International Comfort Products Corporation NASA001WS Installation Instructions Manual

INSTALLATION INSTRUCTIONS
Winter Start Control
NASA001WS
These instructions must be read and understood completely before attempting installation.
Safety Considerations:
Installing and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained personnel should install or service air conditioning equipment.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAU­TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only used on product labels to signify an immediate haz­ard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and through­out this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or opera­tion.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
INTRODUCTION
This instruction covers the installation of Winter Start Control Part No. NASA001WS on splitsystem air conditioners.
The Winter Start Control prevents nuisance tripping of the lowpressure switch when air conditioners are operated in cold (winter) temperatures.
!
ELECTRICAL SHOCK HAZARD
Failure to turn off electric power could result in personal injury or death.
Before installing or servicing system, turn off main power to the system. There may be more than one disconnect switch, including accessory heater(s).
WARNING
482 01 5180 00 January 2006
INSTALLATION INSTRUCTIONS Winter Start Control
DESCRIPTION AND USAGE
The Winter Start Control must be used where low evaporator temperatures or nuisance tripping of lowpressure switch may be encountered. The Winter Start Control bypasses the lowpressure switch for the first 3 minutes of operation during each cycle.
Included in the kit are:
TimeDelay Relay (TDR) CESO13006200 1 Installation Instructions 1
INSTALLATION
Mount winter start control inside control box. Wire the timedelay relay in parallel with the lowpressure switch (refer to Figure 1.)
Figure 1 Winter Start Control Wiring
T1 T3
L
NOTE: There will be a delay of approximately 3 minutes before low−pressure switch becomes part of the control circuit.
WINTER START CONTROL
T2
C
LPS C L
LPS
LOWPRESSURE SWITCH CONTACTOR COIL LOGIC TIME DELAY
FACTORY WIRING FIELD WIRING
A98527
2 482 01 5180 00