriate areas.
2. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Suggest they call a qualified service agency, if required.
3
2. Installation
/
Cab
i
S
A
i
NTG3/NTN3
!
Poison carbon monoxide gas hazard.
If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances(s). See applicable codes and Venting and Combustion Air Check in Gas Vent Installation section.
Failure to properly vent this furnace or other appliances can result in death, personal injury and/or property damage.
Figure 1
Dimensions and Clearances (Upflow/Horizontal NTG3/NTN3 &FBF/NBF)
Location and Clearances
If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or evaluate the exist­ing location based upon the minimum clearance and furnace di­mensions (Figure 1, Figure 2 and Figure 3).
CAUTION
Do NOT operate furnace in a corrosive atmosphere contain­ing chlorine, fluorine or any other damaging chemicals. Re­fer to Combustion & Ventilation Air section, Contaminated Combustion Air.
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR 0
FRONT 3² *
Recommended For Service 30²
ALL SIDES Of SUPPLY PLENUM 1²
SIDES 0
VENT
Single Wall Vent 6²
Type B--1 Double Wall Vent 1²
TOP OF FURNACE 1²
*6² with accessory Masonry Chimney drafthood kit installed.
30² min.
DIMENSIONAL INFORMATION
Unit
Capacity
NTN3
NTG3
FBF/NBF
50FB / 050B12
75FB / 075B12
75HF/ 075F16
100KF / 100F20
100KJ/100J20 125KJ/125J20
40 151/2281/211/211/215/811/241/2175/16181/214 231/8125/8221/2121/4237/8281/426 281/
40 191/8281/211/211/215/811/241/2175/16181/2175/8231/8143/4221/2141/2237/8281/426 281/
40 223/4281/211/211/215/811/241/2175/16181/2211/4231/8183/4221/2141/2237/8281/426 281/
net
A B C D E D E R P O N F G J H M K L K
Top Left/Right Side Low Volt
4
Electrical Connections
25--22--28
Drawing is representative some models may vary
upply
r
Return Air Gas Connections
Bottom Side Right Side Left Side
4
4
4
441 01 2603 02
Figure 2
CABINETSUPPLYAI
R
GASCONNECTION
Upflow Dimensions and Clearances (NTC6/GNE & NTN6/NNE)
150,000 BTU ONLY Air Baffle DO NOT REMOVE
MINIMUM CLEARANCES TO
MATERIALS FOR ALL UNITS
REAR 0
FRONT 3² (75mm)*
Recommended For Service 30² (760mm)
ALL SIDES Of SUPPLY PLENUM 1² (25mm)
SIDES 0
VENT
Single Wall Vent 6² (150mm)
Type B--1 Double Wall Vent 1² (25mm)
TOP OF FURNACE 6² (150mm)
*6² with accessory Masonry Chimney drafthood kit installed.
COMBUSTIBLE
30² min.
DIMENSIONAL INFORMATION
MODEL
A B C D E F G H J K L M
050FB / 075FB 050B12 / 075B12
075HF & 075F16 100KF / 100F20
100KJ / 100J20 125KJ / 125J20 150KJ / 150J20
40 151/
40 191/
40 223/
2
8
4
281/
281/
281/
Drawing is representative some models may vary
RETURN AIR
BOTTOM SIDE
181/
2
181/
2
181/
2
2
2
2
14 231/
175/
8
211/
4
231/
231/
125/
8
143/
8
183/
8
121/
8
141/
4
141/
4
221/
4
221/
2
221/
2
281/
2
281/
2
281/
2
4
4
4
26 237/
26 237/
26 237/
8
8
8
441 01 2603 02
5
Figure 3
25-20-45
Water Heater
G
F
C
K
H
H
J
B
A
D
E
7/8"
3/4"
24" MIN.
MODEL
MODEL
Dimensions and Clearances (Downflow)
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR 0
FRONT 3²
For Service 30²
ALL SIDES Of SUPPLY PLENUM 1²
SIDES 0
VENT
Single Wall Vent 6²
Type B--1 Double Wall Vent 1²
TOP OF FURNACE 1²
37/8²
30² MIN.
DIMENSIONAL INFORMATION
MODEL
NDN3050/075FB NDF050/075B
NDN3075HF & 100GF/KF NDF075F/100F
NDN3125KJ/NDF125J 223/
MODEL
NDN6050/075FB GDE050/075B
NDN6075HF & NDN6100GF/KF GDE075F/100F
NDN6125KJ/GDE125J 223/
Installation Requirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of build­ings or structures under construction.
3. Install the vent pipes as short as practical. (See Gas Vent
Installation section).
CABINET
A B C D E F G H
151/
191/
281/
2
8
4
281/
281/
2
2
2
CABINET
A B C D E F G H
151/
191/
281/
2
8
4
281/
281/
2
2
2
Drawing is representative some models may vary
BOTTOM
OPENING
40 14 151/
40 179/
40 213/
151/
16
151/
16
BOTTOM
OPENING
40 14 151/
40 179/
40 213/
151/
16
151/
16
5. Maintainclearance for fire safety and servicing. A front clear­ance of 30² is minimum for access to the burner,controls and filter.
6. Use a raised base if the floor is damp or wet at times.
7. Residential garage installations require:
· Burners and ignition sources installed at least 18 ² (457mm)
above the floor.
2
2
2
2
2
2
RETURN
OPENING
14 1817/
175/
8
211/
4
RETURN
OPENING
14 1817/
179/
16
213/
16
1817/
1817/
1817/
1817/
GAS CONNECTIONS
411/
411/
411/
K
16
16
16
J
97/
32
97/
32
97/
32
21/
16
16
16
21/
21/
2
2
2
GAS CONNECTIONS
411/
411/
411/
K
16
16
16
J
913/
32
913/
32
913/
32
21/
16
16
16
21/
21/
2
2
2
4. Do NOT install furnace directly on carpeting, tile or other combustible material other than wood flooring.
6
· Furnace must be located or physically protected from pos-
sible damage by a vehicle.
441 01 2603 02
Horizontal Furnace Installation
25-20-27
IMPORTANT
NOTE: Inspect unit rating plate to be certain model number be- gins with “NTN3”, “FBF”, “NTG3”, “NBF”, “NTC6”, “GNE, “NTN6” or “NNE”. This identifies unit as horizontally mountable.
If unit does NOT bear this designation, you may NOT mount this unit horizontally. Horizontal furnace may not be mounted on
its back.
If you purchased a horizontally mountable furnace, it can be installed horizontally in an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room in either a right or left airflow position. See Figure 4.
Thirty inches (30²) is recommended between the front of the fur­nace and adjacent construction or other appliances. This should be maintained for service clearance.
Keep all insulating materials clear from louvered door. Insulating materials may be combustible.
The horizontal furnaces may be installed directly on combustible wood flooring or supports, however, it is recommended for further fire protection cement board or sheet metal is placed between the furnace and the combustible wood floor and extend 12² beyond the front of the furnace louver door. (This is a recommendation only, not a requirement).
This furnace MUST NOT be installed directly on wood flooring or supports, carpeting, tile or other combustible material other than wood flooring.
Figure 4
The following minimum clearances to combustibles MUST be maintained between the furnace and adjacent construction, as shown in Figure 1. ONLY the corner of the cabinet is allowed to contact the rafters (see Figure 4). All other clearances MUST be observed as shown in Figure 1 .
If the furnace is to be suspended from the floor joists in a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to attach the furnace. These straps should be attached to the furnace with sheet metal screws and to the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists.
If the furnace is to be installed ground level i n a crawl space, con­sult local codes. A concrete pad 1² to 2² thick is recommended.
Typical Horizontal Installation
Pressure Switch Relocation
If the furnace is installed in a right to left airflow position (left side of furnace facing down), the pressure switch will remain in the same position as installed by the factory (see Figure 5). If the furnace is installed in a left to right airflow position (right side of furnace fac ­ing down), the pressure switch MUST be relocated to the left side of the furnace using the holes provided in the top panel. Position the pressure switch in the same orientation as the original loca­tion. Toprevent possible kinking of the pressure switch hose, trim the hose to remove excess.
Note:CareMUST be taken not to cut the tube too short.
Figure 5
Optional pressure switch location for Right to Left Airflow
25--20--95a
Pressure Switch Relocation for Upflow
Shown As
Shipped
If furnace is placed on its right side, relocate switch to left side in same orientation as originally mounted.
3. Combustion & Ventilation Air
!
Poison carbon monoxide gas hazard.
Use methods described here to provide combustion and ventilation air.
Failure to provide adequate combustion and ventilation air can result in death and/or personal injury.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open­ings for supplying combustion and ventilation air must comply
441 01 2603 02
with the gas codes, or in the absence of local codes, the applica ­ble national codes.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting And Combustion Air Check in “Gas Vent Installation” Section i n this manual.
Contaminated Combustion Air
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the fur­nace. These instances must use only outside air for combustion.
7
The following areas or types of structures may contain or have ex­posure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the area.
· Commercial buildings.
· Buildings with indoor pools.
· Furnaces installed in laundry rooms.
· Furnaces installed in hobby or craft rooms.
· Furnaces installed near chemical storage areas.
· Permanent wave solutions for hair.
· Chlorinated waxes and cleaners.
· Chlorine based swimming pool chemicals.
· Water softening chemicals.
· De--icing salts or chemicals.
· Carbon tetrachloride.
· Halogen type refrigerants.
· Cleaning solvents (such as perchloroethylene).
· Printing inks, paint removers, varnishes, etc.
· Hydrochloric acid.
· Sulfuric Acid.
· Solvent cements and glues.
· Antistatic fabric softeners for clothes dryers.
· Masonry acid washing materials.
Figure 6
Outside Air (This is O NLY a guide. Subject to codes of country having jurisdiction.)
This installation NOT approved in Canada
Gas Vent
Top Above Insulation
Ventilated Attic
Gable Vent
Optional Inlet Air (1)
Gas Vent
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances MUST be considered
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, the openings
4. Theminimum dimension of rectangular air ducts MUST NOT
5. When sizing grille or louver, use the free area of opening. If
Requirements
1. Provideconfined space with sufficient air for proper combus-
2. Figure 6 illustrates how to provide combustion and ventila -
Gable Vent
Ventilated Attic
Top Above Insulation
when determining free area of openings.
MUST be no smaller than
1
/4² mesh.
be less than 3² .
free area is NOT stamped or marked on grill or louver, as­sume a 20% free area for wood and 60% for metal.
tion and ventilation of flue gases using horizontal or vertical ducts or openings.
tion air. A minimum of two permanent openings, one inlet and one outlet, are required.
Gas Vent
Outlet Air (1)
Soffit Vent
Inlet Air (1)
Furnace
Ventilated Crawl Space
Minimum One Inlet and One Outlet Air Supply is Required
Inlet Air Opening Must be Within12²(300mm) of floor
Outlet Air Opening Must be Within12²(300mm) of ceiling
(1) 1 Square Inch (6cm
(2) 1 Square Inch (6cm
May be in and Combination Shown
2
) per 4000 BTUH
2
) per 2000 BTUH
Inlet Air (1)
Furnace
Outlet Air (1)
3. Oneopening MUST be within 12² of the floor and the second opening within 12² of the ceiling.
4. Size openings and ducts per Tabl e 1.
5. Horizontal duct openings require 1 s quare inch of free area per 2,000 BTUH of combined input for all gas appliances in area (see Ta ble 1).
6. Vertical duct openings or openings directly to outside require 1 square inch of free area per 4,000 BTUH for combined input of all gas appliances in area (see Tabl e 1).
Soffit Vent
Inlet Air (2)
Outlet Air (1)
Inlet Air (1)
Furnace
Outlet Air (2)
Inlet Air (2)
One permanent opening, commencing within 12² of the top of the enclosure, shall be permitted where the equipment has clear­ances of at least 1² from the s ides and back and 6² from the front of the appliance. The opening shall directly communicate with the outdoors or s hall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communi­cate with the outdoors, and shall have a minimum free area of:
· 1 sq. in per 3000 Btu per hr. of the total input rating of all
equipment located in the enclosure, and
· Not less than the sum of the areas of all vent connectors in
the confined space.
8
441 01 2603 02
Table 1 Free Area
Minimum Free Area Required for Each Opening
BTUH
Input
Rating
50,000 25 sq. in. 12.5 sq. in. 4²
75,000 35.5 sq. in. 18.75 sq. in. 5²
100,000 50 sq. in. 25 sq. in. 6²
125,000 62.5 sq. in. 31.25 sq. in. 7²
Horizontal Duct
(sq. in./2,000 BTUH)
VerticalDuct or openings
to outside
(sq. in./4,000 BTUH)
Rd Duct
(sq. in.
/4,000
BTUH)
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000 ¸ 4,000) = 32.5 Sq. In. Vertical Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 ¸ 2,000) = 65 Sq. In. Horizontal
Adjoining rooms can be considered part of an unconfined area if there are no doors between rooms.
An attic or crawl space may be considered an unconfined space provided there are adequate ventilation openings directly to out­doors. Openings MUST remain open and NOT have any means of being closed off. Ventilation openings to outdoors MUST be at least 1 square i nch of free area per 4,000 BTUH of total input rat­ing for all gas appliances in area.
In unconfined spaces, infiltration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in section titled Con- fined Space Installation:
Unusually tight construction is defined as: Construction with
Unconfined Space Installation
!
Poison carbon monoxide gas hazard.
Most homes will require additional air.
An unconfined space or homes with tight construction may not have adequate air infiltration for proper combustion and ventilation of flue gases.
Failure to supply additional air by means of ventilation grilles or ducts could result in death and/or personal injury.
An unconfined space is defined as an area having a minimum vol­ume of 50 cubic feet per 1,000 Btuh total input rating for all gas appliances in area.
4. Gas Vent Installation
!
Poison carbon monoxide gas, fire and explosion hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in death, personal injury and/or property damage.
1 Wallsand ceilings exposed to the outside have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
2 Doors and openable windows are weather stripped and
3. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Some provincial codes and local municipalities require ventilation or make--up air be brought into the conditioned space as replace­ment air. Whichever method is used, the mixed return air temper­ature across the heat exchanger MUST not fall below 60°Forflue gases will condense in the heat exchanger. This will shorten the life of the heat exchanger and possibly void your warranty.
2. Do NOT vent furnace into any chimney serving an open fire­place or solid fuel burning appliance.
3. Use the same diameter Category I connector or pipe as per­mitted by the United States National Fuel Gas Code vent­ing tables.
4. Keep vertical Category I vent pipe or vent connector runs as short and direct as possible.
Install the vent in compliance with codes of the country having ju­risdiction, local codes or ordinances and these instructions.
These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure.
Category I Safe Venting Requirements
NOTE: The following instructions comply with the United States National Fuel Gas Code. Based on the highest input rate on the furnace rating plate.
1. If a Category I vent passes through an attic, any concealed space or floor, use ONLY Type B or Type L double wall vent pipe. If vent pipe passes through interior wall, use type B vent pipe with ventilated thimble ONLY.
441 01 2603 02
5. Vertical outdoor runs of type B or ANY single wall vent pipe below the roof line are NOT permitted.
6. Slope all horizontal runs up away from furnace a minimum of
1
/4² per foot.
7. Support all horizontal vent pipe every 6¢ using proper clamps and metal straps.
8. Check existing gas vent or chimney to ensure they meet clearances and local codes.
9. Thefurnace MUST be connected to a factory built chimney or vent complying with a recognized standard. Venting into a
masonry or concrete chimney is only permitted as out­lined in the United States National Fuel Gas Code vent ­ing tables or Masonry Chimney section in these instructions.
9
!
Poison carbon monoxide gas hazard.
If this furnace is replacing a previously common -­vented furnace, it may be necessary to resize the existing chimney liner or vent to prevent over sizing problems for the other remaining appliances(s). See codes of country having jurisdiction.
Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death.
Figure 7
Typical Gas Water Heater
8. If improper venting is observed, the cause MUST be cor­rected.
Vent Check
Draft HoodVent Pipe
Match
Venting and Combustion Air Check
NOTE: If this installation removes an existing furnace from a vent­ing system serving one or more other appliances, and to make sure there is adequate combustion air for all appliances, MAKE THE FOLLOWING CHECK.
1. Seal any unused openings in the venting system.
2. Visually inspect the venting system for proper size and hori­zontal pitch to ensure there is no blockage or restriction,leak­age, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all doors and windows and all doors between the space in which the appliance(s) remain­ing connected to the venting system are located and other spaces of the building.
4. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi­mum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
5. Follow the lighting instructions for each appliance being in­spected. Adjust thermostat so appliance(s) will operate con­tinuously.
6. Allow 5 minutes of main burner operation, then check for spillage at the draft hood relief opening of each appliance. Use the flame of a match or candle (Figure 7).
7. After it has been determined that each appliance vents prop­erly, return doors, windows, appliances etc. to their normal condition.
NOTE: If flame pulls towards draft hood, this indicates sufficient infiltration air.
Venting to Existing Masonry Chimney
NOTE: The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables.
Use the United States National Fuel Gas Code or NFGC Tablesto size the chimney or vent. Dedicated venting of one fan as- sisted furnace into any masonry chimney is restricted.The chimney must first be lined with either type B vent sized in accor­dance with tables 1 or 2 or a listed single wall, metal lining system, sized in accordance with the vent tables: or (Venting as outlined
with use of optional masonry chimney kit as applicable.) (See Section 5)
Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using United States National Fuel
Gas Code tables for dedicated v enting and United States Na­tional Fuel Gas Code tables for common venting with the maxi-
mum capacity reduced by 20% (0.80 X maximum capacity) and the minimum capacity as shown in the applicable table. Corru­gated metal vent systems installed with bends or offsets require additional reduction of 10% of the vent capacity for each 90° el­bow.
NOTE:Two(2)45° elbows are equivalent to one (1) 90° elbow.
Combined Venting into a Masonry Chimney
Venting into a masonry or concrete chimney is only per­mitted as outlined in the United States National Fuel Gas Code venting tables. Follow all safe venting requirements.
Note: See section “Masonry Chimney Venting”.
5. Horizontal Venting
Category I Furnaces With External Power Venters
In order to maintain a Category I classification of fan assisted fur­naces when vented horizontally with sidewall termination, a pow­er venter is REQUIRED to maintain a negative pressure in the venting system. Please consult the Fields Controls Co. or Tjern­lund Products, Inc. for power venters certified for use with our fur­naces.
Vent Termination
Venting Through a Non--Combustible and Combustible Wall
Consult External Power Venter manufacturer instructions.
10
CAUTION
It is the responsibility of the installer to properly termi­nate the vent and provide adequate shielding. This is essential in order to avoid water/ice damage to build­ing, shrubs and walk--ways.
441 01 2603 02
6. Masonry Chimney Venting with Optional K it Upflow/Horizontal
(USA ONLY)
Not recommended for Downflow Furnaces
Chimney Inspection
All masonry chimney construction must conform to Standard ANSI/NFPA211 and to any state or local codes applicable. The chimney must be in good condition and a complete investigation must be conducted prior to installation. If the inspection reveals damage or abnormal conditions, make necessary repairs or seek expert help. See “The Chimney Inspection Chart”. Measure area of tile--liner and exact height of chimney.
Connector Type
To reduce flue gas heat loss and the chance of condensate prob­lems, the vent connector must be double wall Type B vent.
Venting Restrictions for Chimney Types
Interior Chimney -- has no sides exposed to the outside below the roofline. All installations can be single furnace or common vented with another draft hood equipped Category I appliance.
Exterior Chimney -- has one or more sides exposed to the out­side below the roof line. All installations must be common vented only with another draft hood equipped Category I appliance.
!
Caution -- failure to follow these guide-
lines may cause severe property damage.
Optional Masonry Vent Kit Draft Hood Assy. Installation
NOTE: These instructions apply to the NTG3, NTN3, FBF & NBF series furnaces only.
1. Disconnect power and gas supply to furnace.
2. Remove louvered door. NTG3, NTN3, FBF & NBF Series furnaces -- Discard lou­vered door.
3. NTG3,NTN3,FBF & NBF may be installed upflow or horizon­tal position per furnace application. When installing NTG3,
(See Figure 8)
NTN3, FBF & NBF furnaces in a horizontal left hand applica­tion you will need to mount the pressure switch to the side of the cabinet.
4. NTG3,NTN3, FBF & NBF series furnaces -- Detach pressure switch from top panel by removing two screws. Set aside screws.
5. Detach field connect box from top panel by removing two screws. Set aside screws.
6. Remove four screws holding top panel to casing. Remove top panel. Discard top panel. Set screws aside.
7. Installdraft hood assy.tocasing using four screws previously set aside.
8. Attach field connect box to draft hood assy. using two screws previously set aside.
9. NTG3,NTN3, FBF & NBF Series furnaces -- Attach pressure switch to draft hood assy. using two screws previously set aside.
Vent Limit Switch Wiring (See Figure 8)
1. Locate wire harness assy. which is supplied with kit. Attach terminals on one end of wire harness assy. to vent limitswitch located on draft hood assy.
2. Locatefurnace’s main limit. Detach wire with insulated termi­nal from one side of main limit.
3. Route wire harness assy. from vent limit switch to main limit. Attach female terminal of wire harness assy.to vacated main limit terminal. Attach male terminal of wire harness assy. to insulated terminal of wire previously detached from main lim­it.
Completion of Installation
1. NTG3,NTN3, FBF & NBF Series furnaces -- Locate louvered door supplied with kit. Install on furnace.
2. Refer to installation instructions provided with furnace to put the furnace into operation.
Figure 8 Draft Hood Assembly Installation
Pressure switch (old location) on selected models
old top panel (discard)
wire harness
25--21-- 98a
Masonry chimney venting shall be approached as follows: Using Ta ble 1and Tabl e 2 in the masonry chimney draft hood kit instructions, the NFGC Z223.1--1992 or the GAMA Venting Tables.
441 01 2603 02
assembly
Pressure switch
draft hood assembly
Main
Limit
Left hand Horizontal
Pressure
switch
Location
Vent
Limit
Switch
new wire harness assy.
11
7. Gas Supply and Piping
!
Poison carbon monoxide g as, fire and explosion hazard.
Models designated for Natural Gas are to be used with Natural Gas ONLY, unless properly converted to use with LP gas.
Failure to follow these instructions can result in death, personal injury and/or property damage.
Gas Supply Requirements
· Use only the Type of gas approved for this furnace. See rat-
ing plate for approved gas type.
· Gas input must not exceed the rated input shown on the rat-
ing plate. Overfiring will result in failure of heat exchanger and cause dangerous operation.
· Do not allow minimum supply pressure to vary downward.
Doing so will decrease input to furnace. Refer to Ta ble 2 for Gas supply and manifold pressures.
Tab le 2 Gas Pressures
Gas
Typ e
Natural 7²
Propane 11²
Recommended Max. Min.
(1.7 kPa)
(2.7 kPa)
Supply Pressure
14²
(3.5 kPa)
14²
(3.5 kPa)
4.5²
(1.1 kPa)
11²
(2.7 kPa)
Manifold Pressure
3.5²
(0.9 kPa)
10²
(2.5 kPa)
Natural Gas Input Rating Check
The gas meter can be used to measure input to furnace. Rating is based on a natural gas BTU content of 1,000 BTU’s per cubic foot. Check with gas supplier for actual BTU content.
1. Turn OFF gas supply to all appliances other than furnace and start furnace.
2. Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution. Refer to Example. Note: If meter uses a 2 cubic foot dial, divide results (se­conds) by two.
Example
Natural Gas
BTU Content
1,000 3,600 48 75,000
3. Relight all appliances and ensure all pilots are operating.
No. of Seconds
Per Hour
1,000 x 3,600 ¸ 48 = 75,000 BTUH
Time Per Cubic Foot in Seconds
BTU Per
Hour
Orifice Sizing
NOTE: Factory sized orifices for natural and LP gas are listed in the furnace Technical Support manual.
Tab le 3
Gas
Typ e
Natural
Propane
Orifice Sizes (below 2000¢)
Manifold
Pressure
3.5² w. c.
0.9kPa w.c .
10² w.c.
2.5kPa w.c .
Specif-
Gravity
0.6
1.53 2500 54
ic
Heating Value
(BTU per
Cubic Ft.)
Orifice Size
(Drill #)
800 40
900 41
1000 42
1100 43
Operation Above 2000¢ Altitude
!
Fire, Explosion, Poison carbon monoxide gas haz­ard.
This conversion shall be done by a qualified ser ­vice agency in accordance with the Manufactur­er’s instructions and all applicable codes and re­quirements, or in the absence of local codes, the applicable national codes.
Failure to follow these instructions exactly can re­sult in death, personal injury and/or property dam­age.
These units may be used at full input rating when installed at alti­tudes up to 2000¢. When installed above 2000¢,theinputmustbe decreased 2%(natural) or 4%(LP) for each 1000¢ above sea level. This may be accomplished by a simple adjustment of manifold pressure or an orifice change, or a combination of a pressure ad­justment and an orifice change. The changes required depend on the installation altitude and the heating value of the fuel. Tabl e 4 & Tabl e 5 show the proper furnace manifold pressure and gas ori­fice size to achieve proper performance based on elevation above sea level for both natural gas and propane.
To use the natural gas table, first consult your local gas utility for the heating value of the gas supply. Select the heating v alue on the vertical border and follow across the table until the appropriate elevation for the installation is reached. The first value in the box at the intersection of the heating value and elevation will be the manifold pressure required. If a gas orifice change is also re­quired, the box is shaded. The required orifice size is shown at the bottom of the table.
Sea Level
High Altitude Input Rate = Nameplate x (Multiplier)
Input Rate
Elevation
2000¢ - 2999¢ 0.96 0.92
3000¢ - 3999¢ 0.94 0.88
4000¢ - 4999¢ 0.92 0.84
5000¢ - 5999¢ 0.90 0.80
6000¢ - 6999¢ 0.88 0.76
7000¢ - 7999¢ 0.86 0.72
High Altitude Multiplier
Natural LP Gas
Ensure furnace is equipped with the correct main burner orifices. Refer to Tabl e 3 for correct orifice size for a given heating value and specific gravity for natural and propane gas. Note that this chart is ONLY for installations below 2000¢ in altitude.
12
A High Altitude Kit is available for downflow which includes re­strictors, orifices and installation instructions.
Natural Gas -- 1160993 LP Gas -- 1160992
441 01 2603 02
MANIFOLD PRESSURE AND ORIFICE SIZE FOR HIGH ALTITUDE APPLICATIONS
Tab le 4 NATURAL GAS
MEAN ELEVATION FEET ABOVE SEA LEVEL
HEATING VALUE
BTU/CU. FT.
800 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc
850 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc
900 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.4² wc
950 3.5² wc 3.5² wc 3.5² wc 3.5² wc 3.3² wc 3.2² wc 3.1² wc
1000 3.5² wc 3.4² wc 3.3² wc 3.2² wc 3.0² wc 2.9² wc 2.8² wc
1050 3.2² wc 3.1² wc 3.0² wc 2.9² wc 2.7² wc 2.6² wc 2.5² wc
1100 2.9² wc 2.8² wc 2.7² wc 2.6² wc 2.5² wc 2.4² wc 2.3² wc
Orifice Size #42 #42 #42 #42 #42 #42 #42
0to
1999
2000 to
2999
3000 to
3999
4000 to
4999
5000 to
5999
6000 to
6999
7000 to
8000
Tab le 5
HEATING VALUE
BTU/CU. FT.
2500 10.0² wc 10.0² wc 9.4² wc 10.0² wc 9.8² wc 8.8² wc 7.9² wc
Orifice Size #54 #54 #54 #55 #55 #55 #55
PROPANE
0to
1999
2000 to
2999
MEAN ELEVATION FEET ABOVE SEA LEVEL
3000 to
3999
4000 to
4999
5000 to
5999
6000 to
6999
7000 to
8000
NOTE: NATURAL GAS DATA BASED ON 0.60 SPECIFIC GRAVITY. PROPANE DATA BASED ON 1.53 SPECIFIC GRAVITY. FOR FUELS WITH DIFFERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1 and CAN B149.
Changing Orifices
Figure 1 0
Manifold (Downflow)
1. After disconnecting power and gas supply to the furnace, re­move the access door, exposing the burner compartment.
Figure 9
Manifold (Upflow/Horizontal)
25- 23- 15
25--20--95
2. Disconnect gas line and pilot tubing from gas valve so man­ifold can be removed.
3. Disconnect wiring at gas valve. Be sure to note the proper location of any and all electrical wiring disconnected.
4. Remove the four (4) screws holding the manifold and gas valve to the manifold supports. Do not discard any screws. See Figure 9 or Figure 10.
5. Carefully remove the manifold assembly.
441 01 2603 02
6. Removethe orifices from the manifold and replace them with proper sized orifices. See Figure 11.
7. Tighten orifices so it is seated and gas tight. See Figure 11.
Figure 11
+1.5
29.3 mm
-- 1 . 1
Clearances
Measure from face of orifice to the back side of the manifold.
1.11²
1.21²
13
8. Reassembleallparts in reverse order as removed. Be sure to engage the main burner orifices in the proper opening in the burners.
9. After reassembling, turn gas on and check all joints for gas leaks using a soapy solution. All leaks must be repaired im­mediately.
Gas Piping Requirements
1. Installgas piping in accordance with local codes, or in the ab ­sence of local codes, the applicable national codes.
2. It is recommended that a manual shutoff valve be installed in the gas supply line outside the unit. Locate valve as close to the furnace as possible where it is readily accessible. Refer to Figure 12.
3. Use black iron or steel pipe and fittings or other pipe ap­proved by local code.
4. Use pipe thread compound which is resistant to natural and LP gases.
5. Install a drip leg no less than 3² long to trap dirt and moisture before it can enter gas valve.
6. Providea ly up stream of gas supply connection to furnace.
Figure 12
1
/8² inch plug for test gauge connection immediate-
Typical Gas Piping
11. Measure pipe length from gas meter or LP second stage reg­ulator.
!
Fire or explosion hazard.
The flexible corrugated m etal gas connector must be properly installed, cannot go through the side of the furnace, and can not be used inside the furnace.
Failure to properly install metal gas connector can result in death, bodily injury and/or property damage.
Additional LP Piping Requirements
· Have a licensed LP gas dealer make all connections at stor-
age tank and check all connections from tank to furnace.
· If copper tubing is used, it MUST comply with limitation set in
Local Codes, or in the absence of local codes, the gas codes of the country having jurisdiction.
· Two--stage regulation of LP gas is recommended.
Final Check
· Test all pipe for leaks.
· If orifices where changed, make sure they are checked for
leaks.
· During pressure testing of gas piping system, observe the
following:
a. If test pressure does not exceed1/2² PSIG, isolate the fur­nace by closing its individual manual shutoff valve.
b. If test pressure exceeds vidual shutoff valve must be disconnected from the gas sup­ply system.
· To check for leaks apply soap suds or a liquid detergent to
each joint. Bubbles forming indicate a leak.
· Do not use an open flame to test for gas leaks. Fire or explo-
sion could occur.
· Correct even the smallest leak at once.
1
/2² PSIG, the furnace and its indi-
7. Usetwo pipe wrenches when making connections to prevent gas valve from turning.
8. Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or ductwork.
9. Properly size gas pipe to handle combined appliance l oad or run gas pipe directly from gas meter or LP gas regulator.
10. Install correct pipe size for run length and furnace rating.
14
!
Fire or explosion hazard.
Liquid petroleum (LP) gas is heavier than air and will settle and remain in low areas and open depressions.
Thoroughly ventilate area and dissipate gas. Do NOT use a match or open flame to test for leaks, or attempt to start up furnace before thoroughly ventilating area.
An open flame or spark can result in death, personal injury and/or property damage.
441 01 2603 02
8. Electrical Wiring
!
Electrical shock hazard.
Turn OFF electrical power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
Failure to do so can result in death, personal injury and/or property damage.
Power Supply Wiring
The furnace MUST be electrically wired and grounded in accor­dance with local codes, or in the absence of local codes, the appli­cable national codes.
Field wiring connections must be made inside the furnace con­nection box. A suitable strain relief should be used at the point the wires exit the furnace casing.
Copper conductors shall be used. Line voltage wires should be sized for the input amps stated on the rating plate. Furnace must be connected to its own separate circuit.
Thermostat
Thermostat location has an important effect on the operation of the unit. Follow instructions included with thermostat for correct mounting and wiring.
Low voltage connections to furnace must be made on terminal board to fan control. (See Figure 13 or Figure 1 4 )
If cooling is used, the Y from the thermostat must be connected to the c ontrol board Y to energize cooling blower speed.*
Set thermostat heat anticipator in accordance with the Technical Support Manual.
Figure 13
Figure 14
Electrical Connections (Upflow/Horizontal)
25--22--30
Electrical Connections (Downflow)
Optional Equipment
All wiring from furnace to optional equipment MUST conform to local codes or, in the absence of local codes, the applicable na­tional codes. Install wiring in accordance with manufacturer’s instructions.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner connection.
CAUTION
Do NOT exceed 115V/0.8 amp. maximum current load for both the EAC terminal and the HUM terminal com­bined.
NOTE: The humidifier will be powered when the furnace is fired
and the circulating air blower comes on. The electronic air cleaner will be powered anytime the thermostat calls for air movement. However,the electronic air cleaner is NOT energized during c on­tinuous fan operation controlled by the electronic fan control.
2 5 -- 2 1 -- 0 5 b
Control Center Fuse
The 24V circuit contains a 5--amp, automotive--type fuse located on control center. (See Figure 15) Any electrical shorts of 24V wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (5 amp.)
441 01 2603 02
15
Loading...
+ 32 hidden pages