International Comfort Products NXA6, N4A3, C4A3, H4A3, T4A3 Installation Manual

...
INSTALLATION INSTRUCTIONS
R410A Split System Air Conditioner
N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2...............................
Safety Considerations 2...........................
Location 2.......................................
Clearances 2 3................................
Unit Support 4...................................
Refrigeration System 5 − 9.......................
Electrical Wiring 10 11..........................
Startup Procedure 12............................
Refrigerant Charge 12 − 15.......................
Sequence of Operation 16.........................
Troubleshooting 16...............................
Maintenance 16..................................
Comfort Alertt Diagnostics Codes 17..............
R410A Quick Reference Guide 18.................
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is in­tended for use by a qualified service technician fa­miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
421 01 5103 00 May 2010
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual instructions packaged with the kit or accessory when installing.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material such as a wet rag during brazing operations. Keep a fire extinguisher available. Consult local codes and the National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
company immediately and file a concealed damage claim.
!
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device. Lock out and tag switch with a suitable warning label.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage
R410A systems operate at higher pressures than R22 systems. When working with R410A sys­tems, use only service equipment and replace­ment components specifically rated or approved for R410A service.
WARNING
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
CLEARANCES
Nominal minimum clearances are 48 inches (1.2m) above unit for discharge air and 18 inches (457mm) on each side of the coil for intake air. Clearance on any one side of the coil (normally between unit and structure) may be reduced to 6 inches (152mm). Nominal minimum clearances are based on a solid parallel object such as a wall or roof overhang.
The clearance may be reduced for a single object with small surface area, such as the end of a wall, outside corner of a wall, fence section, post, etc. As a general rule, the minimum clearance from the unit should equal the width of the object. For example, a 6 inch (152mm) fence post should be a minimum of 6 inches (152mm) from the unit.
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCES section of this document).
Rooftop installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
Do not install unit under roof overhangs unless gutters are present. A minimum vertical clearance of 48 inches (1.2m) is required to the overhang.
Inside corner locations on single story structures require evaluation. Large overhanging soffits may cause air recirculation in a corner area even though recommended minimum clearances are maintained. As a guide, locate the unit far enough out so that half of the discharge grille is out from under the soffit.
When placing two or more units sidebyside, provide a minimum of 18 inches (457mm) between units.
Provide minimum service clearance of 24 inches (610mm) from control box corner and side service panel.
Refer to Figure 1.
2 421 01 5103 00
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
Figure 1 Clearances (various examples)
24”
(610mm)
Service
Wall
6”
(152mm)
18”
(457mm)
Wall
6”
(152mm)
18”
(457mm)
18”
(457mm)
Wall
24”
(610mm)
Service
Wall
6”
(152mm)
18”
(457mm)
Wall
6”
(152mm)
24”
(610mm)
Service
18”
(457mm)
24”
(610mm)
Service
4”
(102mm)
(457mm)
18”
(152mm)
18”
(102mm)
wide fence
Wall
24”
(610mm)
Service
4”
24”
(610mm)
Service
18”
(457mm)
18”
(457mm)
6”
(152mm)
6”
(152mm)
Post
24”
(610mm)
Service
18”
(457mm)
421 01 5103 00 3
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
UNIT SUPPORT
NOTE: Unit must be level | 2 degrees {a inch rise or fall
per foot of run (10mm rise or fall per 305 mm of run) }or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches (152mm) above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are selfsupporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane holddown details and the P.E. (Professional Engineer) certification, when required.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage.
Inadequate unit support may cause excessive vibration, noise, and/or stress on the refrigerant lines, leading to refrigerant line failure.
Figure 2 Tie Down Knockouts
a(10mm) dia. Tie Down Knockouts In Base Pan (2 places)
A
Base Pan Width
View From Top
Base
Pan
Depth
C
B
Inches (mm)
Base Pan
Width x Depth
@# ~ @#
(584 x 584)
@%n ~ @%n
(652 x 652)
#!8 ~ #!8
(791 x 791)
#$, ~ #$,
(887 x 887)
Tie Down
Knockouts
A B C
&w
(197)$v(113)!*(457)
(z
(230)$v(113)
(z
(230)^2(165)
(z
(230)^2(165)
@!4
(540)
@$s
(625)
@*v
(722)
Minimum
Mounting Pad
Dimensions
@# X~ @#
(584 x 584)
@^ X~ @^
(660 x 660)
#!2 ~ #!2
(800 x 800)
#% ~ #%
(889 x 889)
4 421 01 5103 00
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
R410A outdoor units can only be used with R410A specific indoor coils. If there is a refrigerant mis−match, consult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device or Piston with Teflon ring metering device. If any other type of metering device is installed on the indoor coil, consult the indoor coil manufacturer to determine if a TXV conversion kit is available.
Installing with TXV
When installing a TXV on an indoor coil, follow the instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
Figure 3 Typical TXV Installation
Installing with Indoor Piston cooling operation.
Check piston size shipped with indoor unit to see if it matches required indoor piston size.
If it does not match, replace indoor piston with correct piston size. (Indoor pistons are shipped with some outdoor models in the accessory bag and are only qualified for Piston fan coils.)
Example fan coils with piston: FEM4P, FSM4P, FSU4P (12 thru 4 ton).
See Figure 4. When changing indoor piston, use a back−up wrench.
Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ftlbs.The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Figure 4 Indoor (cooling) Piston
BRASS
HEX NUT
TEFLON SEAL
TEFLON RING
DISTRIBUTOR
EQUALIZER TUBE
SENSING BULB
TXV
10 O’Clock
7/8
2 O’Clock
SUCTION TUBE
IN. OD & SMALLER
INDOOR
COIL
STRAP
SUCTION TUBE
LIQUID TUBE
SENSING BULB
PISTON
FLOW IN COOLING
PISTON RETAINER
STRAINER
BRASS HEX BODY
L10S017
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation. If using a TXV in conjunction with a singlephase reciprocat­ing compressor, a compressor start capacitor and relay are required. Consult outdoor unit presale literature for start as­sist kit part number.
CAUTION
421 01 5103 00 5
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m). A crankcase heater must be used when the refrigerant
line length exceeds 80 feet (24.4m). If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline for instructions.
When the outdoor unit is higher than the indoor coil, the vertical separation must not exceed 100 feet (30m).
When the outdoor unit is lower than the indoor coil, the vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
!
WARNING
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
Relieve pressure and recover all refrigerant be­fore servicing existing equipment, and before fi­nal unit disposal. Use all service ports and open all flowcontrol devices, including solenoid valves.
C. ROUTING AND SUSPENDING REFRIGERANT
LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or when routed through an underground raceway.
When routing refrigerant lines through a foundation or wall, do not allow refrigerant lines to come in direct contact with the building structure. Make openings large enough so that lines can be wrapped with extra insulation. Fill all gaps with RTV caulk. This will prevent noise transmission between the tubing and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork. Use insulated or suspension type hangers. Metal straps must be at least 1” (25mm) wide to avoid cutting into the tube insulation. Keep the liquid and suction lines separate. Refer to Figure 5.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in im­proper product operation.
Do not leave system open to atmosphere any lon­ger than absolutely required for installation. Inter­nal system components especially refrigerant oils are extremely susceptible to moisture con­tamination. Keep ends of tubing sealed during installation until the last possible moment.
Figure 5 Routing and Suspending Refrigerant Lines
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL SUSPENSION
LIQUID TUBE
SUCTION TUBE
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25mm)
MIN
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
6 421 01 5103 00