International Comfort Products G9MAC0601714, G9MAC0602120, G9MAC0801714, G9MAC0802120, G9MAC1002122 Installation Manual

...
INSTALLATION INSTRUCTIONS
Modulating Gas Valve, Variable Speed Motor
35” Tall High Efficiency Condensing Gas Furnace
(F/G)9MAC
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
Safetyalert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 3..............................
INTRODUCTION 4.........................................
CODES AND STANDARDS 4................................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 5.......
DIMENSIONS 6...........................................
LOCATION 7..............................................
LOCATION RELATIVE TO COOLING EQUIPMENT 9...........
AIR FOR COMBUSTION AND VENTILATION 9................
CONDENSATE TRAP 10....................................
INSTALLATION 17..........................................
UPFLOW INSTALLATION 17.................................
DOWNFLOW INSTALLATION 19..............................
HORIZONTAL INSTALLATION 21.............................
FILTER ARRANGEMENT 23.................................
AIR DUCTS 25.............................................
GAS PIPING 25.............................................
ELECTRICAL CONNECTIONS 27.............................
JBOX INSTALLATION 28...................................
VENTING 32...............................................
SPECIAL VENTING REQUIREMENTS
FOR INSTALLATIONS IN CANADA 32........................
DIRECT VENT / 2PIPE SYSTEM 33..........................
VENTILATED COMBUSTION AIR SYSTEMS 33................
TERMINATION REQUIREMENTS FOR THE PROVINCES
OF ALBERTA AND SASKATCHEWAN 38......................
INSTALLING THE VENT TERMINATION 43....................
Portions of the text and tables are reprinted from NFPA 54 /ANSI Z223.1−2009©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DC
20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
MAXIMUM EQUIVALENT VENT LENTH 47.....................
MAXIMUM LENGTH OF UNINSULATED AND
INSULATED VENT PIPE-FT (M) 49...........................
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org .
INSTALLER: Affix these instructions on or adjacent to the furnace. CONSUMER: Retain these instructions for future reference.
Printed in U.S.A. 440 01 4201 02 Dec. 2011
Required Notice for Massachusetts Installations
Important
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified license professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery backup may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirement; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than onehalf (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas
Fitters, 239 Causeway Street, Boston, MA 02114. 617−727−9952
2
Specifications are subject to change without notice.
440 01 4201 02
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Safety Considerations
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factoryauthorized and listed kits or accessories when modifying this product.
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and
qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic
maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
WARNING
CAUTION
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
This is the safetyalert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the
potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify hazards which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature−rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start−Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas−fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section. (See Figure 4)
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section on page 7 of these instructions.
10. These Multipoise GasFired Furnaces are CSA designcertified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factoryshipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Table 1 for required clearances to combustible
construction.
440 01 4201 02 3
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
12. Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Table 1
POSITION
Minimum Clearances to
Combustible Materials for All Units
CLEARANCE
In(mm)
REAR 0
FRONT (Combustion air openings in
furnace and in structure)
1 (25)
Required for service 24 (610)
All Sides of Supply Plenum 1 (25)
Sides 0
Vent 0
Top of Furnace 1 (25)
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly is used. See Table 1 for clearance to combustible construction information.
Introduction
The 4way multipoise Category IV condensing furnace is CSA designcertified as a directvent (2pipe) and ventilated combustion air venting installations. (See Figure 3) The furnace is factory−shipped for use with natural gas. The furnace can be converted in the field for use with propane gas when a factorysupplied conversion kit is used. Refer to the furnace rating plate for conversion kit information.
This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return−air temperature of 60°F (15°C) db or intermittent operation down to 55°F (15°C) db such as when used with a night setback thermostat. Returnair temperature must not exceed 80°F (27°C) db. Failure to follow these returnair temperature limits may affect reliability of heat exchangers, motors, and controls (See Figure 1)
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and AirConditioning Engineers; or other approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely.
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping materials, parts assemblies and literature before operating the furnace.
Figure 1
Freeze Protection and Return Air Temperature
SUPPLY
MAX 80°F/27°C
AIR
MIN 60°F/16°C
32° F/0° C MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
Codes and Standards
Follow all national and local codes and standards in addition to these instructions. The installation must comply
with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Safety
US: National Fuel Gas Code (NFGC) NFPA
542009/ANSI Z223.12009 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
CANADA: National Standard of Canada, Natural Gas
and Propane Installation Code (NSCNGPIC) CAN/CSA B149.12010
General Installation
US: NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001.
CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
Combustion and Ventilation Air
US: Section 9.3 of the NFPA54/ANSI Z223.1−2009,
Air for Combustion and Ventilation
CANADA: Part 8 of the CAN/CSA B149.12010,
Venting Systems and Air Supply for Appliances
4 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Duct Systems
US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35.
Acoustical Lining and Fibrous Glass Duct
US and CANADA: current edition of SMACNA, NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
U.S.A.: NFPA 54/ANSI Z223.1−2009, NFGC; Chapters
5, 6, 7, and 8 and national plumbing codes.
CANADA: CAN/CSA−B149.12010, Parts 4, 5, 6 and
9.
In the state of Massachusetts:
This product must be installed by a licensed plumber or
gas fitter.
When flexible connectors are used, the maximum
length shall not exceed 36in. (914 mm).
When lever type gas shutoffs are used they shall be
T−handle type.
The use of copper tubing for gas piping is not
approved by the state of Massachusetts.
Electrical Connections
U.S.A.: National Electrical Code (NEC) ANSI/NFPA
702011
CANADA: Canadian Electrical Code CSA C22.1
Electrostatic Discharge (ESD) Precautions Procedure
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit com­ponent damage.
Electrostatic discharge can affect electronic compon­ents. Take precautions during furnace installation and servicing to protect the furnace electronic control. Pre­cautions will prevent electrostatic discharges from per­sonnel and hand tools which are held during the pro­cedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same elec­trostatic potential.
CAUTION
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
Accessories
See Specification Sheets for a list of accessories for this product.
Table 2
QUANTITY COMPONENT NAME
1 Air Intake Pipe Flange 1 Vent Pipe Flange 2 Coupling Flange Gaskets
10 Sharp Tip Screws (Vent and Inlet Flanges)
1 Vent Pipe Coupling 2 Vent Pipe Coupling Clamps 1 Rubber Drain Tube 4 Drain Tube Clamps 1 1/2” CPVC to 3/4” PVC Pipe Adapter 1 Gas Line Grommet 1 Junction Box Cover 1 Junction Box Base 1 Green Ground Screw 3 Blunt Tip Screws (Junction Box) 1 Thermostat Wire Grommet
Provided separately in furnace
1 Drain Extension Tube “Z” Pipe
Loose Parts Bag Contents (shipped in blower compartment)
440 01 4201 02 5
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Figure 2 Dimensions
(F/G9MAC)
FURNACE SIZE
0601714 171/2 (445) 157/8 (403) 16 (406) 8 3/4 (222) 154 (69) 0602120 21 (533) 193/8 (492) 191/2 (495) 10 1/2 (267) 159 (72) 0801714 171/2 (445) 157/8 (403) 16 (406) 8 3/4 (222) 164 (74) 0802120 21 (533) 193/8 (492) 191/2 (495) 10 1/2 (267) 169 (77) 1002122 21 (533) 193/8 (492) 191/2 (495) 10 1/2 (267) 179 (80) 1202422 241/2 (622) 227/8 (581) 23 (584) 12 1/4 (311) 203 (91)
A B C D
CABINET WIDTH OUTLET WIDTH
BOTTOM
INLET WIDTH
AIR INTAKE
NOTE:
1. Doors may vary by model.
2. Recommended air duct dimensions and configurations: a. For 800 CFM 16in. (406 mm) round or 14 ½ x 12in. (368 x 305 mm) rectangle. b. For 1200 CFM 20in. (508mm) round or 14 ½ x 19 ½in. (368 x 495 mm) rectangle.
c. For 1600 CFM 22in. (559 mm) round or 14 ½ x 22 1/16in. (368 x 560 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Installation Instructions for specific use of single side
inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only return air openings may be required for airflow requirements above 1800 CFM at 0.5 in. w.c. ESP
SHIP WT.
LB (KG)
6 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Location
!
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may result in premature furnace component failure. This gas furnace may be used for heating buildings under construction provided that:
The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
General
These furnaces are shipped with materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
See Table 2 for loose parts bag contents. This furnace must:
be installed so the electrical components are protected from water.
not be installed directly on any combustible material other than wood flooring (refer to SAFETY CONSIDERATIONS).
CAUTION
be located close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown in Table 1 or on the furnace clearance to combustible construction label.
! WARNING
CARBON MONOXIDE POISONING / COMPONENT DAMAGE HAZARD
Failure to follow this warning could result in personal in­jury or death and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, clean­ing solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contam­inated atmosphere. Make sure all combustion and circu­lating air requirements are met, in addition to all local codes and ordinances.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms, and
Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
Deicing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All fuelburning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the returnair duct to prevent pulling air from the burner area.
440 01 4201 02 7
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Figure 3 Multipoise Orientations
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal in­jury, death and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18in. (457 mm) above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmo­sphere, the furnace must be installed in accordance with the NFPA 54/ANSI Z223.1−2009 or CAN/CSA B149.12010. (See Figure 4)
Figure 4 Installation in a Garage
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal in­jury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect re­turnair ducts to the back of the furnace. (See Figure 5)
Figure 5 Prohibited Installations
A10494
A93044
8 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full−heat or full−cool position.
Air for Combustion and Ventilation
Introduction
Direct Vent (2−Pipe) Applications
When the furnace is installed as a direct vent (2-pipe) furnace, no special provisions for air for combustion are required. However, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the guidelines below to insure that other gas appliances have sufficient air for combustion.
Ventilated Combustion Air Applications
When the furnace is installed using the ventilated combustion air option, the attic or crawlspace must freely communicate with the outdoor to provide sufficient air for combustion. The combustion air pipe cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent/ 2-Pipe system.
All air for combustion is piped directly to the furnace from a space that is well ventilated with outdoor air (such as an attic or crawlspace) and the space is well isolated from the living space or garage. In addition, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the guidelines below to insure that the roof or crawlspace walls have sufficient free area to provide sufficient air for combustion and ventilation for the furnaces. The guidelines below can be used to insure that other gas appliances have sufficient air for combustion.
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.12009 , Air for Combustion and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 8 of
CAN/CSAB149.12010, Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
CAUTION
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Makeup air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of makeup air is available.
Figure 6
*Minimum dimensions of 3‐in.
NOTE: Use any of the following combinations
of openings: A & B C & D D & E F & G
Air for Combustion, Ventilation, and Dilution for Outdoors
A03174
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Figure 6 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air openings to the outdoors.
a. One opening MUST commence within 12-in.
(300 mm) of the ceiling and the second opening MUST commence within 12-in. (300 mm) of the floor.
b. Size openings and ducts per Figure 6 and Table 3. c. TWO HORIZONTAL DUCTS require 1 square inch
(25.4 square mm) of free area per 2,000 Btuh (1,100
2
mm
/kW) of combined input for all gas appliances in
the space per Figure 6 and Table 3.
440 01 4201 02 9
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch (25.4 square mm)of free area per 4,000 Btuh (550 mm appliances in the space per Figure 6 and Table 3.
3. ONE OUTDOOR OPENING requires: a. 1 sq. in. (25.4 square mm)of free area per 3,000 Btuh
(734 mm appliances in the space per Table 3 and
2
/kW) for combined input of all gas
2
/kW) for combined input of all gas
b. Not less than the sum of the areas of all vent
connectors in the space.
The opening shall commence within 12-in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1-in. (25 mm) from the sides and back and 6-in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Table 3 Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of Open-
ing and Duct
Sq. In (mm)
Round Duct
In. (mm)
FURNACE
INPUT
(BTUH)
60,000
80,000 100,000 120,000
140,000 *
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
Sq. In (Sq. mm)
30 (19355) 6 (152) 20 (13043) 5 (127) 15 (9678) 5 (127) 40 (25807) 7 (178) 27 (17391) 6 (152) 20 (12904) 5 (127) 50 (32258) 8 (203) 34 (21739) 7 (178) 25 (16130) 6 (152) 60 (38709) 9 (229) 40 (26087) 7 (178) 30 (19355) 6 (152) 70 (45161) 10 (254) 47 (30435) 8 (203) 35 (22581) 7 (178)
Round
Duct
In. (mm)
Dia
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of Open-
ing and Duct
Sq. In (Sq. mm)
Round
Duct
In. (mm)
Dia
EXAMPLE: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
100,000 + 30,000 = (130,000 divided by 4,000) = 32.5 Sq. In. for each two Vertical Ducts or Openings
60,000 + 40,000 = (100,000 divided by 3,000) = 33.3 Sq. In. for each Single Duct or Opening 80,000 + 30,000 = (110,000 divided by 2,000) = 55.0 Sq. In. for each two Horizontal Ducts
Dia.
Table 4 Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00
NP = Not Permitted
30 40 50 40 60 80 100 120 140
1,050 (29.7)
1,260 (35.6)
1,575 (44.5)
2,100 (59.4)
3,150 (89.1)
6,300
(178.0)
NP NP NP NP NP NP NP NP NP
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
CONDENSATE TRAP
!
CAUTION
1,750
(49.5)
2,100 (59.4)
2,625 (74.3)
3,500 (99.1)
5,250
(148.6) 10,500
(297.3)
Space Volume Ft
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
1,500 (42.5)
1,800 (51.0)
2,250 (63.7)
3,000 (84.9)
4,500
(127.3)
9,000
(254.6)
PROPERY DAMAGE HAZARD
FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
3
3
(M
)
2,000
(56.6)
2,400
(67.9)
3,000
(84.9)
4,000
(113.2)
6,000
(169.8) 12,000
(339.5)
!
2,500 (70.8)
3,000 (84.9)
3,750
(106.1)
5,000
(141.5)
7,500
(212.2) 15,000
(424.4)
CAUTION
3,000 (84.9)
3,600
(101.9)
4,500
(127.3)
6,000
(169.8)
9,000
(254.6) 18,000
(509.2)
Failure to follow this caution may result in burst water
FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result in property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to equipment. If furnace environment has the potential of freezing, the drain trap and drain line must be protected. The use of electric heat tape or RV antifreeze is recommended for these installations.
pipes and/or property damage. If a condensate pump is installed, a plugged condensate
drain or a failed pump may cause the furnace to shut down. Do not leave the home unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace. If possible, DO NOT route the drain line where it may freeze. The drain line
3,500 (99.1)
4,200
(118.9)
5,250
(148.6)
7,000
(198.1) 10,500
(297.1) 21,000
(594.1)
10 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the furnace environment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot of 115 volt, 40° F (4° C) selfregulating shielded and water proof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer’s recommendations. Prime the trap before furnace operation.
Condensate Trap Upflow Orientation
When the furnace is installed in the upflow position, it is not necessary to relocate the condensate trap or associated tubing. Refer to Figure 7 for upflow condensate trap information. Refer to Condensate Drain section for information how to install the condensate drain.
Figure 7 Upflow Trap Configuration
Condensate Trap
Relief Port
Collector Box
Plugs
Condensate Trap Downflow Orientation
When the furnace is installed in the downflow position, the factory-installed trap will be located at the upper left corner of the collector box. When the furnace is installed in the downflow orientation, the factory-installed trap must be relocated for proper condensate drainage.
To Relocate the Condensate Trap:
Orient the furnace in the downflow position.Figure 8 shows the condensate trap and tubing before and
after relocation. Refer to Figure 8 to begin the trap conversion.
Refer to Condensate Drain section for information how to install
the condensate drain.
Vent Pipe Clamp
Vent Elbow Clamp
Vent Elbow
Pressure Switch
Port
Collector Box
Plug
Condensate Trap
Relief Port
Condensate Trap
Outlet
A11306Representative drawing only, some models may vary in appearance.
440 01 4201 02 11
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Figure 8 Unconverted Factory Configuration as viewed in the Downflow Orientation
Remove pressure switch tube from pressure switch port.
Remove relief tube from relief port on condensate trap.
Remove trap from collector box.
Loosen clamp on inlet to vent elbow.
Install plugs on open ports on collector box.
Connect relief tube to port on collector box.
Rotate elbow to desired position and
9
tighten clamp to 15 lb.in.
Slide tube in standoffs to adjust length.
Representative drawing only, some models may vary in appearance.
Downflow Trap Configuration
Remove tube from relief port.
Remove middle and bottom plugs. DO NOT DISCARD.
Trim excess tube.
7
Connect pressure switch tube to port on collector box.
Attach condensate trap with screw to collector box.
Connect relief tube to relief port on condensate trap.
Align condensate trap over middle and bottom ports of collector box.
A11585A
Representative drawing only, some models may vary in appearance.
Condensate Trap Horizontal Orientation
When the furnace is installed in the horizontal right position, the factory-installed trap will be located at the bottom of the collector box. When the furnace is installed in the horizontal left position, the factory-installed trap will be located at the top of the collector box. The trap must be repositioned on the collector box for proper condensate drainage.
When the furnace is installed as a directvent furnace, a field supplied, accessory Horizontal Installation Kit (trap grommet) is required for all direct−vent horizontal installations (only). The kit contains a rubber casing grommet designed to seal between the furnace casing and the condensate trap. (See Figure 16)
NOTE: The Horizontal Installation Kit (trap grommet) is NOT required for singlepipe, ventilated combustion air, or other nondirect vent applications.
NOTE: The condensate trap extends below the side of the casing in the horizontal position. A minimum of 2 in. (51 mm) of clearance is required between the casing side and the furnace platform for the trap to extend out of the casing in the horizontal position. Allow at least 1/4in. (6 mm) per foot of slope away from the furnace in horizontal sections of drain line.
To Relocate the Condensate Trap:
Remove the knockout in the casing for the condensate trap.Install the grommet in the casing when required.
NOTE: This grommet is only required for direct−vent applications
A11585B
Orient the furnace in the desired position.
12 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Allow for 2 in. (51 mm) of clearance underneath the furnace for
the condensate trap and drain line.
Figure 9 shows the condensate trap and tubing before and
after relocation in the horizontal right position.
after relocation in the horizontal left position.
Refer to the appropriate figure to begin the trap conversion.Refer to Condensate Drain section for information how to install
the condensate drain.
Figure 10 shows the condensate trap and tubing before and
Figure 9 Unconverted Factory Configuration as viewed in the Horizontal Left Orientation
Remove trap from
If alternate vent position is required, loosen clamp on vent elbow inlet.
collector box.
Remove relief tube from relief port on condensate trap.
Remove pressure switch tube from port on collector box.
Remove relief tube from port on collector box.
Representative drawing only, some models may vary in appearance.
Rotate elbow to desired position and torque clamp on inlet 15 lb.in.
Slide relief tube in standoffs to adjust length.
Attach condensate trap to collector box with screw.
Align trap over middle and righthand port on collector box.
Representative drawing only, some models may vary in appearance.
Horizontal Left Trap Configuration
Remove middle and right plug from collector box. DO NOT DISCARD
Install plugs in open ports on collector box.
Connect relief tube to port on collector box.
Trim excess tube. Route pressure switch tube underneath relief tube and connect to port on collector box.
Connect relief tube to relief port on condensate trap.
A11586A
A11586B
440 01 4201 02 13
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Figure 10 Unconverted Factory Configuration as viewed in the Horizontal Right Orientation
Remove plug from collector box. DO NOT DISCARD.
If alternate vent position is required, loosen clamp on inlet of vent elbow.
Remove trap from collector box.
Representative drawing only, some models may vary in appearance.
Horizontal Right Trap Configuration
Attach condensate trap to collector box with screw.
Install plug in open port on collector box.
Representative drawing only, some models may vary in appearance.
Slide relief tube in stand-offs to adjust length.
Vent elbow shown in alternate orientation. Tighten clamp on inlet to vent elbow 15 lb.-in.
Align trap over middle and right-hand port on collector box.
A11281
14 440 01 4201 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)MAC
Condensate Drain Connection
!
FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result in property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to equipment. If furnace environment has the potential of freezing, the drain trap and drain line must be protected. The use of electric heat tape or RV antifreeze is recommended for these installations.
!
PROPERY DAMAGE HAZARD
Failure to follow this caution may result in burst water pipes and/or property damage.
If a condensate pump is installed, a plugged condensate drain or a failed pump may cause the furnace to shut down. Do not leave the home unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace. If possible, DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the furnace environment has the potential of freezing, the drain trap and drain line must be protected. A selfregulating, shielded and waterproof heat tape rated at 3 to 6 watt per foot of 115 volt, 40° F (4° C) may be used to help provide freeze protection. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer’s recommendations. Prime the trap before furnace operation.
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is inside the furnace casing. The condensate drain must be routed from the trap through the furnace casing. The condensate drain can be routed through the left or right side of the casing. (The left or right side is as you are viewing/facing the furnace from the front.) The furnace condensate drain can be connected to the Air Conditioning condensate drain as shown in Figure 11.
NOTE: On narrower casings, it may be easier to remove the condensate trap, connect the drain line components and re-install the condensate trap. Read the steps thoroughly to familiarize yourself with the required steps.
For Right Side Condensate Drain:
1. Remove the 7/8in. knockout from the right side of the
casing. (See Figure 12)
2. Remove the preformed rubber drain tube and two spring clamps from the loose parts bag.
3. Slide a spring clamp 1 in. (25 mm) down the plain end (the end without the formed grommet) of the drain tube.
CAUTION
CAUTION
4. From inside the casing, insert the formed grommet end of the elbow through the 7/8in. knockout in the casing.
5. Pull the grommet through the casing from the outside until it is seated in the knockout
6. Attach the plain end of the drain tube to the outlet stub on the drain trap. Secure the drain tube to the trap with the spring clamp.
The remaining drain line can be constructed from field supplied 1/2in. CPVC or 3/4in. PVC pipe in compliance with local building codes. A factory−supplied 1/2−in. CPVC to 3/4−in PVC adapter is supplied in the loose parts bag for use as required.
7. Install the adapter or connect the 1/2in. CPVC pipe by sliding a spring clamp over the open end of the grommet on the outside of the furnace casing.
8. Open the spring clamp and insert the long end of the adapter of the 1/2−in. CPVC pipe into the outlet stub on the drain tube.
9. Connect additional condensate piping to a codeapproved drain, or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils, such as canola oil.
NOTE: Allow at least 1/4−in. (6mm) per foot of slope away from the furnace in horizontal sections of drain line.
Figure 11 Example of Field Drain Attachment
OPEN STAND PIPE FOR A/C OR HUMIDIFIER DRAIN
TEE
TO OPEN DRAIN
A11276
For Left Side Condensate Drain Connection:
1. For left side condensate drainage, the drain line is routed from the condensate trap, behind the inducer (upflow) or gas valve (downflow) and out through the left side of the furnace casing. A pre-formed 1/2−in. CPVC “Z” pipe is provided with the furnace. The “Z“ pipe is long enough to extend across the casing for drain connections.
2. The “Z” pipe is connected to the condensate trap and the outside of the furnace by modifying the formed rubber
drain tube as shown in Figure 13.
3. Locate the “Z” pipe. Remove the pre-formed drain tube and four spring clamps from the loose parts bag.
4. Remove the formed grommet from the rubber drain tube by cutting the elbow along the vertical line located about 1 3/8−in. (35 mm) away from the formed grommet. See Figure 12. DO NOT DISCARD THE FORMED GROMMET OR THE RUBBER ELBOW. Both of these pieces will be used.
440 01 4201 02 15
Specifications subject to change without notice.