The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only
used on product labels to signify an immediate hazard. The signal words WARNING,CAUTION, and
NOTE will be used on product labels and throughout this manual and other manuals that may apply
to the product.
DANGER− Immediate hazards which will result in
severe personal injury or death.
WARNING − Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
!
The signal word CAUTION is used throughout this
manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
Model Number Identification17 − 18................
R4A318A*KA100 WCA3184GKA1
R4A324A*KA100 WCA3244GKA1
R4A330A*KA100 WCA3304GKA1
R4A336A*KB100 WCA3364GKA1
R4A342A*KB100 WCA3424GKA1
R4A348A*KB100 WCA3484GKA1
R4A360A*KB100 WCA3604GKA1
* = A for standard inlet grille,
G for inlet grille with 3/8” (10mm) tight−wire spacing
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning
could result in equipment malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with
the proper tools and test instruments.
Installation must conform with local building
codes and with the National Electrical Code
NFPA70 current edition or Canadian Electrical
Code Part 1 CSA C.22.1.
WARNING
421 04 6001 00 April 2010
2421 04 6001 00
TECHNICAL SUPPORT MANUALSplit System Air Conditioner: R4A3, WCA3**4
Model Sizes: 18, 24, 30, 36, 42, 48, 60
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F).
6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead.
8. When start capacitor and relay are installed, start thermistor (PTC) is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting.
14. Wire not present if HPS, LPS or CTD are used.
335620−101 REV. B
TECHNICAL SUPPORT MANUALSplit System Air Conditioner: R4A3, WCA3**4
R−410A CHARGING CHART
Rating Plate (required) Subcooling Temperature ° F (° C)
† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set.
†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 ° F db
^System amps are total of indoor and outdoor amps.
‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the
formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below.
(Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)
† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 ° F db
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
^System amps are total of indoor and outdoor amps.
‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the
formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below.
(Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)
TECHNICAL SUPPORT MANUALSplit System Air Conditioner: R4A3, WCA3**4
Sensible Capacity at Indoor db LOWER than 80 ° F = ( MBh x S/T ) −
Sensible Capacity at Indoor db HIGHER than 80 ° F = ( MBh x S/T ) +
( 80 − Indoor db ) x 835 x Indoor CFM
(
( Indoor db − 80 ) x 835 x Indoor CFM
(
1000
1000
)
)
6421 04 6001 00
† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set.
†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 ° F db
^System amps are total of indoor and outdoor amps.
‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the
formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below.
(Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)