distributor or branch for information or assistance. The qualified
installer or agency must use factory−authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety−alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety−alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury
or equipment damage.
R−410A refrigerant systems operate at higher pressures than
standard R−22 systems. Do not use R−22 service equipment
or components on R−410A refrigerant equipment.
!
!
IMPORTANT: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
Information in these installation instructions pertains only to
CVH8, HVH8, TVH8 series units.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
Specifications subject to change without notice.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
WARNING
428 01 5700 00 10/19/15
Indoor Thermostat Control Options
Model
CVH8, HVH8,
TVH8
NOTE: TSTAT0201CW Communicating Wi-Fi wall control. Non Wi-Fi
cannot be used.
All trademarks are the property of their respective owners. Wi-Fi® is a regis
tered trademark of Wi-Fi Alliance Corporation.
* Version 5.0 software or newer required.
** Using standard HP thermostat limits functionality of system.
Observer® Wall
Control
Yes*Yes**
!
WARNING
Standard
HP Thermostat
ELECTRICAL HAZARD − HIGH VOLTAGE!
Failure to follow this warning could result in personal injury
or death.
Electrical components may hold charge. DO NOT remove
control box cover for 2 minutes after power has been
removed from unit.
PRIOR TO TOUCHING ELECTRICAL COMPONENTS:
Verify zero (0) voltage at inverter connections shown on
inverter cover.
!
WARNING
8. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with tubing (see Fig. 1).
9. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
10. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 1.)
11. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
12. If these installation recommendations were not followed,
gas pulsation may be transmitted through improperly
mounted line sets. In this case, an external vapor line muffler accessory (part no. 1187979) is available to minimize
noise due to gas pulsations.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
If proper lineset routing techniques are not followed, variable
speed systems can be susceptible to lineset transmitted noise
inside the dwelling and, in extreme cases, tubing breakage.
OUTDOOR WALLINDOOR WALL
CAULK
LIQUID TUBE
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
Inverter Cover
IMPORTANT: The inverter cover should NEVER be removed
because there is no reason to remove the inverter cover to access
the inverter. The inverter has limited serviceability. Refer to
Service Manual for details on field replaceable parts. A
replacement cover is provided with a replacement inverter.
INSTALLATION RECOMMENDATIONS
In some cases noise in the living area has been traced to gas
pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. In noise sensitive applications (such as bedrooms), when a
lineset is mounted to ceiling joists or floor joists, the outdoor unit must be located at least 10 ft (3.05 m) away. If
this is not possible, create a line set configuration with
enough bends to provide 10 ft (3.05 m) of total line set
length outside the dwelling
3. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
4. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
5. Leave some slack between structure and unit to absorb vibration.
6. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon−based caulk (see Fig.
1).
7. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
INSULATION
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25.4 mm)
MIN
THROUGH THE WALL
SUSPENSION
SUCTION TUBE
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
A07588
Fig. 1 − Connecting Tubing Installation
The outdoor unit contains the correct amount of refrigerant charge
for operation with AHRI rated indoor units when connected by 15
ft (4.57 m) of field−supplied or factory accessory tubing.
See Step 12. on page 8 for proper charging procedure.
IMPORTANT: Liquid−line size is 3/8−in. OD for all CVH8,
HVH8, TVH8 applications. The maximum allowable equivalent
line set length is 100 ft. (30.5 m).
IMPORTANT: Always install the factory−supplied liquid−line
filter drier. Obtain replacement filter driers from your distributor or
branch.
INSTALLATION
Specifications for this unit in residential new construction market
require the outdoor unit, indoor unit (including metering device),
refrigerant tubing sets, and filter drier listed in pre−sale literature.
There can be no deviation. Consult the Service Manual – Air
Conditioners and Heat Pumps Using R−410A Refrigerant to obtain
required unit changes for specific applications and for R−22
retrofit.
Step 1 — Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage
unit.
2428 01 5700 00
Specifications subject to change without notice.
Inspect Equipment
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Step 2 — Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE
(Professional Engineer) Certification, if required.
On rooftop applications, mount on level platform or frame. Place
unit above a load−bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult the Service Manual − Residential Split
System Air Conditioners and Heat Pumps Using R−410A
Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ±2° (±3/8 in./ft,±9.5 mm/m.)
per compressor manufacturer specifications.
Step 3 — Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above
unit. For proper airflow, a 6−in. (152.4 mm) clearance on 1 side of
unit and 12−in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between
units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above
roof surface.
3/8-in. (9.53 mm) Dia.
Tie-down Knockouts in
Basepan(2) Places
Step 4 — Operating Ambient
The minimum outdoor operating ambient in cooling mode is 40_F
(4.4_C) with Observer
non−communicating systems. The maximum outdoor operating
ambient in cooling mode is 115_F (46.1_C). Compressor
protections will prevent cooling mode operation below minimum
ambient temperature range. The system may operate in cooling up
to 125_F (52_C) (52C) with significant reduced capacity cutback
above 115_F (46.1_C). Refer to Product Data “Detailed Cooling
Capacity” table. Low ambient cooling operation is not currently
available. The maximum heating operation ambient is 66_F
(18.9_C). Compressor protections will prevent starting below 10_F
(−12.2_C) and operation below 2_F (−16.7_C).
®
Wall Control, 55_F (12.8_C) with
Step 5 — Elevate Unit
Elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate
drainage of unit.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not allow water and/or ice to build up in base pan.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Locate the unit in such a way that it is stable in all
circumstances including adverse weather conditions.
CAUTION
CAUTION
Step 6 — Make Piping Connections
UNIT BASE PAN
Dimension in. (mm)
23 X 23
(596 X 596)
31.2 X 31.2
(792 X 792)
Fig. 2 − Tie−down Knockout Locations
View From Top
A05177
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
ABC
7-13/16 (198)4-7/16 (102)18-1/8 (458)
9-1/8 (232)6-9/16 (167)24-11/16 (627)
!
PERSONAL INJURY AND UNIT DAMAGE
HAZARD
Failure to follow this warning could result in personal injury or
death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal. Use all service ports and open all
flow−control devices, including solenoid valves.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not leave system open to atmosphere any longer than
minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep
ends of tubing sealed during installation.
WARNING
CAUTION
428 01 5700 003
Specifications subject to change without notice.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4
mm) vertical rise at service valve. Refrigerant tubing lengths
up to 36 in. (914.4 mm) may be buried without further
special consideration. Do not bury lines longer than 36 in.
(914.4 mm).
CAUTION
Outdoor units may be connected to indoor section using accessory
tubing package or field−supplied refrigerant grade tubing of correct
size and condition. For tubing requirements between 80 − 100 ft.
(24.38 − 30.48 m), capacity and performance losses can occur.
Follow the pipe sizing recommendations in the CVH8, HVH8,
TVH8 Product data to manage these losses. This unit shall not be
installed with greater than 100 ft (30.48 m) of equivalent line
length.
Refer to Table 1 for field tubing diameters. No additional
accessories are required for line lengths between 80 − 100 ft. (24.4
− 30.5 m) on this product.
Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)
UNIT SIZE
24 3/8 3/8 3/4 3/4 5/8
25 3/8 3/8 3/4 7/8 5/8
36, 37 3/8 3/8 3/4 7/8 5/8
48 3/8 3/8 7/8(1-1/8) 3/4
{ Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length line sets.
Notes:
1. Do not apply capillary tube indoor coils to these units.
60 3/8 3/8 7/8(1-1/8) 3/4
Connection
Diameter
Outdoor Unit Connected to Factory−Approved Indoor
Unit
Outdoor unit contains correct system refrigerant charge for
operation with factory−approved, AHRI−rated indoor units when
connected by 15 ft. (4.57 m) of field−supplied or factory−accessory
tubing, and factory−supplied filter drier. Check refrigerant charge
for maximum efficiency.
NOTE: If the indoor furnace coil width is more than the furnace
casing width, refer to the indoor coil Installation Instructions for
transition requirements.
Install Liquid−Line Filter Drier Indoor
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5−in. (127 mm) liquid tube to the indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
LIQUIDVAPOR
Tube
Diameter
Connection
Diameter
Refrigerant Tubing connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service valves
(see Table 1).
No Installation of Adapter Tube
Although it is a heat pump this unit has a standard AC liquid
service valve. An electronic expansion valve (EXV) inside the unit
serves as the heating expansion device.
Sweat Connections
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Use a brazing shield
S Wrap service valves with wet cloth or heat sink material.
CAUTION
†
Max (Rated)
Diameter
Minimum
Tube Diameter
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage or
improper operation.
Installation of filter drier in liquid line is required.
Fig. 3 − Liquid−Line Filter Drier
CAUTION
A05227
Use refrigerant grade tubing. Service valves are closed from factory
and ready for brazing. After wrapping service valve with a wet
cloth, braze sweat connections using industry accepted methods
and materials. Consult local code requirements. Refrigerant tubing
and indoor coil are now ready for leak testing. This check should
include all field and factory joints.
Evacuate Refrigerant Tubing and Indoor Coil
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used. See Service Manual for
triple evacuation method. Always break a vacuum with dry
nitrogen prior to opening the refrigerant system for servicing.
CAUTION
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gauge capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 4)
4428 01 5700 00
Specifications subject to change without notice.
5000
4500
4000
3500
LEAK IN
SYSTEM
3000
2500
2000
MICRONS
1500
1000
500
01234567
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
A95424
MINUTES
A95424
Fig. 4 − Deep Vacuum Graph
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.
Step 7 — Make Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not supply power to unit with compressor terminal box
cover removed.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440−14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
control box.
!
WARNING
WARNING
Connect Ground and Power Wires
Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 5.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
GROUND
LUG
TERMINAL
BLOCK
A14028
Fig. 5 − Line Power Connections
Connect Control Wiring−Observer® Wall
Connect four wires from Observer to communicating furnace / fan
coil with communicating motor capability. Only two wires from
furnace / fan coil DX+ (GR), DX− (YL) are connected to the
outside inverter wiring GR (DX+), YL (DX−) (see Fig. 6).
Connect C (WT) is recommended if wires are available (see Fig.
6). This will reduce the chance of communication issues. Unused
low voltage wires should be bundled together and terminated with
a wire nut at each end. The end nearest indoor coil should be
connected to C terminal.
IMPORTANT: This system requires the power supplied to the
outdoor unit, and the indoor unit, for the wall control to
communicate with the outdoor unit.
Wall Control
R
C
DXï
DX+
Humidifier
C
24vac
Furnace or Fan Coil
R
C
DXï
DX+
OAT
RYOWC
HUM
’R’ not required
Shielded cable
’C’ connection optional
Fig. 6 − Communicating Furnace or Fan Coil Wiring with
Communicating Variable Speed HP
Outdoor Unit
RD
WT
YL
GR
A150636
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault
should occur. The ground may consist of electrical wire or
metal conduit when installed in accordance with existing
electrical codes.
Connect Control Wiring− Non−Communicating
Six wires are required when connecting CVH8, HVH8, TVH8
models to non−communicating 2−stage thermostats. Use Fig. 7
For required connections. Unit is configured by factory for
Observer communicating control. To wire unit for
non−communicating control, disconnect the DX+ = GN and DX−
= YL wires from green plug and connect appropriate wires to low
voltage terminal block. Use wire nuts to attach thermostat wire to
low voltage choke harness (LVCH).
428 01 5700 005
Specifications subject to change without notice.
General Information
Use 18−20 solid AWG color−coded, insulated (355C minimum)
wire for low voltage control wires. All wiring must be NEC Class
2 and must be separated from incoming power leads.
Installations using greater than 200 feet of low voltage wiring
should consult the Evolution wall control manual for additional
guidelines regarding daisy chaining wiring method and terminating
resistors.
Never route control wiring in parallel to high voltage power wires
when possible as electrical noise may transfer and generate
nuisance fault codes. Where low voltage control and high voltage
wires must cross paths, do so at perpendicular angles to eliminate
transferred noise. If further communication issues exist, consider
using shielded low voltage wires and only connect shielding to C
terminal at end nearest indoor coil.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power requirement of system accessories
external to the OD unit. The outdoor unit has its own transformer
power.
Use No. 18 AWG or larger color−coded, insulated (35°C
minimum) wire for low voltage control wires.
All wiring must be NEC Class 2 and must be separated from
incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power requirement of system accessories
external to the OD unit. The outdoor unit has its own transformer
power.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to
ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.
Ensure that high and low voltage is separated where possible, to
minimize induced noise from VFD to communication wiring.
Indoor Control
RVS Cooling
Heat/Cool
Stage 1
Heat Stage 3
Heat/Cool
Stage 2
Fan
24 VAC Hot
Dehumidify
24 VAC Comm
Humidify
RVS Heating
Outdoor
O/W2
Y1/W2
W/W1
Y/Y2
DHUM
HUM
Fan Coil
O
Y1
W1
Remove J2 Jumper
s
s
For Heat Staging
W2
G
R
C
B
S1
S2
Y/Y2
G
R
DH
C
Humidifier
(24 VAC)
Outdoor
Sensor
Heat Pump
O
Y1
W1
J1 Jumper on Control Board
Jumper Wire
Requred for
Single Stage
Y2
R
C
A150198
Indoor Control
W2
Y1
W1
Y2
G
R
H
C
L
O/B
OD
GND
Variable Speed
Furnace
W2
Y1
W/W1
Y/Y2
G
R
DHUM
COM
HUM
OUTDOOR
SENSOR
Heat Pump
O
Y1
W1
Y2
R
C
Jumper Wire
Requred for
Single Stage
A150199
Fig. 7 − Low Voltage Wiring (Non−Communicating)
Step 8 — Compressor Crankcase Heater
This compressor has an internal crankcase heater. Furnish
power to the unit a minimum of 24 hr before starting the unit
for the first time.
Upon initial start−up of unit, status code 68 will be generated and
system will operate at stage 2 for 11 minutes. This operation is
important to system reliability and cannot be bypassed. Each time
high voltage is removed and reapplied this behavior will be
repeated.
To furnish power to heater only, set thermostat to OFF and close
electrical disconnect to outdoor unit.
Power is not required to the indoor unit or Wall Control for proper
operation of heater. Crankcase heater will be intelligently
energized as needed between operations, even when the Wall
Control or thermostat and indoor unit is not installed, as long as
there is power to the outdoor unit.
Airflow Setup for Observer® Wall Control
Furnace or FCM4X Fan Coil (communicating)
This system can only be installed with communicating indoor and
Observer Wall Control TSTAT0201CW with Version 5.0 or higher
software or newer. When using an Observer Wall Control, airflow
is automatically selected based on equipment size. The user has the
option of selecting Comfort, Efficiency and Max airflow for
Heating and/or Cooling modes. These should be selected based on
balance between the homeowner’s comfort and energy
consumption expectations. See Observer Wall Control Installation
Instructions for additional available adjustments.
Due to using a communicating control with the fan coil or the
furnace, dip switch adjustments are not necessary. The outdoor
unit configuration and the indoor airflows are determined by
communicating control setup.
Airflow Setup for Non−communicating Fan Coil
The system can be installed with a standard 2−stage heat pump
thermostat and FVM4X fan coil without additional accessories.
Select appropriate unit size on fan coil Easy select board.
Airflow Setup for Non−communicating Furnaces
For installations with non−communicating furnaces, set airflows to
350−400 cfm/nominal ton in high stage and 70−80 percent of high
stage airflow in low stage.
Step 9 — Install Accessories
No refrigeration circuit accessories are required or are available for
installation within the unit. External to the unit, the same
accessories such as support feet, wind baffle etc., available on other
units, can also be used on this line of product. For models utilizing
23 inch x 23 inch base pans, it is recommended to use 5 support
feet in order to fully support unit. See Fig. 8. Refer to the
6428 01 5700 00
Specifications subject to change without notice.
individual Installation Instructions packaged with kits or
accessories when installing.
Fig. 8 − Recommended Support Feet Location
(for 23” x 23” basepan)
A14008
Step 10 — Start−Up
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in minor personal
injury, equipment damage or improper operation.
Observe the following:
1.Do not overcharge system with refrigerant.
2.Do not operate unit in a vacuum or at negative pressure.
3.Do not disable low pressure transducer or system safety
devices such as discharge thermistor or the high pressure
switch.
4.Dome temperatures may be hot.
5.Discharge thermistor is engaged tight on the discharge tube.
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when
handling refrigerant.
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
damage.
Federal regulations require that you do not vent refrigerant to
the atmosphere. Recover during system repair or final unit
disposal.
CAUTION
CAUTION
CAUTION
Step 11 — System Functions and Sequence of
Operation
The CVH8, HVH8, TVH8 models utilize either Observer® Wall
Control or conventional HP thermostat. When using Wall Control
controls, a call for cooling will energize the outdoor fan and
compressor to run at lowest cooling demand. If this does not satisfy
cooling demand, the system will ramp up in stages until it satisfies
the demand. After coping with the higher demand, the unit returns
to lower capacity operation until the demand is satisfied or until an
increase in demand. When using a conventional thermostat, the
thermostat controls the staging of outdoor unit.
When all demand is satisfied, the compressor will shut off. As the
unit operates at lower capacity, system vapor (suction) pressure will
428 01 5700 007
Specifications subject to change without notice.
be higher than it is during a standard single−stage system operation
or during a higher capacity operation.
The Observer Wall Control displays the operation mode and fault
codes as specified in the troubleshooting section. See Table 6 for
codes and definitions.
The conventional thermostat inputs are designed to work with most
indoor units. See AHRI for approved combinations. Connections
are Y/Y2, Y1, O, R, W, and C. Depending on thermostat and
indoor unit, the system will operate at 1 or 2 capacities in heating
or cooling mode.
NOTE: Only one code will be displayed on the outdoor unit
control board (the most recent, with the highest priority). The
latest codes are stored and can be accessed via the Observer Wall
Control.
Upon a call for cooling through the Observer Wall Control (or the
Y1 and/or Y2 connections in a non−communicating system), the
Application Operation Control (AOC) board (see Fig. 22) will
open the EXV to the fully open position. For heating, the AOC
board will open the EXV to a preset position, depending upon the
conditions. Based upon the indoor space demand and the outdoor
conditions, the Observer Wall Control will then request a
compressor speed and outdoor fan motor speed.
If the conditions are correct for operation, the control board will
allow the requested operation to begin, but if the control board
determines that the conditions are not correct, the board will decide
what other operation nearing that condition is acceptable. The
inverter Motor Operational Control (MOC) then outputs the
three−phase PWM signal and frequency that gently ramps the
compressor speed up to stage 2, and then will adjust to the
demanded speed. The gentle ramp−up results in no locked rotor
amps to the compressor motor. The unit 0 for compressor LRA will
be stamped N/A (not applicable).
During operation, the AOC monitors itself and the compressor
operation along with the system pressures and temperatures. The
MOC board monitors the temperature, current and operational
status of the compressor, OD fan and the inverter itself. During
operation, the compressor speed will be adjusted to meet the
changes to the demand.
When the demand is satisfied, the inverter will ramp−down the
compressor speed and stop. The EXV will step down to the
completely closed position.
When the compressor stops, a 3.5 minute Time Guard period is
activated which is followed by opening of the PEV valve for 150
seconds to equalize the refrigerant pressure difference between the
high and low sides of the compressor. Upon equalizing the
refrigerant pressure, and an additional 15 seconds of the Time
Guard period, the compressor will be ready for the next operational
demand.
If there is a power cycle, the Pressure Equalizer Valve (PEV) will
open for 150 seconds before the compressor start−up. Opening the
PEV valve returns the discharge gas directly back to the suction
side of the compressor. This is done in either cooling or heating
mode so that the rotary compressor will start with a very low
pressure differential.
The 3.5 minute Time Guard can be bypassed by momentarily
shorting the Forced Defrost pins. Only the 3.5 minute time delay
can be bypassed. Because it is important for compressor reliability,
the 150−second PEV delay cannot be bypassed.
Crankcase Heater Operation
This unit has an internal crankcase heater that will be energized
during the off cycle and is intelligently demanded by the system to
prevent the compressor from being the coldest part of the system
thus enhancing the reliability. The crankcase heater will function
as needed any time the outdoor unit is powered. The indoor unit
and Observer Wall Control do not need to be installed for the
crankcase heater to operate properly.
The compressor windings will occasionally be energized during
the OFF cycle (depending on the length of the OFF cycle) to start
the stator heat operation, thus maintaining a sump temperature that
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.